GE Industrial Solutions AF-600 FP User Manual

AF-600 FP
TM
Fan & Pump Drive
(230V to 60HP, 460/575V to 125HP
Operating Instructions
GE
Safety AF-600 FP Operating Instructions
Safety
WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when connected to AC mains input power. Installation, start up, and maintenance should be performed by qualified personnel only. Failure to perform installation, start up, and maintenance by qualified personnel could result in death or serious injury.
High Voltage Frequency converts are connected to hazardous mains voltages. Extreme care should be taken to protect against shock. Only trained personnel familiar with electronic equipment should install, start, or maintain this equipment.
WARNING
UNINTENDED START!
When the drive is connected to AC mains, the motor may start at any time. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when the drive is connected to AC mains could result in death, serious injury, equipment, or property damage.
Unintended Start When the drive is connected to the AC mains, the motor may be started by means of an external switch, a serial bus command, an input reference signal, or a cleared fault condition. Use appropriate cautions to guard against an unintended start.
WARNING
DISCHARGE TIME!
Frequency converters contain DC link capacitors that can remain charged even when AC mains is disconnected. To avoid electrical hazards, remove AC mains from the drive before doing any service or repair and wait the amount of time specified in Table 1.1. Failure to wait the specified time after power has been removed prior to doing service or repair on the unit could result in death or serious injury.
Voltage (V) Minimum Waiting Time (Minutes)
415
200 - 240 0.75 - 3.7 kW
1 - 5 hp
380 - 480 0.75 - 7.5 kW
1 - 10 hp
525 - 600 0.75 - 7.5 kW
1 - 10 hp
High voltage may be present even when the warning LEDs are
off!
Discharge Time
Symbols The following symbols are used in this manual.
5.5 - 45 kW
7 1/2 - 60 hp
11 - 90 kW
15 - 125 hp
11 - 90 kW
15 - 125 hp
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment or property-damage-only accidents.
NOTE
Indicates highlighted information that should be regarded with attention to avoid mistakes or operate equipment at less than optimal performance.
Approvals
Safety AF-600 FP Operating Instructions
Contents AF-600 FP Operating Instructions
Contents
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Product Overview
1.4 Internal Drive Controller Functions
1.5 Unit Sizes and Power Ratings
2 Installation
2.1 Installation Site Check List
2.2 Drive and Motor Pre-installation Check List
2.3 Mechanical Installation
2.3.1 Cooling 8
2.3.2 Lifting 9
2.3.3 Mounting 9
2.3.4 Tightening Torques 9
2.4 Electrical Installation
2.4.1 Requirements 11
2.4.2 Earth (Grounding) Requirements 12
4
6
6
6
6
7
8
8
8
8
10
2.4.2.1 Leakage Current (>3,5mA) 12
2.4.2.2 Grounding Using Shielded Cable 13
2.4.2.3 Grounding Using Conduit 13
2.4.3 Motor Connection 13
2.4.4 AC Mains Connection 14
2.4.5 Control Wiring 15
2.4.5.1 Access 15
2.4.5.2 Control Terminal Types 15
2.4.5.3 Wiring to Control Terminals 16
2.4.5.4 Using Screened Control Cables 17
2.4.5.5 Control Terminal Functions 17
2.4.5.6 Terminal 53 and 54 Switches 17
2.4.6 Serial Communication 18
3 Start Up and Functional Testing
3.1 Pre-start
3.1.1 Safety Inspection 19
3.1.2 Start Up Check List
19
19
20
3.2 Applying Power to the Drive
3.3 Basic Operational Programming
3.4 Auto Tune
3.5 Check Motor Rotation
21
21
21
22
1
Contents AF-600 FP Operating Instructions
3.6 Local-control Test
3.7 System Start Up
4 User Interface
4.1 Keypad
4.1.1 Keypad Layout 24
4.1.2 Setting Keypad Display Values 25
4.1.3 Display Menu Keys 25
4.1.4 Navigation Keys 26
4.1.5 Operation Keys 26
4.2 Back Up and Copying Parameter Settings
4.2.1 Uploading Data to the keypad 27
4.2.2 Downloading Data from the keypad 27
4.3 Restoring Default Settings
4.3.1 Recommended Initialisation 27
4.3.2 Manual Initialisation 27
5 About Drive Programming
22
23
24
24
26
27
28
5.1 Introduction
5.2 Programming Example
5.3 Control Terminal Programming Examples
5.4 International/North American Default Parameter Settings
5.5 Parameter Menu Structure
5.5.1 Quick Menu Structure 32
5.5.2 Main Menu Structure 33
5.6 Remote Programming with DCT-10
6 Application Set-Up Examples
6.1 Introduction
6.2 Application Examples
7 Status Messages
7.1 Status Display
7.2 Status Message Definitions Table
8 Warnings and Alarms
28
28
30
31
32
40
41
41
41
46
46
46
49
8.1 System Monitoring
8.2 Warning and Alarm Types
8.3 Warning and Alarm Displays
8.4 Warning and Alarm Definitions
8.4.1 Fault Messages 51
9 Basic Troubleshooting
2
49
49
49
50
57
Contents AF-600 FP Operating Instructions
9.1 Start Up and Operation
10 Specifications
10.1 Power-dependent Specifications
10.2 General Technical Data
10.3 Fuse Tables
10.3.1 Recommendations 71
10.3.2 CE Compliance 72
10.3.3 NEC and UL Compliance 77
10.3.4 Substitute Fuses for 240 V 83
10.4 Connection Tightening Torques
Index
57
59
59
66
71
83
84
3
1
Introduction AF-600 FP Operating Instructions
1Introduction
Illustration 1.1 Exploded View Unit Size 1X
1 Keypad 10 Motor output terminals 96 (U), 97 (V), 98 (W)
2 RS-485 serial bus connector (+68, -69) 11 Relay 1 (01, 02, 03)
3 Analog I/O connector 12 Relay 2 (04, 05, 06)
4 Keypad input plug 13 Brake (-81, +82) and load sharing (-88, +89) terminals
5 Analog switches (A53), (A54) 14 Mains input terminals 91 (L1), 92 (L2), 93 (L3)
6 Cable strain relief / PE ground 15 USB connector
7 Decoupling plate 16 Serial bus terminal switch
8 Grounding clamp (PE) 17 Digital I/O and 24 V power supply
9 Shielded cable grounding clamp and strain relief 18 Control cable cover plate
4
Introduction AF-600 FP Operating Instructions
1
1
Illustration 1.2 Exploded View Unit Sizes 21, 22, 31, and 32
1 Keypad 11 Relay 2 (04, 05, 06)
2Cover 12Lifting ring
3 RS-485 serial bus connector 13 Mounting slot
4 Digital I/O and 24 V power supply 14 Grounding clamp (PE)
5 Analog I/O connector 15 Cable strain relief / PE ground
6 Cable strain relief / PE ground 16 Brake terminal (-81, +82)
7 USB connector 17 Load sharing terminal (DC bus) (-88, +89)
8 Serial bus terminal switch 18 Motor output terminals 96 (U), 97 (V), 98 (W)
9 Analog switches (A53), (A54) 19 Mains input terminals 91 (L1), 92 (L2), 93 (L3)
10 Relay 1 (01, 02, 03)
5
1
Introduction AF-600 FP Operating Instructions
1.1 Purpose of the Manual
This manual is intended to provide detailed information for the installation and start up of the frequency converter. Chapter 2 Installation provides requirements for mechanical and electrical installation, including input, motor, control and serial communications wiring, and control terminal functions. Chapter 3 Start Up and Functional Testing provides detailed procedures for start up, basic operational programming, and functional testing. The remaining chapters provide supplementary details. These include user interface, detailed programming, application examples, start-up troubleshooting, and specifi­cations.
Illustration 1.3 Drive Block Diagram
Area Title Functions
1Mains input
2Rectifier
1.2 Additional Resources
Other resources are available to understand advanced drive functions and programming.
The Programming Guide provides greater detail
in how to work with parameters and many application examples.
The Design Guide is intended to provide detailed
capabilities and functionality to design motor control systems.
Optional equipment is available that may change
some of the procedures described. Be sure to see the instructions supplied with those options for specific requirements.
3DC bus
4DC reactors
5 Capacitor bank
1.3 Product Overview
A drive is an electronic motor controller that converts AC mains input into a variable AC waveform output. The frequency and voltage of the output are regulated to control the motor speed or torque. The drive can vary the speed of the motor in response to system feedback, such as changing temperature or pressure for controlling fan, compressor, or pump motors. The drive can also regulate the motor by responding to remote commands from external controllers.
In addition, the drive monitors the system and motor status, issues warnings or alarms for fault conditions, starts and stops the motor, optimizes energy efficiency, and offers many more control, monitoring, and efficiency functions. Operation and monitoring functions are available as status indications to an outside control system or serial communication network.
6Inverter
7 Output to motor
8 Control circuitry
1.4 Internal Drive Controller Functions
Table 1.1 Drive Internal Components
Below is a block diagram of the frequency converter's internal components. See Table 1.1 for their functions.
Three-phase AC mains power
supply to the drive
The rectifier bridge converts
the AC input to DC current to
supply inverter power
The frequency converter's
intermediate DC-bus circuit
handles the DC current
Filter the intermediate DC
circuit voltage
Prove line transient protection
Reduce RMS current
Raise the power factor
reflected back to the line
Reduce harmonics on the AC
input
Stores the DC power
Provides ride-through
protection for short power
losses
Converts the DC into a
controlled PWM AC waveform
for a controlled variable
output to the motor
Regulated three-phase output
power to the motor
Input power, internal
processing, output, and motor
current are monitored to
provide efficient operation
and control
User interface and external
commands are monitored and
performed
Status output and control can
be provided
6
Introduction AF-600 FP Operating Instructions
1.5 Unit Sizes and Power Ratings
References to unit sizes used in this manual are defined in Table 1.2.
Unit sizes
IP20 / Open Chassis IP55 / Nema 12
Volts1213232433341521223132
200-240 1-3 HP 5 HP 7.5-15 HP 20-25 HP 30-40 HP 50-60 HP 1-5 HP 7.5-15 HP 20 HP 25-40 HP 50-60 HP
380-480 1-5 HP 7.5-10 HP 15-25 HP 25-40 HP 50-75 HP
525-600 - 1-10 HP 15-25 HP 25-40 HP 50-75 HP
100-125
HP 1-10 HP 15-25 HP 25-40 HP 50-75 HP
100-125
HP 1-10 HP 15-25 HP 25-40 HP 50-75 HP
100-125
HP
100-125
HP
1
1
7
Installation AF-600 FP Operating Instructions
2 Installation
2
2.1 Installation Site Check List
The drive relies on the ambient air for cooling.
Observe the limitations on ambient air temperature for optimal operation
Ensure that the installation location has sufficient
support strength to mount the drive
Keep the drive interior free from dust and dirt.
Ensure that the components stay as clean as possible. In construction areas, provide a protective covering. Optional IP55 (NEMA 12) enclosures may be necessary.
Keep the manual, drawings, and diagrams
accessible for detailed installation and operation instructions. It is important that the manual is available for equipment operators.
Locate equipment as near to the motor as
possible. Keep motor cables as short as possible. Check the motor characteristics for actual tolerances. Do not exceed
300m (1000ft) for unshielded motor
leads
150m (500ft) for shielded cable.
2.3 Mechanical Installation
2.3.1 Cooling
To provide cooling airflow, mount the unit to a
solid flat surface or to the optional back plate (see 2.3.3 Mounting)
Top and bottom clearance for air cooling must be
provided. Generally, 100-225mm (4-10in) is required. See Illustration 2.1 for clearance requirements
Improper mounting can result in over heating
and reduced performance
Derating for temperatures starting between 40°C
(104°F) and 50°C (122°F) and elevation 1000m (3300ft) above sea level must be considered. See the equipment Design Guide for detailed information.
2.2 Drive and Motor Pre-installation Check List
Compare the model number of unit on the
nameplate to what was ordered to verify the proper equipment
Ensure each of the following are rated for same
voltage:
Mains (power)
Drive
Motor
Ensure that drive output current rating is equal to
or greater than motor full load current for peak motor performance
Motor size and drive power must match for proper overload protection
If drive rating is less than motor, full motor output cannot be achieved
Illustration 2.1 Top and Bottom Cooling Clearance
Size 12 13 - 15 21 22
a/b (mm) 100 100 - 100 200 200
a/b (in) 4 4 - 4 8 8
Size 23 24 31 32 33 34
a/b (mm) 200 200 200 225 200 225
a/b (in) 8 8 8 9 8 9
Table 2.1 Minimum Airflow Clearance Requirements
8
Installation AF-600 FP Operating Instructions
2
2.3.2 Lifting
Check the weight of the unit to determine a safe
lifting method
Ensure that the lifting device is suitable for the
task
If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit
For lifting, use hoist rings on the unit, when
provided
2.3.3 Mounting
Mount the unit vertically
The drive allows side by side installation
Ensure that the strength of the mounting location
will support the unit weight
Mount the unit to a solid flat surface or to the
optional back plate to provide cooling airflow (see Illustration 2.2 and Illustration 2.3)
Improper mounting can result in over heating
and reduced performance
Use the slotted mounting holes on the unit for
wall mounting, when provided
Illustration 2.3 Proper Mounting with Railings
NOTE
Back plate is needed when mounted on railings.
2.3.4 Tightening Torques
See 10.4 Connection Tightening Torques for proper tightening specifications.
2
Illustration 2.2 Proper Mounting with Back Plate
Item A is a back plate properly installed for required airflow to cool the unit.
9
2
Installation AF-600 FP Operating Instructions
2.4 Electrical Installation
This section contains detailed instructions for wiring the drive. The following tasks are described.
Wiring the motor to the drive output terminals
Wiring the AC mains to the drive input terminals
Connecting control and serial communication wiring
After power has been applied, checking input and motor power; programming control terminals for their intended
functions
Illustration 2.4 shows a basic electrical connection.
Illustration 2.4 Basic Wiring Schematic Drawing.
10
Installation AF-600 FP Operating Instructions
2
2.4.1 Requirements
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be hazardous. All electrical work must conform to national and local electrical codes. It is strongly recommended that instal­lation, start up, and maintenance be performed only by trained and qualified personnel. Failure to follow these guidelines could result in death or serious injury.
CAUTION
WIRING ISOLATION!
Run input power, motor wiring and control wiring in three separate metallic conduits or use separated shielded cable for high frequency noise isolation. Failure to isolate power, motor and control wiring could result in less than optimum drive and associated equipment performance.
2
For your safety, comply with the following requirements.
Electronic controls equipment is connected to
hazardous mains voltage. Extreme care should be taken to protect against electrical hazards when applying power to the unit.
Run motor cables from multiple frequency
converters separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out.
Overload and Equipment Protection
An electronically activated function within the
drive provides overload protection for the motor. The overload calculates the level of increase to activate timing for the trip (controller output stop) function. The higher the current draw, the quicker the trip response. The overload provides Class 20 motor protection. See 8 Warnings and Alarms for details on the trip function.
Because the motor wiring carries high frequency
current, it is important that wiring for mains, motor power, and control are run separately. Use metallic conduit or separated shielded wire. Failure to isolate power, motor, and control wiring could result in less than optimum equipment performance. See Illustration 2.5.
Illustration 2.5 Proper Electrical Installation Using Conduit
All frequency converters must be provided with
short-circuit and over-current protection. Input fusing is required to provide this protection, see
Illustration 2.6. See maximum fuse ratings in
10.3 Fuse Tables.
Illustration 2.6 Drive Fuses
Wire Type and Ratings
All wiring must comply with local and national
regulations regarding cross-section and ambient temperature requirements.
GE recommends that all power connections be
made with a minimum 75° C rated copper wire.
See 10.1 Power-dependent Specifications for
recommended wire sizes.
11
Installation AF-600 FP Operating Instructions
2
2.4.2 Earth (Grounding) Requirements
WARNING
GROUNDING HAZARD!
For operator safety, it is important to ground drive properly in accordance with national and local electrical codes as well as instructions contained within these instructions. Ground currents are higher than 3,5mA. Failure to ground drive properly could result in death or serious injury.
NOTE
It is the responsibility of the user or certified electrical installer to ensure correct grounding (earthing) of the equipment in accordance with national and local electrical codes and standards.
Follow all local and national electrical codes to
ground electrical equipment properly
Proper protective grounding for equipment with
ground currents higher than 3,5mA must be established, see Leakage Current (>3,5mA)
A dedicatedground wire is required for input
power, motor power and control wiring
Use the clamps provided with on the equipment
for proper ground connections
Do not ground one drive to another in a “daisy
chain” fashion
Keep the ground wire connections as short as
possible
Use of high-strand wire to reduce electrical noise
is recommended
Follow motor manufacturer wiring requirements
2.4.2.1 Leakage Current (>3,5mA)
EN/IEC61800-5-1 (Power Drive System Product Standard) requires special care if the leakage current exceeds 3,5mA. Earth grounding must be reinforced in one of the following ways:
Earth ground wire of at least 10mm
Two separate earth ground wires both complying
with the dimensioning rules
See EN 60364-5-54 § 543.7 for further information.
Using RCDs Where residual current devices (RCDs), also known as earth leakage circuit breakers (ELCBs), are used, comply with the following:
Use RCDs of type B only which are capable of detecting AC and DC currents
Use RCDs with an inrush delay to prevent faults due to transient earth currents
Dimension RCDs according to the system configu­ration and environmental considerations
2
Follow national and local codes regarding protective earthing of equipment with a leakage current > 3,5mA. Drive technology implies high frequency switching at high power. This will generate a leakage current in the earth connection. A fault current in the drive at the output power terminals might contain a DC component which can charge the filter capacitors and cause a transient earth current. The earth leakage current depends on various system configurations including RFI filtering, screened motor cables, and drive power.
12
Installation AF-600 FP Operating Instructions
2
2.4.2.2 Grounding Using Shielded Cable
Earthing (grounding) clamps are provided for motor wiring (see Illustration 2.7).
Illustration 2.7 Grounding with Shielded Cable
2.4.2.3 Grounding Using Conduit
CAUTION
GROUNDING HAZARD!
Do not use conduit connected to the drive as a replacement for proper grounding. Ground currents are higher than 3.5mA. Improper grounding can result in personal injury or electrical shorts.
Dedicated grounding clamps are provided (See Illustration 2.8).
1. Use a wire stripper to remove the insulation for proper grounding.
2. Secure the grounding clamp to the stripped portion of the wire with the screws provided.
3. Secure the grounding wire to the grounding clamp provided.
2.4.3 Motor Connection
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple frequency converters separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output motor cables separately could result in death or serious injury.
For maximum wire sizes see 10.1 Power-dependent
Specifications
Comply with local and national electrical codes
for cable sizes
Motor wiring knockouts or access panels are
provided at the base of IP55 / Nema 12 units
Do not install power factor correction capacitors
between the drive and the motor
Do not wire a starting or pole-changing device
between the drive and the motor
Connect the 3-phase motor wiring to terminals
96 (U), 97 (V), and 98 (W)
Ground the cable in accordance with grounding
instructions provided
Torque terminals in accordance with the
information provided in 10.4.1 Connection
Tightening Torques
Follow motor manufacturer wiring requirements
The three following illustrations represent mains input, motor, and earth grounding for basic frequency converters. Actual configurations vary with unit types and optional equipment.
2
Illustration 2.8 Grounding with Conduit
13
2
Installation AF-600 FP Operating Instructions
Illustration 2.9 Motor, Mains and Earth Wiring for Frame Sizes 1X
Illustration 2.11 Motor, Mains and Earth Wiring for Frame Sizes
2X and Above Using Conduit
Illustration 2.10 Motor, Mains and Earth Wiring for Frame Sizes
2X and Above Using Shielded Cable
2.4.4 AC Mains Connection
Size wiring based upon the input current of the
drive. For maximum wire sizes see 10.1 Power- dependent Specifications.
Comply with local and national electrical codes
for cable sizes.
Connect 3-phase AC input power wiring to
terminals L1, L2, and L3 (see Illustration 2.12).
Input power will be connected to the mains input
terminals.
14
Illustration 2.12 Connecting to AC Mains
Installation AF-600 FP Operating Instructions
2
Ground the cable in accordance with grounding
instructions provided in 2.4.2 Earth (Grounding)
Requirements
All frequency converters may be used with an
isolated input source as well as with ground reference power lines. When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded delta), set SP-50 RFI Filter to OFF. When off, the internal RFI filter capacitors between the chassis and the intermediate circuit are isolated to avoid damage to the intermediate circuit and to reduce earth capacity currents in accordance with IEC 61800-3.
Illustration 2.14 Control Wiring Access for IP55 / Nema 12
enclosures
2.4.5.2 Control Terminal Types
2
130BT334.11
2.4.5 Control Wiring
Isolate control wiring from high power
components in the drive.
If the drive is connected to a thermistor, for PELV
isolation, optional thermistor control wiring must be reinforced/double insulated. A 24 VDC supply voltage is recommended.
2.4.5.1 Access
Remove access cover plate with a screw driver.
See Illustration 2.13.
Or remove front cover by loosening attaching
screws. See Illustration 2.14. Tightening torque for front cover is 2.0Nm for unit size 15 and 2.2Nm for unit sizes 2X and 3X.
Illustration 2.18 shows the removable drive connectors. Terminal functions and default settings are summarized in Table 2.2.
130BT248
Illustration 2.13 Control Wiring Access for IP20 / Open chassis
enclosures
Illustration 2.15 Control Terminal Locations
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals programmable as either input or output, a 24V DC terminal supply voltage, and a common for optional customer supplied 24V DC voltage
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
Connector 3 provides two analog inputs, one
analog output, 10V DC supply voltage, and commons for the inputs and output
15
Installation AF-600 FP Operating Instructions
2
Connector 4 is a USB port available for use with
the DCT-10
Also provided are two Form C relay outputs that
are in various locations depending upon the drive configuration and size
Some options available for ordering with the unit
may provide additional terminals. See the manual provided with the equipment option.
See 10.2 General Technical Data for terminal ratings details.
