Scope of supply ......................................................................................................................................4
Function .................................................................................................................................................5
System components ...............................................................................................................................5
Fault-finding list for TRV 5-40 / NRS 1-40.1 / NRS 1-40.2 .....................................................................22
Annex
CAN bus ...............................................................................................................................................23
Factory settings of node ID ...................................................................................................................23
Node ID ................................................................................................................................................24
Changing node ID for safety part .......................................................................................................... 24
Declaration of Conformity .....................................................................................................................26
3
Important Notes
Usage for the intended purpose
The temperature transmitter TRV 5-40 in conjunction with the temperature sensors TRG 5-63,
TRG 5-64, TRG 5-65, TRAG 5-67 and TRG 5-58 must only be used for measuring temperatures.
Safety note
The equipment must only be installed and commissioned by qualified and competent staff.
Retrofitting and maintenance work must only be performed by qualified personnel who – through
adequate training – have achieved a recognised level of competence.
PED (Pressure Equipment Directive)
The equipment fulfils the requirements of the Pressure Equipment Directive 97/23/EC and can be used
with fluids of group 1 and 2. With CE marking.
ATEX (Atmosphère Explosible)
According to the European Directive 94/9/EC the equipment must not be used in explosion risk areas.
Explanatory Notes
Scope of supply
TRV 5-40
1 Temperature transmitter TRV 5-40
4 Fixing lugs
1 M 12 sensor connector, 5 poles, A-coded, with terminating resistor 120 Ω
1 Installation manual
Description
The temperature transmitter TRV 5-40 is designed for the connection of three temperature sensors
TRG 5-6x (platinum resistance thermometer Pt 100 to EN 60751). The temperatures measured by the
temperature sensors are converted by the temperature transmitter TRV 5-40 and sent to the CAN bus
in the form of a data telegram.
The data are transferred via CAN bus, using the CANopen protocol.
4
Explanatory Notes – continued –
Description – continued –
The temperature transmitter TRV 5-40 can be used as:
n safety temperature monitor / limiter in conjunction with a temperature sensor type TRG 5-6x and
the control unit NRS 1-40.1 / NRS 1-40.2 and
n temperature monitor & limiter in conjunction with one or two temperature sensors TRG 5-6x and the
control unit TRS 5-40 or any other equipment that is approved for this application.
The equipment combination can be used for monitoring, limiting or control purposes in steam plants
and (pressurised) hot water installations according to TRD and EN 12952 and EN 12953.
Function
The temperature transmitter TRV 5-40 consists of the safety part for temperature limiting and the part
for temperature monitoring & control.
The safety part is connected with the temperature sensor. The temperature sensor detects the temperature and sends the measured values to the safety part of the temperature transmitter, where the
measured values are recorded redundantly and monitored.
The adjustable temperature limit T
indicated by the temperature transmitter. The temperature sensing element on the electronic insert
monitors continuously the temperature inside the transmitter housing. An automatic self-testing routine
checks every 10 seconds the safety and reliability of the functions of the temperature sensor and the
detection of the measured values.
The actual temperatures, the exceeding of the adjusted temperature limit T
periodic self test and the temperature inside the transmitter housing are sent as a data telegram via
CAN bus to the control equipment NRS 1-40.1 / NRS 1-40.2.
Regardless of the safety part two additional temperature sensors TRG 5-6x can be used for temperature monitoring & control in order to measure further actual temperature values. These readings are
also sent as data telegrams via CAN bus and will be evaluated e. g. by the control unit TRS 5-40.
(°C), the actual temperature and system malfunctions are
MAX
(°C), the result of the
MAX
System components
TRG 5-6x
Temperature sensor with resistance thermometer Pt 100
TRS 5-40
Digital temperature switch
Functions: MIN / MAX temperature monitor and temperature controller
Data exchange: CAN bus to ISO 11898 via CANopen protocol
NRS 1-40.1 and NRS 1-40.2
Digital control unit for four sensors (level, temperature)
Functions: Signalling MIN alarm and MAX alarm in freely adjustable combinations
Data exchange: CAN bus to ISO 11898 via CANopen protocol
URB 2
Operating & visual display unit
Functions: Parameterisation, visual indication via LCD display
Data exchange: CAN bus to ISO 11898, with CANopen protocol
Input/Output
CAN bus interface with current supply 18 – 36 V DC, short circuit protected
Temperature sensors
TRG 5-63
1x Pt 100 to EN 60751
TRG 5-64
2x Pt 100 to EN 60751
TRG 5-65, TRG 5-66
1x Pt 100 to EN 60751
TRG 5-67
1x Pt 100 to EN 60751
TRG 5-68
2x Pt 100 to EN 60751
Temperature limit T
Min. adjustable limit value: 20°C
Max. adjustable limit value: 650°C
Indicators and adjustors
1 Red three-digit, seven-segment LED display for indicating limit values
1 Green three-digit, seven-segment LED display for indicating the actual value
3 Pushbuttons for limit settings
5 LEDs for internal status messages
1 Code switch with 10 poles for setting the node ID and baud rate
1 Code switch with 10 poles for configuring the system
Internal self-checking routine
Every 10 seconds
Fault response time
30 sec.
