System 18RLFCC Submittal
AOU18RLFC, AUU18RLF Compact Cassette
Job Name:_______________________________ Approval:__________________Date:_________
Location: ________________________________ Construction: ____________________________
Engineer:________________________________ Unit #:__________________________________
Submitted to:_____________________________ Drawing #:_______________________________
Submitted by:_____________________________ Reference:_______________________________
|
Outdoor Unit Power |
|
208-230/VAC-1Ph-60Hz |
|
||||||
|
Available Voltage Range |
|
|
187-253VAC |
|
|||||
|
Fuse Size, Max. |
|
|
|
20A |
|
||||
|
MCA |
|
|
|
17.3A |
|
|
|||
|
Compressor |
|
Inverter Driven Variable Speed DC Rotary |
|
||||||
|
No. used |
|
|
|
1 |
|
|
|
|
|
|
Output |
|
|
|
1000W |
|
||||
|
Lubrican Oil |
|
|
|
POE (RB68) |
|
|
|||
|
Fan type |
|
|
|
Propeller |
|
||||
|
Motor Output |
|
|
|
115W |
|
||||
|
Airflow Rate |
Cooling/Heating |
(High) |
1457 / 1407CFM |
|
|
||||
|
Refrigerant |
|
|
|
410A |
|
||||
|
Outdoor Unit |
|
|
|
2lbs 14oz |
|
||||
|
Contrlol |
|
|
Electronic Expansion Valve |
|
|||||
|
O.D. Discharge |
|
(in) |
|
1/4”(Flare) |
|
||||
|
O.D Suction |
|
(in) |
|
1/2”(Flare) |
|
|
|||
|
Dimensions |
|
|
|
H x W x D |
|
||||
|
Uncrated |
|
(in) |
24-1/2 x 31-3/32 x 11-11/32 |
|
|||||
|
|
|
||||||||
|
|
|
|
(mm) |
|
(620 x 790 x 290) |
|
|||
|
Crated |
|
(in) |
28-1/16 x 37-7/32 x 15-9/16 |
|
|||||
|
|
|
||||||||
|
|
|
|
(mm) |
|
(713 x 945 x 395) |
|
|
||
|
Weight |
|
|
|
Outdoor |
|
||||
|
Net |
|
|
|
86lbs (39kg) |
|
||||
|
Gross Shipping |
|
|
|
93lbs (42kg) |
|
||||
|
Cooling |
|
|
|
|
|
|
|
|
|
|
Rated Capacity |
|
|
|
18,000BTU/h |
|
||||
|
Min-Max Capacity |
|
|
|
3,100~20,100BTU/h |
|
||||
|
Rated Power Input |
|
|
1.61kw |
|
|||||
|
Max. Power Input |
|
|
|
2.15kw |
|
||||
|
SEER |
|
|
|
20.1 |
|
|
|
|
|
|
Outdoor Sound Rating |
|
|
54dB |
|
|||||
|
Heating |
|
|
|
|
|
|
|
|
|
|
Rated Capacity |
|
|
|
21,600BTU/h |
|
||||
|
Min-Max Capacity |
|
|
|
3,100~25,600BTU/h |
|
||||
|
Rated Power Input |
|
|
1.76kw |
|
|||||
|
Max. Power Input |
|
|
|
2.60kw |
|
||||
|
HSPF |
|
|
|
11.5 |
|
|
|
|
|
|
Outdoor Sound Rating |
|
|
55dB |
|
|||||
|
Piping Lengths |
|
|
|
|
|
|
|
|
|
|
Max. Piping Length (Total) |
|
66ft |
|
||||||
|
Max. Pipe Height Difference |
|
49ft |
|
||||||
|
Connection method |
|
|
(Flared) |
|
|||||
|
Operating Range |
|
|
. |
. |
|
|
|
|
|
|
Cooling |
|
|
|
14°F~115°F DB |
|
||||
|
Heating |
|
|
|
-5°F~75°F DB |
|
||||
Fujitsu General America, Inc. |
|
|
|
|
|
|
||||
Fairfield, NJ 07004 |
|
|
|
|
|
|
|
|
||
Toll Free: 1-888-888-3424 |
|
|
|
|
|
|
|
|||
Fax: (973) 836-0447 |
Fujitsu products are subject to continuous improvements. Fujitsu reserves the right to modify product design, specifications and |
|
||||||||
www.fujitsugeneral.com |
information in this data sheet without notice and without incuring any obligations. |
|