SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Contents
1 Introduction 6
2 Product Capabilities and Features 7
3 Actuator Weights 10
4 Installation Instructions 11
4.1 Safety Precautions 11
4.2 Safety Practices 12
4.3 Actuator Preparation 12
4.3.1 Mounting Base 13
4.3.2 Stem Acceptance 13
4.3.3 Terminal Connections 14
4.4 Setting The Limit Switch 14
4.4.1 Two-Train Geared Limit Switch 15
4.4.2 Four-Train Geared Limit Switch 18
4.5 Setting Torque Switch 20
4.5.1 SMB-000 “Cam Style” Double Torque Switch 20
4.5.2 SMB-000 and SMB-00 “C Style” Double Torque Switch 23
4.5.3 SMB-0 through SMB-5 Double Torque Switch 25
4.6 Position Indication 27
4.6.1 Local Position Indicator 27
4.6.2 Remote Position Indicator (50 ohm or 1000 ohm Potentiometer) 27
4.6.3 Remote Position Indicator (Resistance-to-Current Signal Converter) 28
4.7 Additional Electrical Components 30
4.7.1 Reversing Starter 30
4.7.2 Overload Relays 30
4.7.3 Control Station 31
5 Operation 32
5.1 Motor Operation 32
5.2 Manual Operation 33
5.2.1 SMB-000 and SMB-00 33
5.2.2 SMB-0 through SMB-4 34
5.2.3 SMB-5 through SMB-5T 34
6 Maintenance 35
6.1 Routine Maintenance 35
6.2 Major Maintenance 36
6.3 Lubrication 36
6.3.1 Lubrication Inspection 36
6.3.2 Standard Lubricant 37
6.3.3 Minimum Lubricant Qualities Required 38
7 SMB Disassembly and Reassembly 39
7.1 SMB-000 39
2
7.1.1 To Replace the Stem Nut Only 39
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
7.1.2 SMB-000 Disassembly 40
7.1.3 SMB-000 Reassembly 41
7.1.4 Gasket Instructions 41
7.2 SMB-00 46
7.2.1 To Replace the Stem Nut Only 46
7.2.2 SMB-00 Disassembly 47
7.2.3 SMB-00 Reassembly 48
7.2.4 Gasket Instructions 49
7.3 SMB-0, 1, 2, 3 and 4 57
7.3.1 To Replace the Stem Nut Only 57
7.3.2 SMB-0, 1, 2, 3 and 4 Disassembly 58
7.3.3 Worm and Torque Spring Disassembly 59
7.3.4 SMB-0, 1, 2, 3 and 4 Reassembly 60
7.3.5 Gasket Instructions 60
7.4 SMB-5 (Thrust and Torque) and SMB-5T (Torque Only) 67
7.4.1 SMB-5 and SMB-5T Disassembly 67
7.4.2 SMB-5 and SMB-5T Reassembly 70
8 SB Disassembly and Reassembly 80
8.1 SB-00 80
8.1.1 SB-00 Disassembly/Stem Nut Removal 80
8.1.2 SB-00 Reassembly/Stem Nut Installation 81
8.2 SB-0 84
8.2.1 SB-0 Disassembly/Stem Nut Removal 84
8.2.2 SB-0 Reassembly/Stem Nut Installation 85
8.3 SB-1 88
8.3.1 SB-1 Disassembly/Stem Nut Removal 88
8.3.2 SB-1 Reassembly/Stem Nut Installation 88
8.4 SB-2 91
8.4.1 SB-2 Disassembly/Stem Nut Removal 91
8.4.2 SB-2 Reassembly/Stem Nut Installation 92
8.5 SB-3 95
8.5.1 SB-3 Disassembly/Stem Nut Removal 95
8.5.2 SB-3 Reassembly/Stem Nut Installation 96
8.6 SB-4 99
8.6.1 SB-4 Disassembly/Stem Nut Removal 99
8.6.2 SB-4 Reassembly/Stem Nut Installation 99
9 Troubleshooting 103
10 How to Order Parts 104
11 EC Declaration of Conformity 105
flowserve.com
3
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Figures
Figure 2.1 – Typical SMB (0 through 4) 8
Figure 4.1 – Wiring Connections 14
Figure 4.2 – Two-Train Geared Limit Switch – Rotor-Type 16
Figure 4.3 – Four-Train Geared Limit Switch – Rotor Type 18
Figure 4.4 – SMB-000 “Cam Style” Double Torque Switch 21
Figure 4.5 – SMB-000 and SMB-00 “C Style” Double Torque Switch 23
Figure 4.6 – SMB-0 through SMB-5 Double Torque Switch 25
