Fisher PCG-06, PCG-08, PCG-09, PCG-12, PCG-16 Installation, Operation And Service Manual

Page 1
INSTALLATION
OPERATION AND SERVICE MANUAL
PCG – PS SERIES
4 PIPE HYDRONIC CASSETTE
AIR CONDITIONERS
2010 V.1.0
Page 2
INVESTING IN QUALITY, RELIABILITY & PERFORMANCE.
ISO 9001 QUALITY
Every product is manufactured to meet the stringent requirements of the internationally recognized ISO 9001 standard for quality assurance in design,
development and production.
CE SAFETY STANDARDS
All products conform to the Certificate Europe directives (Machinery Safety, Electromagnetic Compatibility
and Low Voltage), as required throughout the European Community, to guarantee correct standards of safety.
WEEE MARK
All products conform to the “weee” directive to guarantee correct standards of environmental solutions.
World Leading Design and Technology
Equipped with the latest CAD/CAM computer aided design and manufacturing technology, our factories in China and Thailand produce over 2,000,000 air conditioning units each year, all conforming to the highest international standards of quality and safety.
The Highest Standards of Manufacturing
In order to guarantee the very highest standards and performance, we manage every stage in the manufacturing of our products. Throughout the production process we maintain strict control, originating with our extensive resources in research and development through to the design and manufacture of almost every individual component, from molded plastics to the assembly of units and controllers.
Quality Controlled from Start to Finish
Our highly trained staff and strict quality control methods enable us to produce products with an exceptional reputation for reliability and efficiency, maintained over many years. As well as full CE certification and ISO 9001, several products have UL/CSA (NRTL) safety approval plus ARI Certification in the USA, ROHS compliance for Europe, giving you the confidence of knowing our company is the right choice when selecting air conditioning equipment.
ALWAYS MAKE SURE THAT THIS MANUAL REMAINS WITH THE PCG-VS WATER CASSETTE. READ THIS MANUAL BEFORE PERFORMING ANY OPERATION ON THE PCG-VS WATER CASSETTE.
Page 3
HYDRONIC CASSETTE 3
INDEX
PCG-PS SERIES 4 PIPE HYDRONIC CASSETTES
PAGE A. CASSETTE MODEL ASSIGNMENTS 4 B. SPECIFICATIONS 5-6
a) COIL DATA b) COOLING CAPACITY TABLES c) ETHYLENE GLYCOL SOLUTIONS d) HEATING CAPACITY TABLE
7
7-9
10
11-13
C. INSTALLATION MANUAL
SAFETY CONSIDERATIONS OPERATING LIMITS BEFORE INSTALLATION SELECT LOCATION INSTALLATION LOCATION INSTALLATION METHOD OPENING DIMENSIONS AND POSITIONS FOR SUSPENSION BOLTS DRAIN PIPE WORK WATER CONNECTIONS VALVE CONFIGURATION EXTERNAL DRAIN PAN FRESH AIR RENEWAL CONNECTION BRANCH DUCT CONNECTION INTERCONNECTING WIRING CONTROL BOX CONFIGURATION MOUNTING FRONT PANEL ASSEMBLY FILTER REMOVAL MAINTENANCE HOW TO ACCESS AIR VENT AND WATER PURGE HOW TO CONNECT NON-DEFAULT FAN SPEED HOW TO FIX THE MOTOR AND FAN BLOWER HOW TO FIX CONDENSATE PUMP AND INTERNAL VALVE HOW TO FIX CONTROL BOX HOW TO INSTALL ELECTRIC HEATER
14-36
14 14 15 15 16 17
18-20
21 21
21-22
23 23-24 24-25
26
27
28
28
29
30 30-31
32
33
34 35-36
D. EXPLODED DRAWINGS WITH PARTS DESCRIPTIONS 37-38 E. DIMENSIONAL DRAWINGS 39-41 F. VALVE INFORMATION 42-43 G. REMOTE CONTROL HANDSET 44-45 H. I. J. K. L. M. N.
WIRED WALL PAD CONTROL CONTROLS SPECIFICATION WITH MASTER-SLAVE CONTROL SENSOR RESISTANCE R-T CONVERSION TABLE CONTROL AND POWER SUPPLY WIRING DIAGRAM MASTER-SLAVE CONTROL WIRING DIAGRAM TROUBLE SHOOTING APPENDIX I – MASTER SLAVE COMMUNICATION SETTING
46-49 50-57 58-59
60
61
62 63-65
Page 4
HYDRONIC CASSETTE 4
CASSETTE MODEL ASSIGNMENTS
P C G - 0 6 - P S
S 230V/1PH/50HZ
P CHILLED/HOT WATER, 4-PIPE
06 NOMINAL 3.24 KW 08 NOMINAL 3.60 KW 09 NOMINAL 4.15 KW 12 NOMINAL 5.10 KW 16 NOMINAL 5.90 KW
PCG HYDRONIC CASSETTE
G SERIES
Page 5
HYDRONIC CASSETTE 5
PCG – PS (4-PIPE) SERIES 3-SPEED SPECIFICATIONS
Model PCG-06 PCG-08 PCG-09 PCG-12 PCG-16
Number Of Fan Blowers Single Single Twin Twin Twin
H 750 846 1098 1296 1650
M 648 540 924 1176 1300
Total flow
L
m3/hr
588 410 858 1098 1100
H 3.24 3.60 4.15 5.10 5.90
M 2.86 3.02 3.23 4.70 4.80
Cooling Capacity*
L
kW
2.60 2.42 3.06 3.95 3.65
H 2.75 2.94 3.82 4.40 4.93
M 2.48 2.60 3.16 4.04 4.31
Sensible Cooling Capacity
L
kW
2.33 2.22 2.98 3.54 3.56
H 4.14 4.43 6.67 7.20 7.90
M 3.84 4.00 5.85 6.60 6.95
Heating Capacity **
L
kW
3.64 3.41 5.57 5.95 5.96
Noise Level @ 1 M (H/M/L) dB(A) 43/41/35 46/43/35 40/38/32 43/42/36 48/44/38
Power Supply (V/Ph/Hz) 230/1/50
Fan Motor Power W 58 60 62 116 124
Fan Motor Running Current A 0.24 0.32 0.34 0.48 0.64
Fan Motor Starting Current A 0.76 0.89 0.88 1.52 1.77
Operation Control & Thermostat Remote Control Handset & Wired Wall Pad
Cooling Water Flow Rate L/h 580 636 733 901 1043
Heating Water Flow Rate L/h 354 380 571 617 677
Cooling Water Pressure Drop kPa 12.0 14.7 27.8 22.4 29.0
Heating Water Pressure Drop kPa 3.0 3.5 8.7 10.1 12.0
Cooling Water Content L 1.07 1.07 1.36 1.91 1.90
Heating Water Content L 0.49 0.49 0.86 0.86 0.86
Cond. Drain Connection I.D. mm(in) 19.05(3/4)
L mm 585 585 1140 1140 1140
W mm 585 585 580 580 580
Dimensions
H mm 290 290 250 290 290
Panel Dimensions (L x W x H) mm 680×680×28 680x1240x28
Gross Weight Kg 33 33 52 59 59
Connection Method
Socket (Threaded Female)
Water In mm(in) 19.05(3/4)
Connection Out mm(in) 19.05(3/4)
* Cooling : 27C db/19C wb entering air temperature,7C entering water and 12C leaving water temperature with water flow rates as
above.