Power consumption
2 W
Fuse
Electronic thermal fuse T
Protection
IP 65 to EN 60529
Max. admissible ambient temperature
70°C
(°C) (cut-off temperature)
MAX
85°C, hysteresis –2K
MAX
6
Technical Data – continued –
TRV 5-40 – continued –
Housing
Material: polycarbonate
Cable entry / Wiring
For connecting the temperature sensor:
Cable glands with integrated cable clamp, 3 x M 16,
1 three-pole and 1 six-pole screw-type terminal strip, conductor size 1.5 mm
For CAN bus connection:
M 12 sensor connector, 5 poles, A coded
M 12 sensor jack, 5 poles, A coded
Weight
Approx. 0.7 kg
Name plate / Marking
Safety note
Equipment designation
2
Fig. 1
Manufacturer
Adjusted limit
Admissible ambient temperature
Specification CAN bus
Temperature sensor
Bus system
Node ID
Disposal note
CE marking
Spare part specification
7
Technical Data – continued –
Dimensions TRV 5-40
Fig. 2
8
A
130
180
163.5
168
B
b = 60
C
Installation
Temperature transmitter TRV 5-40
The temperature transmitter TRV 5-40 is designed for wall mounting. Screw the four fixing lugs
supplied with the transmitter into the housing. You can now attach the equipment to the wall without
having to open the housing cover.
Note
After mounting the housing you must:
n connect the temperature sensor,
n set the temperature limit T
n check and if necessary change the baud rate setting (see chapter “Wiring”)
n check and if necessary change the system configuration (see chapter
“Commissioning”)
n check and if necessary change the node ID (see chapter “Annex”)
Check and if necessary change settings
(°C) (see chapter “Commissioning”)
MAX
1. Undo cross recess head screws
2. Use pushbuttons
3. Use code switches
K for setting the temperature limit T
F and G to set the system parameters.
4. Close the housing cover
A and swing up the housing cover B.
B and fasten the cross recess head screws A.
Tools
n Screwdriver 5.5/100
n Screwdriver for cross recess head screws, size 2
MAX
(°C).
9
Functional Elements
TRV 5-40
K
J
Fig. 3
Key
I
A Cross recess head screws
B Housing cover
D
E B
A
F
G
C
H
C Fixing lugs for wall mounting
D Indication of limit setting
E Indication of actual value
F Code switch for node ID and baud rate setting
G Code switch for system configuration
H M 12 connector/jack, 5 poles, A-coded
I Cable gland for temperature sensor
J Terminals for temperature sensor
K Pushbuttons for limit setting
10
Wiring
Wiring of the temperature sensor
Note that screened four-core cable, e. g. Ölflex® 110CH, Lapp, 4 x 0.5 mm2 is required for wiring
the equipment. Max. cable length between temperature sensor and temperature transmitter
TRV 5-40: 25 m.
When the equipment is open:
1. Undo cable gland
2. Strip off approx. 40 mm of cable insulation coating, remove approx. 5 mm of conductor end
insulation and disconnect the screen. Note that the screen must only be connected to the
temperature sensor.
3. Connect the sensor cables according to the wiring diagram to the terminal strip
4. Fasten cable glands
not used.
Bus line, cable length and size
I and pull the cables of the sensors through the glands.
J.
I to achieve a good seal. Use sealing plugs to seal off cable glands that are
Note that screened multi-core twisted-pair control cable is required for the BUS line, e. g. UNITRONIC®
BUS CAN 2 x 2 x … mm
2
or RE-2YCYV-fl 2 x 2 x … mm2.
Preassembled control cables (with connector and coupler) for connecting the equipment are available
as accessories.