Terminal Description
Digital Inputs/Outputs
Default
Terminal Parameter
12, 13 - +24V DC 24V DC supply
18 E-01 [8] Start
19 E-02 [0] No
32 E-05 [0] No
33 E-06 [0] No
27 E-03 [0] No
29 E-04 [14] JOG
20 - Common for digital
39 -
42 AN-50 Speed 0 -
50 - +10V DC 10V DC analog supply
53 AN-1# Reference Analog input.
54 AN-2# Feedback
Setting Description
operation
operation
operation
operation
Analog Inputs/Outputs
High Limit
voltage. Maximum
output current is
200mA total for all
24V loads. Useable for
digital inputs and
external transducers.
Digital inputs.
Selectable for either
digital input or
output. Default setting
is input.
inputs and 0V
potential for 24V
supply.
Common for analog
output
Programmable analog
output. The analog
signal is 0-20mA or
4-20mA at a
maximum of 500
voltage. 15mA
maximum commonly
used for potenti-
ometer or thermistor.
Selectable for voltage
or current. Switches
A53 and A54 select
mA or V.
Ω
Terminal Description
Digital Inputs/Outputs
Default
Terminal Parameter
55 -
61 -
68 (+) O-3# RS-485 Interface. A
69 (-) O-3#
01, 02, 03 E-24 [0] [0] Alarm Form C relay output.
04, 05, 06 E-24 [1] [0] Running
Table 2.2 Terminal Description
Setting Description
Serial Communication
Relays
Common for analog
input
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
when experiencing
EMC problems.
control card switch is
provided for
termination resistance.
Usable for AC or DC
voltage and resistive
or inductive loads.
2.4.5.3 Wiring to Control Terminals
Control terminal connectors can be unplugged from the drive for ease of installation, as shown in Illustration 2.16.
Illustration 2.16 Unplugging Control Terminals
1. Open the contact by inserting a small screwdriver into the slot above or below the contact, as shown in Illustration 2.17.
2. Insert the bared control wire into the contact.
3. Remove the screwdriver to fasten the control wire into the contact.
4. Ensure the contact is firmly established and not loose. Loose control wiring can be the source of equipment faults or less than optimal operation.
16
Installation AF-600 FP Operating Instructions
2
See 10.1 Power-dependent Specifications for control terminal wiring sizes.
See 6 Application Set-Up Examples for typical control wiring connections.
Illustration 2.17 Connecting Control Wiring
2.4.5.4 Using Screened Control Cables
Correct screening The preferred method in most cases is to secure control and serial communication cables with screening clamps provided at both ends to ensure best possible high frequency cable contact.
50/60Hz ground loops With very long control cables, ground loops may occur. To eliminate ground loops, connect one end of the screen-to­ground with a 100nF capacitor (keeping leads short).
2.4.5.5 Control Terminal Functions
Drive functions are commanded by receiving control input signals.
Each terminal must be programmed for the
function it will be supporting in the parameters associated with that terminal. SeeTable 2.2 for terminals and associated parameters.
It is important to confirm that the control
terminal is programmed for the correct function. See 4 User Interface for details on accessing parameters and for details on programming.
The default terminal programming is intended to
initiate drive functioning in a typical operational mode.
2.4.5.6 Terminal 53 and 54 Switches
Analog input terminals 53 and 54 can select
either voltage (0 to 10V) or current (0/4-20mA) input signals
Remove power to the drive before changing
switch positions
Set switches A53 and A54 to select the signal
type. U selects voltage, I selects current.
The switches are accessible when the keypad has
been removed (see Illustration 2.18). Note that some option cards available for the unit may cover these switches and must be removed to change switch settings. Always remove power to the unit before removing option cards.
Terminal 53 default is for a speed reference signal
in open loop set in DR-61 Terminal 53 Switch
Setting
Terminal 54 default is for a feedback signal in
closed loop set in DR-63 Terminal 54 Switch
Setting
2
Avoid EMC noise on serial communication To eliminate low-frequency noise between frequency converters, connect one end of the screen to terminal 61. This terminal is connected to ground via an internal RC link. Use twisted-pair cables to reduce interference between conductors.
17
2
Installation AF-600 FP Operating Instructions
For basic serial communication set-up, select the following
1. Protocol type in O-30 Protocol.
2. Drive address in O-31 Address.
3.
130BT310.10
Illustration 2.18 Location of Terminals 53 and 54 Switches
2.4.6 Serial Communication
Connect RS-485 serial communication wiring to terminals (+)68 and (-)69.
Screened serial communication cable is
recommended
See 2.4.2 Earth (Grounding) Requirements for
proper grounding
Baud rate in O-32 Drive Port Baud Rate.
Four communication protocols are internal to the drive. Follow motor manufacturer wiring requirements.
Drive profile
Modbus RTU
Metasys N2
Apogee FLN
Functions can be programmed remotely using the protocol software and RS-485 connection or in parameter group O-## Options / Comms
Selecting a specific communication protocol changes various default parameter settings to match that protocol’s specifications along with making additional protocol-specific parameters available
Option cards which install into the drive are available to provide additional communication protocols. See the option-card documentation for installation and operation instructions
®
®
Illustration 2.19 Serial Communication Wiring Diagram
18
Start Up and Functional Tes... AF-600 FP Operating Instructions
3
3 Start Up and Functional Testing
3.1 Pre-start
3.1.1 Safety Inspection
WARNING
HIGH VOLTAGE!
If input and output connections have been connected improperly, there is potential for high voltage on these terminals. If power leads for multiple motors are improperly run in same conduit, there is potential for leakage current to charge capacitors within the drive, even when disconnected from mains input. For initial start up, make no assumptions about power components. Follow pre-start procedures. Failure to follow pre-start procedures could result in personal injury or damage to equipment.
1. Input power to the unit must be OFF and locked out. Do not rely on the drive disconnect switches for input power isolation.
2. Verify that there is no voltage on input terminals L1 (91), L2 (92), and L3 (93), phase-to-phase and phase-to-ground,
3. Verify that there is no voltage on output terminals 96 (U), 97 (V), and 98 (W), phase-to­phase and phase-to-ground.
4. Confirm continuity of the motor by measuring ohm values on U-V (96-97), V-W (97-98), and W-U (98-96).
5. Check for proper grounding of the drive as well as the motor.
6. Inspect the drive for loose connections on terminals.
7. Record the following motor-nameplate data: power, voltage, frequency, full load current, and nominal speed. These values are needed to program motor nameplate data later.
8. Confirm that the supply voltage matches voltage of drive and motor.
3
19
Start Up and Functional Tes... AF-600 FP Operating Instructions
3.1.2 Start Up Check List
CAUTION
Before applying power to the unit, inspect the entire installation as detailed in Table 3.1. Check mark those items when completed.
3
Inspect for Description
Auxiliary equipment
Cable routing
Control wiring
Cooling clearance
EMC considerations
Environmental considerations
Fusing and circuit breakers
Grounding
Input and output power wiring
Panel interior
Switches
Vibration
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit
breakers that may reside on input power side of drive or output side to motor.
Examine their operational readiness and ensure that they are ready in all
respects for operation at full speed.
Check function and installation of any sensors used for feedback to drive
Remove power factor correction caps on motor(s), if present
Ensure that input power, motor wiring, and control wiring are separated or in
three separate metallic conduits for high frequency noise isolation
Check for broken or damaged wires and loose connections
Check that control wiring is isolated from power and motor wiring for noise
immunity
Check the voltage source of the signals, if necessary
The use of shielded cable or twisted pair is recommended. Ensure that the
shield is terminated correctly.
Measure that top and bottom clearance is adequate to ensure proper air flow
for cooling
Check for proper installation regarding electromagnetic compatibility
See equipment label for the maximum ambient operating temperature limits
Humidity levels must be 5-95% non-condensing
Check for proper fusing or circuit breakers
Check that all fuses are inserted firmly and in operational condition and that all
circuit breakers are in the open position
The unit requires a ground wire from its chassis to the building ground
Check for good ground connections that are tight and free of oxidation
Grounding to conduit or mounting the back panel to a metal surface is not a
suitable ground
Check for loose connections
Check that motor and mains are in separate conduit or separated screened
cables
Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion
Ensure that all switch and disconnect settings are in the proper position
Check that the unit is mounted solidly or that shock mounts are used, as
necessary
Look for any unusual amount of vibration the unit may be subjected to
Table 3.1 Start Up Check List
20
Start Up and Functional Tes... AF-600 FP Operating Instructions
3
3.2 Applying Power to the Drive
WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when connected to AC mains. Installation, start-up and maintenance should be performed by qualified personnel only. Failure to perform installation, start-up and maintenance by qualified personnel could result in death or serious injury.
WARNING
UNINTENDED START!
When drive is connected to AC mains, the motor may start at any time. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when the drive is connected to AC mains could result in death, serious injury, equipment, or property damage.
1. Confirm input voltage is balanced within 3%. If not, correct input voltage imbalance before proceeding. Repeat procedure after voltage correction.
2. Ensure optional equipment wiring, if present, matches installation application.
3. Ensure that all operator devices are in the OFF position. Panel doors closed or cover mounted.
4. Apply power to the unit. DO NOT start the drive at this time. For units with a disconnect switch, turn to the ON position to apply power to the drive.
3.3 Basic Operational Programming
Drives require basic operational programming prior to running for best performance. Basic operational programming requires entering motor-nameplate data for the motor being operated and the minimum and maximum motor speeds. Enter data in accordance with the following procedure. Parameter settings recommended are intended for start up and checkout purposes. Application settings may vary. See 4 User Interface for detailed instructions on entering data through the keypad.
Enter data with power ON, but prior to operating the drive.
1. Press [Quick Menu] on the keypad.
3. Use the navigation keys to scroll to Quick Start and press [OK].
4. Select language and press [OK]. Then enter the motor data in parameters P-02, P-03, P-06, P-07, F-04 and F-05. The information can be found on the motor nameplate. The entire quick menu is shown in 5.5.1 Quick Menu Structure
P-07 Motor Power [kW] or P-02 Motor Power [HP]
F-05 Motor Rated Voltage
F-04 Base Frequency
P-03 Motor Current
P-06 Base Speed
5. F-07 Accel Time 1 is recommended as 60 seconds for fans or 10 seconds for pumps.
6. F-08 Decel Time 1 is recommended as 60 seconds for fans or 10 seconds for pumps.
7. For F-10 enter Elec OL Trip 1 for Class 20 overload protection. For further information, please see 2.4.1 Requirements
8. For F-16 Motor Speed Low Limit [Hz] enter the application requirements. If these values are unknown at this time, the following values are recommended. These values will ensure initial drive operation. However, take any precautions necessary to prevent equipment damage. Make sure that the recommended values are safe to use for functional testing before starting the equipment.
Fan = 20Hz
Pump = 20Hz
Compressor = 30Hz
9. In F-15 Motor Speed High Limit [Hz] enter the motor frequency from F-04 Base Frequency.
This concludes the quick set-up procedure. Press [Status] to return to the operational display.
In P-04 Auto Tune select Reduced Auto Tune or Full Auto Tune and follow on-screen instructions. See 3.4 Auto Tune
3.4 Auto Tune
Auto tune is a test procedure that measures the electrical characteristics of the motor to optimize compatibility between the drive and the motor.
The drive builds a mathematical model of the
motor for regulating output motor current. The procedure also tests the input phase balance of electrical power. It compares the motor character-
3
21
Start Up and Functional Tes... AF-600 FP Operating Instructions
3
istics with the data entered in P-02, P-03, P-06, P-07, F-04 and F-05.
It does not cause the motor to run or harm to
the motor
Some motors may be unable to run the complete
version of the test. In that case, select Reduced
Auto Tune
If an output filter is connected to the motor,
select Reduced Auto Tune
If warnings or alarms occur, see 8 Warnings and
Alarms
Run this procedure on a cold motor for best
results
3.5 Check Motor Rotation
Prior to running the drive, check the motor rotation. The motor will run briefly at 5Hz or the minimum frequency set in F-16 Motor Speed Low Limit [Hz].
1. Press [Main Menu] twice on the keypad.
2. Enter Parameter Data Set and scroll to P-## Motor Data and press [OK] to enter.
3. Scroll to P-08 Motor Rotation Check.
4. Press [OK].
5. Scroll to Enable.
The following text will appear: Note! Motor may run in wrong direction.
6. Press [OK].
7. Follow the on-screen instructions.
To change the direction of rotation, remove power to the drive and wait for power to discharge. Reverse the connection of any two of the three motor cables on the motor or drive side of the connection.
NOTE
The hand key on the keypad provides a local start command to the drive. The OFF key provides the stop function. When operating in local mode, the up and down arrows on the keypad increase and decrease the speed output of the drive. The left and right arrow keys move the display cursor in the numeric display.
1. Press [Hand].
2.
Accelerate the drive by pressing [ Moving the cursor left of the decimal point provides quicker input changes.
3. Note any acceleration problems.
4. Press [OFF].
5. Note any deceleration problems.
If acceleration problems were encountered
If warnings or alarms occur, see 8 Warnings and
Alarms
Check that motor data is entered correctly
Increase the accel time in F-07 Accel Time 1
Increase current limit in F-43 Current Limit
Increase torque limit in F-40 Torque Limiter
(Driving)
If deceleration problems were encountered
If warnings or alarms occur, see 8 Warnings and
Alarms
Check that motor data is entered correctly
Increase the decel time in F-08 Decel Time 1
See 8.4 Warning and Alarm Definitions for resetting the drive after a trip.
] to full speed.
3.6 Local-control Test
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached equipment is ready for start. It is the responsibility of the user to ensure safe operation under any operational condition. Failure to ensure that the motor, system, and any attached equipment is ready for start could result in personal injury or equipment damage.
22
NOTE
3.1 Pre-start through 3.6 Local-control Test in this chapter concludes the procedures for applying power to the drive, basic programming, set-up, and functional testing.
Start Up and Functional Tes... AF-600 FP Operating Instructions
3
3.7 System Start Up
The procedure in this section requires user-wiring and application programming to be completed. is intended to help with this task. Other aids to application set-up are listed in 1.2 Additional Resources. The following procedure is recommended after application set-up by the user is completed.
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached equipment is ready for start. It is the responsibility of the user to ensure safe operation under any operational condition. Failure to ensure that the motor, system, and any attached equipment is ready for start could result in personal injury or equipment damage.
1. Press [Auto].
2. Ensure that external control functions are properly wired to the drive and all programming completed.
3. Apply an external run command.
4. Adjust the speed reference throughout the speed range.
5. Remove the external run command.
6. Note any problems.
If warnings or alarms occur, see 8 Warnings and Alarms.
3
23
User Interface AF-600 FP Operating Instructions
4 User Interface
4.1 Keypad
4
The keypad is the combined display and keys on the front of the unit. The keypad is the user interface to the frequency converter.
The keypad has several user functions.
Start, stop, and control speed when in local
control
Display operational data, status, warnings and
cautions
Programming frequency converter functions
Manually reset the frequency converter after a
fault when auto-reset is inactive
NOTE
The display contrast can be adjusted by pressing [STATUS] and the up/ down key.
4.1.1 Keypad Layout
The keypad is divided into four functional groups (see Illustration 4.1).
24
Illustration 4.1 Keypad
a. Display area.
b. Display menu keys for changing the display to
show status options, programming, or error message history.
c. Navigation keys for programming functions,
moving the display cursor, and speed control in local operation. Also included are the status indicator lights.
d. Operational mode keys and reset.
User Interface AF-600 FP Operating Instructions
4
4.1.2 Setting Keypad Display Values
The display area is activated when the frequency converter receives power from mains voltage, a DC bus terminal, or an external 24V supply.
The information displayed on the keypad can be customized for user application.
Each display readout has a parameter associated
with it.
Options are selected in the menu Keypad Set-up.
Display 2 has an alternate larger display option.
The frequency converter status at the bottom line
of the display is generated automatically and is not selectable. See 7 Status Messages for definitions and details.
Display Parameter number Default setting
1.1 K-20 Motor RPMs
1.2 K-21 Motor current
1.3 K-22 Motor power (kW)
2 K-23 Motor frequency
3 K-24 Reference in percent
4.1.3 Display Menu Keys
Menu keys are used for menu access for parameter set-up, toggling through status display modes during normal operation, and viewing fault log data.
Key Function
Status Press to show operational information.
In Auto mode, press and hold to toggle
between status read-out displays
Press repeatedly to scroll through each
status display
Press and hold [Status] plus [▲] or [▼] to
adjust the display brightness
The symbol in the upper right corner of the
display shows the direction of motor
rotation and which set-up is active. This is
not programmable.
Quick Menu Allows access to programming parameters for
initial set up instructions and many detailed
application instructions.
Press to access Quick Start for sequenced
instructions to program the basic frequency
controller set up
Press to access Fan Macros, Pump Macros,
Compressor Macros, or Closed Loop for
sequenced instructions to program
applications
Press to access Trending for realtime
logging on keypad display.
Press to access Parameter Data Check for
changes in parameter data set.
Follow the sequence of parameters as
presented for the function set up
Main Menu Allows access to all programming parameters.
Press twice to access top-level index
Press once to return to the last location
accessed
Press and hold to enter a parameter
number for direct access to that parameter
Alarm Log Displays a list of current warnings, the last 10
alarms, and the maintenance log.
For details about the drive before it entered
the alarm mode, select the alarm number
using the navigation keys and press [OK].
4
25
4
User Interface AF-600 FP Operating Instructions
4.1.4 Navigation Keys
Navigation keys are used for programming functions and moving the display cursor. The navigation keys also provide speed control in local (hand) operation. Three drive status indicator lights are also located in this area.
Key Function
Hand Press to start the drive in local control.
Off Stops the motor but does not remove power to
Auto Puts the system in remote operational mode.
Reset Resets the drive manually after a fault has been
Use the navigation keys to control drive
speed
An external stop signal by control input or
serial communication overrides the local hand
the drive.
Responds to an external start command by
control terminals or serial communication
Speed reference is from an external source
cleared.
Key Function
Back Reverts to the previous step or list in the menu
structure.
Cancel Cancels the last change or command as long as
the display mode has not changed.
Info Press for a definition of the function being
displayed.
Navigation
Keys
OK Use to access parameter groups or to enable a
Light Indicator Function
Green ON The ON light activates when the
Yellow WARN When warning conditions are met,
Red ALARM A fault condition causes the red
Use the four navigation arrows to move between
items in the menu.
choice.
drive receives power from mains
voltage, a DC bus terminal, or an
external 24 V supply.
the yellow WARN light comes on
and text appears in the display
area identifying the problem.
alarm light to flash and an alarm
text is displayed.
4.1.5 Operation Keys
Operation keys are found at the bottom of the keypad.
4.2 Back Up and Copying Parameter Settings
Programming data is stored internally in the drive.
The data can be up loaded into the keypad
memory as a storage back up
Once stored in the keypad, the data can be
downloaded back into the drive
Or downloaded into other frequency converters
by connecting the keypad into those units and downloading the stored settings. (This is a quick way to program multiple units with the same settings.)
Initialisation of the drive to restore factory default
settings does not change data stored in the keypad memory
WARNING
UNINTENDED START!
When drive is connected to AC mains, the motor may start at any time. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when the drive is connected to AC mains could result in death, serious injury, equipment, or property damage.
26
User Interface AF-600 FP Operating Instructions
4
4.2.1 Uploading Data to the keypad
1. Press [OFF] to stop the motor before uploading or downloading data.
2.
Go to K-50 Keypad Copy.
3. Press [OK].
4. Select All to keypad.
5. Press [OK]. A progress bar shows the uploading process.
6. Press [Hand] or [Auto] to return to normal operation.
4.2.2 Downloading Data from the keypad
1. Press [OFF] to stop the motor before uploading or downloading data.
2. Go to K-50 Keypad Copy.
3. Press [OK].
4. Select All from keypad.
5. Press [OK]. A progress bar shows the downloading process.
6. Press [Hand] or [Auto] to return to normal operation.
4.3.1 Recommended Initialisation
1. Press [Main Menu] twice to access parameters.
2. Scroll to H-03 Restore Factory Settings.
3. Press [OK].
4.
Scroll to Initialisation.
5. Press [OK].
6. Remove power to the unit and wait for the display to turn off.
7. Apply power to the unit.
Default parameter settings are restored during start up. This may take slightly longer than normal.
8. Alarm 80 is displayed.
9. Press [Reset] to return to operation mode.
4.3.2 Manual Initialisation
1. Remove power to the unit and wait for the display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at the same time and apply power to the unit.
Factory default parameter settings are restored during start up. This may take slightly longer than normal.
4
4.3 Restoring Default Settings
CAUTION
Initialisation restores the unit to factory default settings. Any programming, motor data, localization, and monitoring records will be lost. Uploading data to the keypad provides a backup prior to initialisation.
Restoring the drive parameter settings back to default values is done by initialisation of the frequency converter. Initialisation can be through H-03 Restore Factory Settings or manually.
Initialisation using H-03 Restore Factory Settings
does not change drive data such as operating hours, serial communication selections, personal menu settings, fault log, alarm log, and other monitoring functions
Using H-03 Restore Factory Settings is generally
recommended
Manual initialisation erases all motor,
programming, localization, and monitoring data and restores factory default settings
Manual initialisation does not reset the following drive information
ID-00 Operating Hours
ID-03 Power Up's
ID-04 Over Temp's
ID-05 Over Volt's
27
About Drive Programming AF-600 FP Operating Instructions
5About Drive Programming
5.1 Introduction
5
The drive is programmed for its application functions using parameters. Parameter are accessed by pressing either [Quick Menu] or [Main Menu] on the keypad. (See 4 User Interface for details on using the keypad function keys.) Parameters may also be accessed through a PC using the DCT-10 (see 5.6 Remote Programming with ).
The quick menu is intended for initial start up and detailed instructions for common drive applications . Step-by-step instructions are provided. These instructions enable the user to walk through the parameters used for programming applications in their proper sequence. Data entered in a parameter can change the options available in the parameters following that entry. The quick menu presents easy guidelines for getting most systems up and running.
The main menu accesses all parameters and allows for advanced drive applications.
5.2 Programming Example
Here is an example for programming the drive for a common application in open loop using the quick menu.
1. Parameter Data Set
3.
Fundamental Parameters
This procedure programs the drive to receive a
0-10V DC analog control signal on input terminal 53
The drive will respond by providing 20-50Hz
output to the motor proportional to the input signal (0-10V DC = 20-50Hz)
This is a common pump or fan application.
Press [Main Menu] twice and select the following parameters using the navigation keys to scroll to the titles and press [OK] after each action.