**Heating : 20C db entering air temperature ,70C entering water temperature and 60C leaving water temperature.
Page 6
HYDRONIC CASSETTE 6
PCG – PS (4-PIPE) SERIES 5-SPEED SPECIFICATIONS
Model PCG-06 PCG-08 PCG-09 PCG-12 PCG-16
Number Of Fan Blowers Single Single Twin Twin Twin
5 710 846 1080 1350 1650
4 648 708 738 1236 1350
3 600 648 600 1140 1236
2 450 600 500 852 1140
Total flow
1
M3/hr
350 450 400 650 852
5 3.02 3.60 4.24 5.00 5.98
4 2.86 3.02 2.78 4.75 5.00
3 2.60 2.86 2.32 3.98 4.75
2 1.98 2.60 2.00 3.22 3.98
Cooling Capacity*
1
kW
1.72 1.98 1.62 2.65 3.22
5 2.60 2.94 3.73 4.27 4.85
4 2.48 2.60 2.72 4.04 4.27
3 2.33 2.48 2.27 3.58 4.04
2 1.82 2.33 1.95 2.82 3.58
Sensible Cooling Capacity
1
kW
1.56 1.82 1.58 2.32 2.82
5 4.00 4.43 6.67 6.98 7.91
4 3.84 4.00 5.27 6.60 6.98
3 3.63 3.84 4.63 5.92 6.60
2 2.79 3.63 4.11 5.10 5.92
Heating Capacity **
1
kW
2.05 2.79 3.58 4.20 5.10
Noise Level @ 1 M (H/M/L) dB(A) 44/40/38/32/30 46/44/40/38/32 39/35/33/31/28 45/41/39/33/31 47/45/41/39/33
Power Supply (V/Ph/Hz) 230/1/50
Fan Motor Power W 58 66 100 116 132
Fan Motor Running Current A 0.26 0.29 0.44 0.52 0.58
Fan Motor Starting Current A 0.77 0.88 1.33 1.54 1.77
Operation Control & Thermostat Remote Control Handset & Wired Wall Pad
Cooling Water Flow Rate L/h 533 636 749 883 1057
Heating Water Flow Rate L/h 342 380 571 598 678
Cooling Water Pressure Drop kPa 10.7 14.7 28.8 20.9 29.0
Heating Water Pressure Drop kPa 3.0 3.5 13.0 15.0 17.5
Cooling Water Content L 1.07 1.07 1.36 1.91 1.91
Heating Water Content L 0.49 0.49 0.86 0.86 0.86
Cond. Drain Connection I.D. mm(in) 19.05(3/4)
L mm 585 585 1140 1140 1140
W mm 585 585 580 580 580
Dimensions
H mm 290 290 250 290 290
Panel Dimensions (L x W x H) mm 680×680×28 680x1240x28
Gross Weight Kg 33 33 52 59 59
Connection Method
Socket (Threaded Female)
Water In mm(in) 19.05(3/4)
Connection Out mm(in) 19.05(3/4)
* Cooling : 27C db/19C wb entering air temperature,7C entering water and 12C leaving water temperature with water flow rates as
above.
**Heating : 20C db entering air temperature ,70C entering water temperature and 60C leaving water temperature.
Page 7
HYDRONIC CASSETTE 7
COIL DATA - COOLING
Fin Length (mm.)
Model
Fin Height
(mm)
Inner Outer
Fins per
inch
No. of
rows
No. of
circuits
Tube
Diameter
PCG-06-08-PS 250 1176 1277 13 2 3 3/8”
PCG-09-PS 200 2148 2286 13 2 3 3/8”
PCG-12-16-PS 250 2148 2286 13 2 5 3/8”
COIL DATA - HEATING
Fin Length (mm.)
Model
Fin Height
(mm)
Inner Outer
Fins per
inch
No. of
rows
No. of
circuits
Tube
Diameter
PCG-06-08-PS 250 1176 1277 13 1 3 3/8”
PCG-09-PS 200 2148 2286 13 1 3 3/8”
PCG-12-16-PS 250 2148 2286 13 1 3 3/8”
COOLING CAPACITY TABLES
PCG-06-PS TAI DB24℃-WB17.4℃ TAI DB27℃-WB19℃ TAI DB27℃-WB19.5℃ TAI DB28℃-WB21
Twi qa Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw
°C m3/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h
750 3.3 2.52 13.8 12.5 12.1 583 4.45 3.08 14.5 12.6 20.7 786 4.85 3 14.6 12.6 24 857 5.9 3.14 15.2 12.9 34.3 1043
648 2.87 2.28 13.2 12.4 9.45 507 3.86 2.79 13.8 12.5 16.1 682 4.2 2.74 14 12.5 18.6 742 5.1 2.85 14.4 12.8 26.4 901
5
588 2.66 2.14 12.9 12.3 8.2 470 3.56 2.63 13.3 12.4 14 630 3.88 2.58 13.6 12.4 16.1 685 4.7 2.68 14 12.7 22.7 830
750 2.75 2.33 14.55 13.35 8.93 486 3.865 2.915 15.15 13.5 16.35 683 4.225 2.83 15.35 13.55 19 746.5 5.28 2.965 15.9 13.85 28.35 933
648 2.405 2.09 14.1 13.25 6.985 425 3.36 2.635 14.5 13.4 12.74 593.5 3.7 2.585 14.7 13.4 15 653.5 4.57 2.69 15.15 13.75 21.85 807.5
6
588 2.24 1.96 13.8 13.1 6.15 395. 3.08 2.48 14.05 13.35 15.95 545 3.395 2.435 14.3 13.35 12.85 599.5 4.215 2.53 14.75 13.65 18.8 744.5
750 2.2 2.14 15.3 14.2 5.76 389 3.24 2.75 15.8 14.4 12 580 3.6 2.66 16.1 14.5 14 636 4.66 2.79 16.6 14.8 22.4 823
648 1.94 1.9 15 14.1 4.52 343 2.86 2.48 15.2 14.3 9.37 505 3.2 2.43 15.4 14.3 11.4 565 4.04 2.53 15.9 14.7 17.3 714
7
588 1.82 1.79 14.7 14 4.1 321 2.6 2.33 14.8 14.3 7.9 460 2.91 2.29 15 14.3 9.6 514 3.73 2.38 15.5 14.6 14.9 659
750 1.86 1.81 16.6 14.7 4.18 328. 2.8 2.51 16.7 15.1 9.1 495 3.09 2.5 16.7 15.2 10.8 546 4.13 2.62 17.2 15.5 18.2 729.
