The control valve, series ZK 210, is intended solely for cutting off and/or regulating the flow of
fluids consisting of water, steam, or steam condensate.
Its use is permissible only within the allowable limits of pressure and temperature and only if
the chemical and corrosive influences on the pressure equipment are taken into account.
Before installation and operation, a check must be performed to ascertain that the valve is
resistant to the medium in the operational conditions that will exist.
Opening of the valve body and/or structural changes may be performed only if the
manufacturer's written permission is obtained.
Any type of use differing from the usage described above must be considered as improper.
The resulting risk will have to be borne by the user alone. The manufacturer hereby expressly
rejects any claims for any resulting damage.
Safety Note
The control valve ZK 210 must not be installed, removed, commissioned, operated or
maintained by anyone other than qualified staff.
"Qualified staff" are persons who are familiar with the procedures for installation, removal,
commissioning, operation and maintenance of the product, and who have qualifications
appropriate for their work, for example staff who have received the following:
Training as specialists.
Training or instruction in the use of appropriate safety procedures in accordance with the
standards of safety engineering.
Training or instruction in first aid and in accident prevention regulations.
For installation, removal, commissioning, operation and maintenance, every person who
works with the control valve must have read and understood the complete installation
instructions. Furthermore, responsibilities must have been defined clearly and unambiguously
and must be adhered to.
In addition to these installation instructions, the documents issued by the manufacturers of
the actuators, and in particular the safety information contained in these documents, must be
observed.
Usage of the control valve ZK 210 for the intended purpose includes compliance with the
rules and notes in these installation instructions for installation, removal, commissioning,
operation and maintenance.
The operating company must ensure that, whenever the control valve ZK 210 is being
operated, it is in perfect condition.
Working methods that jeopardise safety must not be used.
3
Important Notes
Warning
Danger
If the control valve is used in an inexpert or improper manner by unqualified
staff, it can cause danger to life and limb for the user or for third parties,
possibly resulting in death.
During operation, the control valve ZK 210 is under pressure. In this condition,
screws, nuts or bolts must not be slackened. Hot water or steam could flow out
and could cause severe scalding over the entire body.
During operation, the valve might be hot. If the valve is touched when in the
operational condition, severe burns are possible. It must be ensured that,
when handwheels are being operated, the operator wears gloves.
Any installation or removal work may only be performed when the equipment
is at zero pressure and has cooled down. When such work is to be done, the
pressure in the pipes upstream and downstream of the valve must have been
reduced to zero and the valve must have cooled down sufficiently. It must be
ensured that, during the work, the system section in which pressure has been
reduced to zero cannot be accidentally put back into operation. The shut-off
valves needed for this purpose must be separately secured and marked.
In addition, it must be ensured that the actuators of the valve are not in the
connected state. The connection to the energy supply (electric, pneumatic,
hydraulic) must be disconnected and must be secured to prevent it from being
operated accidentally. One or more warning notices, for example containing
the text "DO NOT SWITCH ON", must be displayed in a clearly visible manner
at each operating element.
(continued)
Ratings Pursuant to Article 9 of the Pressure Equipment Directive
GaseousLiquid
Fluid
1212
Use
Category
Nominal size of connection, DN
CE marking
The control valve may only be used in accordance with the above-mentioned ratings pursuant
to Article 9 of the Pressure Equipment Directive. Any other type of use must be considered as
improper.
NoYesNoYes
Exception
according
to Art.3.3
2532 – 100
NoYesYes---
IIIIV(safety
≥125
equipment)
---
4
Explanatory Notes
Scope of Supply
Control valve ZK 210 with or without an attached actuator, according to the order
Installation instructions for the control valve
Parts list with drawing
Operation instructions for the actuator
Acceptance certificates according to the order
Description
The control valve ZK 210 is used to reduce large differential pressures. It is used mainly in
industrial plants and power stations in which ease of maintenance and high resistance to
wear are required.
The valve consists of the valve body, a yoke suitable for the various actuators, and a ZK
radial stage nozzle with valve plug integrated in the valve body to act at the control element.
Depending on requirements, the bodies are designed as straight-through (ZK210-D/..) or
angle versions (ZK210-E/..).
