Flowserve PMV Valve Control System User Manual

Manual F5
PMV Valve Control System
Manual F5
alve Control System
– 1 –
Manufacturers declaration • Hersteller-Erklärung • Déclaration de fabricant
GB
Manufacturers declaration
and 93/68/EEC.
We hereby confirm that the appliances described in this sheet has been manufactured in compliance
with the applicable standards and is intended for installation in a machine/application, and that
commissioning is strictly prohibited until evidence has been provided that the machine/application in
question is also in compliance with
EC directive 89/392/EEC/91/368/EEC, 89/336/EEC, 73/23/EEC and 93/68/EEC.
This manufacturers declaration is applicable to the following PMV series:
F5.
D
Hersteller-Erklärung
im Sinne der EG-Richtlinie 89/392/EWG/91/368/EWG, 89/336/EWG, 73/23/EWG
und 93/68/EWG.
Hiermit erklären wir, daß die in diesem Blatt beschriebenen Geräte entsprechend den gültigen Normen
gebaut und zum Einbau in eine Maschine oder Applikation bestimmt sind, sowie daß deren
Inbetriebnahme so lange untersagt ist, bis festgestellt wurde, daß diese
Maschine/Applikation ebenfalls der EG-Richtlinie
89/392/EWG/91/368/EWG, 89/336/EWG, 73/23/EWG und 93/68/EWG entspricht.
Diese Herstellererklärung hat für folgende PMV-Serien Gültigkeit:
F5.
F
Déclaration de fabricant
au sens dela directive de la 89/392/CEE/91/368/CEE, 89/336/CEE, 73/23/CEE et 93/68/CEE.
Nous déclarons par la présente que les appareils décrits sur cette page sont construits en conformité avec les normes en vigueur et qu'ils sont destinés à être montés dans une machine ou une application, nous déclarons également que leur mise en service est interdite tant qu'il n'a pas été constaté que cette
macine/application satisfait
également à la directive 89/392/CEE/91/368/CEE, 89/336/CEE, 73/23/CEE et 93/68/CEE.
Cette déclaration de fournisseur est valable pour les types d'appareils PMV suivants:
F5.
Mr. Jan-Eric Andersson
President, Palmstiernas Instrument AB
Manual F5
– 2 –
PMV Feedback module storage and handling procedures
PMV feedback modules are precision instruments which should be stored and handled accordingly to avoid problems or damage. Feedback modules contain electronic components which can be damaged by exposure to water. Appropriate precautions should be taken to protect units while in storage.
Warehouse storage
-Stored in original PMV shipping containers, units should be stored in an environmentally controlled area, i.e. clean, cool (15-26°C, 60-80°F) and dry, out of direct sunlight or weather exposure.
Field storage
- If feedback units must be stored outdoors, make sure front covers are tightened, all conduits entries are sealed and that units not are exposed to direct sunlight, rain or snow.
Potential damage mechanism
When units are stored in hot, humid climates, the daily heating/cooling cycle will cause air to expand/contract and be drawn in and out of the feedback housing through ports left open. Dependent on the local temperature variations, humidity and dew points and time in storage, condensation could occur and accumulate inside causing erratic operation or failure due to water and corrosion. The potential for condensation damage is especially high in southern climates and aggravated if units are exposed to direct sunlight.
For further assistance, please contact you nearest PMV office.
Storage Seal
F5 is supplied with conduit entry points sealed. The seal is only a storage seal, not to be used as seal when F5 is in operation. If Storage Seal is removed or damaged, make sure conduit entry points are resealed before further shipping or storage. Use proper cable glands or vapour proof tape.
Mount F5 on positioner P5/EP5 or actuator/valve package. Remove Storage Seal for conduit entry E & E2, make electrical connections, install proper cable glands or plugs to ensure the units sealing.
1
Manual F5
– 3 –
Description
The PMV F5 is a feedback unit uniquely designed to mount on top of the PMV P5, EP5 or P-2000 positioners with minimum parts required. The F5 can also be mounted on actuators with an additional mounting kit. The F5 is available in two different enclosures, standard or explosion proof.