648 1.62 1.55 16.4 14.6 3.21 286. 2.45 2.24 16.3 15 7.18 432. 2.73 2.28 16.1 15.1 8.75 482. 3.59 2.38 16.6 15.4 14.2 635
8
588 1.5 1.47 16.3 14.6 2.8 264 2.25 2.09 16 14.9 6.1 398 2.51 2.14 15.7 15.0 7.5 443. 3.32 2.23 16.2 15.3 12.2 587.
750 1.52 1.48 17.9 15.2 2.6 268 2.32 2.27 17.7 15.8 6.2 410 2.58 2.34 17.4 16 7.7 456 3.6 2.45 17.9 16.3 14.1 636
648 1.3 1.27 17.9 15.2 1.9 230 2.04 2 17.4 15.7 5 360 2.26 2.13 16.8 15.9 6.1 400 3.15 2.23 17.3 16.2 11.1 556
9
588 1.18 1.15 17.9 15.2 1.5 208 1.91 1.86 17.2 15.6 4.2 337 2.11 1.99 16.5 15.8 5 .4 373 2.92 2.09 17 16.1 9.6 516
TAI: Air in temperature Twi: Fluid in temperature Pf: Total cooling capacity Qw: Fluid flow rate in heat exchanger Pfs: Sensible cooling capacity Dpw: Pressure drop standard coil Tad: Discharge air dry bulb temperature Qa: Air flow Taw: Discharge air wet bulb temperature
Note: Design and specification are subject to change without prior notice for product improvement.
Page 8
HYDRONIC CASSETTE 8
PCG-08-PS TAI DB24℃-WB17.4℃ TAI DB27℃-WB19℃ TAI DB27℃-WB19.5℃ TAI DB28℃-WB21
Twi qa Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw
°C m3/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h
846 3.7 2.69 14.3 12.5 15.4 654 4.92 3.29 15.1 12.7 25.6 870 5.45 3.28 15.3 12.7 31.1 963 6.62 3.35 15.8 12.9 43.8 1170
700 3.1 2.4 13.5 12.4 11.3 548 4.1 2.93 14.1 12.6 18.5 724 4.45 2.89 14.2 12.6 21.5 786 5.5 3 14.7 12.8 31.5 972
5
550 2.48 2.05 12.6 12.3 7.5 438 3.27 2.5 13 12.5 12.3 578 3.56 2.48 13.1 12.5 14.4 630 4.78 2.66 14.2 12.6 24.5 845
846 3.05 2.52 14.9 13.4 11.2 538 4.26 3.12 15.7 13.6 20.15 753 4.72 3.10 15.85 13.65 24.4 833 5.92 3.18 16.4 13.85 36.25 1046
700 2.57 2.19 14.4 13.3 8.15 453 3.56 2.77 14.8 13.5 14.6 628.5 3.89 2.74 14.9 13.55 17.15 687 4.93 2.84 15.4 13.75 26.1 871
6
550 2.06 1.83 13.8 13.2 5.4 364 2.85 2.36 13.75 13.4 9.75 502.5 3.14 2.34 13.85 13.4 11.65 554.5 4.15 2.485 14.6 13.55 19.35 733.5
846 2.39 2.34 15.5 14.3 7 422 3.6 2.94 16.3 14.5 14.7 636 3.98 2.91 16.4 14.6 17.7 703 5.22 3.01 17 14.8 28.7 922
700 2.03 1.98 15.3 14.2 5 358 3.02 2.60 15.5 14.4 10.7 533 3.33 2.58 15.6 14.5 12.8 588 4.36 2.68 16.1 14.7 20.7 770
7
550 1.64 1.6 15 14.1 3.3 290 2.42 2.22 14.5 14.3 7.2 427 2.71 2.2 14.6 14.3 8.9 479 3.52 2.31 15 14.5 14.2 622
846 2.015 1.965 16.85 14.8 5.05 356 3.06 2.7 17.15 15.2 11.05 540.5 3.315 2.755 16.95 15.45 13.15 585.5 4.55 2.825 17.65 15.65 22.75 804
700 1.685 1.64 16.75 14.75 3.75 297 2.575 2.34 16.6 15.1 8 454.5 2.785 2.38 16.45 15.35 9.45 491.5 3.8 2.51 16.8 15.55 16.4 671
8
550 1.35 1.315 16.6 14.7 2.3 238.5 2.075 1.96 15.95 15 5.35 366.5 2.3 2.02 15.95 15.25 6.6 406.5 3.065 2.16 15.8 15.4 11.22 541.5
846 1.64 1.59 18.2 15.3 3.1 290 2.52 2.46 18 15.9 7.4 445 2.65 2.6 17.5 16.3 8.6 468 3.88 2.64 18.3 16.5 16.8 686
700 1.34 1.3 18.2 15.3 2.5 236 2.13 2.08 17.7 15.8 5.3 376 2.24 2.18 17.3 16.2 6.1 395 3.24 2.34 17.5 16.4 12.1 572
9
550 1.06 1.03 18.2 15.3 1.3 187 1.73 1.7 17.4 15.7 3.5 306 1.89 1.84 17.3 16.2 4.3 334 2.61 2.01 16.6 16.3 8.23 461
TAI: Air in temperature Twi: Fluid in temperature Pf: Total cooling capacity Qw: Fluid flow rate in heat exchanger Pfs: Sensible cooling capacity Dpw: Pressure drop standard coil Tad: Discharge air dry bulb temperature Qa: Air flow Taw: Discharge air wet bulb temperature
Note: Design and specification are subject to change without prior notice for product improvement.
