Flowserve APKD User Manual

USER INSTRUCTIONS
APKD
Double-Case, Double Suction Vertical Pump
PCN=26999903 07-13 (E) "Original Instructions"
Installation
Operation
Maintenance
operating, using and maintaining this equipment
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
1 INTRODUCTION AND SAFETY ....................... 3
1.1 General ......................................................... 3
1.2 CE marking and approvals ........................... 3
1.3 Disclaimer ..................................................... 3
1.4 Copyright ...................................................... 3
1.5 Duty conditions ............................................. 3
1.6 Safety ............................................................ 4
1.7 Safety labels summary ................................. 7
1.8 Noise level .................................................... 7
1.9 Specific machine performance ..................... 8
2 TRANSPORT AND STORAGE ........................ 8
2.1 Consignment recipt and unpacking .............. 8
2.2 Handling........................................................ 9
2.3 Lifting ............................................................ 9
2.4 Storage ....................................................... 12
2.5 Recycling and end or product life ............... 12
3 DESCRIPTION ............................................... 12
3.1 Configuration .............................................. 12
3.2 Nomenclature ............................................. 13
3.3 Design of major parts ................................. 15
3.4 Performance and operation limits ............... 16
4 INSTALLATION .............................................. 17
4.1 Location ...................................................... 17
4.2 Part Assemblies .......................................... 22
4.3 Foundation .................................................. 22
4.4 Grouting ...................................................... 24
4.5 Initial Alignment .......................................... 24
4.6 Piping .......................................................... 25
4.7 Electrical Connections ................................ 27
4.8 Final shaft alignment check ........................ 27
4.9 Protection systems ..................................... 27
5 COMMISSIONING, START-UP, OPERATION
AND SHUTDOWN ................................................... 28
5.1 Pre-commissioning procedure .................... 28
5.2 Pump lubricants .......................................... 28
5.3 Impeller adjustment .................................... 28
5.4 Direction of rotation .................................... 30
5.5 Guarding ..................................................... 30
5.6 Priming and auxiliary supplies .................... 31
5.7 Starting the pump ....................................... 31
5.8 Operating the pump .................................... 33
5.9 Stopping and shutdown .............................. 34
5.10 Hydraulic mecanical and electrical duty . 34
6 MAINTENANCE .............................................. 35
6.1 General ....................................................... 35
6.2 Maintenance schedule ................................ 36
6.3 Spare parts ................................................. 37
6.4 Recommended spares and consumables .. 38
6.5 Tools required ............................................. 38
6.6 Fastener torques ........................................ 39
6.7 Setting impeller clearance .......................... 39
6.8 Disassembly ............................................... 39
6.9 Examination of parts ................................... 40
6.10 Assembly ................................................ 43
7 FAULTS, CAUSES AND REMEDIES ............. 44
8 DRAWINGS AND PARTS LISTS ................... 46
8.1 Cross section: Product lubricated APKD .... 46
8.2 Cross section: Suction barrel APKD ........... 49
8.3 General arrangement drawing .................... 52
9 CERTIFICATION ............................................. 52
10 OTHER RELEVANT DOCUMENTATION AND
MANUALS ................................................................ 52
10.1 Supplementary user instructions ............ 52
10.2 Change notes ......................................... 52
10.3 Additional sources of information ........... 52
Page 2 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
1 INTRODUCTION AND SAFETY

1.1 General

These instructions must always be kept
close to the product's operating location or directly with the product.
Flowserve products are designed, developed and manufactured with state-of-the-art technologies in modern facilities. The unit is produced with great care and commitment to continuous quality control, utilizing sophisticated quality techniques, and safety requirements.
Flowserve is committed to continuous quality improvement and being at service for any further information about the product in its installation and operation or about its support products, repair and diagnostic services.
These instructions are intended to facilitate familiarization with the product and its permitted use. Operating the product in compliance with these instructions is important to help ensure reliability in service and avoid risks. The instructions may not take into account local regulations; ensure such regulations are observed by all, including those installing the product. Always coordinate repair activity with operations personnel, and follow all plant safety requirements and applicable safety and health laws and regulations.
These instructions must be read prior to installing, operating, using and maintaining the equipment in any region worldwide. The equipment must not be put into service until all the conditions relating to safety noted in the instructions, have been met. Failure to follow and apply the present user instructions is considered to be misuse. Personal injury, product damage, delay or failure caused by misuse are not covered by the Flowserve warranty.
1.2 CE marking and approvals
It is a legal requirement that machinery and equipment put into service within certai n regions of t he world sha ll conform with the applicable CE Marking Directive s covering Machinery and, where ap plicable, L ow Voltag e Equipment, Electromagnetic Compatibility (EMC), Pressure Equipment Directive (PED) and Equipment for Potentially Explosive Atmospheres (ATEX).
Where applicable the Directives and any additional Approvals cover important safety aspects relating to
machinery and equipment and the satisfactory provision of technical documents and safety instructions. Where applicable this document incorporates information relevant to these Directives and App rovals. To confirm the Approvals applying and if the product is CE marked, check the serial number plate markings and the Certification. (See section 9, Certification.)