Figure 4.7 – Typical Connection for a 50-ohm Potentiometer 29
Figure 4.8 – Typical Connection for a 1000-ohm Potentiometer 29
Figure 4.9 – Typical Connection for R/I Signal Converter (Older Version) 29
Figure 4.10 – Typical Connection for PT20SD R/I Converter 30
Figure 4.11 – Typical Wiring Diagram – Built-in Reversing Starter and Control Station for a
Three-Phase Power Supply 31
Figure 7.1 – SMB-000 Parts Diagram – Side View 42
Figure 7.2 – SMB-000 Parts Diagram – Top View 43
Figure 7.3 – SMB-000 Exploded View 44
Figure 7.4 – SMB-00 Parts Diagram – Motor End View 50
Figure 7.5 – SMB-00 Parts Diagram – Top View 51
Figure 7.6 – SMB-00 Parts Diagram – Side View 52
Figure 7.7 – SMB-00 Parts Diagram – Side Mounted Handwheel Detail 53
Figure 7.8 – SMB-00 Exploded View 54
Figure 7.9 – SMB-0 through SMB-4 Parts Diagram – Top View 61
Figure 7.10 – SMB-0 through SMB-4 Parts Diagram – Worm Shaft Side View 62
Figure 7.11 – SMB-0 through SMB-4 Parts Diagram – Drive Sleeve Side View 63
Figure 7.12 – SMB-0 through SMB-4 Exploded View 64
Figure 7.13 – SMB-5 and 5T Parts Diagram 73
Figure 7.14 – SMB-5 and 5T Parts Diagram– Top View 74
Figure 7.15 – SMB-5 and 5T Parts Diagram – Declutch Housing Detail 75
Figure 7.16 – SMB-5 and 5T Exploded View 76
Figure 8.1 – SB-00 Parts Diagram 82
Figure 8.2 – SB-0 Parts Diagram 86
Figure 8.3 – SB-1 Parts Diagram 89
Figure 8.4 – SB-2 Parts Diagram 93
Figure 8.5 – SB-3 Parts Diagram 97
Figure 8.6 – SB-4 Parts Diagram 101
4
Tables
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Table 3.1 – Actuator Weights
Table 4.1 – Mounting Base Dimensions 13
Table 4.2 – Maximum Stem Acceptance 13
Table 4.3– Terminal Connections 14
Table 4.4 – Two-Train Geared Limit Switch Parts List 17
Table 4.5 – Four-Train Geared Limit Switch Parts List 19
Table 4.6 – SMB-000 “Cam Style” Double Torque Switch Parts List 22
Table 4.7 – SMB-000 and SMB-00 “C Style” Torque Switch Parts list 24
Table 4.8 – SMB-0 through SMB-5 Double Torque Switch Parts List 26
Table 6.1 – Approximate Volume and Weights of Lubricants 37
Table 7.1 – SMB-000 Parts List 45-46
Table 7.2 – SMB-00 Parts List 55-57
Table 7.3 – SMB-0 through SMB-4 Parts List 65-67
Table 7.4 – SMB-5 and 5T Parts List 77-79
Table 8.1 – SB-00 Parts List 83-84
Table 8.2 – SB-0 Parts List 87
Table 8.3 – SB-1 Parts List 90
Table 8.4 – SB-2 Parts List 94
Table 8.5 – SB-3 Parts List 98
Table 8.6 – SB-4 Parts List 102
Table 10.1 – Space Heater Size per Voltage Rating 104
10
flowserve.com
5
1
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Introduction
1.1 Purpose
This Installation and Maintenance Manual explains how to install and maintain SMB and SB actuators. Information on installation, operation, disassembly, lubrication, and spare parts is provided.
1.2 User Safety
Safety notices in this manual detail precautions the user must take to reduce the risk of personal
injury and damage to the equipment. The user must read and be familiar with these instructions
before attempting installation, operation, or maintenance. Failure to observe these precautions could
result in serious bodily injury, damage to the equipment, void of the warranty, or operational difficulty.