PCG-09-PS TAI DB24℃-WB17.4℃ TAI DB27℃-WB19℃ TAI DB27℃-WB19.5℃ TAI DB28℃-WB21
Twi qa Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw
°C m3/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h
1098 4.5 3.21 15.4 13.5 32 795 5.9 4.08 16.1 13.5 52.3 1043 6.3 4 16.1 13.6 58.9 1113 8.03 4.16 16.6 13.7 91.3 1419
924 3.51 2.8 14.2 13.4 20.7 620 4.56 3.51 14.7 13.4 32.7 806 5.03 3.48 14.8 13.4 39.3 889 6.34 3.65 15.2 13.6 59.7 1120
5
858 3.3 2.63 14 13.3 18.4 583 4.26 3.33 14.3 13.3 29.2 753 4.63 3.31 14.4 13.4 34 818 5.89 3.46 14.8 13.5 52.4 1041
1098 3.68 3.005 16.1 14.15 22.75 650 5.07 3.905 16.75 14.4 40.55 896 5.44 3.79 16.75 14.5 46.15 961 7.105 3.915 17.3 14.65 74 1255.5
924 2.835 2.45 15.4 14.05 14.55 500.5 3.91 3.305 15.4 14.25 25.2 691 4.295 3.275 15.5 14.35 30.25 759.5 5.585 3.435 15.9 14.55 48.2 986.5
6
858 2.675 2.315 15.15 13.95 13.04 472.5 3.655 3.135 15 14.15 22.5 646 3.945 3.115 15.1 14.35 26.1 697 5.2 3.235 15.6 14.45 42.25 919
1098 2.86 2.8 16.8 14.8 13.5 505 4.15 3.82 17.4 15.3 27.8 733 4.58 3.58 17.4 15.4 33.4 809 6.18 3.67 18 15.6 56.7 1092
924 2.16 2.1 16.6 14.7 8.4 381 3.23 3.16 16.1 15.1 17.7 576 3.56 3.07 16.2 15.3 21.2 630 4.83 3.22 16.6 15.5 36.7 853
7
858 2.05 2 16.3 14.6 7.68 362 3.06 2.98 15.7 15 15.8 539 3.26 2.92 15.8 15.3 18.2 576 4.51 3.01 16.4 15.4 32.1 797
1098 2.72 2.63 17.1 15.1 12.7 480.5 4 3.47 17.9 15.45 26.1 706.5 4.41 3.36 17.95 15.55 31.25 779.5 5.99 3.445 18.55 15.75 53.75 1058.5
924 2.06 1.995 16.95 15.05 7.75 363.5 3.095 2.925 16.7 15.3 16.25 547 3.43 2.885 16.8 15.45 19.8 606.5 4.715 3.025 17.3 15.65 35.05 833
8
858 1.925 1.87 16.8 15 6.59 340 2.905 2.78 16.3 15.2 14.6 513.5 3.18 2.755 16.4 15.4 17.4 562 4.405 2.855 17 15.55 30.9 778.5
1098 2.58 2.46 17.4 15.4 11.9 456 3.76 3.21 18.4 15.6 23.4 664 4.24 3.14 18.5 15.7 29.1 750 5.8 3.22 19.1 15.9 50.8 1025
924 1.96 1.89 17.3 15.4 7.1 346 2.93 2.75 17.3 15.5 14.8 518 3.3 2.7 17.4 15.6 18.4 583 4.6 2.83 18 15.8 33.4 813
9
858 1.8 1.74 17.3 15.4 5.5 318 2.76 2.62 16.9 15.4 13.4 488 3.1 2.59 17 15.5 16.6 548 4.3 2.7 17.6 15.7 29.7 760
TAI: Air in temperature Twi: Fluid in temperature Pf: Total cooling capacity Qw: Fluid flow rate in heat exchanger Pfs: Sensible cooling capacity Dpw: Pressure drop standard coil Tad: Discharge air dry bulb temperature Qa: Air flow Taw: Discharge air wet bulb temperature
Note: Design and specification are subject to change without prior notice for product improvement.
Page 9
HYDRONIC CASSETTE 9
PCG-12-PS TAI DB24℃-WB17.4℃ TAI DB27℃-WB19℃ TAI DB27℃-WB19.5℃ TAI DB28℃-WB21
Twi qa Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw
°C m3/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h
1296 5.25 4.08 15.2 13.3 23.7 928 7.42 5.04 16.1 13.4 44.2 1311 8.05 4.94 16.3 13.5 50.9 1423 10 5.05 17 13.8 74.4 1767
1171 4.5 3.7 14.5 13.2 18 795 6.43 4.58 15.4 13.3 34.2 1136 7 4.52 15.6 13.4 39.7 1237 8.7 4.64 16.1 13.6 58.4 1538
5
1098 3.81 3.29 13.8 13.1 13.4 673 5.32 4.06 14.4 13.2 24.3 940 5.75 3.98 14.6 13.3 27.7 1016 7.25 4.19 15 13.5 42.3 1281
1296 4.615 3.785 15.9 13.85 18.75 815.5 6.435 4.76 16.85 14.25 34.35 1137 6.805 4.64 16.75 14.4 38.45 1202.5 8.825 4.795 17.5 14.7 60.4 1559 .5
1171 4 3.44 15.3 13.75 14.5 706.5 5.59 4.31 16.2 14.15 26.65 987.5 6.005 4.25 16.2 14.3 30.7 1061 7.7 4.395 16.75 14.55 47.5 1361
6
1098 3.355 3.035 14.6 13.65 10.63 592.5 4.59 3.785 15.25 14.05 18.7 811 4.975 3.755 15.3 14.2 21.75 879 6.41 3.92 15.8 14.45 34.1 1132.5
1296 3.98 3.49 16.6 14.4 13.8 703 5.10 4.48 17.6 15.1 22.4 901 5.56 4.34 17.2 15.3 26 982 7.65 4.54 18 15.6 46.4 1352
1171 3.5 3.18 16.1 14.3 11 618 4.70 4.04 17 15 19.1 839 5.01 3.98 16.8 15.2 21.7 885 6.7 4.15 17.4 15.5 36.6 1184
7
1098 2.9 2.78 15.4 14.2 7.86 512 3.95 3.54 16.1 14.9 13.1 682 4.2 3.53 16 15.1 15.8 742 5.57 3.65 16.6 15.4 25.9 984
1296 3.49 3.19 17.15 14.75 11.2 616.5 5.175 4.075 18.3 15.25 22.65 914.5 5.395 4.02 18.05 15.5 24.7 953 7.455 4.195 18.75 15.75 44.5 1317.5
1171 3.095 2.895 16.75 14.65 9 547 4.525 3.71 17.7 15.15 17.85 799.5 4.79 3.685 17.55 15.4 20.1 846 6.5 3.835 18.15 15.65 34.8 1148.5
8
1098 2.535 2.44 16.4 14.6 6.43 447.5 3.71 3.25 16.85 15.05 12.45 656 4.01 3.275 16.75 15.3 14.6 708.5 5.42 3.4 17.35 15.55 24.9 957.5
1296 3 2.89 17.7 15.1 8.6 530 4.9 3.67 19 15.4 20.8 866 5.23 3.7 18.9 15.7 23.4 924 7.26 3.85 19.5 15.9 42.6 1283
1171 2.69 2.61 17.4 15 7 476 4.3 3.38 18.4 15.3 16.6 760 4.57 3.39 18.3 15.6 18.5 807 6.3 3.52 18.9 15.8 33 1113
9
1098 2.17 2.1 17.4 15 5 383 3.56 2.99 17.6 15.2 11.8 630 3.82 3.02 17.5 15.5 13.4 675 5.27 3.15 18.1 15.7 23.9 931
TAI: Air in temperature Twi: Fluid in temperature Pf: Total cooling capacity Qw: Fluid flow rate in heat exchanger Pfs: Sensible cooling capacity Dpw: Pressure drop standard coil Tad: Discharge air dry bulb temperature Qa: Air flow Taw: Discharge air wet bulb temperature
Note: Design and specification are subject to change without prior notice for product improvement.