The baud rate (data transfer rate) dictates the cable length between the bus nodes and the total power
consumption of the sensor dictates the conductor size.
S 8S 9S 10Baud rateCable length
OFFONOFF250 kBit/s 125 m
Factory setting
ONONOFF125 kBit/s 250 m2 x 2 x 0.5
OFFOFFON100 kBit/s 335 m2 x 2 x 0.75
ONOFFON 50 kBit/s 500 m
OFFONON 20 kBit/s1000 m
ONONON 10 kBit/s1000 m
Number of pairs
and conductor size [mm2]
2 x 2 x 0.34
on request, dependent on
bus configuration
When the equipment is open you can set the baud rate by using the code switch FFig. 3 (S 8 to 10).
The baud rate of the temperature transmitter TRV 5-40 is set at our works to 250 kBit/s (for a max.
cable length of 125 m). Reduce the baud rate if the cable length exceeds 125 m. Make sure that all
bus nodes feature the same baud rate setting.
Note
The specified max. baud rates and cable lengths are based on empirical values
ascertained by GESTRA. However for some applications it might be necessary to reduce
the baud rate in order to ensure trouble-free operation.
UNITRONIC® is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.
11
Wiring – continued –
Wiring diagram for temperature transmitter TRV 5-40
Connection of temp. sensor
used as safety limiter
3144512253
ConnectorCoupler
Central
earthing point
Operating unit
URB 2
6
CEP
Control unit
NRS 1-4x
NRS 2-40
NRR 2-40
LRR 1-40
TRS 5-40
Connection of temp. sensor
used as temperature monitor
Key
1 Screen
2 Voltage supply
24 V DC+
3 Voltage supply
24 V DC–
4 CAN data line C
5 CAN data line C
H
L
6 Terminating resistor 120 Ω
Level/
Conductivity
electrode
NRG x6-4x
LRG xx-4x
Temperature
transmitter
TRV 5-40
Coupler with terminating resistor 120 ΩConnector with terminating resistor 120 Ω
Fig. 4
12
Wiring – continued –
Wiring diagram for temperature transmitter TRV 5-40 – continued –
Attention
n Wire equipment in series. Start-type wiring is not permitted!
n Link screens of bus cables such that electrical continuity is ensured and connect them
once to the central earthing point (CEP).
n Connect the screens of the sensor lines only once to the temperature sensor
(EMC cable gland).
n If two or more system components are connected in a CAN bus the first and the last
item of equipment must be provided with a terminating resistor of 120 Ω (terminals
CH/CL). We recommend that you use the TRV 5-40 equipped with the connector fitted
with the terminating resistor either as first or as last equipment.
n The CAN bus network must not be interrupted during operation.
In the event of an interruption an alarm message will be triggered.
Connecting the connector and jack
If you do not use the preassembled control cables connect the connector and the jacks for the CAN bus
lines in accordance with the wiring diagram.
Tools
n Screwdriver for slotted screws, size 2.5, completely insulated to VDE 0680-1
n Screwdriver for cross recess head screws, size 2
13
Basic Settings
Factory settings
The temperature transmitter TRV 5-40 features the following factory set default values:
n Node ID: 005 for the safety part
n Baud rate: 250 kBit/s (125 m cable length)
n Configuration: temperature transmitter TRV 5-40 set as limiter 4.
Commissioning
Checking wiring
Before installation check the wiring:
n Are the temperature sensors wired according to the wiring diagram?
n Is the wiring of all CAN bus devices in accordance with the wiring diagrams?
n Is the polarity of the bus line always correct?
n Are all the end-of-line devices of the bus line provided with a 120 Ω terminating resistor?
Applying supply voltage
Switch on supply voltage. The two seven-segment indicators are tested, which means that all
segments and decimal points are flashing. The test is also carried out whenever the connector for the
bus line is pulled out of the transmitter and then plugged in again.
Changing system configuration
The control units NRS 1-40.1 and NRS 1-40.2 associated with the temperature transmitter TRV 5-40
are designed for four limiting functions for monitoring liquid level and temperature. The level electrodes
NRG 1x-40, NRG 1x-41.1 and the temperature transmitter TRV 5-40 are to be connected to the control
unit NRS 1-40.1. The level electrode NRG 1x-41 and the temperature transmitter TRV 5-40 have to be
connected to the control unit 1-40.2.