Safety notices are presented in this manual in three forms:
c WARNING: Refers to personal safety. Alerts the user to potential danger. Failure to follow warning
notices could result in personal injury or death.
a CAUTION: Directs the user’s attention to general precautions that, if not followed, could result in
personal injury and/or equipment damage.
NOTE: Highlights information critical to the user’s understanding of actuator installation and
operation.
6
2
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Product Capabilities and Features
SMB and SB Series actuators easily operate all types of valves: gate, globe, plug, ball, and butterfly
valves, and specialized valves and mechanisms.
The actuators meet rigid safety requirements. The housing is durable cast-iron or ductile iron,
acceptable for use in the nuclear power industry as well as other industries.
The actuators are available with optional integral controls and other features.
The actuators have a removable stem nut that allows transferring of the actuator from one valve to
another without major disassembly.
2.1 Initial Inspection and Storage Instructions
c WARNING: Read this Installation and Maintenance Manual carefully and completely before
attempting to install, operate, disassemble, or troubleshoot the actuator. Be aware of the electrical
hazards.
2.2 Product Identification
The actuator unit nameplate is located on the back of the unit opposite the limit switch compartment. The nameplate contains the following information:
• Point of Manufacture
• Unit Size
• Order Number
• Serial Number
• Customer Tagging
• CE Stamp
7
flowserve.com
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
The motor nameplate is located on the motor. The nameplate contains the following information:
• ID Number
• Run Torque
• RPM
• Full Load Amps
• Insulation Class
• Horsepower
• Service Factor
• Hertz
• Ambient Temperature
• Start Torque
• Enclosure Type
• Volts
• Locked Rotor Amps
• Duty
• Phase
• Motor Code
• Connection Diagram
Figure 2.1 – Typical SMB (0 through 4)
Housing
Motor
Handwheel
Declutch lever
Switch compartment
8
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
2.3 Inspection and Recording
Upon receipt of the actuator:
1. Carefully remove the actuator from the shipping carton or skid. Thoroughly examine the equipment for any physical damage that may have occurred during shipment. If damaged, immediately
report the damage to the transport company.
2. A nameplate is attached to each actuator. Record this information for future reference, i.e.
ordering parts or obtaining further information.
2.4 Storage Procedure
NOTE: The following is our recommended storage procedure to retain maximum product integrity
during storage. Failure to comply with recommended procedures will void the warranty. For longerterm storage, contact Limitorque for procedures and recommendations.
Storage (less than 1 year)
Actuators are not weatherproof until properly installed on the valve or prepared for storage.
Store actuators in a clean, dry, protected warehouse, away from excessive vibration and rapid
temperature changes. If the actuators must be stored outside, they must be stored off the ground,
high enough to prevent them from being immersed in water or buried by snow.
1. Position the actuator in storage with motor and switch compartment horizontal.
2. Connect the internal heaters (if supplied) or place desiccant in the switch compartment.
3. Replace all plastic caps or plugs with metal pipe plugs and ensure that all cover bolts are tight.
4. If the actuator is mounted on a valve and the stem protrudes from the actuator, a suitable stem
cover must be provided.
flowserve.com
9
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
3
Actuator Weights
The approximate weights of the SMB actuators and SB and SBD options are provided below:
Table 3.1 – Actuator Weights
Actuator
SMB-00013562N/AN/AN/AN/A
SMB-0020090653010046
SMB-03501591808321097
SMB-146020920092325150
SMB-2580263220101345159
SMB-31200553500230825380
SMB-420209167953661285591
SMB-5&5T 33751531N/AN/AN/AN/A
SMB-5XT58752665N/AN/AN/AN/A
Note 1: With the largest motor, no integral controls, and standard compartment cover.
1
1
Weight
lb.kglb.kglb.kg
Adder for SBAdder for SBD
10
4
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Installation Instructions
4.1 Safety Precautions
c WARNING: Read this Installation and Maintenance Manual carefully and completely before
attempting to install, operate, or troubleshoot the Limitorque actuator.
c WARNING: Be aware of electrical hazards. Turn off incoming power before working on the
actuator and before opening the switch compartment.
c WARNING: Potential HIGH PRESSURE vessel — be aware of high-pressure hazards associated
with the attached valve or other actuated device when installing or performing maintenance on
the actuator. Do not remove the actuator mounting bolts from the valve or actuated device unless
the valve or device stem is secured or there is no pressure in the line.