4. Extended References
28
About Drive Programming AF-600 FP Operating Instructions
5
5. F-52 Minimum Reference. Set minimum internal drive reference to 0Hz. (This sets the minimum drive speed at 0Hz.)
6. F-53 Maximum Reference. Set maximum internal drive reference to 60Hz. (This sets the maximum drive speed at 60Hz. Note that 50/60Hz is a regional variation.)
8. Analog Input 53
9. AN-10 Terminal 53 Low Voltage. Set minimum external voltage reference on Terminal 53 at 0V. (This sets the minimum input signal at 0V.)
5
7. Press [Back] twice to return to Parameter Data Set and scroll to Analog In/Out
10. AN-11 Terminal 53 High Voltage. Set maximum external voltage reference on Terminal 53 at 10V. (This sets the maximum input signal at 10V.)
29
5
About Drive Programming AF-600 FP Operating Instructions
11. AN-14 Terminal 53 Low Ref./Feedb. Value. Set minimum speed reference on Terminal 53 at 20Hz. (This tells the drive that the minimum voltage received on Terminal 53 (0V) equals 20Hz output.)
Illustration 5.1 Wiring Example for External Device Providing
0-10V Control Signal
5.3 Control Terminal Programming
12. AN-15 Terminal 53 High Ref./Feedb. Value. Set maximum speed reference on Terminal 53 at 50Hz. (This tells the drive that the maximum voltage received on Terminal 53 (10V) equals 50Hz output.)
Examples
Control terminals can be programmed.
See Table 2.2 for control terminal parameter number and default setting. (Default setting can change based on the selection in K-03 Regional Settings.)
With an external device providing a 0-10V control signal connected to drive terminal 53, the system is now ready for operation. Note that the scroll bar on the right in the last illustration of the display is at the bottom, indicating the procedure is complete.
Illustration 5.1 shows the wiring connections used to enable this set up.
The following example shows accessing Terminal 18 to see the default setting.
1. Press [Main Menu] twice, scroll to Parameter Data
Each terminal has specified functions it is capable of performing
Parameters associated with the terminal enable the function
For proper drive functioning, the control terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
Set and press [OK].
30
About Drive Programming AF-600 FP Operating Instructions
5
2. Scroll to parameter group E-## Digital In/Out and press [OK].
3. Scroll to parameter group E-0# Digital Inputs and press [OK]
4. Scroll to E-01 Terminal 18 Digital Input. Press [OK] to access function choices. The default setting Start is shown.
5.4 International/North American Default Parameter Settings
Parameter International
Default Parameter
North American
Default Parameter
Value
F-04 Base
Frequency
F-53 Maximum
Reference
F-54 Reference
Function
F-17 Motor Speed
High Limit [RPM]
See Note 3
F-15 Motor Speed
High Limit [Hz]
See Note 4
F-03 Max Output
Frequency 1
H-73 Warning
Speed High
E-03 Terminal 27
Digital Input
E-24 Function Relay Alarm No alarm
AN-15 Terminal 53
High Ref./Feedb.
Value
AN-50 Terminal 42
Output
H-04 Auto-Reset
(Times)
AP-85 Speed at
Design Point [RPM]
See Note 3
AP-86 Speed at
Design Point [Hz]
FB-04 Fire Mode
Max Reference
50Hz 60Hz
50Hz 60Hz
Sum External/Preset
1500RPM 1800RPM
50Hz 60Hz
100Hz 120Hz
1500RPM 1800RPM
Coast inverse External interlock
50 60
Speed 0 - HighLim Speed 4-20mA
Manual reset Infinite auto reset
1500RPM 1800RPM
50Hz 60Hz
50Hz 60Hz
Value
5
Setting K-03 Regional Settings to [0]International or [1] North America changes the default settings for some parameters. Table 5.1 lists those parameters that are effected.
Parameter International
Default Parameter
Value
K-03 Regional
Settings
K-71 Date Format DD-MM-YYYY MM/DD/YYYY
K-72 Time Format 24h 12h
P-07 Motor Power
[kW]
P-02 Motor Power
[HP]
F-05 Motor Rated
Voltage
International North America
See Note 1 See Note 1
See Note 2 See Note 2
230V/400V/575V 208V/460V/575V
North American
Default Parameter
Value
Table 5.1 International/North American Default Parameter Settings
Note 1: P-07 Motor Power [kW] is only visible when K-03 Regional Settings is set to [0] International. Note 2: P-02 Motor Power [HP], is only visible when K-03 Regional Settings is set to [1] North America. Note 3: This parameter is only visible when K-02 Motor Speed Unit is set to [0] RPM. Note 4: This parameter is only visible when K-02 Motor Speed Unit is set to [1] Hz. Changes made to default settings are stored and available for viewing in the quick menu along with any programming entered into parameters.
5.4.1 Parameter Data Check
1. Press [Quick Menu].
2. Scroll to Q5 Changes Made and press [OK].
31
5
About Drive Programming AF-600 FP Operating Instructions
5.5.1 Quick Menu Structure
Quick Start
K-01 Language
K-02 Motor Speed Unit
P-02 Motor Power [HP]
P-07 Motor Power [kW]
F-05 Motor Rated Voltage
P-03 Motor Current
F-04 Base Frequency
P-06 Base Speed
F-01 Frequency Setting 1
3. Select Q5-2 Since Factory Setting to view all programming changes or Q5-1 Last 10 Changes for the most recent.
5.5 Parameter Menu Structure
Establishing the correct programming for applications often requires setting functions in several related parameters. These parameter settings provide the drive with system details for the drive to operate properly. System details may include such things as input and output signal types, programming terminals, minimum and maximum signal ranges, custom displays, automatic restart, and other features.
F-02 Operation Method
F-07 Accel Time 1
F-08 Decel Time 1
F-10 Electronic Overload
F-15 Motor Speed High Limit [Hz]
F-16 Motor Speed Low Limit [Hz]
H-08 Reverse Lock
P-04 Auto Tune
See the keypad display to view detailed
parameter programming and setting options
Press [Info] in any menu location to view
additional details for that function
Press and hold [Main Menu] to enter a parameter
number for direct access to that parameter
Details for common application set ups are
provided in 6 Application Set-Up Examples
32
About Drive Programming AF-600 FP Operating Instructions
5
5.5.2 Main Menu Structure
5
K-8# Days and Date/Time
F-17 Motor Speed High Limit
[RPM] F-92 Power Restore E-52 Terminal 29 Mode
F-18 Motor Speed Low Limit
F-15 Motor Speed High Limit
[Hz] F-90 Step Size E-5# I/O Mode / Add On I/O
F-16 Motor Speed Low Limit
K-83 Additional Non-Working
Readout F-2# Fundamental 2 E-## Digital In/Out
K-0# Keypad Basic Settings K-38 Display Text 2 K-81 Working Days F-24 Holding Time E-0# Digital Inputs
K-## Keypad Set-Up K-37 Display Text 1
Days F-27 Motor Tone Random E-01 Terminal 18 Digital Input
K-61 Access to Main Menu w/o
Password F-08 Decel Time 1 F-53 Maximum Reference E-20 Terminal 27 Digital Output
K-66 Access to Quick Menu w/o
Password F-10 Electronic Overload F-6# References E-24 Function Relay
K-23 Display Line 2 Large K-70 Date and Time F-12 Motor Thermistor Input F-9# Digital Pot.Meter E-27 Off Delay, Relay
K-14 Readout: Edit Set-ups / Channel K-60 Main Menu Password F-07 Accel Time 1 F-52 Minimum Reference E-2# Digital Outputs
K-2# Keypad Display
K-11 Edit Set-up K-50 Keypad Copy F-03 Max Output Frequency 1 F-41 Torque Limiter (Braking) E-1# Additional Accel Decel Ramps
K-12 This Set-up Linked to K-51 Set-up Copy F-04 Base Frequency F-43 Current Limit E-10 Accel Time 2
K-03 Regional Settings K-40 [Hand] Button on Keypad K-89 Date and Time Readout F-3# Fundamental 3 E-02 Terminal 19 Digital Input
K-01 Language K-39 Display Text 3 K-82 Additional Working Days F-26 Motor Noise (Carrier Freq) E-00 Digital I/O Mode
K-04 Operating State at Power-up K-41 [Off] Button on Keypad F-## Fundamental Parameters F-37 Adv. Switching Pattern E-03 Terminal 27 Digital Input
K-02 Motor Speed Unit K-4# Keypad Buttons
K-10 Active Set-up K-5# Copy/Save F-02 Operation Method F-40 Torque Limiter (Driving) E-06 Terminal 33 Digital Input
K-05 Local Mode Unit K-42 [Auto] Button on Keypad F-0# Fundamental 0 F-38 Overmodulation E-04 Terminal 29 Digital Input
K-1# Keypad Set-Up Operations K-43 [Reset] Button on Keypad F-01 Frequency Setting 1 F-4# Fundamental 4 E-05 Terminal 32 Digital Input
K-13 Readout: Linked Set-ups K-6# Password Protection F-05 Motor Rated Voltage F-5# Extended References E-11 Decel Time 2
K-20 Display Line 1.1 Small K-65 Quick Menu Password F-1# Fundamental 1 F-54 Reference Function E-21 Terminal 29 Digital Output
K-22 Display Line 1.3 Small K-7# Clock Settings F-11 Motor External Fan F-64 Preset Relative Reference E-26 On Delay, Relay
K-21 Display Line 1.2 Small
[Hz] F-91 Accel/Decel Time E-51 Terminal 27 Mode
K-24 Display Line 3 Large K-71 Date Format
K-25 Quick Start K-72 Time Format
[RPM] F-93 Maximum Limit E-53 Terminal X30/2 Digital Input
K-30 Unit for Custom Readout K-76 DST/Summertime Start
K-31 Min Value of Custom Readout K-77 DST/Summertime End F-94 Minimum Limit E-54 Terminal X30/3 Digital Input
K-3# Keypad Custom Readout K-74 DST/Summertime
K-32 Max Value of Custom Readout K-79 Clock Fault F-95 Accel/Decel Ramp Delay E-55 Terminal X30/4 Digital Input
33
5
About Drive Programming AF-600 FP Operating Instructions
AN-24 Terminal 54 Low Ref./Feedb.
Value
AN-25 Terminal 54 High Ref./Feedb.
AN-14 Terminal 53 Low Ref./Feedb.
Value
H-65 Resonance Dampening Time
Constant
AN-15 Terminal 53 High Ref./Feedb.
Value
Value
H-81 Min Speed for Function at Stop
AN-34 Term. X30/11 Low Ref./Feedb.
Value
AN-35 Term. X30/11 High Ref./Feedb.
Value
AN-36 Term. X30/11 Filter Time
Constant
H-82 Min Speed for Function at Stop
[Hz] AN-30 Terminal X30/11 Low Voltage
[RPM] AN-3# Analog Input X30/11
AN-02 Fire Mode Live Zero Timeout
Function AN-37 Term. X30/11 Live Zero
34
E-9# Bus Controlled P-0# Motor Data H-4# Advanced Settings AN-## Analog In/Out AN-31 Terminal X30/11 High Voltage
E-90 Digital & Relay Bus Control P-02 Motor Power [HP] H-40 Configuration Mode AN-0# Analog I/O Mode
E-93 Pulse Out #27 Bus Control P-03 Motor Current H-43 Torque Characteristics AN-00 Live Zero Timeout Time
E-94 Pulse Out #27 Timeout Preset P-04 Auto Tune H-48 Clockwise Direction AN-01 Live Zero Timeout Function
E-67 Term. 33 Low Ref./Feedb. Value C-2# Jog Setup H-0# High Perf Operations H-73 Warning Speed High AN-20 Terminal 54 Low Voltage
E-68 Term. 33 High Ref./Feedb. Value C-20 Jog Speed [Hz] H-03 Restore Factory Settings H-74 Warning Reference Low AN-21 Terminal 54 High Voltage
E-69 Pulse Filter Time Constant #33 C-21 Jog Speed [RPM] H-04 Auto-Reset (Times) H-75 Warning Reference High AN-22 Terminal 54 Low Current
E-7# Pulse Output C-22 Jog Accel/Decel Time H-05 Auto-Reset (Reset Interval) H-76 Warning Feedback Low AN-23 Terminal 54 High Current
E-70 Terminal 27 Pulse Output Variable C-3# Frequency Setting 2 and 3 H-06 Fan Operation H-77 Warning Feedback High
E-71 Pulse Output Max Freq #27 C-30 Frequency Command 2 H-08 Reverse Lock H-78 Missing Motor Phase Function
E-72 Terminal 29 Pulse Output Variable C-34 Frequency Command 3 H-09 Start Mode H-8# Stop Adjustments AN-26 Terminal 54 Filter Time Constant
E-74 Pulse Output Max Freq #29 C-4# Semi-Auto Jump Freq Set-up H-3# Stop Speed H-80 Function at Stop AN-27 Terminal 54 Live Zero
E-75 Terminal X30/6 Pulse Output
Variable C-40 Semi-Auto Jump Freq Set-up H-36 Trip Speed Low [RPM]
E-61 Term. 29 High Frequency C-0# Frequency Control Functions P-3# Adv. Motor Data H-64 Resonance Dampening AN-13 Terminal 53 High Current
E-62 Term. 29 Low Ref./Feedb. Value C-01 Jump Frequency From [Hz] P-30 Stator Resistance (Rs)
E-63 Term. 29 High Ref./Feedb. Value C-02 Jump Speed From [RPM] P-31 Rotor Resistance (Rr) H-7# Adjustable Warnings
E-64 Pulse Filter Time Constant #29 C-03 Jump Speed To [RPM] P-35 Main Reactance (Xh) H-70 Warning Current Low AN-16 Terminal 53 Filter Time Constant
E-65 Term. 33 Low Frequency C-04 Jump Frequency To [Hz] P-36 Iron Loss Resistance (Rfe) H-71 Warning Current High AN-17 Terminal 53 Live Zero
E-56 Term X30/6 Digi Out (OPCGPIO) E-96 Pulse Out #29 Timeout Preset P-07 Motor Power [kW] H-5# Load Indep. Setting AN-1# Analog Input 53
E-57 Term X30/7 Digi Out (OPCGPIO) E-97 Pulse Out #X30/6 Bus Control P-08 Motor Rotation Check H-58 Flystart Test Pulses Current AN-10 Terminal 53 Low Voltage
E-6# Pulse Input E-98 Pulse Out #X30/6 Timeout Preset P-09 Slip Compensation H-59 Flystart Test Pulses Frequency AN-11 Terminal 53 High Voltage
E-60 Term. 29 Low Frequency C-## Frequency Control Functions P-10 Slip Compensation Time Constant H-6# Load Depen. Setting AN-12 Terminal 53 Low Current
E-66 Term. 33 High Frequency C-05 Multi-step Frequency 1 - 8 H-## High Perf Parameters H-72 Warning Speed Low AN-2# Analog Input 54
E-76 Pulse Output Max Freq #X30/6 P-## Motor Data H-37 Trip Speed Low [Hz]
E-95 Pulse Out #29 Bus Control P-06 Base Speed
About Drive Programming AF-600 FP Operating Instructions
5
O-13 Configurable Status Word
STW O-8# Drive Port Diagnostics
AO-14 Term. X42/1 Low Ref./Feedb.
Value
5
SP-59 Actual Number of Inverter
Units O-33 Drive Port Parity O-89 Diagnostics Count
SP-60 Function at Over
Temperature O-35 Minimum Response Delay O-90 Bus Jog 1 Speed
SP-62 Drive Overload Derate
Current O-37 Maximum Inter-Char Delay O-94 Bus Feedback 1
O-04 Control Word Timeout
Function O-50 Coasting Select AO-01 Terminal X42/3 Mode
AN-4# Analog Input X30/12 SP-## Special Functions SP-5# Environment
AN-40 Terminal X30/12 Low Voltage SP-1# Line On/Off SP-50 RFI Filter O-3# Drive Port Settings O-80 Bus Message Count
AN-41 Terminal X30/12 High Voltage SP-10 Line failure SP-51 DC Link Compensation O-30 Protocol O-81 Bus Error Count
AN-44 Term. X30/12 Low Ref./Feedb.
Value SP-11 Line Voltage at Input Fault SP-53 Fan Monitor O-31 Address O-82 Slave Messages Rcvd
AN-45 Term. X30/12 High Ref./Feedb.
Value SP-12 Function at Line Imbalance SP-55 Output Filter O-32 Drive Port Baud Rate O-83 Slave Error Count
AN-46 Term. X30/12 Filter Time Constant SP-2# Reset Functions
AN-47 Term. X30/12 Live Zero SP-23 Typecode Setting SP-6# Automatic Derate O-34 Estimated cycle time O-9# Bus Jog / Feedback
AN-5# Analog Output 42 SP-25 Trip Delay at Torque Limit
AN-50 Terminal 42 Output SP-26 Trip Delay at Drive Fault SP-61 Function at Drive Overload O-36 Maximum Response Delay O-91 Bus Jog 2 Speed
AN-51 Terminal 42 Output Min Scale SP-28 Production Settings
AN-52 Terminal 42 Output Max Scale SP-29 Service Code O-## Options / Comms O-4# Drive MC protocol set O-95 Bus Feedback 2
AN-53 Terminal 42 Output Bus Control SP-3# Current Limit Ctrl. O-0#General Settings O-40 Telegram Selection O-96 Bus Feedback 3
AN-54 Terminal 42 Output Timeout
Preset SP-30 Current Lim Ctrl, Proportional Gain O-01 Control Site O-42 PCD write configuration AO-## Analog I/O Option
AN-6# Analog Output X30/8 SP-31 Current Lim Ctrl, Integration Time O-02 Control Word Source O-43 PCD read configuration AO-0# Analog I/O Mode
AN-60 Terminal X30/8 Output SP-32 Current Lim Ctrl, Filter Time O-03 Control Word Timeout Time O-5# Digital/Bus AO-00 Terminal X42/1 Mode
AN-61 Terminal X30/8 Min. Scale SP-4# Energy Savings
AN-62 Terminal X30/8 Max. Scale SP-40 VT Level O-05 End-of-Timeout Function O-52 DC Brake Select AO-02 Terminal X42/5 Mode
AN-63 Terminal X30/8 Output Bus
Control SP-41 Energy Savings Min. Magnetization O-06 Reset Control Word Timeout O-53 Start Select AO-1# Analog Input X42/1
AN-64 Terminal X30/8 Output Timeout
Preset SP-42 Energy Savings Min. Frequency O-07 Diagnosis Trigger O-54 Reversing Select AO-10 Terminal X42/1 Low Voltage
SP-43 Motor Cosphi O-1# Control Settings O-55 Set-up Select AO-11 Terminal X42/1 High Voltage
O-10 Control Word Profile O-56 Preset Reference Select
35
5
About Drive Programming AF-600 FP Operating Instructions
EN-89 Transparent Socket
Channel Port DN-01 Baud Rate Select
EN-9# Advanced Ethernet
Services DN-02 MAC ID
EN-94 Broadcast Storm
Protection DN-10 Process Data Type Selection
36
AO-15 Term. X42/1 High Ref./Feedb.
Value AO-6# Analog Out X42/11 PB-94 Changed Parameters (5) EN-33 CIP Revision BN-73 MS/TP Max Info Frames
AO-16 Term. X42/1 Filter Time Constant AO-60 Terminal X42/11 Output EN-## Ethernet EN-34 CIP Product Code BN-74 "I-Am" Service
AO-17 Term. X42/1 Live Zero AO-61 Terminal X42/11 Min. Scale EN-0# IP Settings EN-8# Other Ethernet Services BN-75 Initialization Password
AO-2# Analog Input X42/3 AO-62 Terminal X42/11 Max. Scale EN-00 IP Address Assignment EN-80 FTP Server DN-## DeviceNet Fieldbus
AO-21 Terminal X42/3 High Voltage AO-63 Terminal X42/11 Bus Control EN-01 IP Address EN-81 HTTP Server DN-0# Common Settings
AO-21 Terminal X42/3 High Voltage AO-64 Terminal X42/11 Timeout Preset EN-02 Subnet Mask EN-82 SMTP Service DN-00 DeviceNet Protocol
AO-24 Term. X42/3 Low Ref./Feedb. Value PB-## Profibus EN-03 Default Gateway
AO-25 Term. X42/3 High Ref./Feedb.
Value PB-15 PCD Write Configuration EN-04 DHCP Server
AO-26 Term. X42/3 Filter Time Constant PB-16 PCD Read Configuration EN-05 Lease Expires EN-90 Cable Diagnostic DN-05 Readout Transmit Error Counter
AO-27 Term. X42/3 Live Zero PB-18 Node Address EN-06 Name Servers EN-91 MDI-X DN-06 Readout Receive Error Counter
AO-3# Analog Input X42/5 PB-22 Telegram Selection EN-07 Domain Name EN-92 IGMP Snooping DN-07 Readout Bus Off Counter
AO-30 Terminal X42/5 Low Voltage PB-23 Parameters for Signals EN-08 Host Name EN-93 Cable Error Length DN-1# DeviceNet
AO-31 Terminal X42/5 High Voltage PB-27 Parameter Edit EN-09 Physical Address
AO-34 Term. X42/5 Low Ref./Feedb. Value PB-28 Process Control EN-1# Ethernet Link Parameters EN-95 Broadcast Storm Filter DN-11 Process Data Config Write
AO-35 Term. X42/5 High Ref./Feedb.