For the operation of the limiting system it is necessary to establish in the control unit the number of
sensors with which the equipment has to work.
For more information see chapter “Commissioning” in the installation manual NRS 1-40.1 and
NRS 1-40.2.
The following settings can be adjusted with the TRV 5-40:
n Communication with control unit NRS 1-40.1 or NRS 1-40.2
n Communication with the control unit operating as limiter 1, 2, 3 or 4
1 Example
The following items of equipment are connected to the control unit NRS 1-40.1:
2 Level electrodes NRG 1x-40 for low water level LW 1 and 2
1 Level electrode NRG 1x-41.1 for high water level HW and
1 Temperature transmitter TRV 5-40 for MAX temperature
As only in the temperature transmitter TRV 5-40 the limiter number can be adjusted, the control unit
NRS 1-40.1 has to be configured as follows:
LimiterB1B2B3B4
FunctionWater level LW 1Water level LW 2High water HWTemperature MAX
Set the temperature transmitter TRV 5-40 as limiter 4.
2 Example
The following items of equipment are connected to the control unit NRS 1-40.1:
2 Level electrodes NRG 1x-40 for water level LW 1 and 2 and
1 Temperature transmitter TRV 5-40 for MAX temperature
LimiterB1B2B3B4
FunctionWater level LW 1Water level LW 2Temperature MAX
Set the temperature transmitter TRV 5-40 as limiter 3.
15
Commissioning – continued –
Adjusting temp. limit T
Fig. 5
Pushbuttons for
(°C)
MAX
Indication of
limit value
limit setting
Indication of
actual value / error code
When the housing is open:
Setting the temperature limit T
Use the three pushbuttons to set the temperature limit T
MAX
(°C)
MAX
(°C).
The pushbuttons have the following functions:
n Pushbutton to the right: setting in increments of 1°C
n Pushbutton in the middle: setting in increments of 10°C
n Pushbutton to the left: +/– (increase/decrease)
Upon application of the supply voltage and during operation, the adjusted temp. limit T
(°C) and the
MAX
actual value are indicated.
Press any of the three pushbuttons to switch to the parameter setting mode of the TRV 5-40. Both
seven-segment LED displays show the adjusted limit value T
The adjusted limit T
(°C) remains valid until the setting of the new value is finished.
MAX
(°C) and all digital points are flashing.
MAX
If no other pushbutton is pressed within 10 seconds the temperature transmitter switches back to
normal operation.
Increasing the limit value
When you are in the parameter setting mode press the right (increments of 1°) and/or middle
(increments of 10°C) pushbutton to adjust the desired new limit T
MAX
(°C).
To increase or decrease the setting use the left pushbutton (+/–).
Decreasing the limit value
When you are in the parameter setting mode first press the left pushbutton (+/–). Then press the
right (increments of 1°) and/or middle (increments of 10°C) pushbutton to adjust the desired new limit
T
(°C).
MAX
To increase or decrease the setting use the left pushbutton (+/–).
After you have finished the new setting do not press a pushbutton for 10 seconds. The new limit value
T
(°C) is then accepted by the temperature transmitter TRV 5-40 and the equipment switches back
MAX
to normal operation. The new limit value T
Please write the new temperature limit T
(°C) and the actual value will now be indicated.
MAX
(°C) on the name plate.
MAX
16
Note
In the parameter setting mode the currently adjusted value is indicated by both sevensegment LED displays.
Start, Operation and Test
TRV 5-40
Indication of
limit value
Fig. 6
Apply supply voltage.All segments and decimal
Actual value T (°C) below limit
value T
MAX
(°C)
Actual value T (°C) above limit
value T
MAX
(°C)
The pushbutton for the TRV
5-40 on the control unit NRS 1-40.1 / NRS 1-40.2 must be
pressed and held down until
the test is finished.
points of the displays
T
and T are flashing.
MAX
Operation
Display T
MAX
Display TIndication of the actual value
Display T
MAX
Display TIndication of the actual value and triggering of
Display TAn increase in temperature is simulated and
Indication of
actual value / error code
Start
The LED displays are being tested.
Indication of the adjusted limit
Indication of the adjusted limit
an alarm.
Control unit NRS 1-40.1 / NRS 1-40.2 opens the
output contacts after the time delay has elapsed.
Test
the indicated actual value rises steadily. When
the adjusted limit value is exceeded, the control
unit NRS 1-40.1 / NRS 1-40.2 opens the output
contacts after the time delay has elapsed.