c WARNING: For maintenance and/or disassembly of the actuator while installed on the valve,
ensure that the actuator is not under thrust or torque load. If the valve must be left in service, the
valve stem must be locked in such a way as to prevent any movement of the valve stem.
c WARNING: Do not attempt to remove the spring cartridge cap, housing cover, or stem nut
locknut from the actuator while the valve or actuated device is under load.
c WARNING: Do not manually operate the actuator with devices other than the installed handwheel
and declutch lever. Using force beyond the ratings of the actuator and/or using additive force
devices such as cheater bars, wheel wrenches, pipe wrenches, or other devices on the actuator
handwheel or declutch lever may cause serious personal injury and/or damage to the actuator
and valve.
c WARNING: Do not exceed any design limitations or make modifications to this equipment
without first consulting Limitorque.
c WARNING: Actuators equipped with electrical devices (motors, controls) requiring field wiring
must be wired and checked for proper operation by a qualified tradesman.
c WARNING: Use of the product must be suspended any time it fails to operate properly.
flowserve.com
11
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
a CAUTION: Do not use oversized motor overload heaters. Instead, look for the cause of the
overload.
a CAUTION: Do not operate the valve under motor operation without first setting or checking the
limit switch setting and motor direction.
a CAUTION: Do not force the declutch lever into the motor operation position. The lever returns to
this position automatically when the motor is energized.
a CAUTION: Do not depress the declutch lever during motor operation to stop valve travel.
a CAUTION: Do not use replacement parts that are not genuine Flowserve Limitorque parts, as
serious personal injury and/or damage to the actuator and valve may result.
a CAUTION: Do not lift actuator/gearbox or actuator/valve combinations with only the eye bolts in
the SMB actuator. These eye bolts are designed for lifting the SMB actuator only.
a CAUTION: Do not lift the actuator by the handwheel
4.2 Safety Practices
The following check points should be performed to maintain safe operation of the SMB or SB
actuator:
• Eye bolts in SMB and SB actuators are designed for lifting only the actuator and not associated
gearboxes or valves.
• Mount the actuator with the motor in a horizontal plane, if possible.
• Keep the switch compartment clean and dry.
• Keep the valve stem clean and lubricated.
• Set up a periodic operating schedule for infrequently used valves.
• Verify all actuator wiring is in accordance with the applicable wiring diagram.
• Carefully check for correct motor rotation direction. If the valve closes when open button is
pushed, the motor leads may have to be reversed.
• Verify the stem nut is secured tightly by the locknut and that the top thread of the locknut is
crimped or staked in two places.
• Use a protective stem cover. Check valve stem travel and clearance before mounting covers on
rising stem valves.
4.3 Actuator Preparation
Replace all molded plastic conduit and top protectors (installed for shipping purposes only) with
metal pipe plugs when installation wiring is complete.
12
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
4.3.3 Terminal Connections
Wiring connections to the SMB geared limit switch, torque switch, and Marathon terminal strips are
to be made using ring-tongue terminals* as shown below:
Figure 4.1 – Wiring Connections
A
C
B
Table 4.3– Terminal Connections
AWGScrew HoleInsulation
22-16#10Vinyl18RA-10.97.31.27
18-14#10Vinyl14RB-10.97.31.27
12-10#10Vinyl14RC-101.06.31.27
Note: Limit switch and torque switch contacts are rated 300 volts per NEMA ICS-2
Thomas &
Betts P/N
ABC
14
Terminals are to be crimped using Thomas & Betts crimping tool WT112M or ERG4001.
Manufacturer: *Thomas and Betts or equal
4.4 Setting The Limit Switch
c WARNING: Disconnect all incoming power before opening or replacing the limit switch compart-
ment cover.
a CAUTION: When wiring control circuits, distinguish between “normally open” and “normally
closed” terminals on the geared limit switch.
a CAUTION: Do NOT attempt to repair the limit switch gear box. Replace entire limit switch gear
box.
a CAUTION: Do NOT use abrasive cloth to clean the silver contacts on the limit switch. Contacts
should be burnished using appropriate burnishing tool.
a CAUTION: Before motor operation, reset the geared limit switch if the actuator has been
dismantled or removed from the valve.
NOTE: Clean the limit switch cover thoroughly and apply a thin coat of grease on machined flange
surfaces before mounting on an explosion proof actuator.