The control valve can be operated by means of various actuators, e.g. electric rotary
actuators, pneumatic actuators or by means of a handwheel.
Special equipment is available, such as sampling valves, a sealing-fluid connection and selftightening stuffing boxes.
If the operating conditions of the plant change, the Kvs value and the characteristic curve of
the control valves can be adapted to suit the new conditions by turning of the sleeve insert of
the ZK radial stage nozzle, without having to remove the valve.
Control valve ZK 210-D/14 DN 25 with
handwheel
Control valve ZK 210-E/14 DN 80 with electric
rotary actuator
5
Explanatory Notes
(continued)
Function
Every control valve is equipped with a ZK radial stage nozzle .
This is a system comprising several sleeves nesting within one another and containing radial
orifices drilled in them. By rotation of the sleeves, the orifices are shifted relative to one
another, thus forming a large number of throttling points in parallel, with turbulence chambers
(expansion chambers) in between.
The throughput through the ZK radial stage nozzle is set by means of the valve plug.
Depending on its position, this valve plug opens up the individual orifices partially or
completely, thus producing different flow rates.
As a result of this design, the pressure drop is reduced in steps and the medium flowing
through is split up into many partial flows. This ensures high resistance to wear and reduces
the noise level.
On the valve plug, there is a control edge which is separate from the seat surface and closes
the orifices of the sleeve insert before the valve plug comes to rest completely against the
seat ring. As a result, wear is prevented on the surfaces of the seat. Because of the multiple,
step-by-step expansion in the turbulence chambers, the pressure drop in the region of the
seat is minimised.
Setting slotsControl edge
Orifices of sleeve
insert (sleeves
not shifted)
Seat
Orifices
Flash chambers
(sleeves shifted)
Control valve ZK 210: 3-stage radial nozzle,∆p
100 bar
max
6
7
Explanatory Notes
(continued)
Function
(continued)
For differential pressures up to 180 bar a nozzle with more than three stages is used. A fourstage nozzle is required for nominal size DN 25 and a five-stage nozzle is used for DN 50
and DN 80.
For corresponding kvs values and valve lift specifications see data sheet ZK 210.
Plug
Control edge
Setting slots
Orifices of sleeve
shown without sleeves
being shifted.
Direction of flow
Valve seat
Protective sleeve
against wear
Control valve ZK 210 DN 50: 5-stage radial nozzle, ∆p
max
180 bar
8
Explanatory Notes
(continued)
Technical Data
Important
For the technical data of the control valve ZK 210, see the name plate.
Valve positionName plate drawingName plate data
Type with nominal size of body
Gestra serial number
Valve lift
1234
50
250
Nominal size of connection [DN]
Rated pressure [bar]
Max. allowable temperature [°C] 1)
Max. allowable pressure [barg] 1)
10 LIN
1
) If there is no rated pressure stated on the name plate, the maximum allowable pressure
Kvs value, characteristic curve
limits are stated together with the associated temperatures.
Example: °C 300 | 550
barg250 | 54
The statement of differential pressure corresponds to valve inlet pressure minus valve
outlet pressure.
The scope and layout of the name plate data comply with EN 19.
Pressure/Temperature Rating
Important
In the installation instructions, standard pressure/temperature ratings are
described. For possible deviations, please see the name plate of the control
valve.
Max. allowable pressure PMA[barg]25021754
Max. allowable inlet temperature TMA[°C]300450550
Max. allowable differential pressure ∆PMX[bar]
3-stage 100 4/5-stage 180
9
Explanatory Notes
Material
Important
In the installation instructions, standard materials are described. For possible
deviations, please see the parts list supplied.
Body13 CrMo 4 4 (1.7335)
(continued)
Valve seat
Valve plug and stemX 35 CrMo 17 (1.4122)
Corrosion Resistance
If the unit is used for the intended purpose, its safety is not impaired by corrosion.
Nominal Sizes
The control valve ZK 210 is delivered with bodies of nominal size DN 25, DN 50 and DN 80.
Different connection sizes are possible as special versions.