1.3 Disclaimer

Information in these User Instructions is believed to be complete and reliable. However, in spite of all of the efforts of Flowserve Corporation to provide comprehensive instructions, good engineering and safety practice should always be used.
Flowserve manufactures products to exacting International Quality Management System Standards as certified and audited by external Qual ity Assurance organizations. Genuine parts and accessories have been designed, tested and incorporated into the products to help ensure their continued product quality and performance in use. As Flowserve cannot test parts and accessories sourced fr om other vendo rs the incorrect incorporation of such parts and accessories may adversely affect the performance and safety features of the products. The failure to properly select, install or use authorized Flow serve parts an d accessories is considered to be misuse. Damage or failure caused by misuse is not cov ered by the Flowserve warranty. In addition, any modification of Flowserve products or removal of original components may impair the safety of these products in their use.

1.4 Copyright

All rights reserved. No part of these instructions may be reproduced, stored in a retrieval system or transmitted in any form or by any means without prior permission of Flowserve.

1.5 Duty conditions

This product has been selected to meet the specifications of your purchaser order. The acknowledgement of these conditions has been sent separately to the Purchaser. A copy should be kept with these instructions.
The product must not be operated beyond the parameters specified for the application. If there is any doubt as to the suitability of the product for the application intended, contact Flowserve for advice, quoting the serial number.
If the conditions of service on your purchase order are going to be changed (for example liquid pumped,
Page 3 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
temperature or duty) it is requested that the user seeks the written agreement of Flowserve before start up.