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
4.4.1 Two-Train Geared Limit Switch
The rotor-type, two-train geared limit switch employs two rotors. Each rotors contains four contacts.
When the rotor is properly set to trip at the desired position, two of these contacts open electric
circuits and two of the contacts close electric circuits. One rotor is normally set to trip at the full open
position of the valve, and the other rotor is normally set to trip at the full close position of the valve.
Each rotor may be adjusted independently of the other:
• First rotor—one circuit is used to open the “open” holding coil circuit of the motor controller, one
circuit is used to control the “open” indicating light.
• Second rotor—one circuit is used to open the “close” holding coil circuit of the motor controller,
one circuit is used to control the “closed” indicating light.
For the geared limit switches to trip at any desired position, follow the setting procedure below.
Piece numbers refer to Figure 4.2 and Table 4.4.
1. Verify all power is OFF.
2. Using the handwheel, manually open the valve to the full open position. See Section 5.2 Manual
Operation. Note the direction of rotation of the Intermittent Gear Shaft (piece #42), located over
the Rotor (piece #49) to be set.
3. Using a screwdriver, turn the Set Rod (piece #48) clockwise until it reaches a stop position.
4. If the Rotor (piece #49) you are setting has not turned 90° to open the contacts that should trip
open at this position, insert screwdriver on the Intermittent Gear Shaft (piece #42). Turn in the
direction noted in Step No. 4 until the Rotor (piece #49) turns and opens the contacts to be set.
5. If the Rotor (piece #49) has turned so that the contacts are already open, turn the Intermittent
Gear Shaft (piece #42) in the opposite direction as previously noted in Step No. 4 until the
contacts close. Turn the Intermittent Gear Shaft (piece #42) slightly in the direction noted in Step
No. 4 until the contacts open. The Rotor (piece #49) is set at the correct position for contact
opening.
Note: In the contact “Close” position, ensure a gap exists between the contact finger and the
L-bracket as seen in figure 4.2
6. Back off the Set Rod (piece #48) until it stops. Place the screwdriver on the Intermittent Gear
Shaft (piece #42) to ensure that the shaft is tight and will not rotate. Do not force.
7. Close the valve completely. Repeat Step No. 1 through 6 to set the tripping position for the other
Rotor (piece #49).
flowserve.com
15
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
25
46
43
53 41
54
48
61
4.4.2 Four-Train Geared Limit Switch
The rotor-type, four-train geared limit switch employs four rotary drum switches. Each rotary drum
switch contains four contacts. When the rotor is properly set to trip at the desired position, two of
these contacts open electric circuits and two of the contacts close electric circuits. One rotor is set
to trip at the full open position of the valve, and one rotor is set to trip at the full close position of the
valve. The other two rotors are set at some intermediate position depending on the application.
For the geared limit switches to trip at any desired position, follow the steps in Section 4.4.1,
Two-Train Geared Limit Switch, with the exception that the piece numbers refer to Figure 4.3 and
Table 4.5.
NOTE: The upper Set Rod (piece #48) allows adjustment of the two adjacent upper rotors, and the
lower Set Rod (piece #48) allows adjustment of the two adjacent lower rotors.
Figure 4.3 – Four-Train Geared Limit Switch – Rotor Type
18
26
21
35
22 23
34
26
24
28
27
30
31
32
29
5552445845
42
57 47 5049
68
69
71
01-472-0007-3
01-472-0007-3
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Table 4.5 – Four-Train Geared Limit Switch Parts List
PieceDescription
21Cartridge
22Oilite Bushing
23Drive Shaft
24Drive Pinion (Internal)
25Helical Pinion
26Groove Pin
27Drive Sleeve and Gear
28Declutch Spring
29Drive Pinion Spur
30Pin
31Cartridge Gasket
32Cartridge Mounting Plate
33Long Socket Head Cap Screw and Lockwasher
34O-Ring
35O-Ring
36Fillet Head Cap Screw and Lockwasher
41Gear Frame
42Intermittent Gear Shaft
43Intermittent Pinion Shaft
44Geared Limit Frame Cover
45Intermittent Gear
46Intermittent Pinion
47Stem Spur Pinion
48Set Rod
49Rotor
50Groove Pin
51Cover Gasket
52Long Fillet Head Machine Screw
53O-Ring
54Setting Rod Bushing
55Gear Frame Gasket
56Insert (Rotor)
57O-Ring
58Groove Pin
61Finger Base
62Right Hand Finger Assembly
63Left Hand Finger Assembly
64Long Hex Head Cap Screw
65Lockwasher
66Hex Nut
67Washer
68Long Fillet Head Cap Screw
69Internal Tooth Lockwasher
71Flat Washer
19
flowserve.com
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
4.5 Setting Torque Switch
The torque switch is designed to protect the actuator in open and close directions.