The standard enclosure for F5 offers a gasketed NEMA 4/ IP66 enclosure with optional American and European intrinsically safe approvals. The explosion proof version is approved NEMA 7 / IP66 and carries North American and European approvals. Both enclosures can be furnished with Namur sensors, mechanical or proximity switches, potentiometer or 4-20 mA position trans­mitter or a combination of these items.
Manual F5
– 4 –
Mounting on P5 or EP5
– Remove the front cover and the indicator from the positioner. – Loosen and remove the Allen head screw (3) (5mm hex-wrench) – Install drive coupling (4) on the positioner shaft, secure it with screw (3) – Check that F5is fitted with 4 nos of screws 5 and O-ring 9, install the F5 on
top of the positioner unit, make sure that the coupling is properly engaged before tightening the four screws 5.
– Make connections and calibrate. – Reinstall indicator 2 and front cover 1 on the F5.
5
9
4
3
1
2
5
O-ring seal
Mounting F5 on actuator
Install the spindle adaptor 1 into F5 shaft, make sure that a spring clip 2 is fitted. A solid click should be heard when the spindle adaptor is properly installed into the F5 shaft. Mount F5 on the actuator using a mounting kit and the ISO F05 mounting holes on the bottom of the F5. Make sure that the F5 spindle is properly alligned on top of the actuator. Check that the four fasteners 3 are installed into F5.
2 1
(On/Off control valves)
Manual F5
3
– 5 –
Mounting on P-2000/P-2020
– Remove front cover, indicator and cam nut from the positioner – Replace the cam nut with coupling 1, calibrate the positioner. – Check that the gasket is fitted to the bottom of plate 2, install screws 5 (3x
long, 1x short) plastic washer 6 and O-rings 7. – Secure the F5 to the plate 2 with screws 3. – Install assembly onto the positioner, make sure that coupling 1 is properly
engaged. – Make electrical connections and calibrate.
5
6
2
7
3
1
Manual F5
– 6 –
F5-EX
The F5-EX is approved explosion proof by CSA, FM and CENELEC. Front cover screws shall be tightened 7 Nm (5,2 lbf x ft).
Approvals: CSA, FM Div. 1, Class 1,2 & 3 Group BCDEFG T4-T6
CENELEC EEx d IIB + H2 T4-T6 LCIE 97.D6140
Manual F5
– 7 –
Installing F5-EX on P5/EP5
– Remove front cover, indicator and Allen head screw from the positioner. – Install drive coupling 4 and secure it with the Allen head screw. – Remove front covers and indicator from the F5-EX unit. – Remove screws 3. – Install F5-EX on P5/EP5, , make sure drive coupling is properly engaged
before tightening screws 5. – Reinstall and tight screws 3. Connect and calibrate. – Reinstall front covers and indicator. – Front cover screws 2 shall be tightened to 7 Nm (5,2 lbf x ft)
5
4
3
2
Installing on an actuator
– Remove front covers and indicator from the F5-EX unit. – Remove screws 3 and (5). Reinstall and tight screws 3. – Install drive shaft into F5-EX, a solid click should be heard when spindle
adapter is properly installed. – Mount F5-EX on the actuator using the F05 holes and a mounting kit. – Connect and calibrate, reinstall front covers and indicator. – Front cover screws 2 shall be tightened to 7 Nm (5,2 lbf x ft).
3
2
Manual F5
– 8 –
Connections
WARNING! Units installed in hazardous locations must have proper agency approvals and be installed according to installation drawing F5-2-4-9516.
Conduit entries are PG13,5 (M20) or NPT 1/2“ Make electrical connections according to wiring diagrams and tighten cable glands. Terminals are 2.5 mm2 (AVG 14) screw terminals.
Adjustments
CAUTION! Moving parts – risk of injury.