1.6 Safety

1.6.1 Summary of safety markings
These User Instructions contain specific safety markings where non-observance of an instruction would cause hazards. The specific safety markings are:
This symbol indicates electrical safety instructions where non-compliance will involve a high risk to personal safety or the loss of life.
This symbol indicates safety instruct ions where non-compliance would affect personal safety and could result in loss of life.
This symbol indicates “hazardous and toxic fluid” safety instructions where non-compliance would affect personal safety and could result in loss of life.
This symbol indicates safety instructions where non-compliance will involve some risk to safe operation and personal safety and would damage the equipment or property.
This symbol indicates explosive atmosphere zone marking according to ATEX. It is used in safety instructions where non-compliance in the hazardous area would cause the risk of an explosion.
This symbol is used in safety instructions to remind not to rub non-metallic surfaces with a dry cloth; ensure the cloth is damp. It is used in safety instructions where non-compliance in the hazardous area would cause the risk of an explosion.
This sign is not a safety symbol but indicates
an important instructi on in t he assem bly proce ss.
1.6.2 Personnel qualification and training
All personnel involved in the operation, installation, inspection and maintenance of the unit must be qualified to carry out the work involved. If the personnel in question do not already possess the necessary knowledge and skill, appropriate training and instruction must be provided. If required the operator may commission the manufacturer/supplier to provide applicable training.
Always coordinate repair activity with operations and health and safety personnel, and follow all plant safety requirements and applicable safety and health laws and regulations.
1.6.3 Safety action
This is a summary of conditions and actions to prevent injury to personnel and damage to the environment and to equipment. For products used in potentially explosive atmospheres section 1.6.4 also applies.
NEVER DO MAINTENANCE WORK
WHEN THE UNIT IS CONNECTED TO POWER
GUARDS MUST NOT BE REMOVED WHILE
THE PUMP IS OPERATIONAL
DRAIN THE PUMP AND ISOLATE PIPEWORK BEFORE DISMANTLING THE PUMP The appropriate safety precautions should be taken where the pumped liquids are hazardous.
FLUORO-ELASTOMERS (When fitted.) When a pump has experienced temperatures over 250 ºC (482 ºF), partial decomposition of fluoro­elastomers (example: Viton) will occur . In this condition these are extremely dangerous and skin contact must be avoided.
HANDLING COMPONENTS Many precision parts have sharp corners and the wearing of appropriate safety gloves and equipment is required when handling these components. To lift heavy pieces above 25 kg (55 lb) use a crane appropriate for the mass and in accordance with current local regulations.
APPLYING HEAT TO REMOVE IMPELLER There may be occasions when the impeller has either been shrunk fit on to the pump shaft or has become difficult to remove due to products of corrosion.
If you elect to use heat to remove the impeller , it must be applied quickly to the impeller boss. TAKE GREAT CARE!
Before applying heat ensure any residual hazardous liquid trapped between the impeller and pump shaft is thoroughly drained out through the impeller keyway to prevent an explosion or emission of toxic vapour. This must be carried out with the shaft in the vertical position. On some pump sizes a cavity exists in the impeller bore so on occasions a significant volume of liquid may drain out.
THERMAL SHOCK Rapid changes in the temperature of the liquid within the pump can cause thermal shock, which can result in damage or breakage of components and should be avoided.
Page 4 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
HOT (and cold) PARTS If hot or freezing components or auxiliary heating supplies can present a danger to operators and persons entering the immediate area action must be taken to avoid accidental contact. If complete protection is not possible, the machine access must be limited to maintenance staff only, with clear visual warnings and indicators to those entering the immediate area. Note: bearing housings must not be insulated and drive motors and bearings may be hot.
If the temperature is greater than 80 ºC (175 ºF) or below -5 ºC (20 ºF) in a restricted zone, or exceeds local regulations, action as above shall be taken.
HAZARDOUS LIQUIDS When the pump is handling hazardous liquids care must be taken to avoi d exposure t o the liq uid by appropriate siting of the pump, limiting personnel access and by operator training. If the liquid is flammable and/or explosive, strict safety procedures must be applied.
Gland packing must not be used when pumping hazardous liquids.
PREVENT EXCESSIVE EXTERNAL PIPE LOAD Do not use pump as a support for piping. Do not mount expansion joints, unless allowed by Flowserve in writing, so that their force, due to internal pressure, acts on the pump flange.
ENSURE CORRECT LUBRICATION (See section 5, Commissioning, startup, operation and shutdown.)
START THE PUMP WITH OUTLET VALVE PARTLY OPENED (Unless otherwise instructed at a specific point in the User Instructions.) This is recommended to minimize the risk of overloading and damaging the pump motor at full or zero flow. Pumps may be started with the valve further open only on installations where this situation cannot occur. The pump outlet control valve may need to be adjusted to comply with the duty following the run-up process. (See section 5, Commissioning start-up, operation and shutdown.)
NEVER RUN THE PUMP DRY
DO NOT RUN THE PUMP AT ABNORMALLY HIGH OR LOW FLOW RATES Operating at a flow rate higher than norma l or at a flo w rate with no back pressure on the pump may overload the motor and cause cavitation. Low flow rates may cause a reduction in pump/beari ng life, ov erheatin g of the pump, instability and cavitation/vibrat ion.
1.6.1 Products used in potentially explosive
atmospheres
Measures are required to:
Avoid excess temperature  Prevent build up of explosive mixtures  Prevent the generation of sparks  Prevent leakages  Maintain the pump to avoid hazard
The following instru ctions fo r pumps a nd pum p units when installed in potentially explosive atmospheres must be followed to help ensure explosion protecti on. For ATEX, both electrical and non-electrical equipment must meet the requirements of E uropean Directiv e 94/9/EC. Always observe the reg ional le gal Ex requirements eg Ex elect rical item s out side the E U may be required certified to other than ATEX eg IECEx, UL.
1.6.1.1 Scope of compliance