c WARNING: Disconnect all incoming power before working on the torque switch.
c WARNING: Do not attempt to remove either the spring cartridge cap or the housing cover from
the actuator while the valve is torque-seated.
a CAUTION: Do not use abrasive cloth to clean the contacts on the torque switch.
a CAUTION: A maximum stop setting plate is furnished on all actuators. Do not exceed this
maximum setting without consulting Limitorque.
NOTE: See Section 4.3.3 for wiring connection requirements.
4.5.1 SMB-000 “Cam Style” Double Torque Switch
NOTE: Torque settings must be made with the switch mounted in the actuator.
Piece numbers correspond to Figure 4.4 and Table 4.6.
To set the torque switch:
1. Verify all electric power is OFF.
2. Loosen Pan Head Screws (piece #30).
3. For open or close operation, set Striker (piece #25) to the required torque setting. Match the edge
of the Striker with the desired number. The higher the number, the higher the torque output of the
actuator.
4. Tighten Pan Head Screws (piece #30).
5. For torque seated valves, operate the valve electrically to seat the valve. Ensure tight shut-off by
tripping the torque switch contacts.
20
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Table 4.6 – SMB-000 “Cam Style” Double Torque Switch Parts List
PieceDescription
1Terminal Block
2Contact Block
3Contact Screw
4Finger Holder
5Finger
6Shunt
7Shunt Washer
8Rivet
9Finger Spring Stud
10Compression Spring
11Spring Cup Washer
12Cotter Pin
13Hex Head Machine Screw
14Ring Tongue Connector
15Shakeproof Lockwasher, Internal Teeth
16Torque Switch Mounting Bracket
17O-Ring
18O-Ring
19Socket Head Cap Screw
20Cam
21Torsion Spring
22Spring Mandrel
23Dial
24Shaft
25Striker
26Torque Limiting Plate
27Striker Hub
28Roll Pin
29Swage Nut
30Pan Head Screw
31Shakeproof Lockwasher, External Teeth
32Flatwasher
33Arm
34Roller
35Roller Pin
36Groove Pin
37Arc Barrier
38Pan Head Screw
39Lockwasher, External Tooth
42Spring Pin
43Cam Insert
44Bushing (For piece #16)
45Washer
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
43
4.5.2 SMB-000 and SMB-00 “C Style” Double Torque Switch
NOTE: Torque settings must be made with the switch mounted in the actuator.
NOTE: See Section 4.3.3 for wiring connection requirements.
Piece numbers correspond to Figure 4.5 and Table 4.7.
To set the torque switch:
1. Verify all electric power is OFF.
2. For the open or close direction torque switch, loosen Machine Screw (piece #35) and set Pointer
(piece #7) at the desired torque setting. The higher the number, the higher the torque output of
the actuator.
3. Tighten Machine Screw (piece #35).
4. For torque seated valves, operate the valve electrically to seat the valve. Ensure tight shut-off by
tripping the torque switch contacts.
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Table 4.7 – SMB-000 and SMB-00 “C Style” Double Torque Switch Parts List
PieceDescription
1Terminal Block
2Contact Block
3Hex Nut - Remove and discard
4Contact Arm
5Dial
6Actuating Link
7Pointer
8Tripper Arm
9Shaft
10Contact Support
11Torque Limiter Plate
12Bushing (SMB-00 only)
13Roller
14Roller Pin
15Contact Finger
16Terminal Stud
17Compression Spring
18Torsion Spring
20Bearing
21O-Ring
22O-Ring
23Groove Pin
25Thrust Washer
27Lockwasher
28Groove Pin
29Hex Nut
30Hex Nut
31Cotter Pin
33Pan Head Machine Screw
34Hex Socket Set Screw
35Round Head Machine Screw
36Round Head Machine Screw
37Insulating Material
39Flatwasher
41Round Head Machine Screw
42Lockwasher, Internal Teeth
43Socket Head Cap Screw
44Lockwasher
45Mounting Bracket
46Dial Plate (SMB-00 only)
47Socket Head Cap Screw
48Lockwasher (SMB-000 only)
49Insulator (SMB-000 only) - Not Shown
50Lockwasher (SMB-000 only)
51Lockwasher (SMB-000 only)
52Lockwasher (SMB-000 only)
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
01-473-0057-3
4.5.3 SMB-0 through SMB-5 Double Torque Switch
NOTE: Torque settings must be made with the switch mounted in the actuator.
