Flowserve DataFlo P Smart Positioner User Manual

DataFlo P Smart Positioner
FCD WCAIM2060-00 (Part 08023)
1. Remove cover and apply appropriate voltage to terminals 1 (neutral or negative) and 2 (hot or positive).
2. Connect input source to terminals 10 (-) and 11 (+) and 12 (if applicable).
4. Simultaneously press and hold the “SEL” and “DN” keys for three seconds. “CAL” will be displayed for two seconds and the security code will be checked. If the required security code is not zero (“0000”), the display will begin alternating between “CodE” and “0000.”
NOTE: If the required code is zero, it will not need to be entered, i.e., it will be bypassed and display will automatically flash “SEtL.” Skip to paragraph 8.
5. Enter the security code, if necessary, as follows. (If the code is forgotten, the special number 4800 can be used to gain entry.)
6. Quick tap “SEL” key once. First 0 will flash. Quick tap “UP” key until you reach code number. Quick tap the “DN” key once. The second 0 will flash. Quick tap “UP” key until the next code number is reached. Continue this procedure as needed for the remaining code numbers. Quick tap “SEL” to accept code.
7. The display now flashes between “SEtL” and a value.
8. Simultaneously press and release “SEL” and “UP” keys, then adjust input signal to lower input value, e.g., 4 mA. Quick tap “SEL” to lock in value.
9. Quick tap “DN” key. Display will flash “SEtU” and a value.
Functions
Worcester Actuation Systems
10. Simultaneously press and release “SEL” and “UP” keys, then adjust input signal to higher input value, e.g., 20 mA. Quick tap “SEL” to lock in value.
11. Quick tap “DN” key. Display will flash between “PoC” and a number between 0 and 5 volts.
12. Simultaneously press and release “SEL” and “UP” keys. Using the “DN” key, adjust so shaft is full clockwise. The display should read between .200 and .400 volts. If not, rotate potentiometer face gear with your fingers. It is a friction fit. Quick tap “SEL” to lock in read­ing.
13. Quick tap “DN” key. Display will flash between “PoCC” and the feedback voltage value.
14. Simultaneously press and release “SEL” and “UP” keys. Using the “UP” key, adjust so shaft is full counterclockwise. Quick tap “SEL” to lock in reading.
15. Quick tap “DN” key. Display will flash between “Cyt” and a cycle time reading.
16. Simultaneously press and release “SEL” and “UP” keys. Actuator will automatically close, then open to measure cycle time, displaying “PoC” at the clockwise position and “PoCC” at the counterclockwise position.
Calibration is now complete. Press and hold “SEL” key for three seconds. Positioner reverts to automatic control by input signal.
FLOWSERVE FLOW CONTROL Worcester Actuation Systems
5114 Woodall Road P.O. Box 11318 Lynchburg, VA 24506-1318 Phone: 434-528-4400 Fax: 434-845-9736
Worcester Actuation Systems
For more information about Flowserve Corporation, visit www.flowserve.com or call USA 1-800-225-6989.
© 2004 Flowserve Corporation, Irving, Texas, USA. Flowserve is a registered trademark of Flowserve Corporation.
FCD WCAIM2060-00 Printed in USA.
(Part 08023)
Loading...