Use equipment only in the zone for whic h it is appropriate. Always check that the driver, drive coupling assembly, seal and pump equipment are suitably rated and/or certifie d for the classi fication of the specific atmosphere in which they are to be inst alled.
Where Flowserve has supplied only the bare shaft pump, the Ex rating applies only to the pump. The party responsible for assembling the ATEX pump set shall select the coupling, driver and any additional equipment, with the necessary CE Certificate/ Declaration of Conformity establishing it is suitable for the area in which it is to be installed.
The output from a variable frequency drive (VFD) can cause additional heating affects in the motor and so, for pumps sets with a VFD, the ATEX Certification for the motor must state that it is covers the situation where electrical supply is from the VFD. This particular requirement still applies even if the VFD is in a safe area.
INLET VA LVES TO BE FULLY OPE N WHEN PUMP IS RUNNING Running the pump at zero flow or below the recommended minimum flow continuously will cause damage to the pump and mechanical seal.
Page 5 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
1.6.1.2 Marking
An example of ATEX equipment marking is shown below. The actual classification of the pump will be engraved on the nameplate.
II 2 GD c IIC 135 ºC (T4)
Equipment Group I = Mining II = Non-mining
Category 2 or M2 = high level protection 3 = normal level of protection
Gas and/or dust G = Gas D = Dust
c = Constructional safety
(in accordance with EN13463-5)
Gas Group (Equipment Category 2 only) IIA – Propane (typical) IIB – Ethylene (typical) IIC – Hydrogen (typical)
Maximum surface temperature (Temperature Class) (see section 1.6.4.3.)
1.6.1.3 Avoiding excessive surface
temperatures
ENSURE THE EQUIPMENT TEMPERATURE
CLASS IS SUITABLE FOR THE HAZARD ZONE Pumps have a temperature class as stated in the
ATEX Ex rating on the nameplate. These are based on a maximum ambient of 40 ºC (104 ºF); refer to Flowserve for higher ambient temperatures.
The surface temperature on the pump is influenced by the temperature of the liquid handled. The maximum permissible liquid temperature depends on the temperature class and must not exceed the values in the table that follows.
Temperature class
to EN13463-1
T6 T5 T4 T3 T2 T1
* The table only takes the ATEX tem perature class int o consideration.
Pump design or material, as well as component design or m aterial, may further limit the maximum working temperature of the liquid .
Maximum surface
temperature permitted
85 °C (185 °F) 100 °C (212 °F) 135 °C (275 °F) 200 °C (392 °F) 300 °C (572 °F) 450 °C (842 °F)
Temperature limit of
liquid handled *
Consult Flowserve Consult Flowserve
115 °C (239 °F) 180 °C (356 °F) 275 °C (527 °F) 400 °C (752 °F)
The temperature rise at the seals and bearings and due to the minimum permitted flow rate is taken into account in the temperatures stated.
The responsibility for compliance with the specified maximum liquid temperature is with the plant operator.
Temperature classification “Tx” is used when the liquid temperature varies and the pump could be installed in different hazarous atmospheres. In this case the user is responsible for ensuring that the pump surface temperature does not exceed that permitted in the particular hazardous atmosphere.
If an explosive atmosphere exists during the installation, do not attempt to check the direction of rotation by starting the pump unfilled. Even a short run time may give a high temperature resulting from contact between rotating and stationary components.
Where there is any risk of the pump being run against a closed valve generating high liquid and casing external surface temperatures, fit an external surface temperature protection device.
Avoid mechanical, hydraulic or electrical overload by using motor overload trips, temperature monitor or a power monitor and make routine vibration monitoring checks.
In dirty or dusty environments, make regular checks and remove dirt from areas around close clearances, bearing housings and motors.
1.6.1.4 Preventing the build up of explosive mixtures
ENSURE THE PUMP IS PROPERLY FILLED AND VENTED AND DOES NOT RUN DRY Ensure the pump and relevant suction and discharge pipeline system is totally filled with liquid at all times during the pump operation, so that an explosive atmosphere is prevented. In addition it is essential to make sure that seal chambers, auxiliary shaft seal systems and any heating and cooling systems are properly filled.
If the operation of the system cannot avoid this condition fit an appropriate dry run protection device (for example liquid detection or a power monitor).
To avoid potential hazards from fugitive emissions of vapour or gas to atmosphere the surrounding area must be well ventilated.
Page 6 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
1.6.1.5 Preventing sparks
To prevent a potential hazard from mechanical
contact, the coupling guard must be non-sparking. To avoid the potential hazard from random induced
current generating a spark, the baseplate must be properly grounded.
Avoid electrostatic charge: do not rub n on-metalli c
surfaces with a dry cloth; ensure cloth is damp. For ATEX application sthe coupling must be selected
to comply with 94/9/EC. Correct coupling alignment must be maintained.
Additional requirement for metallic pumps on non-metallic baseplates
When metallic components are fitted on a non­metallic baseplate they must be individually earthed.
1.6.1.6 Preventing leakage
The pump must only be used to handle liquids for which it has been approved to have the correct corrosion resistance.
Avoid entrapment of liquid in the pump a nd associat ed piping due to closing of suct ion an d discharg e valves, which could cause dangerous excessiv e pressures to occur if there is heat input t o the liqu id. This ca n occur if the pump is stationary or running.
Bursting of liquid containing parts due to freezing must be avoided by draining or protecting the pump and ancillary systems.
Where there is the potential hazard of a loss of a seal barrier fluid or external flush, the fluid must be monitored.
If leakage of liquid to atmosphere can result in a hazard, install a liquid detection device.
1.6.1.7 Maintenance to avoid the hazard
CORRECT MAINTENANCE IS REQUIRED TO AVOID POTENTIAL HAZARDS WHICH GIVE A RISK OF EXPLOSION
The responsibility for compliance with maintenance instructions is with the plant operator.
To avoid potential explosion hazards during maintenance, the tools, cleaning and painting materials used must not give rise to sparking or adversely affect the ambient conditions. Where there
is a risk from such tools or materials, maintenance must be conducted in a safe area.
It is recommended that a maintenance plan and schedule is adopted. (See section 6, Maintenance.)