NOTE: See Section 4.3.3 for wiring connection requirements.
Piece numbers correspond to Figure 4.6 and Table 4.8.
To set the torque switch:
1. Verify all electric power is OFF.
2. For the open or close direction torque switch, loosen Machine Screw (piece #35) and set Pointer
(piece #7) at the desired torque setting. The higher the number, the higher the torque output of
the actuator.
3. Tighten Machine Screw (piece #35).
4. For torque seated valves, operate the valve electrically to seat the valve. Ensure tight shut-off by
tripping the torque switch contacts.
Figure 4.6 – SMB-0 through SMB-5 Double Torque Switch
8
23
12
5
4
3
3
2
1
3
2
1
13
25
1
2
43
44
17
33
25
37
30
34
25
4
45
35
39
5
7
11
31
42
47
3
20
27
39
27
2916
36
6
41
27
18
9
01-473-0057-3
2122101528
25
flowserve.com
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Table 4.8 – SMB-0 through SMB-5 Double Torque Switch Parts List
PieceDescription
1Terminal Block
2Contact Block
3Hex Nut - Remove and Discard
4Contact Arm
5Dial
6Actuating Link
7Pointer
8Pinion
9Shaft
10Contact Support
11Torque Limiter Plate
12Bushing
13Spacer
15Contact Finger
16Terminal Stud
17Compression Spring
18Torsion Spring
20Bearing
21O-Ring
22O-Ring
23Pin
25Thrust Washer
27Lockwasher
28Pin
29Hex Nut
30Hex Nut
31Cotter Pin
33Pan Head Self-Tapping Screw
34Hex Socket Set Screw
35Round Head Machine Screw
36Round Head Machine Screw
37Insulating Material
39Flatwasher
41Round Head Machine Screw
42Lockwasher, Internal Teeth
43Socket Head Cap Screw
44Lockwasher
45Mounting Bracket
47Socket Head Cap Screw
26
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
4.6 Position Indication
4.6.1 Local Position Indicator
NOTE: The local dial position indicator displays valve position. The position indicator can only be
adjusted when the actuator is mounted on the valve. See Figures 7.1-7.3 (SMB-000), 7.4-7.8 (SMB-
00), 7.9-7.12 (SMB-0 through 4), 7.13-7.16 (SMB-5).
To set the position indicator:
1. Disconnect all incoming power and open or remove the Limit Switch Compartment Cover.
2. Place the valve in the fully “close” position.
3. Loosen the round head machine screw that holds the pointer in place, move the pointer to the
“C” position, and retighten the screw.
The indicator is now set.
4.6.2 Remote Position Indicator
(50 ohm or 1000 ohm Potentiometer)
The SMB or SB actuator with a potentiometer installed, transmits a 0-10 VDC output signal to a
remote position indicator (meter). The potentiometer is powered by 120 VAC.
To set the potentiometer:
NOTE: The pinion has been disengaged to prevent damaging the potentiometer prior to setting the
valve.
1. Set the potentiometer by turning the pinion until the desired reading is obtained.
2. Loosen the hex nut on the back of the potentiometer and slide the potentiometer in the direction
of the idler pinion until the pinions are engaged.
3. Do not force the engagement of the pinions.
4. Retighten the hex nut on the back of the potentiometer.
5. Do not engage the pinion until the actuator and valve positions have been set.
To calibrate the potentiometer:
1. Position the valve at 50% of full travel.
2. Read the resistance from the wiper to either end of the potentiometer.
3. To set the potentiometer to the proper value, loosen the set screw on the potentiometer shaft
pinion and rotate the potentiometer shaft to a reading of ~500 ohms for the 1000-ohm potentiometer, or ~25 ohms for the 50-ohm potentiometer.
4. Tighten the set screw.
5. Run the actuator to the fully CLOSED position.
6. Adjust the CLOSED position setting to a value at or above 0 ohms.
7. Run the actuator to the fully OPEN position.
27
flowserve.com
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
8. Adjust the OPEN position setting to a value at or below 1000 ohms for the 1000-ohm potentiometer; at or below 50 ohms for the 50-ohm potentiometer.