Indication of an error code
When an error occursDisplay TDisplay switches between indication of error
code (E xx) and actual value T. The control unit
NRS 1-40.1 / NRS 40.2 opens instantaneously
the output contacts and the output of terminal
7,8 is energised/de-energised in a timecontrolled manner.
17
System Malfunctions
Causes
Faulty installation and/or configuration of CAN bus components, excessively high temperatures in
devices, defective electronic component parts or electromagnetic interferences of the supply system
can result in system malfunctions.
Other malfunctions are:
n Incorrect communication in the CAN bus system
n Overloading of the 24 V power supply unit that is integrated in the control unit
Note
Before carrying out the system malfunction analysis please check:
Wiring:
Is the wiring in accordance with the wiring diagrams?
Is the polarity of the bus lines always correct?
Are the bus lines of the first and the last devices provided with 120 Ω terminating
resistors?
Configuration of the level electrode NRG 1x-40 (Low water level LW):
Are the wire bridges (equipment 1 or 2) set correctly?
Does the position of the wire bridge correspond with the node ID setting?
Configuration of the temperature transmitter TRV 5-40:
Is the temperature transmitter TRV 5-40 set correctly as equipment 1, 2, 3 or 4?
Node ID:
Are all node ID settings correct?
Note that no node ID setting must be used twice!
Baud rate:
Does the baud rate setting correspond with the cable length?
Is the baud rate setting of all devices identical?
18
System Malfunctions – continued –
Systematic malfunction analysis
The sources of malfunctions occurring in CAN bus systems operating with several bus-based stations
must be analysed systematically since faulty components or incorrect settings can give rise to
negative interactions with intact bus devices in the CAN bus system. These unwanted interactions
can cause error messages in fully functional bus devices, which will make fault detection even more
difficult.
We recommend the following systematic fault finding procedures:
Step 1 (Start)
Detach terminal strips
in all sensing units of
bus devices.
Level electrode
Conductivity electrode
Pressure sensor
Temperature sensor
etc.
Check
Use fault-finding list to
correct fault(s)!
Final test:
Have all faults been
eliminated?
System
Malfunction
Use fault-finding
list to identify
the fault(s).
Cut off power supply
to the equipment!
Step 2
Plug in terminal strips
of the sensing unit
of a system
e. g. NRS ...
and
NRG ... (electrodes)
Step 3
Apply mains voltage
to bus devices of the
system
e. g. NRS ...
and NRG ...
Check next system
System O. K.
Detach terminal strips
between bus devices
of the system
e. g. NRS ...
and NRG ...
19
System Malfunctions – continued –
Table listing error codes
Indication of
limit value
Indication of
actual value / error code
Fig. 7
Indication of error code
When an error
occurs
Error codePossible causeRemedy
E.01 ... E.32Temperature transmitter defective because
E.11Temperature in transmitter housing too high. Check installation of the temperature
E.12Resistance in temperature sensor too high.Check readings of the temperature sensor
E.17
E.18
E.30Sensor line interrupted or interruption in
E.0b *)Short circuit in temperature sensor.Check sensor line and readings of the
*) Do not confuse indication b and 6!
Indication TDisplay switches between indication of
a malfunction was detected during one or
more self-testing routines.
(see table “Basic values of measuring
resistors”). Replace measuring element if
the measured values are incorrect.
Check and correct position of code switches
S 9 and S 10 (polynom).
Check and correct position of code switches
S 1 to S 8 (limiter number).
Check sensor line and readings of the
temperature sensor (see table “Basic values
of measuring resistors”). If the measured
values are incorrect replace the measuring
element.
temperature sensor (see table “Basic values
of measuring resistor”). If the measured
values are incorrect replace the measuring
element.
20
System Malfunctions – continued –
Note
The system malfunctions caused by the temperature transmitter TRV 5-40 will also
result in system malfunctions in the control units NRS 1-40.1 and NRS 1-40.2, which
means that the output contacts open instantaneously and the signal outputs are
energised/de-energised in a pulse-controlled way.
When contacting our Technical Services please state the indicated error code.
Basic values of measuring resistors according to DIN 43760 for Pt 100.
0.373
Checking Installation and Functions
Checking the switchpoints
The switchpoints should be checked during commissioning and whenever the measuring elements of
the temperature sensors or of the temperature transmitter TRV 5-40 are being exchanged.