1.7 Safety labels summary

1.7.1 Nameplate
For details of nameplate, see the Declaration of Conformity, or separate documentation included with
these User Instructions.
1.7.2 Safety labels
Oil lubricated units only:

1.8 Noise level

Attention must be given to the exposure of personnel to the noise, and local legislation will define when guidance to personnel on noise limitation is required, and when noise exposure reduction is mandatory. This is typically 80 to 85 dBA.
The usual approach is to control the exposure time to the noise or to enclose the machine to reduce emitted sound. You may have already specified a limiting noise level when the equipment was ordered, however if no noise requirements were defined, then attention is drawn to the following table to give an indication of equipment noise level so that you can take the appropriate action in your plant.
Page 7 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
Pump noise level is dependent on a number of operational factors, flow rate, pipework design and acoustic characteristics of the building, and so the values given are subject to a 3 dBA tolerance and cannot be guaranteed.
Similarly the motor noise a ssumed in t he “pump and motor” noise is that typically expected f rom sta ndard and high efficiency motors when on load dire ctly driving the pump. Note that a motor driven by an inverter may show an increased noise at some speeds.
If a pump unit only has been purchased for fitting with your own driver then the “pump only” noise levels in the table should be combined with the level for the driver obtained from the supplier. Consult Flowserv e or a noise specialist if assistance is required in combining the values.
It is recommended that where exposure approaches the prescribed limit, then site noise measurements should be made.
The values are in sound pressure level L
at 1 m
pA
(3.3 ft) from the machine, for “free field conditions over a reflecting plane”.
For estimating sound power level L
(re 1pW) then
WA
add 17 dBA to the sound pressure value.
1.8.1 Typical vertical motor noise data
Motor
Frame
Size.
NEMA
180
210
250
280
320
360
400
440 3600 80.0 90.0
RPM Sound
Pressure
(dBA ) (WP- I
enclosure)
3600 70.0 78.0 1800 60.0 68.0
1200 & slower 55.0 63.0
3600 70.0 78.2 1800 60.0 68.2
1200 & slower 55.0 63.2
3600 75.0 83.4 1800 70.0 78.4
1200 & slower 60.0 68.4
3600 75.0 83.8 1800 70.0 78.8
1200 & slower 60.0 68.8
3600 75.0 84.0 1800 65.0 74.0
1200 & slower 65.0 74.0
3600 75.0 84.2 1800 65.0 74.2
1200 & slower 65.0 74.2
3600 80.0 89.5 1800 70.0 79.5
1200 & slower 65.0 74.5
Sound Power (dBA )
(WP- I
enclosure
1800 70.0 80.0
1200 & slower 70.0 80.0
449
5000
5800
6800
8000
1800 85.0 97.8
1200 & slower 80.0 92.8
3600 90.0 102.8 1800 85.0 97.8
1200 & slower 80.0 92.8
3600 90.0 103.7 1800 90.0 103.7
1200 & slower 80.0 93.7
1800 90.0 103.9
1200 & slower 85.0 98.8
1800 90.0 104.7
1200 & slower 85.0 99.7
The noise levels shown in table 1.8.1 are extracted from typical motor manufacturer’s data/catalogue to provide the average expected motor noise values at no load for reference only and are not guaranteed. The values could vary depending upon the test and surrounding conditions. The combined noise level of the pump and the motor could exceed the values shown. It is to be noted that adding motors with similar noise levels increases the total noise level. Therefore, the dB correction to the values listed above is required to obtain the combined noise levels of motor and the pump. Actual on-site noise measurement by experts is recommended and safety measures are to be taken accordingly.

1.9 Specific machine performance

For performance parameters see section 1.5, Duty conditions. When the contract requirement specifies
these to be incorporated into User Instructions these are included here. Where performance data has been supplied separately to the purchaser these should be obtained and retained with these User Instructions if required.

2 TRANSPORT AND STORAGE

2.1 Consignment receipt and unpacking

Immediately after receipt of the equipment it must be checked against the delivery and shipping documents for its completeness and that there has been no damage in transportation. Any shortage and or damage must be reported immediately to Flowserve and received in writing within one month of receipt of the equipment. Later claims cannot be accepted.
Check any crates, boxes and wrappings for any accessories or spare parts which may be packed
Page 8 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
separately with the equipment or attached to side walls of the box or equipment.
Each product has a unique serial number. Check that this number corresponds with that advised and always quote this number in correspondence as well as when ordering spare parts or further accessories.

2.2 Handling

Boxes, crates, pallets or cartons may be unloaded using fork lift vehicles or slings dependent on their size and construction.