The cams/gear wheel are secured in position by friction provided from the cam/shaft assembly. To adjust switches and/or position transmitter, rotate gear wheel 2 and cams 3 to desired position using tool F5-22 or tip of a screw driver that fits snuggly in one of the slotted holes. Start calibration procedure by adjusting position transmitter first, then continue with the lower switch and complete with the upper switch. If cams exhibit high stiction, rotate them back and forth rapidly several times. Do not adjust nut 4 or lubricate cams, call PMV for assistance.
Manual F5
– 9 –
Calibration
Potentiometer
1. Make electrical connections to terminals 7,8 and 9. Check that the potentiometer is connected to connector C on the printed circuit board.
2. Stroke the actuator to check direction of travel indicated by the potentio-
meter. To change direction of travel, swap wires at terminals 7 and 9.
3. Stroke the actuator to the position where the minimum potentiometer resistance is desired.
4. Adjust the potentiometer output reading to approx. 50 Ohm by rotating gear wheel 2 with special tool F5-22 or tip of a screw driver placed in one of the slotted holes.
5. Stroke the actuator to desired maximum resistance position and check reading.
6. Repeat steps 3-5 if necessary to obtain desired resistance change.
7. Set switches or install frontcover.
4-20 mA position transmitter
1. Set direction of rotation by placing potentiometer jumper in location A or
B. (Location A for counter clockwise CCW valve/actuator rotation (Direct), location B for clockwise CW valve/actuator rotation (Reverse).
2. Set jumper X to the desired valve rotation angle, for 30 deg or 45 deg
rotation choose position 30, For 60 deg or 90 deg rotation choose position 90, for 180 deg rotation choose position 30 and for 270 deg rotations choose position 90. For 30° deg - 45° deg choose pos 30.
3. Make electrical connections according to wiring diagram. Power supply
should be >9 to <28 VDC (24 VDC recommended).
4. Connect a 4-20 mA meter to testoutlet 1. Adjust potentiometer P1 20 revolutions CW & P2 20 revolutions CCW. Stroke actuator to the desired 4 mA position and check that current deflection is correct. Rotate gear wheel 2 with tool F5-22 or tip of a screw driver placed in one of the slotted holes until minimum valve is reached.
Potentiometer
7
8 9
5. Adjust the output signal 4,0 mA with potentio­meter P2. LED will illuminate when out put is 4 mA (±1%) or less. Stroke actuator to the desired 20 mA position and adjust the output to 20,0 mA with potentiometer P1. LED will illuminate when out put is 20 mA (±1%) or more.
6. Stroke actuator again, check and adjust 4 mA and 20 mA readings. Install front cover or set switches first, as follows:
Manual F5
4-20 mA position transmitter
4-20 mA position transmitter
+
89-
Display 4-20 mA
+-
Power
+
Supply
-
24 VDC
– 10 –
Switches & Sensors
NAMUR switches
2 3
5 6
Upper switch
Lower switch
+
-
+
-
Limit switches cams must be adjusted separately with valve in an open and closed position. With the valve in fully open or closed position adjust the lower cam 3 to desired position by rotating it with special tool F5-22 or by the tip of a screw driver placed in one of the slotted holes on the cam. Stroke the valve fully and repeat the procedure above to set the upper cam. Stroke valve open/closed to check proper limit switch operation.