Value PB-53 Profibus Warning Word EN-10 Link Status EN-98 Interface Counters DN-12 Process Data Config Read
AO-36 Term. X42/5 Filter Time Constant PB-63 Actual Baud Rate EN-11 Link Duration EN-99 Media Counters DN-13 Warning Parameter
AO-37 Term. X42/5 Live Zero PB-70 Edit Set-up EN-12 Auto Negotiation LN-## LONWORKS DN-14 Net Reference
AO-4# Analog Out X42/7 PB-71 Profibus Save Data Values EN-13 Link Speed LN-0# LonWorks ID DN-15 Net Control
AO-40 Terminal X42/7 Output PB-72 ProfibusDriveReset EN-14 Link Duplex LN-00 Neuron ID DN-2# COS Filters
AO-41 Terminal X42/7 Min. Scale PB-75 DO Identification EN-2# Process Data LN-1# LON Functions DN-20 COS Filter 1
AO-42 Terminal X42/7 Max. Scale PB-80 Defined Parameters (1) EN-20 Control Instance LN-10 Drive Profile DN-21 COS Filter 2
AO-43 Terminal X42/7 Bus Control PB-81 Defined Parameters (2) EN-21 Process Data Config Write LN-15 LON Warning Word DN-22 COS Filter 3
AO-44 Terminal X42/7 Timeout Preset PB-82 Defined Parameters (3) EN-22 Process Data Config Read LN-17 XIF Revision DN-23 COS Filter 4
AO-5# Analog Out X42/9 PB-83 Defined Parameters (4) EN-28 Store Data Values LN-18 LonWorks Revision DN-3# Parameter Access
AO-50 Terminal X42/9 Output PB-84 Defined Parameters (5) EN-29 Store Always LN-2# LON Param. Access DN-30 Array Index
AO-53 Terminal X42/9 Bus Control PB-92 Changed Parameters (3) EN-31 Net Reference BN-70 BACnet Device Instance DN-33 Store Always
AO-52 Terminal X42/9 Max. Scale PB-91 Changed Parameters (2) EN-30 Warning Parameter BN-## BACnet DN-32 Devicenet Revision
AO-54 Terminal X42/9 Timeout Preset PB-93 Changed Parameters (4) EN-32 Net Control BN-72 MS/TP Max Masters DN-34 DeviceNet Product Code
AO-51 Terminal X42/9 Min. Scale PB-90 Changed Parameters (1) EN-3# EtherNet/IP LN-21 Store Data Values DN-31 Store Data Values
About Drive Programming AF-600 FP Operating Instructions
5
LG-03 Maintenance Log: Date and
Time
DR-61 Terminal 53 Switch
Setting LG-## Logs & I/O Opt Status
DR-63 Terminal 54 Switch
Setting LG-00 Maintenance Log: Item
5
ID-30 Alarm Log: Error Code DR-02 Reference [%] DR-52 Feedback [Unit] DR-86 Drive Port REF 1 AP-20 Low Power Auto Set-up
ID-31 Alarm Log: Value DR-03 Status Word DR-53 Digi Pot Reference DR-9# Diagnosis Readouts AP-21 Low Power Detection
ID-32 Alarm Log: Time DR-05 Main Actual Value [%] DR-54 Feedback 1 [Unit] DR-90 Alarm Word AP-22 Low Speed Detection
ID-33 Alarm Log: Date and Time DR-09 Custom Readout DR-55 Feedback 2 [Unit] DR-91 Alarm Word 2 AP-23 No-Flow Function
ID-4# Drive Identification DR-1# Motor Status DR-56 Feedback 3 [Unit] DR-92 Warning Word AP-24 No-Flow Delay
ID-40 Drive Type DR-10 Power [kW] DR-58 PID Output [%] DR-93 Warning Word 2 AP-26 Dry Pump Function
ID-20 Historic Log: Event ID-93 Modified Parameters DR-40 Trending Buffer Full DR-8# Fieldbus & Drive Port LG-35 Analog Out X42/11 [V]
ID-21 Historic Log: Value DR-## Data Readouts DR-43 Timed Actions Status DR-80 Fieldbus CTW 1 AP-## HVAC Appl. Param.
ID-22 Historic Log: Time DR-0# General Status DR-49 Current Fault Source DR-82 Fieldbus REF 1 AP-0# Miscellaneous
ID-11 Trending Interval ID-61 Option SW Version DR-35 Drive Thermal DR-72 Counter A LG-30 Analog Input X42/1
ID-## Drive Information ID-42 Voltage DR-12 Motor Voltage DR-6# Inputs & Outputs DR-95 Ext. Status Word 2
ID-0# Operating Data ID-43 Software Version DR-13 Frequency DR-60 Digital Input DR-96 Maintenance Word
ID-00 Operating Hours ID-44 GE Model Number DR-14 Motor Current
ID-01 Running Hours ID-45 Actual Typecode String DR-15 Frequency [%] DR-62 Analog Input 53 LG-0# Maintenance Log
ID-02 kWh Counter ID-46 GE Product No. DR-16 Torque [Nm]
ID-03 Power Up's ID-47 GE Power Card Model No DR-17 Speed [RPM] DR-64 Analog Input 54 LG-01 Maintenance Log: Action
ID-04 Over Temp's ID-48 Keypad ID Number DR-18 Motor Thermal DR-65 Analog Output 42 [mA] LG-02 Maintenance Log: Time
ID-05 Over Volt's ID-49 SW ID Control Card DR-22 Torque [%] DR-66 Digital Output [bin]
ID-06 Reset kWh Counter ID-50 SW ID Power Card DR-3# Drive Status DR-67 Freq. Input #29 [Hz] LG-1# Fire Mode Log
ID-07 Reset Running Hours Counter ID-51 Drive Serial Number DR-30 DC Link Voltage DR-68 Freq. Input #33 [Hz] LG-10 Fire Mode Log: Event
ID-08 Number of Starts ID-53 Power Card Serial Number DR-32 Brake Energy /s DR-69 Pulse Output #27 [Hz] LG-11 Fire Mode Log: Time
ID-1# Data Trending Settings ID-6# Option Ident DR-33 Brake Energy /2 min DR-70 Pulse Output #29 [Hz] LG-12 Fire Mode Log: Date and Time
ID-10 Trending Source ID-60 Option Mounted DR-34 Heatsink Temp. DR-71 Relay Output [bin] LG-3# I/O Option Status
ID-12 Trigger Event ID-62 Option Ordering No DR-36 Drive Nominal Current DR-73 Counter B LG-31 Analog Input X42/3
ID-2# Historic Log ID-92 Defined Parameters DR-39 Control Card Temp. DR-77 Analog Out X30/8 [mA] LG-34 Analog Out X42/9 [V]
ID-13 Trending Mode ID-63 Option Serial No DR-37 Drive Max. Current DR-75 Analog In X30/11 LG-32 Analog Input X42/5
ID-14 Samples Before Trigger ID-9# Parameter Info DR-38 Logic Controller State DR-76 Analog In X30/12 LG-33 Analog Out X42/7 [V]
ID-23 Historic Log: Date and Time DR-00 Control Word DR-5# Ref. & Feedb. DR-84 Comm. Option STW AP-00 External Interlock Delay
ID-3# Alarm Log DR-01 Reference [Unit] DR-50 External Reference DR-85 Drive Port CTW 1 AP-2# No-Flow Detection
ID-41 Power Section DR-11 Power [hp] DR-94 Ext. Status Word AP-27 Dry Pump Delay
37
5
About Drive Programming AF-600 FP Operating Instructions
T-14 Maintenance Date and
Time CL-03 Feedback 2 Source
38
AP-3# No-Flow Power Tuning AP-71 Compressor Start Max Speed [Hz] FB-09 Fire Mode Alarm Handling
AP-30 No-Flow Power AP-72 Compressor Start Max Time to Trip FB-1# Drive Bypass T-15 Reset Maintenance Word CL-04 Feedback 2 Conversion
AP-70 Compressor Start Max Speed
AP-42 Wake-up Speed [RPM] AP-87 Pressure at No-Flow Speed T-## Timed Functions T-65 Minimum Bin Value CL-30 Refrigerant
AP-43 Wake-up Speed [Hz] AP-88 Pressure at Rated Speed T-0# Timed Actions T-66 Reset Continuous Bin Data CL-31 User Defined Refrigerant A1
AP-44 Wake-up Ref./FB Difference AP-89 Flow at Design Point T-00 ON Time T-67 Reset Timed Bin Data CL-32 User Defined Refrigerant A2
AP-46 Maximum Boost Time FB-## Fire/Bypass Operation T-02 OFF Time T-80 Power Reference Factor CL-34 Duct 1 Area [m2]
AP-5# End of Curve FB-0# Fire Mode T-03 OFF Action T-81 Energy Cost CL-35 Duct 1 Area [in2]
AP-50 End of Curve Function FB-00 Fire Mode Function T-04 Occurrence T-82 Investment CL-36 Duct 2 Area [m2]
AP-51 End of Curve Delay FB-01 Fire Mode Configuration T-08 Timed Actions Mode T-83 Energy Savings CL-37 Duct 2 Area [in2]
AP-4# Sleep Mode AP-84 Speed at No-Flow [Hz] FB-32 Missing Motor Coefficient 2 T-62 Timed Bin Data CL-22 Setpoint 2
AP-40 Minimum Run Time AP-85 Speed at Design Point [RPM] FB-33 Missing Motor Coefficient 3 T-63 Timed Period Start CL-23 Setpoint 3
AP-31 Power Correction Factor AP-73 Starting Acceleration Time FB-10 Drive Bypass Function T-16 Maintenance Text CL-05 Feedback 2 Source Unit
AP-32 Low Speed [RPM] AP-75 Short Cycle Protection FB-11 Drive Bypass Delay Time T-5# Energy Log CL-06 Feedback 3 Source
AP-33 Low Speed [Hz] AP-76 Interval between Starts FB-20 Locked Rotor Function T-50 Energy Log Resolution CL-07 Feedback 3 Conversion
AP-34 Low Speed Power [kW] AP-77 Minimum Run Time FB-21 Locked Rotor Coefficient 1 T-51 Period Start CL-08 Feedback 3 Source Unit
AP-35 Low Speed Power [HP] AP-8# Flow Compensation FB-22 Locked Rotor Coefficient 2 T-53 Energy Log CL-12 Reference/Feedback Unit
AP-36 High Speed [RPM] AP-80 Flow Compensation FB-23 Locked Rotor Coefficient 3 T-54 Reset Energy Log CL-13 Minimum Reference/Feedb.
AP-38 High Speed Power [kW] AP-82 Work Point Calculation FB-30 Missing Motor Function T-60 Trend Variable CL-20 Feedback Function
AP-39 High Speed Power [HP] AP-83 Speed at No-Flow [RPM] FB-31 Missing Motor Coefficient 1 T-61 Continuous Bin Data CL-21 Setpoint 1
AP-37 High Speed [Hz] AP-81 Square-linear Curve Approximation FB-24 Locked Rotor Coefficient 4 T-6# Trending CL-14 Maximum Reference/Feedb.
AP-41 Minimum Sleep Time AP-86 Speed at Design Point [Hz] FB-34 Missing Motor Coefficient 4 T-64 Timed Period Stop CL-3# Feedback Adv. Conv
AP-45 Setpoint Boost AP-90 Flow at Rated Speed T-01 ON Action T-8# Payback Counter CL-33 User Defined Refrigerant A3
AP-6# Broken Belt Detection FB-02 Fire Mode Unit T-09 Timed Actions Reactivation T-84 Cost Savings CL-38 Air Density Factor [%]
AP-60 Broken Belt Function FB-03 Fire Mode Min Reference T-1# Maintenance CL-## PID Closed Loop CL-7# PID Autotuning
AP-62 Broken Belt Delay FB-05 Fire Mode Preset Reference T-11 Maintenance Action CL-00 Feedback 1 Source CL-71 PID Performance
AP-61 Broken Belt Torque FB-04 Fire Mode Max Reference T-10 Maintenance Item CL-0# Feedback CL-70 Closed Loop Type
AP-7# Compressor FB-06 Fire Mode Reference Source T-12 Maintenance Time Base CL-01 Feedback 1 Conversion CL-72 PID Output Change
[RPM] FB-07 Fire Mode Feedback Source T-13 Maintenance Time Interval CL-02 Feedback 1 Source Unit CL-73 Minimum Feedback Level
About Drive Programming AF-600 FP Operating Instructions
5
5
PC-10 Minimum Run Time
Override PC-80 Pump Status B-01 DC Brake Current
PC-11 Minimum Run Time
Override Value PC-81 Pump Status B-02 DC Braking Time
CL-8# PID Basic Settings XC-24 Ext. 1 Dif. Gain Limit PC-0# System Settings PC-54 Alternation Predefined Time LC-5# States
CL-74 Maximum Feedback Level XC-22 Ext. 1 Integral Time XC-64 Ext. 3 Dif. Gain Limit PC-52 Alternation Time Interval LC-43 Logic Rule Operator 2
CL-81 PID Normal/ Inverse Control XC-3# Ext. CL 2 Ref./Fb. PC-00 Pump Controller PC-55 Alternate if Load < 50% LC-51 Logic Controller Event
CL-79 PID Autotuning XC-23 Ext. 1 Differentation Time PC-## Pump Controller PC-53 Alternation Timer Value LC-44 Logic Rule Boolean 3
CL-82 PID Start Speed [RPM] XC-30 Ext. 2 Ref./Feedback Unit PC-02 Motor Start PC-56 Staging Mode at Alternation LC-52 Logic Controller Action
CL-83 PID Start Speed [Hz] XC-31 Ext. 2 Minimum Reference PC-04 Pump Cycling PC-58 Run Next Pump Delay B-## Braking Functions
CL-84 On Reference Bandwidth XC-32 Ext. 2 Maximum Reference PC-05 Fixed Lead Pump PC-59 Run on Line Delay B-0# DC-Brake
CL-9# PID Controller XC-33 Ext. 2 Reference Source PC-06 Number of Pumps PC-8# Status B-00 DC Hold Current
CL-91 PID Anti Windup XC-34 Ext. 2 Feedback Source
CL-93 PID Proportional Gain XC-35 Ext. 2 Setpoint
CL-94 PID Integral Time XC-37 Ext. 2 Reference [Unit] PC-2# Bandwidth Settings PC-82 Lead Pump B-03 DC Brake Cut In Speed [RPM]
CL-95 PID Differentiation Time XC-38 Ext. 2 Feedback [Unit] PC-20 Staging Bandwidth PC-83 Relay Status B-04 DC Brake Cut In Speed [Hz]
CL-96 PID Diff. Gain Limit XC-39 Ext. 2 Output [%] PC-21 Override Bandwidth PC-84 Pump ON Time B-1# Brake Energy Funct.
XC-## Ext. PID Closed Loop XC-4# Ext. CL 2 PID PC-22 Fixed Speed Bandwidth PC-85 Relay ON Time B-10 Brake Function
XC-0# Ext. CL Autotuning XC-40 Ext. 2 Normal/Inverse Control PC-23 SBW Staging Delay PC-86 Reset Relay Counters B-16 AC brake Max. Current
XC-00 Closed Loop Type XC-41 Ext. 2 Proportional Gain PC-24 SBW Destaging Delay PC-9# Service B-17 Over-voltage Control
XC-01 PID Performance XC-42 Ext. 2 Integral Time PC-25 OBW Time PC-90 Pump Interlock
XC-02 PID Output Change XC-43 Ext. 2 Differentation Time PC-26 Destage At No-Flow PC-91 Manual Alternation
XC-03 Minimum Feedback Level XC-44 Ext. 2 Dif. Gain Limit PC-27 Stage Function LC-## Logic Controller
XC-04 Maximum Feedback Level XC-5# Ext. CL 3 Ref./Fb. PC-28 Stage Function Time LC-0# LC Settings
XC-09 PID Autotuning XC-50 Ext. 3 Ref./Feedback Unit PC-29 Destage Function LC-00 Logic Controller Mode
XC-1# Ext. CL 1 Ref./Fb. XC-51 Ext. 3 Minimum Reference PC-30 Destage Function Time LC-01 Start Event
XC-10 Ext. 1 Ref./Feedback Unit XC-52 Ext. 3 Maximum Reference PC-4# Staging Settings LC-02 Stop Event
XC-11 Ext. 1 Minimum Reference XC-53 Ext. 3 Reference Source PC-40 Decel Ramp Delay LC-03 Reset Logic Controller
XC-12 Ext. 1 Maximum Reference XC-54 Ext. 3 Feedback Source PC-41 Accel Ramp Delay LC-1# Comparators
XC-13 Ext. 1 Reference Source XC-55 Ext. 3 Setpoint PC-42 Staging Threshold LC-10 Comparator Operand
XC-14 Ext. 1 Feedback Source XC-57 Ext. 3 Reference [Unit] PC-43 Destaging Threshold LC-11 Comparator Operator
XC-15 Ext. 1 Setpoint XC-58 Ext. 3 Feedback [Unit] PC-44 Staging Speed [RPM] LC-12 Comparator Value
XC-17 Ext. 1 Reference [Unit] XC-59 Ext. 3 Output [%] PC-45 Staging Speed [Hz] LC-2# Timers
XC-18 Ext. 1 Feedback [Unit] XC-6# Ext. CL 3 PID PC-46 Destaging Speed [RPM] LC-20 Logic Controller Timer
XC-19 Ext. 1 Output [%] XC-60 Ext. 3 Normal/Inverse Control PC-47 Destaging Speed [Hz] LC-4# Logic Rules
XC-2# Ext. CL 1 PID XC-61 Ext. 3 Proportional Gain PC-5# Alternation Settings LC-40 Logic Rule Boolean 1
XC-20 Ext. 1 Normal/Inverse
Control XC-62 Ext. 3 Integral Time PC-50 Lead Pump Alternation LC-41 Logic Rule Operator 1
XC-21 Ext. 1 Proportional Gain XC-63 Ext. 3 Differentation Time PC-51 Alternation Event LC-42 Logic Rule Boolean 2
39
5
About Drive Programming AF-600 FP Operating Instructions
5.6 Remote Programming with DCT-10
GE has a software program available for developing, storing, and transferring drive programming. The DCT-10 allows the user to connect a PC to the drive and perform live programming rather than using the keypad. Also, all drive programming can be done off-line and simply downloaded into drive. Or the entire drive profile can be loaded onto the PC for back up storage or analysis.
The USB connector or RS-485 terminal are available for connecting to the drive.
40
Application Set-Up Examples AF-600 FP Operating Instructions
6
6 Application Set-Up Examples
6.1 Introduction
The examples in this section are intended as a quick reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in K-03 Regional Settings)
Parameters associated with the terminals and
their settings are shown next to the drawings
Where switch settings for analog terminals A53 or
A54 are required, these are also shown
6.2 Application Examples
Parameters
Function Setting
AN-22 Terminal 54
Low Current
AN-23 Terminal 54
High Current
AN-24 Terminal 54
Low Ref./Feedb. Value
AN-25 Terminal 54
High Ref./Feedb. Value
* = Default Value
Notes/comments:
Table 6.1 Analog Current Feedback Transducer
4mA*
20mA*
0*
50*
Parameters
Function Setting
AN-20 Terminal
54 Low Voltage 0.07V*
AN-21 Terminal
54 High Voltage
AN-24 Terminal
54 Low Ref./
Feedb. Value
AN-25 Terminal
54 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Table 6.2 Analog Voltage Feedback Transducer (3-wire)
Parameters
Function Setting
AN-20 Terminal
54 Low Voltage 0.07V*
AN-21 Terminal
54 High Voltage
AN-24 Terminal
54 Low Ref./
Feedb. Value
AN-25 Terminal
54 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
10V*
0*
50*
10V*
0*
50*
6
Table 6.3 Analog Voltage Feedback Transducer (4-wire)
41
Application Set-Up Examples AF-600 FP Operating Instructions
6
Parameters
Function Setting
AN-10 Terminal
53 Low Voltage 0.07V*
AN-11 Terminal
53 High Voltage
AN-14 Terminal
53 Low Ref./
Feedb. Value
AN-15 Terminal
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Table 6.4 Analog Speed Reference (Voltage)
Parameters
Function Setting
AN-12 Terminal
53 Low Current
AN-13 Terminal
53 High Current
AN-14 Terminal
53 Low Ref./
Feedb. Value
AN-15 Terminal
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
10V*
0*
50*
4mA*
20mA*
0*
50*
Parameters
Function Setting
E-01 Terminal 18
Digital Input
E-03 Terminal 27
Digital Input
* = Default Value
Notes/comments:
Table 6.6 Run/Stop Command with External Interlock
Parameters
Function Setting
E-01 Terminal 18
Digital Input
E-03 Terminal 27
Digital Input
* = Default Value
Notes/comments:
[8] Start*
[7] External
Interlock
[8] Start*
[0] No
operation*
Table 6.5 Analog Speed Reference (Current)
42
Table 6.7 Run/Stop Command without External Interlock
Application Set-Up Examples AF-600 FP Operating Instructions
6
Parameters
Table 6.8 External Alarm Reset
Function Setting
E-02 Terminal 19
Digital Input
* = Default Value
Notes/comments:
[1] Reset
Parameters
Function Setting
E-01 Terminal 18
Digital Input
E-02 Terminal 19
Digital Input
E-03 Terminal 27
Digital Input
E-24 Function
Relay
* = Default Value
Notes/comments:
[8] Start*
[52] Run
Permissive
[7] External
Interlock
[167] Start
command
act.
6
Parameters
Function Setting
AN-10 Terminal
53 Low Voltage 0.07V*
AN-11 Terminal
53 High Voltage
AN-14 Terminal
53 Low Ref./
Feedb. Value
AN-15 Terminal
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Table 6.9 Speed Reference (using a manual potentiometer)
10V*
0*
50*.
Table 6.10 Run Permissive
Hand Off Auto (HOA), without the use of the Drive keypad To have a HOA system with an external 0-10V potenti­ometer for the hand reference and a 4-20mA signal for the auto reference, 2 set-ups should be used. In this example set-up 1 is used for the hand mode and set-up 2 for the auto mode. Analog input 53 is used for the hand reference (0-10V potentiometer) and analog input 54 for the auto reference (4-20mA) and digital input 27 for the set-up selector. Please ensure that the analog inputs have the correct dip settings (A-53 [U] and A-54 [I]).
In the upper right corner of the keypad 2 numbers are shown – like 1(1). The number outside the parenthesis is the active set-up and the number inside the parenthesis is the set-up which will be edited. Default will always be 1(1). Make sure you edit set-up 1.
1. Make all the parameter changes you need, that will be common for auto and hand mode, like motor parameters etc.
2. Set par. K-10 Active set-up to [9] Multi Set-up. This parameter change is needed to be able to change set-up from an external source, like a digital input.
3. Set par. K-11 Edit Set-up to [9] Active Set-up. This is recommended because then the active setup
43
Application Set-Up Examples AF-600 FP Operating Instructions
6
will always be the set-up that is edited. If you prefer you can also ignore this and manually control what set-up you want to edit through par. K-11.
4. Set par. E-03 Terminal 27 Digital Input to [23] Set­up select bit 0. When terminal 27 is OFF, set-up 1 (hand) is active, when it is ON, set-up 2 (auto) is active.