PCG-16-PS TAI DB24℃-WB17.4℃ TAI DB27℃-WB19℃ TAI DB27℃-WB19.5℃ TAI DB28℃-WB21
Twi qa Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw Pf Pfs Tad Taw dPw Qw
°C m3/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h kW kW °C °C kPa l/h
1650 6 4.4 15.5 13.2 28.9 1060 8.4 5.5 16.5 13.4 53.3 1484 9 5.4 16.7 13.6 60.1 1591 11.5 5.59 17.3 13.7 93.8 2032
1300 5 3.89 14.8 13.1 20.9 884 6.4 4.83 15.6 13.3 37.4 1220 7.4 4.73 15.7 13.4 42.3 1308 9.3 4.89 16.3 13.6 63.5 1644
5
1100 3.8 3.24 13.7 13 12.7 671 5.32 4.03 14.3 13.1 23.4 940 5.7 3.96 14.4 13.2 26.4 1007 7.17 4.13 14.9 13.4 39.8 1267
1650 5.15 4.14 16.2 13.9 22.45 910 7.19 5.175 17.2 14.3 41.1 1271 7 .75 5.105 17.2 14.45 46.75 1370 10.15 5.26 17.85 14.6 75.7 1793.5
1300 4.3 3.645 15.55 13.8 16.25 760 5.7 4.55 16.4 14.2 29.15 1052 6.35 4.45 16.3 14.3 32.7 1122 8.265 4.625 16.9 14.5 52.05 1461
6
1100 3.37 3.04 14.65 13.65 10.4 595.5 4.65 3.805 15.25 14 18.65 821.5 4.95 3.74 15.1 14.1 20.85 874.5 6.385 3.89 15.6 14.3 32.7 1128.5
1650 4.3 3.88 16.9 14.6 16 760 5.90 4.93 17.9 15.2 29.0 1043 6.5 4.81 17.7 15.3 33.4 1149 8.8 4.93 18.4 15.5 57.6 1555
1300 3.6 3.4 16.3 14.5 11.6 636 4.80 4.31 17.2 15.1 20.9 883 5.3 4.17 16.9 15.2 23.1 936 7.23 4.36 17.5 15.4 40.6 1278
7
1100 2.94 2.84 15.6 14.3 8.1 520 3.65 3.56 16.2 14.9 13.9 703 4.2 3.52 15.8 15 15.3 742 5.6 3.65 16.3 15.2 25.6 990
1650 3.85 3.55 17.35 14.85 13.2 680.5 5.61 4.495 18.45 15.4 25.85 991.5 6.15 4.425 18.45 15.55 30.35 1087 8.45 4.55 19.15 15.75 53.75 1493.5
1300 3.155 3.025 16.95 14.8 9.15 558 4.65 3.935 17.75 15.3 18.45 821.5 5.025 3.87 17.65 15.45 21.1 888 6.915 4.015 18.3 15.65 37.5 1222
8
1100 2.545 2.475 16.6 14.7 6.1 450 3.45 3.315 16.75 15.15 12 646.5 3.97 3.26 16.6 15.25 13.85 701.5 5.4 3.395 17.15 15.45 24.05 954.5
1650 3.4 3.22 17.8 15.1 10.4 601 5.24 4.14 19 15.6 22.8 926 5.8 4.04 19.2 15.8 27.3 1025 8.1 4.17 19.9 16 49.9 1432
1300 2.71 2.65 17.6 15.1 6.7 480 4.3 3.6 18.3 15.5 16 760 4.75 3.57 18.4 15.7 19.1 840 6.6 3.67 19.1 15.9 34.4 1166
9
1100 2.15 2.11 17.6 15.1 4.1 380 3.34 3.05 17.3 15.4 10.1 590 3.74 3 17.4 15.5 12.4 661 5.2 3.14 18 15.7 22.5 919
TAI: Air in temperature Twi: Fluid in temperature Pf: Total cooling capacity Qw: Fluid flow rate in heat exchanger Pfs: Sensible cooling capacity Dpw: Pressure drop standard coil Tad: Discharge air dry bulb temperature Qa: Air flow Taw: Discharge air wet bulb temperature
Note: Design and specification are subject to change without prior notice for product improvement.
Page 10
HYDRONIC CASSETTE 10 ETHYLENE GLYCOL SOLUTIONS
Adding Ethylene Glycol to the water system so as to multiply the performance figures by the values given in the following table.
Freezing point (℃)
0 -5 -10 -15 -20 -25
Percentage of ethylene glycol in weight
0 12% 20% 28% 35% 40% cPf 1 0.985 0.98 0.974 0.97 0.965 cQ 1 1.02 1.04 1.075 1.11 1.14
cdp 1 1.07 1.11 1.18 1.22 1.24
cPf: correction factor cooling capacity cQ: correction factor flow rate cdp: correction factor pressure drop
Page 11
HYDRONIC CASSETTE 11
HEATING CAPACITY TABLES
Note: Design and specification are subject to change without prior notice for product improvement.