2.3 Lifting

A crane must be used for all pump sets or components in excess of 25 kg (55 lb). Fully trained personnel must carry out lifting, in accordance with local regulations.
To avoid distortion, the pump unit should be lifted by using lifting equipment certified to local standards.
The pumps are generally very heavy therefore, size/shape factors will have to be considered before attempting to lift them. It is strongly recommended to attempt lifting from a safe distance to prevent any injury or loss of life. Consulting with experts is recommended.
Pump heads may be shipped with the seal housing installed. For ease of assembly and to prevent damage, we recommend removing the housing before putting the head on the pump.
Flowserve will not supply eyebolts neither fixed nor separately with the pump. It is the responsibility of the installer to arrange appropriate hardware that can handle the weights and results in safe and successful installation.
Before lifting the driver alone, refer to the manufacturer’s instructions.
2.3.1 Lifting of fabricated discharge heads with
or without the pump
If the pump is supplied with a fabricated discharge head use 2 point or 3 point method of lifting as shown in the details provided in 2.3.1.1 & 2.3.1.2. This method is applicable to the lifting of discharge heads with or without the pump.
2.3.1.1 Two point lifting of fabricated discharge head types TF, UF & HFH (with or without pump attached)
Figure 2.1
"L"
FABRICATED WITH 2 POINT LIFTING
50 mm (2in.) HOLE
Fabricated heads with discharge size mm (in.)
100
Pin Dia.
1070
L
(42)
“L” is approximate length
(4) 25 (1)
150
(6) 32
(1.25)
1220
(48)
200
(8) 32
(1.25)
1220
(48)
250 (10)
32
(1.25)
1370
(54)
300 (12)
38 (1.5) 1370
(54)
2.3.1.2 Three point lifting of fabricated discharge head of type HFL (with or without pump attached)
Figure 2.2
HFL STYLE FABRICATED WITH 3 POINT LIFTING
Page 9 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
2.3.2 Lifting of bowl assembly only
Clamp the bowl assembly and center the lifting hook for lifting and lowering the assembly into the sump/suction barrel.
a) Lower the bowl assembly until the clamp
extensions rest on the foundation (use appropriate supports).
b) Build the very first section of the column piping,
and lower the entire assembly to assemble the next column section.
c) Continue to build until it is ready for discharge
head assembly. d) Install the discharge head. e) Assemble the motor.
Example: Lifting of bowl assembly
Figure 2.3
2.3.3 Lifting of suction barrel
Suction barrel (also referred as ‘Can’) is always supplied separately and has to be installed into the sump first. Install eyebolts on the flange of the suction barrel and attach slings and straps to bring the suction barrel to a vertical position. Move the barrel for installation. Provide hand support to prevent the suction barrel from swaying during movement.
Example: Lifting of suction barrel
Figure 2.4
SUCTION BARREL (CAN)
Page 10 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
2.3.4 Lifting of fully assembled pumps
If the pump is fully assembled, it has to be adequately strapped and supported at least two places before it can be lifted from the shipping crate and moved to the installation site. See details shown. Same rules are applicable when the pump is pulled out from the sump and moved to another location.
Figure 2.5
Examples shown here are for illustration only. See section 2.3 1 for specific lifting instructions based on design variations. The pumps vary in weight, length and physical appearances from the types shown here. Therefore, before lifting is attempted, exercise caution to prevent any injuries or loss of life.
Figure 2.6
Page 11 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13

2.4 Storage

Store the pump in a clean , dry location away from vibration. Leave piping connection covers in place to keep dirt and other foreign material out of pump casing. Turn the pump at frequent intervals to prevent brinelling of the bearings and the seal faces, if fitted, from sticking.
2.4.1 Inspection before storage
a) Inspect the preservative coating/painted surfaces
on the various parts. Touch up the areas, If necessary.
b) Inspect all covers over pump openings and piping
connections. If found damaged, remove the covers and inspect interiors of the opening for any deposits of foreign materials or water.
c) If necessary, clean and preserve the interior parts
as noted above to restore the parts to the "as shipped" condition. Replace covers and fasten securely.
2.4.2 Short term storage (up to 6 months)
Follow the steps given in sect ion 2.4. 1. Select a storage space so that the unit will not be subjected to excess moisture, extreme weather conditions, corrosive fumes, or other harmful conditions.
Driver storage instructions: Check driver manufacturer’s User Instructions
2.4.3 Long term or extended storage
If a situation arises for a long-term storage, ( more than 6 months) please contact Flowserve for special storage instructions and warranty related information.

2.5 Recycling and end of product life

At the end of the service life of the product or its parts, the relevant materials and parts should be recycled or disposed of using an environmentally acceptable method and local regulations. If the product contains substances which are harmful to the environment, these should be removed and disposed of in accordance with current regulations. This also includes the liquids and or gases in the "seal system" or other utilities.