5. Set par. F-01 Frequency Setting 1 to Analog input 53 (hand mode).
6. Copy set-up 1 to set-up 2. Set par. K-51 Set up Copy to [2] Copy to set-up 2. Now setup 1 and 2 are identical.
7. If you need to be able to change between hand and auto mode while the motor is running you will have to link the 2 set-ups together. Set par. K-12 This Set-up Linked to to [2] set-up 2.
8. Change to set-up 2 by setting input 27 ON (if par. K-11 is [9]) or by setting par. K-11 Edit Set-up to set-up 2.
9. Set par. F-01 Frequency Setting 1 to Analog input 54 (auto mode). If you want different settings in hand and auto mode, like different accel/decel ramps, speed limits etc. you can now programme them. You just have to make sure you edit the correct set-up. Set-up 1 is Hand mode and set-up 2 is Auto mode.
Parameters
Function Setting
O-30 Protocol Drive*
O-31 Address 1*
O-32 Drive Port
Baud Rate
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
9600*
Parameters
Function Setting
E-01 Terminal 18
Digital Input [8] Start*
E-03 Terminal 27
Digital Input
* = Default Value
Notes/comments:
GE 30mm HOA Cat# (1)
104PSG34B & (3) CR104PXC1
[23[ Set-up
select bit 0
Table 6.12 RS-485 Network Connection (N2, FLN, Modbus RTU, Drive)
CAUTION
Thermistors must use reinforced or double insulation to meet PELV insulation requirements.
Table 6.11 HOA
44
Application Set-Up Examples AF-600 FP Operating Instructions
6
Parameters
Function Setting
F-10 Electronic
Overload
F-12 Motor
Thermistor Input
* = Default Value
Notes/comments:
If only a warning is desired,
F-10 Electronic Overload should
be set to [1] Thermistor warning.
[2]
Thermistor
trip
[1] Analog
input 53
6
Table 6.13 Motor Thermistor
Parameters
Function Setting
E-02 Terminal 19
Digital Input
FB-00 Fire Mode
Function
FB-01 Fire Mode
Configuration
FB-02 Fire Mode
Unit
FB-03 Fire Mode
Min Reference
FB-04 Fire Mode
Max Reference
FB-05 Fire Mode
Preset Reference
FB-06 Fire Mode
Reference Source
FB-07 Fire Mode
Feedback Source
FB-09 Fire Mode
Alarm Handling
* = Default Value
Notes/comments:
Parameters to setup Fire Mode
are all in the FB-## group.
[37] Fire
mode
[0] Disabled*
[0] Open
Loop*
[3] Hz*
0Hz*
50Hz*
0%*
[0] No
function*
[0] No
function*
[1] Trip,
Critical
Alarms*
Table 6.14 Fire Mode
45
Status Messages AF-600 FP Operating Instructions
7 Status Messages
7
7.1 Status Display
When the drive is in status mode, status messages are generated automatically from within the drive and appear in the bottom line of the display (see Illustration 7.1.)
Illustration 7.1 Status Display
a. The first word on the status line indicates where
the stop/start command originates.
b. The second word on the status line indicates
where the speed control originates.
c. The last part of the status line gives the present
drive status. These show the operational mode the drive is in.
NOTE
In auto/remote mode, the drive requires external commands to execute functions.
7.2 Status Message Definitions Table
The next three tables define the meaning of the status message display words.
Operation Mode
Off The drive does not react to any control signal
until [Auto] or [Hand] is pressed.
Auto The drive is controlled from the control
terminals and/or the serial communication.
Hand The drive can be controlled by the navigation
keys on the keypad. Stop commands, reset,
reversing, DC brake, and other signals applied
to the control terminals can override local
control.
Reference Site
Remote The speed reference is given from external
signals, serial communication, or internal
preset references.
Local The drive uses [Hand] control or reference
values from the keypad.
Operation Status
AC Brake AC Brake was selected in B-10 Brake Function.
The AC brake over-magnetizes the motor to
achieve a controlled slow down.
Auto Tune finishOKAuto Tune was carried out successfully.
Auto Tune ready Auto Tune is ready to start. Press [Hand] to
start.
Auto Tune
running
Coast
Ctrl. Ramp-down Control Ramp-down was selected in SP-10 Line
Current High The drive output current is above the limit set
Current Low The drive output current is below the limit set
Auto Tune process is in progress.
Coast inverse was selected as a function
for a digital input. The corresponding
terminal is not connected.
Coast activated by serial communication
failure.
The mains voltage is below the value set
in SP-11 Line Voltage at Input Fault at
mains fault
The drive ramps down the motor using a
controlled ramp down
in H-71 Warning Current High.
in H-70 Warning Current Low
46
Status Messages AF-600 FP Operating Instructions
7
Operation Status
DC Hold DC hold is selected in H-80 Function at Stop
and a stop command is active. The motor is
held by a DC current set in B-00 DC Hold
Current.
DC Stop The motor is held with a DC current (B-01 DC
Brake Current) for a specified time (B-02 DC
Braking Time).
DC Brake is activated in B-03 DC Brake Cut
In Speed [RPM] and a Stop command is
active.
DC Brake (inverse) is selected as a function
for a digital input. The corresponding
terminal is not active.
The DC Brake is activated via serial
communication.
Feedback high The sum of all active feedbacks is above the
feedback limit set in H-77 Warning Feedback
High.
Feedback low The sum of all active feedbacks is below the
feedback limit set in H-76 Warning Feedback
Low.
Freeze output The remote reference is active which holds
the present speed.
Freeze output was selected as a function
for a digital input. The corresponding
terminal is active. Speed control is only
possible via the terminal functions speed
up and speed down.
Hold ramp is activated via serial communi-
cation.
Freeze output
request
Freeze ref. Freeze Reference was chosen as a function for
Jog request A jog command has been given, but the
Jogging The motor is running as programmed in
A freeze output command has been given,
but the motor will remain stopped until a run
permissive signal is received.
a digital input. The corresponding terminal is
active. The drive saves the actual reference.
Changing the reference is now only possible
via terminal functions speed up and speed
down.
motor will be stopped until a run permissive
signal is received via a digital input.
C-21 Jog Speed [RPM].
Jog was selected as function for a digital
input. The corresponding terminal (e.g.
Terminal 29) is active.
The Jog function is activated via the serial
communication.
The Jog function was selected as a
reaction for a monitoring function (e.g. No
signal). The monitoring function is active.
Operation Status
OVC control Overvoltage control was activated in B-17 Over-
voltage Control. The connected motor is
supplying the drive with generative energy.
The overvoltage control adjusts the V/Hz ratio
to run the motor in controlled mode and to
prevent the drive from tripping.
PowerUnit Off (For frequency converters with an external 24V
power supply installed only.) Mains supply to
the drive is removed, but the control card is
supplied by the external 24V.
Protection md Protection mode is active. The unit has
detected a critical status (an overcurrent or
overvoltage).
To avoid tripping, switching frequency is
reduced to 4kHz.
If possible, protection mode ends after
approximately 10sec.
Protection mode can be restricted in
SP-26 Trip Delay at Drive Fault
QStop The motor is decelerating using C-23 Quick
Stop Decel Time.
Quick stop inverse was chosen as a function
for a digital input. The corresponding
terminal is not active.
The quick stop function was activated via
serial communication.
Ramping The motor is accelerating/decelerating using
the active Ramp Up/Down. The reference, a
limit value or a standstill is not yet reached.
Ref. high The sum of all active references is above the
reference limit set in H-75 Warning Reference
High.
Ref. low The sum of all active references is below the
reference limit set in H-74 Warning Reference
Low .
Run on ref. The drive is running in the reference range.
The feedback value matches the setpoint
value.
Run request A start command has been given, but the
motor is stopped until a run permissive signal
is received via digital input.
Running The motor is driven by the drive.
Sleep Mode The energy saving function is enabled. This
means that at present the motor has stopped,
but that it will restart automatically when
required.
Speed high Motor speed is above the value set in
H-73 Warning Speed High.
Speed low Motor speed is below the value set in
H-72 Warning Speed Low.
Standby In Auto mode, the drive will start the motor
with a start signal from a digital input or serial
communication.
7
47
7
Status Messages AF-600 FP Operating Instructions
Operation Status
Start delay In F-24 Holding Time, a delay starting time was
set. A start command is activated and the
motor will start after the start delay time
expires.
Start fwd/rev Start forward and start reverse were selected
as functions for two different digital inputs.
The motor will start in forward or reverse
depending on which corresponding terminal is
activated.
Stop The drive has received a stop command from
the keypad, digital input or serial communi-
cation.
Trip An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
drive can be reset manually by pressing
[Reset] or remotely by control terminals or
serial communication.
Trip lock An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the drive. The drive can
then be reset manually by pressing [Reset] or
remotely by control terminals or serial
communication.
48
Warnings and Alarms AF-600 FP Operating Instructions
8
8 Warnings and Alarms
8.1 System Monitoring
The drive monitors the condition of its input power, output, and motor factors as well as other system performance indicators. A warning or alarm may not necessarily indicate a problem internal to the drive itself. In many cases it indicates failure conditions from input voltage, motor load or temperature, external signals, or other areas monitored by the frequency converter’s internal logic. Be sure to investigate those areas exterior to the drive as indicated in the alarm or warning.
8.2 Warning and Alarm Types
Warnings A warning is issued when an alarm condition is impending or when an abnormal operating condition is present and may result in the drive issuing an alarm. A warning clears by itself when the abnormal condition is removed.
Alarms Trip An alarm is issued when the drive is tripped, that is, the drive suspends operation to prevent drive or system damage. The motor will coast to a stop. The drive logic will continue to operate and monitor the drive status. After the fault condition is remedied, the drive can be reset. It will then be ready to start operation again.
A trip can be reset in any of 4 ways:
Press [RESET] on the keypad
Digital reset input command
Serial communication reset input command
Auto reset
Trip-lock An alarm that causes the drive to trip-lock requires that input power be cycled. The motor will coast to a stop. The drive logic will continue to operate and monitor the drive status. Remove input power to the drive and correct the cause of the fault, then restore power. This action puts the drive into a trip condition as described above and may be reset in any of those 4 ways.
8.3 Warning and Alarm Displays
An alarm or trip-lock alarm will flash on display along with the alarm number.
8
In addition to the text and alarm code on the drive display, the status indicator lights operate.
Warn. LED Alarm LED
Warning ON OFF
Alarm OFF ON (Flashing)
Trip-Lock ON ON (Flashing)
49
8
Warnings and Alarms AF-600 FP Operating Instructions
8.4 Warning and Alarm Definitions
Table 8.1 defines whether a warning is issued prior to an alarm, and whether the alarm trips the unit or trip locks the unit.
No. Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference
1 10 Volts low X
2Live zero error (X) (X) AN-01 Live Zero Timeout
Function
4Mains phase loss (X) (X) (X) SP-12 Function at Line
Imbalance
5 DC link voltage high X
6 DC link voltage low X
7DC over voltage X X
8DC under voltage X X
9 Inverter overloaded X X
10 Motor Electronic Thermal Overload over
temperature
11 Motor thermistor over temperature (X) (X) F-10 Electronic Overload
12 Torque limit X X
13 Over Current X X X
14 Earth fault X X X
15 Hardware mismatch X X
16 Short Circuit X X
17 Control word timeout (X) (X) O-04 Control Word
18 Start Failed
23 Internal Fan Fault X
24 External Fan Fault X SP-53 Fan Monitor
29 Drive over temperature X X X
30 Motor phase U missing (X) (X) (X) H-78 Missing Motor Phase
31 Motor phase V missing (X) (X) (X) H-78 Missing Motor Phase
32 Motor phase W missing (X) (X) (X) H-78 Missing Motor Phase
33 Inrush fault X X
34 Fieldbus communication fault X X
35 Option Fault X X
36 Mains failure X X
38 Internal fault X X
39 Heatsink sensor X X
40 Overload of Digital Output Terminal 27 (X) E-00 Digital I/O Mode,
41 Overload of Digital Output Terminal 29 (X) E-00 Digital I/O Mode,
42 Overload of Digital Output On X30/6 (X) E-56 Term X30/6 Digi Out
42 Overload of Digital Output On X30/7 (X) E-57 Term X30/7 Digi Out
45 45 Earth Fault 2
46 Pwr. card supply X X
47 24V supply low X X X
48 1.8V supply low X X
49 Speed limit X (X) H-36 Trip Speed Low [RPM]
(X) (X) F-10 Electronic Overload
Timeout Function
Function
Function
Function
E-51 Terminal 27 Mode
E-52 Terminal 29 Mode
(OPCGPIO)
(OPCGPIO)
50
Warnings and Alarms AF-600 FP Operating Instructions
8
No. Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference
50 Auto Tune calibration failed X
nom
nom
and I
nom
51 Auto Tune check U
52 Auto Tune low I
53 Auto Tune motor too big X
54 Auto Tune motor too small X
55 Auto Tune Parameter out of range X
56 Auto Tune interrupted by user X
57 Auto Tune timeout X
58 Auto Tune internal fault X X
59 Current limit X
60 External Interlock X
62 Output Frequency at Maximum Limit X
64 Voltage Limit X
65 Control Board Over-temperature X X X
66 Heat sink Temperature Low X
67 Option Configuration has Changed X
69 Pwr. Card Temp X X
70 Illegal Drive configuration X
76 Power Unit Setup X
79 Illegal PS config X X
80 Drive Initialized to Default Value X
91 Analog input 54 wrong settings X
92 NoFlow X X AP-2#
93 Dry Pump X X AP-2#
94 End of Curve X X AP-5#
95 Broken Belt X X AP-6#
96 Start Delayed X AP-7#
97 Stop Delayed X AP-7#
98 Clock Fault X K-7#
201 Fire M was Active
202 Fire M Limits Exceeded
203 Missing Motor
204 Locked Rotor
243 Brake IGBT X X
244 Heatsink temp X X X
245 Heatsink sensor X X
246 Pwr.card supply X X
247 Pwr.card temp X X
248 Illegal PS config X X
250 New spare parts X
251 New Type Code X X
X
X
8
Table 8.1 Alarm/Warning code list
(X) Dependent on parameter
1)
Cannot be Auto reset via H-04 Auto-Reset (Times)
8.4.1 Fault Messages
The warning/alarm information below defines the warning/ alarm condition, provides the probable cause for the condition, and details a remedy or troubleshooting procedure.
WARNING 1, 10 Volts low The control card voltage is below 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V supply is overloaded. Max. 15 mA or minimum 590 Ω.
This condition can be caused by a short in a connected potentiometer or improper wiring of the potentiometer.
Troubleshooting: Remove the wiring from terminal 50. If the warning clears, the problem is with the customer wiring. If the warning does not clear, replace the control card.
51
Warnings and Alarms AF-600 FP Operating Instructions
8
WARNING/ALARM 2, Live zero error This warning or alarm will only appear if programmed by the user in AN-01 Live Zero Timeout Function. The signal on one of the analog inputs is less than 50% of the minimum value programmed for that input. This condition can be caused by broken wiring or faulty device sending the signal.
Troubleshooting
Check connections on all the analog input terminals. Control card terminals 53 and 54 for signals, terminal 55 common. OPCGPIO terminals 11 and 12 for signals, terminal 10 common. OPCAIO terminals 1, 3, 5 for signals, terminals 2, 4, 6 common).
Check that the drive programming and switch settings match the analog signal type.
Perform Input Terminal Signal Test.
WARNING/ALARM 4, Mains phase loss A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier on the drive. Options are programmed at SP-12 Function at Line Imbalance.
Troubleshooting: Check the supply voltage and supply currents to the drive.
WARNING 5, DC link voltage high The intermediate circuit voltage (DC) is higher than the high voltage warning limit. The limit is dependent on the drive voltage rating. The unit is still active.
WARNING 6, DC link voltage low The intermediate circuit voltage (DC) is lower than the low voltage warning limit. The limit is dependent on the drive voltage rating. The unit is still active.
WARNING/ALARM 7, DC overvoltage If the intermediate circuit voltage exceeds the limit, the drive trips after a time.
Troubleshooting
Connect a brake resistor
Extend the ramp time
Change the ramp type
Activate the functions in B-10 Brake Function
Increase SP-26 Trip Delay at Drive Fault
WARNING/ALARM 8, DC under voltage If the intermediate circuit voltage (DC link) drops below the under voltage limit, the drive checks if a 24V DC backup supply is connected. If no 24V DC backup supply is connected, the drive trips after a fixed time delay. The time delay varies with unit size.
Troubleshooting:
Check that the supply voltage matches the drive voltage.
Perform input voltage test
Perform soft charge circuit test
WARNING/ALARM 9, Inverter overload The drive is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection gives a warning at 98% and trips at 100%, while giving an alarm. The drive cannot be reset until the counter is below 90%. The fault is that the drive is overloaded by more than 100% for too long.
Troubleshooting
Compare the output current shown on the keypad with the drive rated current.
Compare the output current shown on the keypad with measured motor current.
Display the Thermal Drive Load on the keypad and monitor the value. When running above the drive continuous current rating, the counter should increase. When running below the drive continuous current rating, the counter should decrease.
See the derating section in the Design Guide for more details if a high switching frequency is required.
WARNING/ALARM 10, Motor overload temperature According to the electronic thermal protection, the motor is too hot. Select whether the drive gives a warning or an alarm when the counter reaches 100% in F-10 Electronic Overload . The fault occurs when the motor is overloaded by more than 100% for too long.
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded
Check that the motor current set in P-03 Motor Current is correct.
Ensure that Motor data in parameters P-02, P-03, P-06, P-07, F-04 and F-05 are set correctly.
If an external fan is in use, check in F-11 Motor External Fan that it is selected.
Running Auto tune in P-04 Auto Tune may tune the drive to the motor more accurately and reduce thermal loading.
WARNING/ALARM 11, Motor thermistor over temp The thermistor might be disconnected. Select whether the drive gives a warning or an alarm in F-10 Electronic Overload .
52
Warnings and Alarms AF-600 FP Operating Instructions
8
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded.
When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10V supply) and that the terminal switch for 53 or 54 is set for voltage. Check F-12 Motor Thermistor Input selects terminal 53 or
54.
When using digital inputs 18 or 19, check that the thermistor is connected correctly between either terminal 18 or 19 (digital input PNP only) and terminal 50. Check F-12 Motor Thermistor Input selects terminal 18 or 19.
WARNING/ALARM 12, Torque limit The torque has exceeded the value in F-40 Torque Limiter
(Driving) or the value in F-41 Torque Limiter (Braking). SP-25 Trip Delay at Torque Limit can change this from a
warning only condition to a warning followed by an alarm.
Troubleshooting
If the motor torque limit is exceeded during ramp up, extend the ramp up time.
If the generator torque limit is exceeded during ramp down, extend the ramp down time.
If torque limit occurs while running, possibly increase the torque limit. Be sure the system can operate safely at a higher torque.
Check the application for excessive current draw on the motor.
WARNING/ALARM 13, Over current The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts about 1.5 secs., then the drive trips and issues an alarm. This fault may be caused by shock loading or fast acceleration with high inertia loads. If extended mechanical brake control is selected, trip can be reset externally.
Troubleshooting:
Remove power and check if the motor shaft can be turned.
Check that the motor size matches the drive.
Check parameters P-02, P-03, P-06, P-07, F-04 and F-05. for correct motor data.
ALARM 14, Earth (ground) fault There is current from the output phases to earth, either in the cable between the drive and the motor or in the motor itself.
Troubleshooting:
Remove power to the drive and repair the earth fault.
Check for earth faults in the motor by measuring the resistance to ground of the motor leads and the motor with a megohmmeter.
ALARM 15, Hardware mismatch A fitted option is not operational with the present control board hardware or software.
Record the value of the following parameters and contact your GE supplier:
ID-40 Drive Type
ID-41 Power Section
ID-42 Voltage
ID-43 Software Version
ID-45 Actual Typecode String
ID-49 SW ID Control Card
ID-50 SW ID Power Card
ID-60 Option Mounted
ID-61 Option SW Version (for each option slot)
ALARM 16, Short circuit There is short-circuiting in the motor or motor wiring.
Remove power to the drive and repair the short circuit.
WARNING/ALARM 17, Control word timeout There is no communication to the drive. The warning will only be active when O-04 Control Word Timeout Function is NOT set to OFF. If O-04 Control Word Timeout Function is set to Stop and Trip, a warning appears and the drive ramps down until it stops then displays an alarm.
Troubleshooting:
Check connections on the serial communication cable.
IncreaseO-03 Control Word Timeout Time
Check the operation of the communication equipment.
Verify a proper installation based on EMC requirements.
ALARM 18, Start failed The speed has not been able to exceed AP-70 Compressor Start Max Speed [RPM] during start within the allowed time. (set in AP-72 Compressor Start Max Time to Trip). This may be caused by a blocked motor.
WARNING 23, Internal fan fault The fan warning function is an extra protective function that checks if the fan is running/mounted. The fan warning can be disabled in SP-53 Fan Monitor ([0] Disabled).
For the 4x, 5x and 6x Frame filters, the regulated voltage to the fans is monitored.
8
53
Warnings and Alarms AF-600 FP Operating Instructions
8
Troubleshooting:
Check for proper fan operation.
Cycle power to the drive and check that the fan operates briefly at start up.
Check the sensors on the heatsink and control card.
WARNING 24, External fan fault The fan warning function is an extra protective function that checks if the fan is running/mounted. The fan warning can be disabled in SP-53 Fan Monitor ([0] Disabled).
Troubleshooting:
Check for proper fan operation.
Cycle power to the drive and check that the fan operates briefly at start up.
Check the sensors on the heatsink and control card.
ALARM 29, Heatsink temp The maximum temperature of the heatsink has been exceeded. The temperature fault will not reset until the temperature falls below a defined heatsink temperature. The trip and reset points are different based on the drive power size.
Troubleshooting:
Check for the following conditions.
Ambient temperature too high.
Motor cable too long.
Incorrect airflow clearance above and below the drive
Blocked airflow around the drive.
Damaged heatsink fan.
Dirty heatsink.
ALARM 30, Motor phase U missing Motor phase U between the drive and the motor is missing.
Remove power from the drive and check motor phase U.
ALARM 31, Motor phase V missing Motor phase V between the drive and the motor is missing.
Remove power from the drive and check motor phase V.
ALARM 32, Motor phase W missing Motor phase W between the drive and the motor is missing.
Remove power from the drive and check motor phase W.
ALARM 33, Inrush fault Too many power-ups have occurred within a short time period. Let the unit cool to operating temperature.