Note: Design and specification are subject to change without prior notice for product improvement.
PCG-06-PS
TAI 18 TAI 20 TAI 22
TAI 24
Twi Two qa Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw
°C °C m3/h kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa
750 2.28 27.4 390 2.36 2.07 28.5 354 1.98 1.86 29.6 318 1.64 1.65 30.7 282 1.3
648 2.12 28 363 2.1 1.92 29.1 329 1.74 1.73 30.2 296 1.44 1.54 31.3 263 1.14
45 40
588 2 28.4 342.8 1.86 1.82 29.5 312 1.6 1.64 30.5 281 1.31 1.46 31.5 250 1.02
750 2.24 27.2 192 0.6 2.04 28.4 175 0.557 1.83 29.5 166.9 0.457 1.62 30.6 158.8 0.357
648 2.07 27.8 177 0.57 1.9 29 162 0.491 1.71 30.1 146.6 0.406 1.52 31.2 131.2 0.321
50 40
588 1.98 28.3 170 0.53 1.8 29.4 154 0.445 1.61 30.4 138 0.362 1.42 31.4 122 0.279
750 4.37 36 374.6 2.2 4.14 37 354 1.98 3.91 38.1 335 1.78 3.68 39.2 316 1.58
648 4.05 37.2 347 1.91 3.84 38.2 329 1.74 3.64 39.3 312 1.58 3.44 40.4 295 1.42
70 60
588 3.83 38 328 1.73 3.63 39 311 1.56 3.46 40.1 296.6 1.44 3.29 41.2 282.2 1.32
TAI: Air in temperature Twi: Fluid in temperature Pf: Total heating capacity Qw: Fluid flow rate in heat exchanger Tad: Discharge air temperature Dpw: Pressure drop standard coil Qa: Air flow
PCG-08-PS
TAI 18 TAI 20 TAI 22 TAI 24
Twi Two qa Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw
°C °C m3/h kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa
846 2.45 26.9 420 2.7 2.21 28 378.9 2.23 1.99 29.2 341 1.85 1.77 30.4 303.1 1.47
700 2.22 27.8 380 2.3 2 28.8 342.9 1.9 1.8 29.9 308 1.55 1.6 31 273.1 1.2
45 40
550 1.93 28.8 330 1.76 1.75 29.8 300 1.47 1.58 30.8 270 1.23 1.41 31.8 240 0.99
846 2.4 26.7 205 0.8 2.18 27.9 186.9 0.7 1.96 29.1 168 0.6 1.74 30.3 149.1 0.5
700 2.16 27.5 185 0.6 1.96 28.6 168 0.52 1.74 30.2 149 0.42 1.52 31.8 130 0.32
50 40
550 1.89 28.6 162 0.5 1.73 29.7 148 0.414 1.55 30.7 132 0.4 1.37 31.7 116 0.386
846 4.68 34.9 401 2.5 4.43 36.1 380 2.3 4.2 37.2 360 2.04 3.97 38.3 340 1.78
700 4.22 36.5 361 2.1 4 37.6 343 1.9 3.73 39.7 319 1.65 3.46 41.8 295 1.4
70 60
550 3.7 38.7 317 1.63 3.41 41 292 1.4 3.32 40.6 284 1.33 3.23 40.2 276 1.26
TAI: Air in temperature Twi: Fluid in temperature Pf: Total heating capacity Qw: Fluid flow rate in heat exchanger Tad: Discharge air temperature Dpw: Pressure drop standard coil Qa: Air flow
Page 12
HYDRONIC CASSETTE 12
Note: Design and specification are subject to change without prior notice for product improvement.
Note: Design and specification are subject to change without prior notice for product improvement.
PCG-09-PS
TAI 18 TAI 20 TAI 22 TAI 24
Twi Two qa Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw
°C °C m3/h kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa
1098 4.22 29.8 723.4 15.3 3.86 30.8 661.7 13.1 3.47 31.7 594 10.7 3.08 32.6 526.3 8.3
924 3.78 30.9 648 12.6 3.42 31.7 586.2 10.4 3.09 32.6 530 8.7 2.76 33.5 473.8 7
45 40
858 3.56 31.4 610 11.2 3.25 32.2 557 9.54 2.95 33 505 8.1 2.65 33.8 453 6.66
1098 4.36 30.2 373.7 4.7 3.98 31.1 341 3.95 3.6 32.1 308.6 3.3 3.22 33.1 276.2 2.65
924 3.88 31.2 332.6 3.8 3.54 32.2 303 3.2 3.21 33 275 2.67 2.88 33.8 247 2.14
50 40
858 3.69 31.8 316.3 3.5 3.38 32.6 289.7 2.95 3.06 33.5 262 2.46 2.74 34.4 234.3 1.97
1098 7.61 40.7 671.3 14.3 6.67 41.5 571 13 6.27 42.4 551 11.8 6.08 43.3 522 10.6
924 7.01 42.6 602.1 11.5 5.85 43.5 546.3 10.5 5.55 44.4 537 9.53 5.82 45.3 507.7 8.56
70 60
858 6.46 43 558.6 10.2 5.57 44.3 537 9.5 5.27 44.9 528 8.5 5.61 45.5 467 7.5
TAI: Air in temperature Twi: Fluid in temperature Pf: Total heating capacity Qw: Fluid flow rate in heat exchanger Tad: Discharge air temperature Dpw: Pressure drop standard coil Qa: Air flow
PCG-12-PS
TAI 18 TAI 20 TAI 22 TAI 24
Twi Two qa Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw
°C °C m3/h kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa
1296 4.54 27.8 778 17.4 4.13 28.9 708 14.6 3.72 30.1 637 12.1 3.31 31.3 566 9.6
1176 4.17 28.5 714.8 15 3.8 29.6 651 12.65 3.43 30.6 588 10.5 3.06 31.6 525 8.35
45 40
1098 3.68 29.6 630.8 12 3.36 30.6 576 10.1 3.03 31.5 519 8.4 2.7 32.4 462 6.7
1296 4.67 28.1 400 5.3 4.3 29.3 368.6 4.6 3.88 30.4 332 3.8 3.46 31.5 295.4 3
1176 4.3 28.8 368 4.54 3.92 29.9 336 3.8 3.57 31 306 3.24 3.22 32.1 276 2.68
50 40
1098 3.8 30 325.7 3.63 3.48 30.9 298 3.1 3.15 31.9 270 2.58 2.82 32.9 242 2.06
1296 8.07 36.8 745 16.2 7.20 38 710 14.8 6.87 39 674 13.5 6.45 40 638 12.2
1176 7.55 38.1 681 13.7 6.6 39 651 12.6 6.25 40.1 621 11.6 5.95 41.2 591 10.6
70 60
1098 6.85 40.1 604 11 5.95 41 576 10.1 5.65 42.1 548 9.3 5.68 43.2 520 8.5
TAI: Air in temperature Twi: Fluid in temperature Pf: Total heating capacity Qw: Fluid flow rate in heat exchanger Tad: Discharge air temperature Dpw: Pressure drop standard coil Qa: Air flow
Page 13
HYDRONIC CASSETTE 13
Note: Design and specification are subject to change without prior notice for product improvement.