Upper switch
Lower switch
Proximity switches
Mechanical switches
C
NC
NO
NO
NC
C
1 2 3
6 5 4
Upper switch
Lower switch
C
C
Mechanical switches
Mechanical switches
Technical specifications
General
Conduit entries 2x 1/2 NPT or 2x PG 13,5 (M20) Housing material Die cast aluminum Surface treatment ED painting Mounting According to VDI/VDE 3845 Fasteners Stainless steel A2/A4 Terminals 2,5 mm Enclosure IP66, NEMA 4
Switches, mechanical
Type Mechanical SPDT V3 Rating *6/2,5A 250 VAC *Res/Ind Approvals CSA,UL,VDE Temp range -20°C to 80°C (-4°F to 185°F)
Sensors, Namur
Type Proximity DIN 19234 NAMUR Load Current 1mA 3mA Voltage range 5-25 VDC Hysteresis 0,2% Temp range -20°C to 80°C (-4°F to 185°F)
2
(AVG 14)
Namur sensors
NC
NO
NO
NC
1 2 3
6 5 4
Weight
Standard enclosure 0.7 kg (lbs 1.5) Explosion proof 2.1 kg (lbs 4.6)
Switches proximity
Contact rating 2 W or 2 VA @ 30 VDC/
VAC, 0.1 A Maximum operating time 0.5 miliseconds Breakdown voltage 200VDC Contact resistance 0.2 Ohms Switch type SPDT hermetically sealed
in one unit Mechanical and
electrical life >10 million operations
Potentiometer
Out put 5k (4k at 90°) Elements Conductive plastic Power rating at 70° 1 W Linearity 1% Resolution Essentially infinite Temp range -20°C to 80°C (-4°F to 185°F)
4-20 mA position transmitter
Power supply 9-28 VDC (24VDC recommended) Out put signal 4-20 mA LED indication at 4 mA ±1% LED indication at 20 mA ±1% Resolution Infinite Minimum rotation travel 30° Maximum rotation travel 90° Linearity <1% of full scale Hysteresis <0,5% of full scale Out put current limit 24 mA DC Load impedance 800 at 24 VDC Temp range -20°C to 80°C (-4°F to 185°F)
Manual F5
– 11 –
F5 IS
Manual F5
– 12 –
F5 IS
Manual F5
– 13 –
Connection of F5 intrinsically safe version
Manual F5
– 14 –
F5-EX
Manual F5
– 15 –
F5-EX
Manual F5
– 16 –
Spare Parts
10-13
10-13
14
14
1
10-13
17
15
15
2-9
16
14
16
15
14
16
16
Manual F5
– 17 –
Spare Parts List
Manual F5
– 18 –
Dimension drawing
Manual F5
– 19 –
T rouble shooting
Switches
Check electrical connections and cam settings.
Potentiometer
If there is no output signal, check electrical connec­tions and for open circuit, check that potentio­meter is not out of it´s mechanical range. If output deflection is wrong reverse connection terminals 7 and 9.
4-20 mA position transmitter
If there is no output signal, check electrical connections, polarity, loop power supply, and that the potentiometer is within its range.
Palmstiernas Instrument AB Korta Gatan 9 SE-171 54 Solna SWEDEN Tel: +46 (0) 8 555 106 00 Fax: +46 (0) 8 555 106 01 E-mail: info@pmv.nu Internet: www.pmv.nu
SUBSIDIARIES:
If full output signal cannot be achieved by adjustment, check supply voltage and jumper X settings.
If output signal increases and decreases in the wrong direction, move connector from A to B or vice versa.
If the 4 mA fine adjustment P2 does not have enough span, zero must be mechanically reali­gned as follows: Turn P2 20 revolutions counter clockwise, then repeat the transmitter calibration procedure.
Distributor
PMV Controls Ltd
Headlands Business Park Ringwood Hampshire BH24 3PB ENGLAND Tel: +44 (0) 1425 48 08 88 Fax: +44 (0) 1425 48 08 89 E-mail: sales@pmv-controls.ltd.uk Internet: www.pmv-controls.ltd.uk
PMV-USA, Inc
1440 Lake Front Circle Unit 160 The Woodlands, Texas 77380 USA Tel: +1 281 292 7500 Fax: +1 281 292 7760 E-mail: pmvusa@pmvusa.com Internet: www.pmvusa.com
(The information in this brochure is subject to change without notice.)
PMV GmbH
Postfach 2310 D-41554 Kaarst GERMANY Tel: +49 (0) 2131 667 081/82 Fax: +49 (0) 2131 667 083 E-mail: info@pmv-germany.de Internet: www.pmv-germany.de
Palmstiernas Svenska AB
Box 21 SE-663 21 Skoghall SWEDEN Tel: +46 (0) 54 52 14 70 Fax: +46 (0) 54 52 14 42 E-mail: info@palmstiernas.se Internet: www.palmstiernas.se
23744/2001.6 Ekvator
Manual F5
– 20 –
Loading...