WARNING/ALARM 34, communication fault The network on the communication option card is not working.
WARNING/ALARM 36, Mains failure This warning/alarm is only active if the supply voltage to the drive is lost and SP-10 Line failure is NOT set to [0] No Function. Check the fuses to the drive and mains power supply to the unit.
ALARM 38, Internal fault When an internal fault occurs, a code number defined in the table below is displayed.
Troubleshooting
Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact your GE supplier or service department. Note the code number for further trouble­shooting directions.
No. Text
0 Serial port cannot be initialised. Contact yourGE
supplier or GEService Department.
256-258 Power EEPROM data is defect or too old
512-519 Internal fault. Contact yourGE supplier or GE
Service Department.
783 Parameter value outside of min/max limits
1024-1284 Internal fault. Contact your GE supplier or the GE
Service Department.
1299 Option SW in slot A is too old
1300 Option SW in slot B is too old
1302 Option SW in slot C1 is too old
1315 Option SW in slot A is not supported (not allowed)
1316 Option SW in slot B is not supported (not allowed)
1318 Option SW in slot C1 is not supported (not
allowed)
1379-2819 Internal fault. Contact yourGE supplier or GEService
Department.
2820 keypad stack overflow
2821 Serial port overflow
2822 USB port overflow
3072-5122 Parameter value is outside its limits
5123 Option in slot A: Hardware incompatible with
control board hardware
5124 Option in slot B: Hardware incompatible with
control board hardware
5125 Option in slot C0: Hardware incompatible with
control board hardware
5126 Option in slot C1: Hardware incompatible with
control board hardware
5376-6231 Internal fault. Contact yourGE supplier or GEService
Department.
ALARM 39, Heatsink sensor No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power card. The problem could be on the power card, on the gate drive card, or the ribbon cable between the power card and gate drive card.
54
Warnings and Alarms AF-600 FP Operating Instructions
8
WARNING 40, Overload of digital output terminal 27 Check the load connected to terminal 27 or remove short­circuit connection. Check E-00 Digital I/O Mode and E-51 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29 Check the load connected to terminal 29 or remove short­circuit connection. Check E-00 Digital I/O Mode and E-52 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or overload of digital output on X30/7 For X30/6, check the load connected to X30/6 or remove short-circuit connection. Check E-56 Term X30/6 Digi Out (OPCGPIO).
For X30/7, check the load connected to X30/7 or remove short-circuit connection. Check E-57 Term X30/7 Digi Out (OPCGPIO).
ALARM 45, Earth fault 2 Earth (ground) fault on start up.
Troubleshooting
Check for proper earthing (grounding) and loose connections.
Check for proper wire size.
Check motor cables for short-circuits or leakage currents.
ALARM 46, Power card supply The supply on the power card is out of range.
There are three power supplies generated by the switch mode power supply (SMPS) on the power card: 24V, 5V, +/- 18V. When powered with three phase mains voltage, all three supplied are monitored.
Troubleshooting
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24V DC power supply is used, verify proper supply power.
WARNING 47, 24V supply low The 24 V DC is measured on the control card. The external 24V DC backup power supply may be overloaded, otherwise contact your GE supplier.
WARNING 48, 1.8V supply low The 1.8V DC supply used on the control card is outside of allowable limits. The power supply is measured on the control card. Check for a defective control card. If an option card is present, check for an overvoltage condition.
WARNING 49, Speed limit When the speed is not within the specified range in F-18 and F-17, the drive will show a warning. When the speed is below the specified limit in H-36 Trip Speed Low [RPM] (except when starting or stopping) the drive will trip.
ALARM 50, Auto tune calibration failed Contact your GE supplier or GE Service Department.
nom
nom
and I
nom
ALARM 51, Auto tune check U The settings for motor voltage, motor current, and motor power are wrong. Check the settings in parameters P-02, P-03, P-06, P-07, F-04 and F-05.
ALARM 52, Auto tune low I The motor current is too low. Check the setting in F-43 Current Limit.
ALARM 53, Auto tune motor too big The motor is too big for the Auto tune to operate.
ALARM 54, Auto tune motor too small The motor is too small for the Auto tune to operate.
ALARM 55, Auto tune Parameter out of range The parameter values of the motor are outside of the acceptable range. Auto tune will not run.
ALARM 56, Auto tune interrupted by user The Auto tune has been interrupted by the user.
ALARM 57, Auto tune timeout Try to restart Auto tune again. Repeated restarts may over heat the motor.
ALARM 58, Auto tune internal fault Contact your GE supplier.
WARNING 59, Current limit The current is higher than the value in F-43 Current Limit. Ensure that Motor data in parameters P-02, P-03, P-06, P-07, F-04 and F-05 are set correctly. Possibly increase the current limit. Be sure the system can operate safely at a higher limit.
WARNING 60, External interlock A digital input signal is indicating a fault condition external to the drive. An external interlock has commanded the drive to trip. Clear the external fault condition. To resume normal operation, apply 24V DC to the terminal programmed for external interlock. Reset the drive.
WARNING 62, Output frequency at maximum limit The output frequency has reached the value set in F-03 Max Output Frequency 1. Check the application to determine the cause. Possibly increase the output frequency limit. Be sure the system can operate safely at a higher output frequency. The warning will clear when the output drops below the maximum limit.
WARNING/ALARM 65, Control card over temperature The cutout temperature of the control card is 80° C.
Troubleshooting
Check that the ambient operating temperature is
within limits.
Check for clogged filters.
Check fan operation.
Check the control card.
8
55
Warnings and Alarms AF-600 FP Operating Instructions
8
WARNING 66, Heatsink temperature low The drive is too cold to operate. This warning is based on the temperature sensor in the IGBT module. Increase the ambient temperature of the unit. Also, a trickle amount of current can be supplied to the drive whenever the motor is stopped by setting B-00 DC Hold Current at 5% and H-80 Function at Stop
ALARM 67, Option module configuration has changed One or more options have either been added or removed since the last power-down. Check that the configuration change is intentional and reset the unit.
ALARM 69, Power card temperaturePower card temperature The temperature sensor on the power card is either too hot or too cold.
Troubleshooting
Check that the ambient operating temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the power card.
ALARM 70, Illegal drive configuration The control card and power card are incompatible. Contact your supplier with the type code of the unit from the nameplate and the part numbers of the cards to check compatibility.
ALARM 80, Unit Restored to Factory Settings Parameter settings are restored to factory settings after a manual reset. Reset the unit to clear the alarm.
ALARM 92, No flow A no-flow condition has been detected in the system. AP-23 No-Flow Function is set for alarm. Troubleshoot the system and reset the drive after the fault has been cleared.
ALARM 93, Dry pump A no-flow condition in the system with the drive operating at high speed may indicate a dry pump. AP-26 Dry Pump Function is set for alarm. Troubleshoot the system and reset the drive after the fault has been cleared.
ALARM 94, End of curve Feedback is lower than the set point. This may indicate leakage in the system. AP-50 End of Curve Function is set for alarm. Troubleshoot the system and reset the drive after the fault has been cleared.
ALARM 95, Broken belt Torque is below the torque level set for no load, indicating a broken belt. AP-60 Broken Belt Function is set for alarm. Troubleshoot the system and reset the drive after the fault has been cleared.
ALARM 96, Start delayed Motor start has been delayed due to short-cycle protection. AP-76 Interval between Starts is enabled. Troubleshoot the system and reset the drive after the fault has been cleared.
WARNING 97, Stop delayed Stopping the motor has been delayed due to short cycle protection. AP-76 Interval between Starts is enabled. Troubleshoot the system and reset the drive after the fault has been cleared.
WARNING 98, Clock fault Time is not set or the RTC clock has failed. Reset the clock in K-70 Date and Time.
WARNING, 200 Fire mode This indicates the drive is operating in fire mode. The warning clears when fire mode is removed. See the fire mode data in the alarm log.
WARNING 201, Fire mode was active This indicates the drive had entered fire mode. Cycle power to the unit to remove the warning. See the fire mode data in the alarm log.
WARNING 202, Fire mode limits exceeded While operating in fire mode one or more alarm conditions have been ignored which would normally trip the unit. Operating in this condition voids unit warranty. Cycle power to the unit to remove the warning. See the fire mode data in the alarm log.
WARNING 203, Missing motor With a drive operating multi-motors, an under-load condition was detected. This could indicate a missing motor. Inspect the system for proper operation.
WARNING 204, Locked rotor With a drive operating multi-motors, an overload condition was detected. This could indicate a locked rotor. Inspect the motor for proper operation.
WARNING 250, New spare part A component in the drive has been replaced. Reset the drive for normal operation.
WARNING 251, New typecode The power card or other components have been replaced and the typecode changed. Reset to remove the warning and resume normal operation.
56
Basic Troubleshooting AF-600 FP Operating Instructions
9
9 Basic Troubleshooting
9.1 Start Up and Operation
Symptom Possible Cause Test Solution
Missing input power See Table 3.1. Check the input power source.
Display dark / No function
Intermittent display
Motor not running
Missing or open fuses or circuit
breaker tripped
No power to the keypad Check the keypad cable for proper
Shortcut on control voltage
(terminal 12 or 50) or at control
terminals
Wrong contrast setting Press [Status] + Up/Down arrows
Display (keypad) is defective Test using a different keypad. Replace the faulty keypad or
Internal voltage supply fault or
SMPS is defective
Overloaded power supply (SMPS)
due to improper control wiring or
a fault within the drive
Service switch open or missing
motor connection
No mains power with 24V DC
option card
Keypad Stop Check if [Off] has been pressed. Press [Auto] or [Hand] (depending
Missing start signal (Standby) Check E-01 Terminal 18 Digital Input
Motor coast signal active
(Coasting)
Wrong reference signal source Check reference signal: Local,
See open fuses and tripped circuit
breaker in this table for possible
causes.
connection or damage.
Check the 24V control voltage
supply for terminal 12/13 to 20-39
or 10V supply for terminal 50 to 55.
Contact supplier.
To rule out a problem in the
control wiring, disconnect all
control wiring by removing the
terminal blocks.
Check if the motor is connected
and the connection is not
interrupted (by a service switch or
other devise).
If the display is functioning but no
output, check that mains power is
applied to the drive.
for correct setting for terminal 18
(use default setting).
Check if a coast inv command is
programmed for the terminal in
parameter group E-0# Digital
Inputs
remote or bus reference? Preset
reference active? Terminal
connection correct? Scaling of
terminals correct? Reference signal
available?
Follow the recommendations
provided
Replace the faulty keypad or
connection cable.
Wire the terminals properly.
to adjust the contrast.
connection cable.
If the display stays lit, then the
problem is in the control wiring.
Check the wiring for shorts or
incorrect connections. If the display
continues to cut out, follow the
procedure for display dark.
Connect the motor and check the
service switch.
Apply mains power to run the unit.
on your operation mode) to run
the motor.
Apply a valid start signal to start
the motor.
Apply 24V on terminal or
programm this terminal to No
operation.
Program correct settings Check
F-02 Operation Method Set preset
reference active in parameter
C-05 Multi-step Frequency 1 - 8 .
Check for correct wiring. Check
scaling of terminals. Check
reference signal.
9
57
9
Basic Troubleshooting AF-600 FP Operating Instructions
Symptom Possible Cause Test Solution
Motor rotation limit Check that H-08 Reverse Lock is
programmed correctly.
Motor running in wrong
direction
Motor is not reaching
maximum speed
Motor speed unstable
Motor runs rough
Motor will not brake
Open power fuses or circuit
breaker trip
Mains current imbalance
greater than 3%
Motor current imbalance
greater than 3%
Active reversing signal Check if a reversing command is
programmed for the terminal in
parameter group E-0# Digital inputs.
Wrong motor phase connection See 3.5 Check Motor Rotation in this
Frequency limits set wrong Check output limits in F-17 Motor
Speed High Limit [RPM], F-15 Motor
Speed High Limit [Hz] and F-03 Max
Output Frequency 1
Reference input signal not scaled
correctly
Possible incorrect parameter
settings
Possible over-magnetization Check for incorrect motor settings
Possible incorrect settings in the
brake parameters. Possible too
short ramp down times.
Phase to phase short Motor or panel has a short phase
Motor overload Motor is overloaded for the
Loose connections Perform pre-startup check for loose
Problem with mains power (See
Alarm 4 Mains phase loss
description)
Problem with the drive unit Rotate input power leads into the
Problem with motor or motor
wiring
Problem with drive unit Rotate output motor leads one
Check reference input signal
scaling in AN-## reference limits in
parameter group F-5# Extended
Reference.
Check the settings of all motor
parameters, including all motor
compensation settings. For closed
loop operation, check PID settings.
in all motor parameters.
Check brake parameters. Check
ramp time settings.
to phase. Check motor and panel
phase to for shorts.
application.
connections.
Rotate input power leads into the
drive one position: A to B, B to C, C
to A.
drive one position: A to B, B to C, C
to A.
Rotate output motor leads one
position: U to V, V to W, W to U.
position: U to V, V to W, W to U.
Program correct settings.
Deactivate reversing signal.
manual.
Program correct limits.
Program correct settings.
Check settings in parameter group
AN-##. For closed loop operation
check settings in parameter group
CL-0#
Check motor settings in parameter
groups P-0# Motor Data, P-3# Adv
Motor Data, and H-5# Load Indep.
Setting.
Check parameter groupB-0# DC
brake and F-5# Extended Reference.
Eliminate any shorts detected.
Perform startup test and verify
motor current is within specifi-
cations. If motor current is
exceeding nameplate full load
current, motor may run only with
reduced load. Review the specifi-
cations for the application.
Tighten loose connections.
If imbalanced leg follows the wire,
it is a power problem. Check mains
power supply.
If imbalance leg stays on same
input terminal, it is a problem with
the unit. Contact supplier.
If imbalanced leg follows the wire,
the problem is in the motor or
motor wiring. Check motor and
motor wiring.
If imbalance leg stays on same
output terminal, it is a problem
with the unit. Contact supplier.
58
Specifications AF-600 FP Operating Instructions
0
10 Specifications
10.1 Power-dependent Specifications
10/7 35/2 50/1/0 95/4/0
10 1
8.3 11.7 18.4 26.6 33.4 65.3 96.8
7.5 10.6 16.7 24.2 30.8 59.4 88
Continuous
(3 x 200-240 V) [A]
Intermittent
(3 x 200-240 V) [A]
5.00 6.40 12.27 18.30
Continuous kVA
(208 V AC) [kVA]
15 20.5 32 46 59 111 172
16.5 22.6 35.2 50.6 64.9 122.1 189.2
Continuous
(1 x 200-240 V ) [A]
Intermittent
(1 x 200-240 V ) [A]
30 40 60 80 100 150 200
[A]
1)
Max. pre-fuses
30 44 74 110 150 300 440
0.98 0.98 0.98 0.98 0.98 0.98 0.98
4)
2)
3)
/ AWG]
2
[mm
at rated max. load [W]
Efficiency
Typical Shaft Output [HP] at 240 V 2.0 3.0 5.0 7.5 10 20 30
Mains Supply 1 x 200-240V AC - Light duty 110% for 1 minute
Typical Shaft Output [kW] 1.5 2.2 3.7 5.5 7.5 15 22
IP 21 / NEMA 1 21 21 21 21 22 31 32
IP 55 / NEMA 12 21 21 21 21 22 31 32
Output current
Max. input current
Additional Specifications
Estimated power loss
Weight enclosure IP21 [kg] 23 23 23 23 27 45 65
Max. cable size (mains, motor, brake)
Weight enclosure IP55 [kg] 23 23 23 23 27 45 65
59
Specifications AF-600 FP Operating Instructions
4/10
54 82 116 185
5.1 8.3 11.7 18.4
4.6 7.5 10.6 16.7
1.66 2.70 3.82 6.00
4.1 6.8 9.5 15.0
10 20 20 32
4.5 7.5 10.5 16.5
0.95 0.96 0.96 0.96
100
4)
[A]
Intermittent
1)
(3 x 200-240 V ) [A]
Max. pre-fuses
Environment
Estimated power loss
3)
Weight enclosure IP55 [kg] 13.5 13.5 13.5 13.5
at rated max. load [W]
Weight enclosure IP20 [kg] 4.9 4.9 4.9 6.6
Efficiency
Typical Shaft Output [HP] at 208 V 1.0 2.0 3.0 5.0
2)
/AWG]
2
Continuous
Continuous
(3 x 200-240 V ) [A]
Intermittent
kVA (208 V AC) [kVA]
(3 x 200-240 V ) [A]
Max. cable size:
(mains, motor)
[mm
Continuous
(3 x 200-240 V ) [A]
60
Mains Supply 3x200-240V AC
IP 20 / Chassis 12 12 12 13
Light duty (LD) 110% for 1 minute
Typical Shaft Output [kW] 0.75 1.5 2.2 3.7
IP 55 / NEMA 12 15 15 15 15
Output current
Max. input current
Table 10.1 Mains Supply 3x200-240V AC
Specifications AF-600 FP Operating Instructions
0
120/250
MCM
95/4/0
50/1/0
(24=35/2)
5.5 7.5 11 15 18.5 22 30 37 45
10/7 35/2
26.6 33.9 50.8 65.3 82.3 96.8 127 157 187
24.2 30.8 46.2 59.4 74.8 88.0 115 143 170
8.7 11.1 16.6 21.4 26.9 31.7 41.4 51.5 61.2
22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0
24.2 30.8 46.2 59.4 74.8 88.0 114.0 143.0 169.0
269 310 447 602 737 845 1140 1353 1636
0.96 0.96 0.96 0.96 0.96 0.97 0.97 0.97 0.97
10 1
4)
2)
/AWG]
2
3)
Continuous
Continuous
(3 x 200-240 V ) [A]
Intermittent
(3 x 200-240 V ) [A]
kVA (208 V AC) [kVA]
Continuous
(3 x 200-240 V ) [A]
Intermittent
(3 x 200-240 V ) [A]
Max. cable size (mains, motor) [mm
Estimated power loss at rated max. load [W]
Efficiency
Mains Supply 3x200-240V AC - Light duty (LD) 110% for 1 minute
IP20/Chassis 23 23 23 24 24 33 33 34 34 IP55/NEMA 12 21 21 21 22 31 31 31 32 32 Frequency converter
Typical Shaft Output [HP] at 208 V 7.5 10 15 20 25 30 40 50 60
Typical Shaft Output [kW]
Output current
Max. input current
Additional Specifications
Weight enclosure IP20 [kg] 12 12 12 23.5 23.5 35 35 50 50
Weight enclosure IP55 [kg] 23 23 23 27 45 45 45 65 65
Table 10.2 Mains Supply 3x200-240V AC
61
Specifications AF-600 FP Operating Instructions
16 24 37.5 73
17.6 26.4 41.2 80.3
14.5 21 34 65
15.4 23.1 37.4 71.5
11.6 16.7 27.1 51.8
11.0 16.6 26 50.6
10/7 35/2 50/1/0 120/4/0
33 48 78 151
30 41 72 135
36 53 85.8 166
33 46 79.2 148
63 80 160 250
300 440 740 1480
0.96 0.96 0.96 0.96
100
4)
[A]
2)
/ AWG]
2
1)
3)
62
Continuous kVA
Intermittent
(3 x 380-440 V) [A]
(3 x 380-440 V) [A]
Continuous
Typical Shaft Output [HP] at 460 V 10 15 25 50
Mains Supply 1x 380 VAC - Light duty 110% for 1 minute
Typical Shaft Output [kW] 7.5 11 18.5 37
Output current
IP 21 / NEMA 1 21 22 31 32
IP 55 / Type 12 21 22 31 32
Intermittent
(3 x 441-480 V) [A]
(3 x 441-480 V) [A]
Continuous kVA
Continuous
(400 V AC) [kVA]
(460 V AC) [kVA]
Continuous
Max. cable size:
(mains, motor, brake)
[[mm
Continuous
(1 x 380-440 V ) [A]
Intermittent
Max. input current
(1 x 441-480 V) [A]
(1 x 380-440 V ) [A]
Intermittent
(1 x 441-480 V) [A]
Max. pre-fuses
Environment
Estimated power loss
Weight enclosure IP 55 [kg] 23 27 45 65
at rated max. load [W]
Weight enclosure IP 21 [kg] 23 27 45 65
Efficiency
Table 10.3 Mains Supply 1x 380V AC
Specifications AF-600 FP Operating Instructions
0
4/10
2.2 3.7 5.0 9.0 11.7 14.4
10 10 20 20 32 32
1.9 3.1 4.3 7.4 9.9 13.0
46 62 88 124 187 255
4.8 4.9 4.9 4.9 6.6 6.6
0.96 0.97 0.97 0.97 0.97 0.97
10 1
4)
[A]
2)
/ AWG]
2
Continuous (3 x 440-480 V) [A] 2.1 3.4 4.8 8.2 11 14.5
Continuous kVA 400 V AC) [kVA] 1.7 2.8 3.9 6.9 9.0 11.0
Continuous (3 x 380-440 V) [A] 2.4 4.1 5.6 10 13 16
Intermittent (3 x 380-440 V) [A] 2.6 4.5 6.2 11 14.3 17.6
Intermittent (3 x 440-480 V) [A] 2.3 3.7 5.3 9.0 12.1 15.4
Max. cable size:
Continuous kVA (460 V AC) [kVA] 1.7 2.7 3.8 6.5 8.8 11.6
(mains, motor)
[[mm
Intermittent (3 x 380-440 V ) [A] 2.4 4.1 5.5 9.9 12.9 15.8
Continuous (3 x 380-440 V ) [A]
1)
3)
Intermittent (3 x 440-480 V) [A] 2.1 3.4 4.7 8.1 10.9 14.3
Max. pre-fuses
Environment
Estimated power loss
at rated max. load [W]
Continuous (3 x 440-480 V) [A]
Efficiency
Weight enclosure IP20 [kg]
Weight enclosure IPø55 [kg] 13.5 13.5 13.5 13.5 14.2 14.2
Mains Supply 3 x 380 - 480 VAC - Light duty (LD) 110% for 1 minute
Typical Shaft Output [kW] 0.75 1.5 2.2 4 5.5 7.5
Typical Shaft Output [HP] at 460 V 12357.510
IP 55 / Type 12 15 15 15 15 15 15
IP 20 / Chassis 12 12 12 12 13 13
Output current
Max. input current
Table 10.4 Mains Supply 3 x 380 - 480 VAC
63
Specifications AF-600 FP Operating Instructions
120/
MCM250
95/
4/0
50/1/0
(24=35/2)
100
16.7 21.5 27.1 31.9 41.4 51.8 63.7 83.7 104 128
Continuous (3 x 440-480 V) [A] 21 27 34 40 52 65 80 105 130 160
Continuous (3 x 380-439 V) [A] 24 32 37.5 44 61 73 90 106 147 177
Intermittent (3 x 380-439 V) [A] 26.4 35.2 41.3 48.4 67.1 80.3 99 117 162 195
Continuous kVA (400 V AC) [kVA] 16.6 22.2 26 30.5 42.3 50.6 62.4 73.4 102 123
Intermittent (3 x 440-480 V) [A] 23.1 29.7 37.4 44 61.6 71.5 88 116 143 176
Continuous kVA 460 V AC) [kVA]
Intermittent (3 x 380-439 V ) [A] 24.2 31.9 37.4 44 60.5 72.6 90.2 106 146 177
Continuous (3 x 380-439 V ) [A] 22 29 34 40 55 66 82 96 133 161
Continuous (3 x 440-480 V) [A] 19 25 31 36 47 59 73 95 118 145
Intermittent (3 x 440-480 V) [A] 20.9 27.5 34.1 39.6 51.7 64.9 80.3 105 130 160
10/7 35/2
278 392 465 525 698 739 843 1083 1384 1474
4)
2)
/ AWG]
2
Max. cable size (mains, motor) [mm
Estimated power lossat rated max. load [W]
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.99
3)
Efficiency
64
Typical Shaft Output [HP] at 460 V 15 20 25 30 40 50 60 75 100 125
Mains Supply 3 x 380 - 480 VAC - Light duty (LD) 110% for 1 minute
Typical Shaft Output [kW] 11 15 18.5 22 30 37 45 55 75 90
IP20/Chassis 23 23 23 24 24 24 33 33 34 34 IP55/Type 12 21 21 21 22 22 31 31 31 32 32 Output current
Max. input current
Additional specifications
Weight enclosure IP20 [kg] 12 12 12 23.5 23.5 23.5 35 35 50 50 Weight enclosure IP55 [kg] 23 23 23 27 27 45 45 45 65 65
Table 10.5 Mains Supply 3 x 380 - 480 VAC
Specifications AF-600 FP Operating Instructions
0
150/
120/
MCM25
95/
4/0
50/
1/0
MCM25
0
95/
50/
4/0
1/0
5)
0
4
25/
7
10/
2
35/
6
16/
10 1
4/
10
4/
10
10 10 20 20 32 32 63 63 63 63 80 100 125 160 250 250
2.42.73.96.19.011.01822273441526283100131
2.9 3.2 4.5 7.0 10.5 12.7 21 25 31 40 47 59 72 96 116 151
2.62.94.16.49.511.51923283643546587105137
Typical Shaft Output [HP] 1 2 3 57.51015202530405060 75100125
Typical Shaft Output [kW] 0.75 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Mains supply 3x525-600V AC Light duty (LD) 110% for 1 minute
Output current
IP 20 / Chassis 1212121213132323232424243333 3434
IP 55 / NEMA 12 15 15 15 15 15 15 21 21 21 22 22 22 31 31 32 32
Continuous
(3 x 525-550 V ) [A]
Continuous
(3 x 525-550 V ) [A]
(3 x 525-600 V ) [A]
Intermittent
2.5 2.8 3.9 6.1 9.0 11.0 18.1 21.9 26.7 34.3 41 51.4 61.9 82.9 100 130.5
2.6 3.0 4.3 6.7 9.9 12.1 20 24 30 37 45 57 68 91 110 144
Intermittent
(3 x 525-600 V ) [A]
Continuous kVA (525 V AC)
[kVA]
Continuous kVA (575 V AC)
2.4 2.7 3.9 6.1 9.0 11.0 17.9 21.9 26.9 33.9 40.8 51.8 61.7 82.7 99.6 130.5
[kVA]
Max. cable size, IP 55
(mains, motor)
2)
]/[AWG]
2
[mm
Max. cable size, IP 20
(mains, motor)
2)
]/[AWG]
2
[mm
Max. input current
2.7 3.0 4.5 6.4 9.5 11.5 19 23 28 36 43 54 65 87 105 137
2.4 2.7 4.1 5.8 8.6 10.4 17.2 20.9 25.4 32.7 39 49 59 78.9 95.3 124.3
[A]
1)
Intermittent
(3 x 525-600 V ) [A]
(3 x 525-600 V ) [A]
Max. pre-fuses
Continuous
50 65 92 145 195 261 300 400 475 525 700 750 850 1100 1400 1500
4)
Environment:
Estimated power loss
Weight enclosure
at rated max. load [W]
6.5 6.5 6.5 6.5 6.6 6.6 12 12 12 23.5 23.5 23.5 35 35 50 50
13.5 13.5 13.5 13.5 14.2 14.2 23 23 23 27 27 27 45 45 65 65
0.97 0.97 0.97 0.97 0.97 0.97 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
4)
IP20 [kg]
Efficiency
Weight enclosure
IP55 [kg]
Table 10.6 Mains supply 3x525-600V AC
65
Specifications AF-600 FP Operating Instructions
10.2 General Technical Data
Mains supply (L1, L2, L3): Supply voltage 200-240V ±10%, 380-480V ±10%, 525-600V ±10%,
Mains voltage low / mains drop-out: During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.