PCG-16-PS
TAI 18 TAI 20 TAI 22 TAI 24
Twi Two qa Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw Pf Tad Qw dPw
°C °C m3/h kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa kW °C l/h kPa
1650 4.96 27 850 20.3 4.57 28.3 783 17.7 4.08 29.4 700 14.3 3.59 30.5 617 10.9
1300 4.4 28 754 16.4 4.02 29.2 689 14 3.62 30.3 620 11.6 3.22 31.4 551 9.2
45 40
1100 3.75 29.4 642.8 12.3 3.43 30.5 588 10.6 3.1 31.6 531 8.8 2.77 32.7 474 7
1650 5.12 27.3 439 6.2 4.7 28.5 402 5.3 4.24 29.7 363 4.4 3.78 30.9 324 3.5
1300 4.54 28.3 389 5 4.14 29.5 354 4.2 3.75 30.6 321 3.54 3.36 31.7 288 2.88
50 40
1100 3.86 29.7 330 3.7 3.53 30.8 302.6 3.2 3.21 31.8 275 2.7 2.89 32.8 247.4 2.2
1650 8.51 35.3 755 18.9 7.90 36.5 677 17.5 7.33 37.7 620 15.9 7.07 38.9 601 14.3
1300 7.42 37.2 681 15.2 6.95 38.4 627 13.9 6.81 39.4 592 12.6 6.20 40.4 567 11.3
70 60
1100 6.50 39.6 617 11.5 5.96 40.8 582 10.3 6.25 41.7 557 9.52 5.82 42.6 532 8.74
TAI: Air in temperature Twi: Fluid in temperature Pf: Total heating capacity Qw: Fluid flow rate in heat exchanger Tad: Discharge air temperature Dpw: Pressure drop standard coil Qa: Air flow
Page 14
HYDRONIC CASSETTE 14
THE INSTALLATION MANUAL
HOT & CHILLED WATER SYSTEM AIR CONDITIONERS
First check the contents of the package.
FACTORY SUPPLIED ACCESSORIES
Check to ensure all factory supplied accessories are supplied with the unit.
The appliance should be installed in accordance with national wiring regulation.
SAFETY CONSIDERATIONS
1. When working on air conditioning equipment, observe precautions in this manual, and on plates and tables attached to the unit. Follow all safety codes and other safety precautions that may apply.
2. Installing and servicing air conditioning equipment should be done by trained and qualified service personnel only. Untrained personnel can perform only basic maintenance functions such as cleaning coils, filters and replacing filters.
3. Ensure that the electrical supply and frequency are adequate for the operating current required for this specific installation.
WARNING - Before any service or maintenance operations turn off the main power switch.
1. The manufacturer denies any responsibility and warranty shall be void if these installation
instructions are not observed.
2. Never switch off the power main supply when unit is operating in the cooling cycle. To
switch off the fan coil unit use only the ON-OFF button.
3. This avoids over-flow in the drain pan, by allowing the pump to drain any condensate
water due to regulating valve losses when chiller is working.
OPERATING LIMITS
1. Power supply
Volt Phase Hz
230 1 50
2. Water circuit
Minimum entering water temperature: +2 °C  Maximum entering water temperature: +80 °C  Water side maximum pressure: 1400 kPa (142 m.w.c)
FACTORY SUPPLIED ACCESSORIES AMOUNT
LCD Remote control 1 Mounting Bracket (Already on the unit) 1 Installation manual 1 Batteries 2 External drain pan 1
Page 15
HYDRONIC CASSETTE 15 BEFORE INSTALLATION
The installation site must be established by the system designer or other qualified professional, taking account of the technical requisites and current standards and legislation.
PCG fan coils must be installed by an authorized company only. PCG fan coils are designed for installation in a false ceiling, for intake of fresh air from outside and for
deviation of a small part of the treated air for discharge in a neighboring room. They must be installed in such a way as to enable treated air to circulate throughout the room and in respect of the minimum distances required for technical maintenance operations.
1. It is advisable to place the unit close to the installation site without removing it from the packaging.
2. Do not put heavy tools or weights on the packaging.
3. Upon receipt, the unit and the packaging must be checked for damage sustained in transit and if
necessary, a damage claim must be filed with the shipping company.
4. Check immediately for installation accessories inside the packaging.
5. Do not lift unit by the condensate drain discharge pipe or by the water connections; lift it by the
four corners.(Fig.1)
6. Check and note the unit serial number.
SELECT LOCATION
1. Do not install the unit in rooms where flammable gas or alkaline acid substances are present.
Aluminum/copper coils and/or internal plastic components can be damaged irreparably.
2. Do not install in workshops or kitchens; oil vapors drawn in by treated air might deposit on the
coils and alter their performance or damage the internal plastic parts of the unit.
3. Installation of the unit will be facilitated by using a stacker and inserting a plywood sheet between
the unit and the elevated stacker.(Fig.2)
4. It is recommended to position the unit as centrally as possible in the room to ensure optimum air
distribution. (Fig.3) Generally the best louver position is the one which allows air diffusion along the ceiling. Alternatively intermediate positions can be selected.
5. Check that it is possible to remove panels from ceiling in the selected position, to allow enough
clearance for maintenance and servicing operations.
Fig.2
Fig.1
Fig.3
Page 16
HYDRONIC CASSETTE 16 INSTALLATION LOCATION
INSTALL THE UNIT IN A POSITION:
1. Having sufficient strength to carry the weight of the unit.
2. Where the inlet and outlet grilles are not obstructed and the conditioned air is able to blow all over
the room.