To check the switchpoint “MAX temperature limit (°C)” the adjusted limit value must be exceeded.
The equipment must then response as if there were an alarm situation.
21
Malfunctions
Fault-finding list for TRV 5-40 / NRS 1-40.1 / NRS 1-40.2
Fault: Temperature sensor TRG 5-6x defective.
Remedy: Check the readings of the temperature sensor TRG 5-6x (Pt 100). (Basic values of
measuring resistors to DIN 43760 for Pt 100). If the measured values are incorrect replace
the measuring element of the temperature sensor TRG 5-6x.
If faults occur that are not listed above or cannot be corrected, please contact our Technical Services
or the authorized agency in your country.
22
Annex
CAN bus
All devices (level, conductivity) are interconnected via CAN bus. The CANopen protocol is used for the
data exchange between the equipment groups. All devices have an electronic address – the node ID.
The four-core bus cable serves as power supply and data highway for high-speed data exchange.
The CAN address (node ID) can be set between 1 and 123.
The temperature transmitter TRV 5-40 has already been configured at our works for operation with
other GESTRA components and can be used straight away without having to set the node ID.
Individual node IDs must be set manually in the respective equipment.
Please observe the pertinent installation instructions.
23
Annex – continued –
Node ID
Should it be necessary to establish other node IDs please take the interdependence of the equipment
into consideration and assign the node ID for the individual group components according to the following
table:
Control unit
NRS 1-40.1
XX + 1X + 2X + 3X + 4
123*45
Sensor 1
e. g.
level electrode
NRG 1x-40
as first device
Sensor 2
e. g.
level electrode
NRG 1x-40
as second device
Reserved area
Sensor 3
level electrode
NRG 1x-41.1
Note
The node ID 3* for the second level electrode NRG 1x-40 must be set in situ because
the default factory setting is 2.
Changing node ID for safety part
When the housing is open:
Use a thin blade screwdriver to set switches S1 to S7 of the code switch
table “Node ID”.
Enter the adjusted node ID on the name plate.
Note
The two node IDs for the two actual value outputs (part for temperature monitoring and
control) are linked with the node ID of the safety part and cannot be adjusted. For more
information see the installation manual of the control unit TRS 5-40.
e. g.
Factory setting
Sensor 4
e. g.
temperature
transmitter
TRV 5-40
FFig. 3 in accordance with
24
Attention
Do not use a node ID for more than one item of equipment in the CAN bus system.
The node ID 0 is not permissible.
Annex – continued –
Table “Node ID”
In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each node has its own
address (node ID). This address can be set via a 10-pole code switch
F
Toggle switch, white
S1
S2
S3ON4
S4OFF8
S5OFF16
S6OFF32
S7OFF64
ON1
OFF2
(Factory setting)
Node ID5
Toggle switch, white
S1
S2
S3OFF4
S4ON8
S5OFF16
S6OFF32
S7OFF64
(Example)
F Fig. 3.
F
Node ID10
OFF1
ON2
Table Baud rate
S 8S 9S 10Baud rateCable length
OFFONOFF250 kBit/s125 m
Factory setting
ONONOFF125 kBit/s 250 m
OFFOFFON100 kBit/s 335 m
ONOFFON 50 kBit/s 500 m
OFFONON 20 kBit/s1000 m
ONONON 10 kBit/s1000 m
25
Annex – continued –
Decommissioning
First disconnect the temperature sensor TRG 5-6x and then withdraw the sensor lines from the cable
glands. Unplug the connecting plug and the connecting jack of the CAN bus lines and plug them
together.
Deinstall the temperature transmitter TRV 5-40.
Attention
If the CAN bus line is interrupted an alarm will be triggered.
Disposal
Deinstall the temperature transmitter TRV 5-40 and separate the waste materials in accordance with
the material specification. Electronic components (boards) must be disposed of separately.
For the disposal of the temperature transmitter TRV 5-40 observe the pertinent legal regulations concerning waste disposal.
Declaration of Conformity
We hereby declare that the equipment TRV 5-40 conforms to the following European guidelines:
n LV guideline 73/23/EC version 93/68/EC
n EMC guideline 89/336/EC version 93/68/EC
n Pressure Equipment Directive (PED) 97/23/EC of 29 May 1997.
Applied conformity assessment procedure: Annex III, Module B and D, verified by notified
body 0525.
This declaration is no longer valid if modifications are made to the equipment without consultation
with us.