To determine the nominal size, the nominal size of the control valve's connection, which is
stated on the name plate, is definitive.
Connections
The control valve ZK 210 is normally delivered with butt-weld ends. Other end connections
are also available on request.
X 90 CrMoV 18 hardened (1.4112) 3-stage
X 35 CrMo 17 hardened (1.4122) 4/5-stage
Operation
The control valve ZK 210 is suitable for the following actuators:
ZK 210-../01Manual operation, not convertible to electric rotary actuators
(DN 25 to DN 50 only, otherwise ZK 210/14 with handwheel)
ZK 210-../13Electric linear actuator
ZK 210-../14Version with insert bush of form B1, DIN EN ISO 5210, for attaching
an electric rotary actuator or a handwheel, whichever is desired
ZK 210-../20Pneumatic diaphragm-actuator
ZK 210-../40Hydraulic cylinder
10
Explanatory Notes
(continued)
Capacity Charts
Cold waterHot water ts –5 K
The charts show the maximum flowrates of cold and hot water at the extreme regulation
position with linear characteristic curves and maximum Kvs value.
Kvs Values and Actuator Selection Data
Important
In the installation instructions, standard values are described. For possible
deviations, please see the name plate of the control valve.
DNNozzle*)CharacteristicKvs value
[m3/h]
Valve
lift
[mm]
Revol.
for full
valve
lift
Max. admiss.
torque for
opening/
closing
[Nm].
Type/size of
actuator
DIN ISO
5210
253-stagelinear0.81.52.3183.620 / 20F10 - B1
253-stageequal %0.81.52.3183.620 / 20F10 - B1
254-stagelinear0.5132.620 / 20F10 - B1
503-stagelinear3.36.51035730 / 60F10 - B1
503-stageequal %36935730 / 60F10 - B1
505-stagelinear2234.630 / 60F10 - B1
803-stagelinear9.51828501080 / 120F10 - B1
803-stageequal %8.51825501080 / 120F10 - B1
805-stagelinear535780 / 120F10 - B1
*) 3-stage: ∆p
= 100 bar (standard), 4/5-stage: ∆p
max
= 180 bar
max
11
Operating Procedure
Installation
It is highly advisable to have the installation work done by qualified staff in the manner
described by these installation instructions. The manufacturer will not accept liability for
damage resulting from improper installation.
In addition, the installation instructions issued by the actuator manufacturers must be
observed.
During installation, it must be ensured that the installation space surrounding the valve is
large enough for the purposes of installation, removal, operation and maintenance.
Please check whether the weight of the valve makes an additional support necessary.
In the case of installation with a horizontal valve-spindle and a pneumatic actuator, the weight
of the actuator must be supported separately.
For the installation work, hoisting gear must be chosen which is designed for the weights
concerned.
The control valves may only be hoisted by the body and/or by the yoke of the valve.
During hoisting, damage to the actuator, the stuffing box and the lubricating device must be
avoided.
The control valve ZK 210 is welded into place directly into the pipe or is mounted between
flanges, depending on the connection facilities that are present.
In the case of welding-connections, the statutory and industrial rules for welding-connections
must be observed. Before welding, the welding locations must be cleaned.
Important
The valve is welded into place in the assembled state; any heat treatment that
is necessary for the welded joints can likewise be performed in the assembled
state. It must be ensured here that the region affected by the heat is limited to
the welded joints.
After the valve has been welded into place, it is recommended that it should
then be opened fully and flushed with water.
Flushing with caustic agents may only be performed if approved by the
manufacturer.
In the case of flange connections, precise positioning of the seals between the flanges must
be ensured. Before installation, the sealing surfaces must be cleaned.
Before the control valve is installed, all transportation packaging and all coverings of
connections must be removed.
12
Operating Procedure
(continued)
Installation
(continued)
Important
Attention must be paid to the direction of flow. It is indicated by an arrow on the
body.
Basically, the valve can be installed with any orientation. As viewed in the direction of flow,
the normal installation orientation of the control valve is horizontal with the spindle vertical
and the stuffing box pointing upwards.
In the case of angle valves, flow normally takes place over the valve plug.
In the case of units with actuators, the installation rules issued by the actuator manufacturers
must be observed.