3 DESCRIPTION

Should questions arise concerning the pump, Flowserve pump division will require the complete serial number to be of assistance. The serial number is stamped on a metal nameplate affixed to the discharge head assembly. The driver will have a separate nameplate attached to it. If you are requesting information on the driver, please provide both the driver serial number and the pump serial number for Flowserve representative.

3.1 Configuration

APKD’s, are engineered pumps as:(a) Wet pit type and (b) suction barrel (can) type pumps. The pumps vary in size, impeller types and length, and type of discharge head used
3.1.1 Sump and deep well VTP Figure 3.1
Make sure that hazardous substances or toxic fluids are disposed of safely and that the correct personal protective equipment is used. The safety specifications must be in accordance with the current regulations at all times.
Page 12 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
3.1.2 Suction barrel (Can) VTP Figure 3.2

3.2 Nomenclature

The pump size/ serial number will be engraved on the nameplate typically. The nameplate is attached to the discharge head assembly. Identify the actual pump size and serial number from the pump nameplate. The driver will have a separate nameplate attached to it.
3.2.1 Discharge head nomenclature
Consists of alphanumeric code as follows. Examples: 10HF20, 6TF16,…….
10 LF 30
Nominal driver base diameter in inches
Discharge head type (see details below)
Nominal discharge diameter in inches
HF = Fabricated head for above the ground discharge TF & LF = Fabricated heads with base flange HFL = Fabricated head for above ground discharge - Low H.P HFH = Fabricated head for above the ground discharge -High H.P.
Please see section 3.2.1.1 for discharge head types and identification.
3.1.3 Most common VTP models
The VTP configurations shown in sec 3.1.1 and 3.1.2 are typical.
Some units will not require a column assembly. In such cases, the bowl assembly is connected directly to the discharge head. Vertical turbine pumps can have single or multiple stages.
Page 13 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
3.2.1.1 Types of discharge heads
Typical discharge head types. Details (a) thru (e). a) HF type fabricated discharge head
(Typically with square base plate)
Figure 3.3
b) TF type fabricated discharge head
Figure 3.4
d) HFL type fabricated discharge head
Figure 3.6
e) HFH type fabricated discharge head
Figure 3.7
c) LF type fabricated discharge head
(Typically with a circular base plate- ANSI type. Also available with suction barrel mounting)
Figure 3.5
The discharge heads shown in section
3.2.1.1 (a) thru (e) are for illustration only. The shaft and coupling arrangements vary. For the actual configuration of the pump that has been purchased, please refer to the drawings supplied with the pump or order specific sectionals from Flowserve.
Page 14 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13

3.3 Design of major parts

3.3.1 Drivers
Solid shaft drivers: where the rotor shaft is solid and projects below the driver-mounting base. This type driver requires an adjustable coupling for connecting to the pump.
3.3.2 Discharge Head Assembly
(See also section 3.2.2.1) The discharge head supports the driver and bowl assembly as well as supplying a discharge connection in most cases.
A shaft sealing arrangement is located in the discharge head to seal the shaft at its exit from the liquid chamber.
The shaft seal will usually be either a mechanical seal assembly or stuffing box with an open lineshaft or a tube-packing box with an enclosed lineshaft.
3.3.3 Column assembly
The column assembly consists of column pipe, which connects the bowl assembly to the discharge head and carries the pumped fluid to the discharge head. Houses and supports the shaft and may contain bearings. T ypical column assembly shown below:
a) flanged column assembly
Figure 3.8
3.3.4 Bowl assemblies
The bowl assembly consists of impellers rigidly mounted on the pump shaft coupled to an electric motor. Impellers are cast wheels with multiple diffuser vanes and are generally coated to meet the hydraulic requirements. See section 8.0 for cross sectional and part details.
3.3.5 Suction strainers
Ina new installation, great care should be taken to prevent dirt, scale and welding beads from entering the pump, as it is particularly important to protect the numerous close running fits form abrasive matter present in new piping.
The suction system should be thoroughly flushed before installation the suction and making up suction piping to the pump
The suction strainer should be installed 4 pipe diameters away from suction.
Cone Type Strainer
Figure 3.9
The column supports shaft assemblies, that are of an open lineshaft construction utilizing the fluid being pumped to lubricate the lineshaft bearings. The shafts are key coupled with clamp ring design.
See sectional drawings supplied with the pump for exact column assembly details as per the order. The size and configuration vary depending upon the specific order requirements and application criteria.
3.3.6 Impellers
The double suction first stage impeller (3A) is keyed and held in position on pump end shaft (10A) by shaft nut. The shaft nut is secured to the shaft with set screws. The remaining single suction intermediate impellers are also keyed. Each impeller is held in position on the upper shaft by use of a split lock collar secured with cap screws. All impellers are of the enclosed type, one piece constructions, and are dynamically balanced.
3.3.7 Stuffing box
Some APKD’s are fitted with stuffing boxes. In such cases, stuffing boxes are normally adequate for working pressures up to 20.7 bar (300 psi). Refer to stuffing box User Instructions for specifications.
Page 15 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13
3.3.7.1 High pressure stuffing box
This type of packing box is fitted on to an open lineshaft for pressures up to 20 bar (300 psi) uses six rings of packing with one seal cage and allows grease lubrication.
Figure 3.10
3.3.8 Mechanical shaft seal
APKD’s can also be fitted with a mechanical seal. The requirement to fit the mechanical seal to be provided at the time of contract.
3.3.9 Accessories
Accessories may be fitted when specified by the customer.