Supply frequency 50/60Hz ±5% Max. imbalance temporary between mains phases 3.0% of rated supply voltage True Power Factor () 0.9 nominal at rated load Displacement Power Factor (cos) near unity (> 0.98) Switching on input supply L1, L2, L3 (power-ups) unit size 1x maximum twice/min. Switching on input supply L1, L2, L3 (power-ups) unit sizes 2x, 3x maximum once/min. Switching on input supply L1, L2, L3 (power-ups) unit sizes 4x, 5x, 6x maximum once/2 min. Environment according to EN60664-1 overvoltage category III / pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V maximum.
Motor output (U, V, W): Output voltage 0 - 100% of supply voltage Output frequency 0 - 1000 Hz Switching on output Unlimited Accel/Decel Times 1 - 3600 sec.
*
Dependent on power size.
Torque characteristics: Starting torque (Constant torque) maximum 110% for 1 min.
Starting torque maximum 135% up to 0.5 sec.
100
Overload torque (Constant torque) maximum 110% for 1 min.
*Percentage relates to the frequency converter's nominal torque.
Cable lengths and cross sections: Max. motor cable length, screened/armoured 150 m Max. motor cable length, unscreened/unarmoured 300 m Max. cross section to motorand mains* Maximum cross section to control terminals, rigid wire 1.5 mm2/16 AWG (2 x 0.75 mm2)
Maximum cross section to control terminals, flexible cable 1 mm2/18 AWG
Maximum cross section to control terminals, cable with enclosed core 0.5 mm2/20 AWG Minimum cross section to control terminals 0.25 mm
* See 10.1 Power-dependent Specifications for more information!
Digital inputs: Programmable digital inputs 4 (6)
Terminal number 18, 19, 27
1)
, 29, 32, 33, Logic PNP or NPN Voltage level 0 - 24V DC Voltage level, logic'0' PNP < 5V DC Voltage level, logic'1' PNP > 10V DC Voltage level, logic '0' NPN > 19 V DC Voltage level, logic '1' NPN < 14V DC Maximum voltage on input 28V DC Input resistance, R
i
approx. 4k
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
*
*
*
*
2
66
Specifications AF-600 FP Operating Instructions
0
Analog inputs: Number of analog inputs 2 Terminal number 53, 54 Modes Voltage or current Mode select Switches A53 and A54 Voltage mode Switch A53/A54 = (U) Voltage level 0 to + 10V (scaleable) Input resistance, R Max. voltage ± 20 V Current mode Switch A53/A54 = (I) Current level 0/4 to 20 mA (scaleable) Input resistance, R Max. current 30 mA Resolution for analog inputs 10 bit (+ sign) Accuracy of analog inputs Max. error 0.5% of full scale Bandwidth 200Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
i
i
approx. 10 k
approx. 200
Pulse inputs: Programmable pulse inputs 2 Terminal number pulse 29, 33 Max. frequency at terminal, 29, 33 110 kHz (Push-pull driven) Max. frequency at terminal, 29, 33 5 kHz (open collector) Min. frequency at terminal 29, 33 4 Hz Voltage level see section on Digital input Maximum voltage on input 28 V DC Input resistance, R Pulse input accuracy (0.1 - 1 kHz) Max. error: 0.1% of full scale Analog output: Number of programmable analog outputs 1 Terminal number 42 Current range at analog output 0/4 - 20 mA Max. resistor load to common at analog output 500 Accuracy on analog output Max. error: 0.8 % of full scale Resolution on analog output 8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS-485 serial communication: Terminal number 68 (P,TX+, RX+), 69 (N,TX-, RX-) Terminal number 61 Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the supply voltage (PELV).
i
approx. 4 k
10 1
67
Specifications AF-600 FP Operating Instructions
Digital output: Programmable digital/pulse outputs 2
Terminal number 27, 29 Voltage level at digital/frequency output 0 - 24 V Max. output current (sink or source) 40 mA Max. load at frequency output 1 k Max. capacitive load at frequency output 10 nF Minimum output frequency at frequency output 0 Hz Maximum output frequency at frequency output 32 kHz Accuracy of frequency output Max. error: 0.1 % of full scale Resolution of frequency outputs 12 bit
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output: Terminal number 12, 13 Max. load 200mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs.
Relay outputs: Programmable relay outputs 2 Relay 01 Terminal number 1-3 (break), 1-2 (make) Max. terminal load (AC-1)1) on 1-3 (NC), 1-2 (NO) (Resistive load) 240V AC, 2A
Max. terminal load (AC-15)1) (Inductive load @ cosφ 0.4) 240V AC, 0.2A Max. terminal load (DC-1)1) on 1-2 (NO), 1-3 (NC) (Resistive load) 60V DC, 1A
Max. terminal load (DC-13)1) (Inductive load) 24V DC, 0.1A Relay 02 Terminal number 4-6 (break), 4-5 (make) Max. terminal load (AC-1)1) on 4-5 (NO) (Resistive load)
Max. terminal load (AC-15)1) on 4-5 (NO) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
100
Max. terminal load (DC-1)1) on 4-5 (NO) (Resistive load) 80V DC, 2A
Max. terminal load (DC-13)1) on 4-5 (NO) (Inductive load) 24V DC, 0.1A
Max. terminal load (AC-1)1) on 4-6 (NC) (Resistive load) 240V AC, 2A Max. terminal load (AC-15)1) on 4-6 (NC) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)1) on 4-6 (NC) (Resistive load) 50V DC, 2A
Max. terminal load (DC-13)1) on 4-6 (NC) (Inductive load) 24V DC, 0.1A Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24V DC 10mA, 24V AC 2 mA Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1) IEC 60947 t 4 and 5 The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300V AC 2A
2)3)
400V AC, 2A
1)
Control card, 10 V DC output: Terminal number 50 Output voltage 10.5 V ±0.5 V Max. load 25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics: Resolution of output frequency at 0 - 1000 Hz +/- 0.003 Hz System response time (terminals 18, 19, 27, 29, 32, 33) 2 ms Speed control range (open loop) 1:100 of synchronous speed Speed accuracy (open loop) 30 - 4000 rpm: Maximum error of ±8 rpm
All control characteristics are based on a 4-pole asynchronous motor
68
Specifications AF-600 FP Operating Instructions
0
Surroundings: Unit Size 1x types IP 20/Chassis, IP 21kit/Type 1, IP55/Type12 Unit Size 21 and 22 types IP55/Type12 Unit Size 23 and 24 types IP20/Chassis Unit Size 31 and 32 types IP55/Type 12 Unit Size 33 and 34 types IP20/Chassis Unit Size 41, 42, and 51 types IP21/Type 1, IP54/Type12 Unit Size 43, 44, and 52 types IP00/Chassis Unit Size 61/63 IP21, 54/Type1, 12 Unit Size 62/64 IP21, 54/Type1, 12 IP21/Nema 1 kit for all unit sizes 1x, 2x, and 3x IP21/NEMA 1/on top of enclosure Vibration test all enclosure types 1.0g Relative humidity 5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation Aggressive environment (IEC 60068-2-43) H2S test Test method according to IEC 60068-2-43 H2S (10 days) Ambient temperature (at 60 AVM switching mode)
- with derating max. 50°C
class Kd
1)
- with full output power of typical EFF2 motors (up to 90% output current) max. 50 °C
- at full continuous Drive output current max. 45 °C
1)
For more information on derating see the AF-600 FP Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation 0°C Minimum ambient temperature at reduced performance - 10°C Temperature during storage/transport -25 - +65/70°°C Maximum altitude above sea level without derating 1000m Maximum altitude above sea level with derating 3000m
Derating for high altitude, see section on special conditions
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
EMC standards, Immunity
See section on special conditions!
Control card performance: Scan interval 5 ms
Control card, USB Serial Communication: USB standard 1.1 (Full speed) USB plug USB type B “device” plug
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
CAUTION
Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB connection is connector on drive or an isolated USB cable/converter.
not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB
1)
1)
10 1
69
Specifications AF-600 FP Operating Instructions
Protection and Features:
Electronic thermal overload motor protection against overload.
Temperature monitoring of the heatsink ensures that the drive trips if the temperature reaches 95°C ± 5°C. An
overload temperature cannot be reset until the temperature of the heatsink is below 70°C ± 5°C (Guideline - these temperatures may vary for different power sizes, enclosures etc.). The drive has an auto derating function to avoid it's heatsink reaching 95°C.
The drive is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the drive trips if the intermediate circuit voltage is too
low or too high.
The drive is protected against earth faults on motor terminals U, V, W.
100
70
Specifications AF-600 FP Operating Instructions
0
10.3 Fuse Tables
It is recommended to use fuses and/ or Circuit Breakers on the supply side as protection in case of component break­down inside the drive (first fault).
NOTE
This is mandatory in order to ensure compliance with IEC 60364 for CE or NEC 2009 for UL.
WARNING
Personnel and property must be protected against the consequence of component break-down internally in the drive.
Branch Circuit Protection In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be protected against short-circuit and over-current according to national/international regulations.
NOTE
The recommendations given do not cover Branch circuit protection for UL.
10.3.1 Recommendations
WARNING
In case of malfunction, not following the recommendation may result in personnel risk and damage to the drive and other equipment.
The following tables list the recommended rated current. Recommended fuses are of the type gG for small to medium power sizes. For larger powers, aR fuses are recommended. Circuit breakers must be used provided they meet the national/international regulations and they limit the energy into the drive to an equal or lower level than the compliant circuit breakers.
If fuses/Circuit Breakers according to recommendations are chosen, possible damages on the drive will mainly be limited to damages inside the unit.
Short-circuit protection: GE recommends using the fuses/Circuit Breakers mentioned below to protect service personnel and property in case of component break-down in the drive.
Over current protection: The drive provides overload protection to limit threats to human life, property damage and to avoid fire hazard due to overheating of the cables in the installation. The drive is equipped with an internal over current protection (F-43 Current Limit) that can be used for upstream overload protection (UL-applications excluded). Moreover, fuses or Circuit Breakers can be used to provide the over current protection in the installation. Over current protection must always be carried out according to national regulations.
10 1
71
Specifications AF-600 FP Operating Instructions
10.3.2 CE Compliance
Fuses or Circuit Breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V, or 600V depending on the drive voltage rating. With the proper fusing the drive short circuit current rating (SCCR) is 100,000 Arms.
AF-600 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level
[HP] [A]
1
2
3
5gG-20 gG-32
7,5
15
20
25
30 gG-125 gG-150
40 aR-160 aR-160
50 aR-200 aR-200
60 aR-250 aR-250
gG-16 gG-25
gG-50 gG-63 PKZM4-50 5010
gG-80 gG-125 NZMB1-A100 100
PKZM0-25 25
NZMB2-A200 150
NZMB2-A250 250
Table 10.7 200-240V, IP20/Open Chassis
AF-600 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level
[HP] [A]
1
100
2
3
5
7,5
10
15
20 gG-80 gG-100 NZMB1-A100 100
25
40 aR-160 aR-160
50 aR-200 aR-200
60 aR-250 aR-250
Table 10.8 200-240V, IP55/Nema 12
gG-20 gG-32 PKZM0-25 25
gG-63 gG-80 PKZM4-63 63
gG-125 gG-160
NZMB2-A200 16030
NZMB2-A250 250
72
Specifications AF-600 FP Operating Instructions
0
AF-600 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level
[HP] [A]
1
2
3
5
7,5
10
15
25
30
40
50
60 gG-125 gG-150
75 aR-160 aR-160
100
125
150 gG-300 gG-300
200 gG-350 gG-350
250 gG-400 gG-400
300 gG-500 gG-500
350 gG-630 gG-630
450 aR-700 aR-700
500
600
650
750
900
1000
1200
1350
gG-16 gG-25
PKZM0-25 25
gG-20 gG-32
gG-50 gG-63 PKZM4-50 5020
gG-80 gG-125 NZMB1-A100 100
NZMB2-A200 150
aR-250 aR-250 NZMB2-A250 250
aR-900 aR-900550
aR-1600 aR-1600
aR-2000 aR-2000
aR-2500 aR-2500
--
10 1
Table 10.9 380-480V, IP20/Open Chassis
73
Specifications AF-600 FP Operating Instructions
AF-600 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level
[HP] [A]
1 gG-20 gG-32 PKZM0-25 25
2
3
5
7,5
10
15 gG-50 gG-80 PKZM4-63 63
20
25
30 gG-80 gG-100 NZMB1-A100 100
40
50 gG-125 gG-160 NZMB2-A200 160
60
75
100 aR-250 aR-250 NZMB2-A250 250
125
150 gG-300 gG-300
200 gG-350 gG-350
250 gG-400 gG-400
300 gG-500 gG-500
350 gG-630 gG-630
450 aR-700 aR-700
500
aR-900 aR-900550
600
650
750
100
900
1000
1200
1350
aR-1600 aR-1600
aR-2000 aR-2000
aR-2500 aR-2500
--
Table 10.10 380-480V, IP55/Nema 12
74
Specifications AF-600 FP Operating Instructions
0
AF-600 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level
[HP] [A]
1
2
3
5
7,5
10
15
25
30
40
50
60
75
100
125
150 aR-315 aR-315
200
250
300 aR-400 aR-400
350 aR-500 aR-500
400 aR-550 aR-550
450
500
600
650
750
950
1000
1150
1350 aR-2000 aR-2000
gG-10 gG-25
PKZM0-25 25
gG-16 gG-32
gG-35 gG-63 PKZM4-50 5020
gG-63 gG-125 NZMB1-A100 100
gG-100 gG-150 NZMB2-A200 150
aR-250 aR-250 NZMB2-A250 250
aR-350 aR-350
aR-700 aR-700
aR-900 aR-900
aR-1600 aR-1600
--
10 1
Table 10.11 525-600V, IP20/Open Chassis
75
Specifications AF-600 FP Operating Instructions
AF-600 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level
[HP] [A]
1
2
3
5
7,5
10
15
25
30
40
50
75
125
150 aR-315 aR-315
200
250
300 aR-400 aR-400
350 aR-500 aR-500
400 aR-550 aR-550
450
500
600
650
750
100
950
1000
1150
1350 aR-2000 aR-2000
gG-16 gG-32 PKZM0-25 25
gG-35 gG-80 PKZM4-63 6320
gG-50 gG-100 NZMB1-A100 100
gG-125 gG-160
aR-250 aR-250100
aR-350 aR-350
aR-700 aR-700
aR-900 aR-900
aR-1600 aR-1600
NZMB2-A200 16060
NZMB2-A250 250
--
Table 10.12 525-600V, IP55/Nema 12
76
Specifications AF-600 FP Operating Instructions
0
10.3.3 NEC and UL Compliance
Fuses or Circuit Breakers are mandatory to comply with NEC 2009. We recommend using a selection of the following
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 600V depending on the drive voltage rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Recommended max. fuse
AF-600 1-
phase
Power
AF-600 3-
phase
Power
HP HP
1 KTN-R-10 JKS-10 JJN-10 FNQ-R-10 KTK-R-10 LP-CC-10
2 KTN-R-15 JKS-15 JJN-15 FNQ-R-15 KTK-R-15 LP-CC-15
2 3 KTN-R-20 JKS-20 JJN-20 FNQ-R-20 KTK-R-20 LP-CC-20
35
57.5-10
7.5 15
10 20
25-30
20 40
30 50
60
Bussmann Bussmann Bussmann Bussmann Bussmann Bussmann
Type RK1
KTN-R-30 JKS-30 JJN-30 FNQ-R-30 KTK-R-30 LP-CC-30
KTN-R-50 KS-50 JJN-50 - - -
KTN-R-60 JKS-60 JJN-60 - - -
KTN-R-80 JKS-80 JJN-80 - - -
KTN-R-125 JKS-125 JJN-125 - - -
KTN-R-150 JKS-150 JJN-150 - - -
KTN-R-200 JKS-200 JJN-200 - - -
KTN-R-250 JKS-250 JJN-250 - - -
1)
Type J Type T Type CC Type CC Type CC
Table 10.13 200-240V
Recommended max. fuse
AF-600 1-
phase
Power
Table 10.14 200-240V
AF-600 3-
phase
Power
HP HP Type RK1 Type RK1 Type CC
1 5017906-010 KLN-R-10 ATM-R-10 A2K-10-R
2 5017906-016 KLN-R-15 ATM-R-15 A2K-15-R
2 3 5017906-020 KLN-R-20 ATM-R-20 A2K-20-R
35
57.5-10
7.5 15
10 20
25-30
20 40
30 50
60
SIBA Littel fuse
5012406-032 KLN-R-30 ATM-R-30 A2K-30-R
5014006-050 KLN-R-50 - A2K-50-R
5014006-063 KLN-R-60 - A2K-60-R
5014006-080 KLN-R-80 - A2K-80-R
2028220-125 KLN-R-125 - A2K-125-R
2028220-150 KLN-R-150 - A2K-150-R
2028220-200 KLN-R-200 - A2K-200-R
2028220-250 KLN-R-250 - A2K-250-R
Ferraz-
Shawmut
Ferraz-
Shawmut
Type RK1
3)
10 1
77
Specifications AF-600 FP Operating Instructions
Recommended max. fuse
AF-600 1-
phase
Table 10.15 200-240V
AF-600 3-
phase
HP HP
1
2
23
35
57.5-10
7.5 15
10 20
25-30
20 40
30 50
60
Bussmann Littel fuse
Type JFHR2
FWX-10 - - HSJ-10
FWX-15 - - HSJ-15
FWX-20 - - HSJ-20
FWX-30 - - HSJ-30
FWX-50 - - HSJ-50
FWX-60 - - HSJ-60
FWX-80 - - HSJ-80
FWX-125 - - HSJ-125
FWX-150 L25S-150 A25X-150 HSJ-150
FWX-200 L25S-200 A25X-200 HSJ-200
FWX-250 L25S-250 A25X-250 HSJ-250
2)
Type JFHR2
1) KTS-fuses from Bussmann may substitute KTN for 240V frequency converters.
