Flowserve 4-75 User Manual

4-75 Position

Indicator
FCD WCAIM2070-00 (Part 06525)
1. Description
The 4-75 position indicator is designed to be used with and mounted in the Series 75, 120 VAC actuator with many of its standard options including the I-75 Interface Kit and the DFC17 controller. Its output is suited for 4-20 mA DC meter with 0-100% scale (such as General Electric Type GE185), which is not part of the package. If properly calibrated, it indicates actuator shaft position from closed (0°, 0%) to open (90°, 100%). It is combined with standard Potentiometer Kit, which supplies information on shaft position. If feedback poten­tiometer is required for other functions such as remote resistance indication, or with a DFC17 controller, a dual Potentiometer Kit must be used. Each potentiometer can serve only one function. For installation procedures and wiring of potentiometer, see Potenti­ometer Kit Instructions (WCAIM2067) or 75 Actuator instructions (WCAIM2013) or DFC17 instructions (WCAIM2026). These instruc­tions can be obtained from your local distributor/supplier or online at www.flowserve.com.
Parts included in kit:
Installation, Operation and Maintenance
2. Installation
(See Figure 1.)
NOTE: This instruction sheet shows standard installation and wiring of a 4-75 Position Indicator only. For 25/30 75 actuator, mount 4-75 assembly on top of limit switch(es) using same procedure as shown below.
Remove the two mounting screws from right limit switch(es), as viewed from terminal strip. Place two spacers (4) (use two spacers (3) for M1 or M2 option) between limit switch and mounting plate (2), and fasten mounting plate in place with two longer flat head screws (5). Locate insulator (8) on top of mounting plate. Using three spacers (3) to separate circuit board (1) from mounting plate (2) and insulator (8), mount circuit board using #4-40 x 3⁄8 round head screws (6) and nuts (7). Check entire assembly and firmly secure all screws.
Figure 1—10-23 75 Installation
Item Qty. Description
1 1 Circuit Board
2 1 Mounting Plate
3 5 Spacers (.06")
4 2 Spacers (.25")
5 2 #4-40 x 1¼" F.H. Screws
6 3
7 3 #4-40 Nuts
8 1 Insulator
9 3 Cable Ties (Not Shown)
10 1 Potentiometer Kit (Not Shown)
11 1 Wiring Label (Figure 2)
12 1 Wire—White (Not Shown)
13 1 Closed End Splice (Not Shown)
#4-40 x
3
8" R.H. Screws
Flow Control
1211987 10
EXTERNAL INTERNAL
BOAR
D
6
POSITIVE
NEGA
TIV
E
54321
NEUT.
HOT
4-20 mA—OUTPUT
FROM EXT. SWITCH
FROM EXT. SWITCH
CLOSE—CW WIRE
4-20 mA—OUTPUT
VAC POWER
TO BOARD
OPEN—CCW WIRE
RED—MOTOR
BLACK—MOTO
R
BLACK—CIRCUI
T
BROWN—CIRCUIT BOAR
D
HO
T
WHITE—CIRCUIT BOARD
COMMON
WHITE MOT.
COMMON(S
)
CCW LIMIT SW
CW LIMIT
S
W
RED—CIRCUI
T
BOA
RD
Worcester Actuation Systems
3. Wiring
(See Figure 2.)
NOTES: All wiring to terminal strip should be inserted only to mid­point of terminal strip.
When there are multiple wires going to terminal 1, use the short white wire included in kit. Connect it to terminal 1 and then splice it to the other white wires (common) using the closed end splice provided.
Internal Wiring
There is internal wiring between the actuator terminal strip, feedback potentiometer, and position indicator PC board. The white wire (common) from PC board is wired to terminal 1 on internal side; the brown wire (hot) from PC board is wired to terminal 2 on internal side. Connect feedback potentiometer wires to the 4-75 position indicator board terminal block (green to terminal 3, white/black to terminal 2, and purple to terminal 1).
Remove yellow wire from terminal 5 and brown wire from terminal 6, disconnect them from N.O. contacts of switches 1 and 2 and discard them. Output signal from PC board red wire (+) is wired to terminal 5 and black wire (-) is wired to terminal 6 on internal strip of terminal strip.
External Wiring
External wiring is between actuator terminal strip and outside power supply and various controls. Common wire of the power supply is wired to terminal 1 and hot wire of the power supply to terminal 2. The actuator motor windings are electrically powered through its own individual external single pole, double throw switch (supplied by customer); counterclockwise and/or “to open” wire is wired to terminal 3; clockwise and/or “to close” wire is wired to terminal 4, as shown in wiring diagram for actuator. An outside position indicator meter is wired with positive connection to terminal 5 and negative connection to terminal 6.
NOTE: External switch not needed when position indicator is used with DFC17 controller, as controller board will power motor windings.
Securely tighten all terminal screws. Secure all wires neatly with the cable ties (9). Keep wiring away from all rotating parts and ensure wiring is not pinched when actuator cover is installed.
Grounding wires should be connected to green-colored grounding screw (if present) on actuator base or to any base plate mounting screw in actuator.
Figure 2—Wiring of 4-75 120 VAC Position Indicator
NOTE: Attach wiring diagram label, included with kit, on inside of cover, or modify existing label for the 4-75 option by marking termi­nal 5 “+”, terminal 6 “-”, and adding “4-20 mA output.”
For actuator using a 4-75 Position Indicator with a DFC17 Control­ler, the red and black wires from the indicator board will have to be spliced directly to the external positive and negative output (Meter) wires, respectively.
NOTE: Prior to wiring, follow Position Indicator board output cali­bration instructions in Section 4.
2 4-75 Position Indicator FCD WCAIM2070-00
Loading...
+ 2 hidden pages