3.4 Performance and operation limits

This product has been selected to meet the specifications of the purchase order. See section 1.5.
The following data is included as additional information to help with the installation. It is typical and factors such as temperature, materials and seal type may influence this data. If required, a definitive statement for your particular application can be obtained from Flowserve.Operating limits
Pumped liquid temperature limits*
Maximum ambient temperature*
Maximum pump speed refer to the nameplate
5 ºC (40 ºF) to +80 ºC (176 ºF)
Up to +40 ºC (104 ºF)
*Subject to written agreement from Flowserve. Special designs and materials may be available for pumps operating above and below these specified limits. Contact Flowserve for upgrade options available for your specific application.
Page 16 of 55 flowserve.com
APKD DOUBLE-CASE, DOUBLE-SUCTION USER INSTRUCTIONS 26999903 07-13

4 INSTALLATION

Equipment operated in hazardous locations must comply with the relevant explosion protection regulations. See section 1.6.4, Products used in
potentially explosive atmospheres.
Inspection prior to installation
Six months prior to the scheduled installation date, a Flowserve Pump Division representative is to be employed to conduct an inspection of the equipment and the facility. If any deterioration of equipment is noticed, the Flowserve Pump Division representative may require a partial or complete dismantling of the equipment including restoration and replacement of some components.

4.1 Location

The pump should be located to allow room for acce ss, ventilation, maintenance and insp ection with ampl e headroom for lifting and should be as close as practicable to the supply of liquid to be pumped.
Refer to the general arrangement drawing for the pump set.
4.1.1 General installation check-list
The following checks should be made before starting actual installation.
a) Make sure that motor nameplate ratings and the
power supply system match correctly.
b) Check the sump depth and pump length match-
up. c) Check the liquid level in the sump. d) Check the installation equipment to be sure that it
will safely handle the pump weight and size. e) Check all pump connections (bolts, nuts etc) for
any shipping and handling related problems.
Always support shafting in at least three places when lifting or installing. No installation should be attempted without adequate equipment necessary for a successful installation.
shaft connection. Excess lubricant should be avoided.
4.1.2 Installation of pumps that are shipped unassembled
4.1.2.1 Lifting
See lifting methods in section 2.3.
4.1.2.2 Equipment and tools required for
installation of unassembled pumps
The following list covers the principal tools/items required for installation.
a) Mobile crane capable of hoisting and lowering the
pump and/or motor. b) Two (2) steel clamps of suitable size. c) Two (2) sets of chain tongs & cable sling for
attaching to the pump and motor lifting eyes. d) Pipe clamp for lifting bowl assembly and the
column pipe. Approximately 4.57 m (15 ft) of 19
mm (3/4 in.) diameter rope may be required. e) General purpose hand tools, pipe wrenches, end
wrenches, socket set, screwdrivers, Allen
wrenches, wire brush, scraper and fine emery
cloth. f) Thread sealing compound designed for stainless
steel and light machinery oil.
Parts and accessories may be placed inside shipping containers or attached to skids in individual packages. Inspect all containers, crates and skids for attached parts before discarding.
4.1.2.3 Uncrating and cleaning of unassembled
pump
a) Clean the parts of any dirt, packing material and
other foreign matter.
b) Flush the pump inside and outside with clean
water. Clean all machined surfaces.
c) Remove any rust spots found on the machined
surfaces with fine emery cloth.
d) Clean all threaded connections and any accessory
equipment.
Be sure to check the motor shaft size against the coupling bore size
Apply thread lubricant sparingly to
male shaft threads only at the time of making up
Page 17 of 55 flowserve.com
should be left in the crate to avoid damage or loss of straightness.
4.1.2.4 Installing the bowl and column assembly
a) Sump and piping should be thoroughly cleaned of
all loose debris before starting installation.
b) Check all bolts for tightness.
Lineshaft when shipped separately
Loading...
+ 38 hidden pages