2) FWH-fuses from Bussmann may substitute FWX for 240V frequency converters.
3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240V frequency converters.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240V frequency converters.
Ferraz-
Shawmut
Type JFHR2
Ferraz-
Shawmut
4)
Type J
Recommended max. fuse
AF-600
1-phase
100
[HP] [HP] Type RK1 Type J Type T Type CC Type CC Type CC
10 30 KTS-R-60 JKS-60 JJS-60 - - -
15 40 KTS-R-80 JKS-80 JJS-80 - - -
25 75 KTS-R-150 JKS-150 JJS-150 - - -
50 100 KTS-R-200 JKS-200 JJS-200 - - -
Table 10.16 380-480V, 125HP and below
AF-600
3-phase
1 KTS-R-6 JKS-6 JJS-6 FNQ-R-6 KTK-R-6 LP-CC-6
2-3 KTS-R-10 JKS-10 JJS-10 FNQ-R-10 KTK-R-10 LP-CC-10
5 KTS-R-20 JKS-20 JJS-20 FNQ-R-20 KTK-R-20 LP-CC-20
7.5 KTS-R-25 JKS-25 JJS-25 FNQ-R-25 KTK-R-25 LP-CC-25
10 KTS-R-30 JKS-30 JJS-30 FNQ-R-30 KTK-R-30 LP-CC-30
15-20 KTS-R-40 JKS-40 JJS-40 - - -
25 KTS-R-50 JKS-50 JJS-50 - - -
50 KTS-R-100 JKS-100 JJS-100 - - -
60 KTS-R-125 JKS-125 JJS-125 - - -
125 KTS-R-250 JKS-250 JJS-250 - - -
Bussmann Bussmann Bussmann Bussmann Bussmann Bussmann
78
Specifications AF-600 FP Operating Instructions
0
Recommended max. fuse
AF-600 1-phase AF-600 3-phase SIBA Littel fuse
[HP] [HP] Type RK1 Type RK1 Type CC Type RK1
1 5017906-006 KLS-R-6 ATM-R-6 A6K-10-6
2-3 5017906-010 KLS-R-10 ATM-R-10 A6K-10-R
5 5017906-020 KLS-R-20 ATM-R-20 A6K-20-R
7.5 5017906-025 KLS-R-25 ATM-R-25 A6K-25-R
10 5012406-032 KLS-R-30 ATM-R-30 A6K-30-R
15-20 5014006-040 KLS-R-40 - A6K-40-R
25 5014006-050 KLS-R-50 - A6K-50-R
10 30 5014006-063 KLS-R-60 - A6K-60-R
15 40 2028220-100 KLS-R-80 - A6K-80-R
50 2028220-125 KLS-R-100 - A6K-100-R
60 2028220-125 KLS-R-125 - A6K-125-R
25 75 2028220-160 KLS-R-150 - A6K-150-R
50 100 2028220-200 KLS-R-200 - A6K-200-R
125 2028220-250 KLS-R-250 - A6K-250-R
Table 10.17 380-480V, 125HP and below
Recommended max. fuse
AF-600 1-phase AF-600 3-phase Bussmann Ferraz- Shawmut Ferraz- Shawmut Littel fuse
[HP] [HP] Type JFHR2 Type J
1FWH-6 HSJ-6 - -
2-3 FWH-10 HSJ-10 - -
5FWH-20 HSJ-20 - -
7.5 FWH-25 HSJ-25 - -
10 FWH-30 HSJ-30 - -
15-20 FWH-40 HSJ-40 - -
25 FWH-50 HSJ-50 - -
10 30 FWH-60 HSJ-60 - -
15 40 FWH-80 HSJ-80 - -
50 FWH-100 HSJ-100 - -
60 FWH-125 HSJ-125 - -
25 75 FWH-150 HSJ-150 - -
50 100 FWH-200 HSJ-200 A50-P-225 L50-S-225
125 FWH-250 HSJ-250 A50-P-250 L50-S-250
Ferraz-
Shawmut
Type JFHR2
1)
Ferraz-
Shawmut
Type JFHR2
10 1
Table 10.18 380-480V, 125HP and below
1) Ferraz-Shawmut A50QS fuses may substitute for A50P fuses.
79
Specifications AF-600 FP Operating Instructions
Recommended max. fuse
AF-600 Bussmann Bussmann Bussmann Bussmann Bussmann Bussmann
[HP] Type RK1 Type J Type T Type CC Type CC Type CC
1 KTS-R-5 JKS-5 JJS-6 FNQ-R-5 KTK-R-5 LP-CC-5
2-3 KTS-R-10 JKS-10 JJS-10 FNQ-R-10 KTK-R-10 LP-CC-10
5 KTS-R20 JKS-20 JJS-20 FNQ-R-20 KTK-R-20 LP-CC-20
7.5 KTS-R-25 JKS-25 JJS-25 FNQ-R-25 KTK-R-25 LP-CC-25
10 KTS-R-30 JKS-30 JJS-30 FNQ-R-30 KTK-R-30 LP-CC-30
15-20 KTS-R-35 JKS-35 JJS-35 - - -
25 KTS-R-45 JKS-45 JJS-45 - - -
30 KTS-R-50 JKS-50 JJS-50 - - -
40 KTS-R-60 JKS-60 JJS-60 - - -
50 KTS-R-80 JKS-80 JJS-80 - - -
60 KTS-R-100 JKS-100 JJS-100 - - -
75 KTS-R-125 JKS-125 JJS-125 - - -
100 KTS-R-150 JKS-150 JJS-150 - - -
125 KTS-R-175 JKS-175 JJS-175 - - -
Table 10.19 525-600V, 125HP and below
Recommended max. fuse
AF-600 SIBA Littel fuse
[HP] Type RK1 Type RK1 Type RK1 Type J
1 5017906-005 KLS-R-005 A6K-5-R HSJ-6
2-3 5017906-010 KLS-R-010 A6K-10-R HSJ-10
5 5017906-020 KLS-R-020 A6K-20-R HSJ-20
7.5 5017906-025 KLS-R-025 A6K-25-R HSJ-25
10 5017906-030 KLS-R-030 A6K-30-R HSJ-30
100
15-20 5014006-040 KLS-R-035 A6K-35-R HSJ-35
25 5014006-050 KLS-R-045 A6K-45-R HSJ-45
30 5014006-050 KLS-R-050 A6K-50-R HSJ-50
40 5014006-063 KLS-R-060 A6K-60-R HSJ-60
50 5014006-080 KLS-R-075 A6K-80-R HSJ-80
60 5014006-100 KLS-R-100 A6K-100-R HSJ-100
75 2028220-125 KLS-R-125 A6K-125-R HSJ-125
100 2028220-150 KLS-R-150 A6K-150-R HSJ-150
125 2028220-200 KLS-R-175 A6K-175-R HSJ-175
Ferraz-
Shawmut
Ferraz-
Shawmut
Table 10.20 525-600V, 125HP and below
1) 170M fuses shown from Bussmann use the -/80 visual indicator. –TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be substituted.
80
Specifications AF-600 FP Operating Instructions
0
Recommended max. fuse
Alternate
AF-600 Bussmann PN
[HP] Type JFHR2 Type JFHR2 Type T/JDDZ Type JFHR2 Type JFHR2 Type JFHR2
150 170M3017 FWH-300 JJS-300 2028220-315 L50-S-300 A50-P-300
200 170M3018 FWH-350 JJS-350 2028220-315 L50-S-350 A50-P-350
250 170M4012 FWH-400 JJS-400 206xx32-400 L50-S-400 A50-P-400
300 170M4014 FWH-500 JJS-500 206xx32-500 L50-S-500 A50-P-500
350 170M4016 FWH-600 JJS-600 206xx32-600 L50-S-600 A50-P-600
450 170M4017 20 610 32.700 6.9URD31D08A070
500 170M6013 22 610 32.900 6.9URD33D08A090
550 170M6013 22 610 32.900 6.9URD33D08A090
600 170M6013 22 610 32.900 6.9URD33D08A090
650 170M7081
750 170M7081
900 170M7082
1000 170M7082
1200 170M7083
1350 170M7083
External
Bussmann PN
Alternate
External
Bussmann PN
Alternate
External
Siba PN
Alternate External
Littlefuse PN
Alternate
External
Ferraz-
Shawmut PN
Alternate External
Ferraz-Shawmut
PN
0
0
0
0
Table 10.21 525-690V, above 125HP
AF-600 Bussmann PN Rating Alternate Siba PN
[HP]
650 170M8611 1100A, 1000V 20 781 32.1000
750 170M8611 1100A, 1000V 20 781 32.1000
900 170M6467 1400A, 700V 20 681 32.1400
1000 170M6467 1400A, 700V 20 681 32.1400
1200 170M8611 1100A, 1000V 20 781 32.1000
1350 170M6467 1400A, 700V 20 681 32.1400
Table 10.22 380-480V, Frame Size 6, Inverter Module DC Link Fuses
10 1
81
Specifications AF-600 FP Operating Instructions
AF-600
[HP] Type JFHR2 Type JFHR2
150 170M3017 2061032,315 6.9URD30D08A0315
200 170M3018 2061032,35 6.9URD30D08A0350
250 170M4011 2061032,35 6.9URD30D08A0350
300 170M4012 2061032,4 6.9URD30D08A0400
350 170M4014 2061032,5 6.9URD30D08A0500
400 170M5011 2062032,55 6.9URD32D08A0550
450 170M4017 20 610 32.700 6.9URD31D08A0700
500 170M4017 20 610 32.700 6.9URD31D08A0700
600 170M6013 22 610 32.900 6.9URD33D08A0900
650 170M6013 22 610 32.900 6.9URD33D08A0900
750 170M7081
950 170M7081
1050 170M7081
1150 170M7081
1350 170M7082
1550 170M7083
Table 10.23 380-480V, above 125HP
AF-600 Bussmann PN Rating Alternate Siba PN
[HP]
750 170M8611 1100A, 1000V 20 781 32.1000
950 170M8611 1100A, 1000V 20 781 32.1000
1050 170M8611 1100A, 1000V 20 781 32.1000
1150 170M8611 1100A, 1000V 20 781 32.1000
1350 170M8611 1100A, 1000V 20 781 32.1000
100
1550 170M8611 1100A, 1000V 20 781 32.1000
Bussmann PN Alternate External
Siba PN
Alternate External
Ferraz-Shawmut PN
Table 10.24 525-690V, Frame Size 6, Inverter Module DC Link Fuses
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be substituted for external use **Any minimum 500V UL listed fuse with associated current rating may be used to meet UL requirements.
82
Specifications AF-600 FP Operating Instructions
0
10.3.4 Substitute Fuses for 240 V
Original fuse Manufacturer Substitute fuses
KTN Bussmann KTS
FWX Bussmann FWH
KLNR LITTEL FUSE KLSR
L50S LITTEL FUSE L50S
A2KR FERRAZ SHAWMUT A6KR
A25X FERRAZ SHAWMUT A50X
10.4 Connection Tightening Torques
Power (HP) Torque (Nm)
Unit 200-240V 380-480V 525-600V Mains Motor
12 1-3 1-5 1-5 1.8 1.8 1.8 1.8 3 0.6
13 5 7.5-10 7.5-10 1.8 1.8 1.8 1.8 3 0.6
15 1-5 1-10 1-10 1.8 1.8 1.8 1.8 3 0.6
21 7.5-15 15-25 15-25 1.8 1.8 1.5 1.5 3 0.6
22
23 7.5-15 15-25 15-25 1.8 1.8 1.8 1.8 3 0.6
24 20-25 30-50 30-50 4.5 4.5 4.5 4.5 3 0.6
31 25-40 50-75 50-75 10 10 10 10 3 0.6
32 50-60 100-125 100-125
33 30-40 60-75 60-75 10 10 10 10 3 0.6
34 50-60 100-125 100-125
Table 10.25 Tightening of Terminals
-
20
30
40
30
40
4.5
4.5
14/24
14/24
2)
1)
1)
4.5
4.5
14/24
14/24
2)
1)
1)
DC
connection
3.7
3.7
14 14 3 0.6
14 14 3 0.6
Brake Earth Relay
3.7
3.7
3
3
0.6
0.6
10 1
1) For different cable dimensions x/y, where x 95mm2 and y 95mm2.
2
2) Cable dimensions above 18.5kW 35mm
and below 22kW 10mm2.
83
Index AF-600 FP Operating Instructions
Index
A
A53............................................................................................................. 17
A54............................................................................................................. 17
AC
Input................................................................................................. 6, 14
Mains......................................................................................... 6, 10, 14
Waveform.............................................................................................. 6
Accel Time............................................................................................... 22
Alarm Log......................................................................................... 27, 25
Alarm/Warning Code List.................................................................. 51
Alarms....................................................................................................... 49
Analog
Inputs..................................................................................... 15, 52, 67
Output........................................................................................... 15, 67
Apogee FLN®.......................................................................................... 18
Application Examples......................................................................... 41
Approvals................................................................................................... 1
Auto
Auto........................................................................................ 26, 46, 47
Mode..................................................................................................... 25
Tune...................................................................................................... 21
Auto-reset............................................................................................... 24
AWG........................................................................................................... 60
B
Back Plate................................................................................................... 9
Branch Circuit Protection................................................................... 71
Cooling
Cooling................................................................................................... 8
Clearance............................................................................................ 20
Copying Parameter Settings............................................................ 26
Current
Limit...................................................................................................... 22
Rating............................................................................................... 8, 52
D
DC
Current............................................................................................ 6, 47
Link........................................................................................................ 52
Decel Time.............................................................................................. 22
Derating................................................................................. 52, 69, 70, 8
Digital
Input.............................................................................................. 47, 53
Inputs..................................................................................... 15, 48, 66
Output.................................................................................................. 68
Disconnect
Switch................................................................................................... 21
Switches.............................................................................................. 19
Drive Profile............................................................................................ 18
E
Electrical Noise...................................................................................... 12
EMC..................................................................................................... 20, 69
External
Commands..................................................................................... 6, 46
Controllers............................................................................................. 6
Interlock........................................................................................ 31, 42
Voltage................................................................................................. 29
C
Cable Lengths And Cross Sections................................................. 66
Circuit Breakers...................................................................................... 20
Clearance
Clearance............................................................................................... 8
Requirements....................................................................................... 8
Closed Loop............................................................................................ 17
Communication Option..................................................................... 54
Conduit....................................................................................... 11, 20, 14
Control
Cables................................................................................................... 17
Card Performance............................................................................ 69
Card, 10 V DC Output..................................................................... 68
Card, 24 V DC Output..................................................................... 68
Card, RS-485 Serial Communication:........................................ 67
Card, USB Serial Communication:.............................................. 69
Characteristics................................................................................... 68
Signal...................................................................................... 28, 30, 46
System.................................................................................................... 6
Terminals................................................... 10, 26, 46, 48, 66, 30, 16
Wire....................................................................................................... 16
Wiring....................................................................... 11, 12, 16, 20, 15
F
Fault
Log.................................................................................................. 25, 27
Messages............................................................................................. 51
Feedback.............................................................. 17, 20, 54, 41, 47, 56
Floating Delta........................................................................................ 15
Full Load Current.............................................................................. 8, 19
Functional Testing.................................................................... 6, 22, 19
Fuses..................................................................................... 20, 54, 57, 71
Fusing................................................................................................ 11, 20
G
General Technical Data...................................................................... 66
Ground
Connections................................................................................ 12, 20
Loops.................................................................................................... 17
Wire................................................................................................ 12, 20
Grounded Delta.................................................................................... 15
84
Index AF-600 FP Operating Instructions
Grounding
Grounding.............................................................. 12, 13, 15, 19, 20
Using Conduit................................................................................... 13
Using Shielded Cable...................................................................... 13
H
Hand............................................................................................ 22, 26, 46
Harmonics.................................................................................................. 6
I
IEC 61800-3...................................................................................... 15, 69
Induced Voltage.................................................................................... 11
Initialisation............................................................................................ 27
Input
Current................................................................................................. 14
Power..................................................... 11, 12, 20, 49, 57, 6, 14, 19
Signal.................................................................................................... 29
Signals.................................................................................................. 17
Terminals................................................................. 10, 14, 17, 19, 52
Voltage.......................................................................................... 21, 49
Installation............................................................ 6, 8, 9, 16, 18, 20, 21
Isolated Mains........................................................................................ 15
L
Leakage
Current.......................................................................................... 19, 12
Current (>3,5mA)............................................................................. 12
Lifting.......................................................................................................... 9
Local
Control................................................................................... 24, 26, 46
Mode..................................................................................................... 22
Operation............................................................................................ 24
Start....................................................................................................... 22
Local-control Test................................................................................. 22
Motor
Cables................................................................................ 8, 11, 13, 22
Current....................................................................... 6, 21, 52, 55, 25
Data........................................................................... 21, 22, 27, 52, 55
Frequency.................................................................................... 21, 25
Output.................................................................................................. 66
Power....................................................................... 10, 11, 12, 55, 25
Protection.................................................................................... 11, 70
Rotation........................................................................................ 22, 25
Speeds.................................................................................................. 21
Status...................................................................................................... 6
Wiring............................................................................................ 11, 13
Wiring, And......................................................................................... 20
Mounting............................................................................................ 9, 20
Multiple
Frequency Converters............................................................. 11, 13
Motors.................................................................................................. 19
N
Navigation Keys................................................................ 28, 46, 24, 26
Noise Isolation................................................................................ 11, 20
O
Open Loop................................................................................ 17, 28, 68
Operation Keys...................................................................................... 26
Optional Equipment................................................................ 13, 21, 6
Output
Current................................................................................... 46, 52, 68
Performance (U, V, W)..................................................................... 66
Signal.................................................................................................... 32
Terminals...................................................................................... 10, 19
Overcurrent............................................................................................ 47
Overload Protection........................................................................ 8, 11
Overvoltage..................................................................................... 66, 47
M
Main Menu....................................................................................... 28, 25
Mains
Mains.................................................................................................... 11
Supply........................................................................................... 59, 65
Voltage............................................................................ 25, 26, 46, 66
Manual Initialisation............................................................................ 27
Menu
Keys................................................................................................ 24, 25
Structure....................................................................................... 26, 32
Metasys N2®............................................................................................ 18
Modbus RTU........................................................................................... 18
P
PELV...................................................................................... 15, 44, 66, 68
Power
Connections....................................................................................... 11
Factor................................................................................. 6, 13, 20, 66
Power-dependent................................................................................ 59
Pre-start.................................................................................................... 19
Programming
Programming.......... 6, 22, 25, 27, 31, 32, 40, 52, 21, 24, 26, 28
Example............................................................................................... 28
Protection And Features.................................................................... 70
Pulse Inputs............................................................................................ 67
Q
Quick
Menu................................................................................ 21, 28, 31, 25
Set-up................................................................................................... 21
85
Index AF-600 FP Operating Instructions
Thermistor
R
RCD............................................................................................................ 12
Reference....................................................................... 1, 41, 46, 47, 25
Relay Outputs................................................................................. 16, 68
Remote
Commands............................................................................................ 6
Programming.................................................................................... 40
Reference............................................................................................ 47
Reset......................................................... 24, 27, 48, 49, 52, 56, 70, 26
RFI Filter................................................................................................... 15
RMS Current.............................................................................................. 6
Run
Command........................................................................................... 23
Permissive........................................................................................... 47
Thermistor............................................................................ 15, 52, 44
Control Wiring................................................................................... 15
Tightening Of Terminals.................................................................... 83
Torque
Characteristics................................................................................... 66
Limit...................................................................................................... 22
Transient Protection.............................................................................. 6
Trip
Trip........................................................................................................ 49
Function.............................................................................................. 11
Trip-lock................................................................................................... 49
Troubleshooting........................................................................ 6, 51, 57
V
Voltage Level.......................................................................................... 66
S
Safety Inspection.................................................................................. 19
Screened Control Cables................................................................... 17
Serial Communication..... 6, 10, 15, 17, 26, 27, 46, 47, 48, 49, 18
Set Up....................................................................................................... 25
Setpoint.................................................................................................... 47
Set-up................................................................................................ 23, 25
Shielded
Cable......................................................................................... 8, 11, 20
Wire....................................................................................................... 11
Sleep Mode............................................................................................. 47
Specifications......................................................................... 6, 9, 18, 59
Speed Reference....................................................... 17, 23, 30, 46, 42
Start Up.................................................................... 6, 27, 28, 19, 20, 57
Status
Messages............................................................................................. 46
Mode..................................................................................................... 46
Supply Voltage.......................................................... 15, 19, 54, 67, 66
Surroundings......................................................................................... 69
Switching Frequency................................................................... 47, 52
Symbols...................................................................................................... 1
System
Feedback............................................................................................... 6
Monitoring.......................................................................................... 49
Start Up................................................................................................ 23
W
Warning
And Alarm Definitions.................................................................... 50
And Alarm Displays......................................................................... 49
And Alarm Types.............................................................................. 49
Warnings.................................................................................................. 49
Wire Sizes.......................................................................................... 11, 13
T
Technical Data....................................................................................... 66
Temperature Limits............................................................................. 20
Terminal
53............................................................................................. 28, 17, 29
54........................................................................................................... 17
Programming.................................................................................... 17
Programming Examples................................................................ 30
86
The instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered suȻciently for the purchaser·s purposes, the matter should be referred to the GE company.
AF-600 FP is a trademark of the General Electric Company.
GE 41 Woodford Avenue Plainville, CT 06062
www.geelectrical.com/drives
130R0357
*MG11Q302*
DET-609B
Loading...