9. Repeat steps 5 through 8 and fine-tune as necessary.
4.6.3 Remote Position Indicator
(Resistance-to-Current Signal Converter)
The SMB or SB actuator with a signal converter installed transmits a 4-20 mA output signal to a
remote position indicator (meter). The signal converter responds to the input of a 1000-ohm
potentiometer and can be powered by 24 VDC or 120 VAC for the older version R/I converter; or
18 VDC, 24 VDC, or 120 VDC for the PT20SD style R/I converter.
To set the R/I signal converter:
NOTE: The pinion has been disengaged to prevent damaging the potentiometer prior to setting the
valve.
1. Set the potentiometer by turning the pinion until the desired reading is obtained.
2. Loosen the hex nut on the back of the potentiometer and slide the potentiometer in the direction
of the idler pinion until the pinions are engaged.
3. Do not force the engagement of the pinions.
4. Retighten the hex nut on the back of the potentiometer.
5. Do not engage the pinion until the actuator and valve positions have been set.
To calibrate the R/I signal converter:
1. Position the valve at 50% of full travel.
2. Read the ohms from the wiper to either end of the potentiometer.
3. To set the potentiometer to the proper value, loosen the set screw on the potentiometer shaft
pinion and rotate the potentiometer shaft to a reading of 500 ohms.
4. Tighten the set screw.
5. Run the actuator to the fully CLOSED position.
6. Adjust the ZERO control to an output of 4 mA.
7. Run the actuator to the fully OPEN position.
8. Adjust the SPAN control to an output of 20 mA.
9. Repeat steps 5 through 8 to fine-tune as necessary.
28
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
Remote position indicator
0-10 volts full scale deflection
Control voltage range
110 volts to 480 volts
Potentiometer 1000 ohm 2 Watt
customer’s equipment
terminal as valve opens
Figure 4.7 – Typical Connection for a 50-ohm Potentiometer
25 Watt, 50 OHM Potentiometer type
variable resistor mounted in SMB/SB housing
Voltmeter
type
P3P2P1
RES
175 Watt, 2500 ohm Adjustable resistor
to be located adjacent to remote position indicator
Figure 4.8 – Typical Connection for a 1000-ohm Potentiometer
for voltage adjustment
in limit switch housing
(CCW)
P1
Potentiometer slider rotates
toward counter clockwise (CCW)
Figure 4.9 – Typical Connection for R/I Signal Converter (Older Version)
4-20 mA
Output Signal
P2
P3
(CW)
To
91
(–)90(+)CL2CL1
1000 ohm
P1
POT
P2
P3
9190 CL2 CL1 P1 P2P3
(–) (+)
R to I
Signal Converter
PC Board
Connection
29
flowserve.com
SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15
POT
24 VDC or
18 VAC
See comments
under Section
4.6.3,
Figure 4.10 – Typical Connection for PT20SD R/I Converter
1000 ohm
(S)
4-20 mA
Output
Signal
(+)
(–)
(+)
(–)
BLU
BLU
18V
115V
Black
Brown
Orange
Green
1
2
3
4
5
6
(CCW)
(+)m A
(–)m A
+V
COM
Signal Converter
1 BLK
3 RED
2 BRN
CCW SC W
1
2
3
LK2
1
AC
2
DC
3
LK3
(CW )
4.7 Additional Electrical Components
4.7.1 Reversing Starter
The reversing starter electrically changes the operation of the electric motor from one direction
of rotation to the other. The starter consists of two contactors mounted on a common base and
mechanically interlocked.
Each contactor consists of the following:
• three normally open power contacts
• one normally open circuit holding contact
• one normally closed interlock
• one magnetic holding coil.
30
The starter can be provided two ways:
• Mounted within the actuator limit switch compartment
• Supplied in a separate enclosure
4.7.2 Overload Relays
Overload relays de-energize the holding coils of the reversing starter, which open the power contacts
to de-energize the electric motor. The relays function at a predetermined current value and can reset
either automatically or manually as follows:
• Reset automatically if mounted as detailed in Figure 4.11.
• Reset manually if the reversing starter is furnished separately.
The relays are sized in accordance with full load (running) motor current.
Loading...
+ 76 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.