Commissioning
The task of commissioning the control valve is performed when the valve is put into operation
for the first time, and also after repairs.
Commissioning may only be carried out by qualified staff who have read and understood the
installation instructions.
For the actuators, the additional documents issued by the manufacturers must be observed.
Before commissioning, a check must be performed to ensure that all fastenings have been
securely tightened.
Commissioning does not require any additional work on the valve.
Unless agreed otherwise, the control valve is delivered in the closed state. The travel
distance of the valve plug is stated on the name plate.
During the task of commissioning, all connections and seals on the valve must be checked for
leaks. Any leaks must be corrected immediately. In the case of flanged connections, this is
done by tightening the nuts; it can also be done on the valve by tightening the stuffing box if
necessary.
In the case of pipes at high temperatures, the valves should not be suddenly exposed to the
high temperatures. Here, slow warming-up should be performed.
13
Operating Procedure
Operation
The control valve ZK 210 may only be operated by qualified staff who have read and
understood the installation instructions. Additional installation instructions issued by the
manufacturers of the actuators must be observed.
Danger
During operation, the control valve ZK 210 is under pressure. In this condition, if
flanged connections, sealing plugs or the stuffing box is slackened, hot water or
steam will flow out and could cause severe scalding over the entire body. There
is danger to life and limb for the user or for third parties, possibly resulting in
death.
During operation, the valve is hot. If the valve is touched when in the
operational condition, severe burns are possible. It must be ensured that, when
handwheels are being operated, the operator wears gloves.
During operation, the spindle is moved. The moving parts of the control valve
and of the actuator must definitely not be touched; otherwise, your hands might
be crushed.
(continued)
Maintenance
The control valve ZK 210 may only be maintained by qualified staff. "Qualified staff" are
persons who have the necessary qualifications for their work and are familiar with the
product.
The additional documents issued by the actuator manufacturers must be observed.
Danger
During operation, the spindle is moved. The moving parts of the control valve
and of the actuator must definitely not be touched; otherwise, your hands might
be crushed.
14
Operating Procedure
(continued)
Maintenance
(continued)
The following maintenance work must be performed:
Type of
Time intervalActivities
maintenance
InspectionQuarter-yearly Checking the stuffing box for leaks 1) (visual inspection)
InspectionQuarter-yearly Checking that connections, body seal, valve spindle and
threaded spindle are free of wear, are clean, and are not
leaking (visual inspection)
InspectionQuarter-yearly Checking of seat tightness
InspectionAnnuallyChecking that the fastening screws of the valve actuator are
seated securely, and tightening them if necessary
LubricationQuarter-yearly Lubricating the spindle bearing with lithium-saponified
grease with penetration grade 2 with MoS2 additive 2)
InspectionEvery three
years
Checking by Gestra specialists to ensure that the internal
parts and threaded spindle are not damaged
1
) Replenishment or exchange of the stuffing box rings may only be performed when there is
no pressure in the valve. In particular, the safety information and danger notes in the
section entitled "Important Notes" must be observed.
Important
The task of opening the body may only be performed by specialists from
Gestra.
2
) Lubricants recommended by the manufacturer are:
Shell Retinax AM with MoS
2
DEA Glissando MEP2
15
Repairs
Repair
Repair work on the control valve ZK 210 may only be performed by specialists from Gestra.
Opening the valve body and making structural changes are regarded as being improper
activities.
The resulting risk will have to be borne by the user alone. The manufacturer hereby expressly
rejects any claims for any resulting damage.
For maintenance and repair, only original Gestra spare parts may be used.
Spare Parts
For every control valve ZK 210, a separate parts-list with the associated overall drawing is
supplied as well by the manufacturer.
When spare parts are being ordered, the necessary spare-part numbers must be taken from
that list.
Spare parts can also be ordered directly from Gestra by quoting the Gestra serial number
stated on the name plate.
Vertretungen weltweit ● Agencies all over the world ● Représentations dans le monde entier ● Representaciones en todo el mundo ● Agenzie in tutto il mondo
Great BritainItalia
Flowserve Flow Control (UK) Ltd.