3. From where condensate can be easily run to drain.
4. Check the distance between the upper slab and false ceiling to ensure the unit will suit the
distance. See Fig.4
A
B
Fig.5
5. Ensure there is sufficient space around the unit to service it. See Fig.5
Model A (mm.) B (mm.)
PCG-09 250 10 or more
PCG-06/08/12/16 290 10 or more
Fig.4
Page 17
HYDRONIC CASSETTE 17 INSTALLATION METHOD
CASSETTE UNIT
Using the installation template open ceiling panels and install the suspension bolts as in Fig.6 below
600 x 600: Dimensions for opening
632 x 280: Suspension Bolts
600 x 1160: Dimensions for opening
750 x 632: Suspension Bolts
FIG. 6
MODELS PCG-06/08
MODELS PCG-09/12/16
Page 18
HYDRONIC CASSETTE 18 OPENING DIMENSIONS AND POSITIONS FOR SUSPENSION BOLTS
1. Mark position of suspension rods, water lines and condensate drain pipe, power supply cables
and remote control cable.
2. Supporting rods can be fixed, depending on the type of ceiling, as shown in Fig. 7 and Fig.8.
3. Fit suspension brackets supplied with the unit to the threaded rods (Fig.9).
4. Do not tighten nuts and counter nuts; this operation has to be done only after final leveling of the
unit, when all the connections have been completed.
Fig.7 Fig.8
Fig.9
5. Ensure the ceiling is horizontally level, otherwise condensate water cannot drain.
6. The casing is fixed to the slab with 4 drop rods. The rods should have two nuts and washers to
lock the unit in position. The Cassette brackets will then hook over the washers.
7. When lifting the Cassette into position care should be taken not to lift the unit by the drip tray,
which could be damaged.
8. Lift unit (without the air panel) with care by its four corners only. Do not lift unit by the condensate
drain discharge pipe or by the piping connections.
9. Incline unit (Fig.10, Fig.11, Fig.13, Fig.14) and insert it into the false ceiling. Insert the rods into
the bracket slot. With minimum height (see table) false ceilings, it might be necessary to remove some T brackets of the false ceiling temporarily.
10. Using a level guide, line up the unit with a spirit level, and keep dimension between the body and
the lower part of the false ceiling (Fig.12 Fig.15).
11. Line up the unit to the supporting bars of the false ceiling tightening the nuts and counter nuts of
the threaded rods.
Page 19
HYDRONIC CASSETTE 19
12. After connection of the condensate drain piping and piping connections, check again that the unit
is level.
MODEL PCG-06/08
A (mm.) 3
Fig. 10
Fig. 11
Fig. 12
Page 20
HYDRONIC CASSETTE 20
MODEL PCG-09/12/16
A (mm.) 3
13. The spaces between the unit and ceiling can now be adjusted. Use the drop rods to make the
adjustment.
14. Check to ensure the unit is level. The drain will then automatically be lower than the rest of the
drip tray.
15. Tighten the nuts on the suspended rods.
Fig. 13
Fig. 14
Fig. 15
Page 21
HYDRONIC CASSETTE 21 DRAIN PIPE WORK
INDOOR UNIT
1. The unit is fitted with a condensate pump with a 500 mm. lift.
2. The unit is provided with 22 mm. bore flexible hose 300 mm. long.
3. The flexible hose should be fitted into a 22 mm O/S Φ. polyvinyl tube and sealed.
4. The drain must be installed with a downward slope.
5. On completion the drain line should be insulated.
WATER CONNECTIONS
The hydraulic connections of the PCG unit is 3/4” water connection with gaskets it is advisable to tighten the gaskets with a spanner.
For piping dimensional drawing please refer to “DIMENSIONAL DRAWINGS”
VALVE CONFIGURATION
There are two types of valve configuration for PCG cassette: a) Internal integrated valve and b) external valve –
a) Pre-installed 2-way and 3-way integrated valves (Fig. 17)
(please refer to “VALVE INFORMATION”)
Integrated valve information
Model
Type inch
PCG-06/08 2-way & 3-way 1/2”
PCG-09/12/16 2-way & 3-way 3/4”
Fig. 16
Fig. 17
Page 22
HYDRONIC CASSETTE 22
b) External valves
i. Replace integrated valve with plug-and-play replacement connector
Procedures:
1) Before connecting water supply to the PCG cassette. First remove the integrated valve using spanner
2) Replace with plug-and-play connector (Fig. 18)
3) Connect the external valve directly onto the cassette.
ii. Disable integrated valve functionality using valve cap
Procedures:
1) Remove integrated valve actuator by pressing on both sides. (Fig. 19)
2) Place the valve cap onto the valve body. (Fig. 20)
3) Connect the external valve directly onto the cassette.
Fig. 18
Fig. 19 Fig. 20
Page 23
HYDRONIC CASSETTE 23 EXTERNAL DRAIN PAN
Procedures:
Align the two (2) screw holes in the fixing plate to the two (2) holes in the external drain pan.
(Fig. 21)
Make sure the drain pan is horizontal.  Tighten the two screws and making sure the external drain pan is installed flush with the fixing
plate. (Fig. 22)
When the installation is completed, it is necessary to wrap connecting pipe with insulation to prevent leakage to ceiling tile.
FRESH AIR RENEWAL CONNECTION
The fresh air system for PCG cassette allows up to 15% of unit airflow as fresh air intake (per connection). Maximum 2 fresh air connections per unit.
1. The corners of the cassette allow separate ductwork to be installed for outside air intake (Fig.23)
2. Cut and remove anti-condensate insulating material.
3. Open the mounting plate (Fig. 24)
3. Install the flanges to casing and fix it with 2 screws. Flange is rectangular duct with dimension 110 x 55mm.
Fig. 21
Fig. 22
Fig. 23
Page 24
HYDRONIC CASSETTE 24
BRANCH DUCT CONNECTION
The side opening allows separate ductwork to be installed for branch ducting. (Fig. 26) Cut and remove anti-condensate insulating material. Install your flanges and conduits to casing. Conduit can be flexible polyester with spring core or
corrugated aluminium externally coated (dia.4 in.) with anti-condensate material (fiberglass 12-25 mm thickness).
Order flanges (spigots) and blanking plates as accessories separately.
BRANCH DUCT DIMENSION
Fig. 24
Fig. 25
Fig. 26
Page 25
HYDRONIC CASSETTE 25
BRANCH DUCT INSTALLATION
St e p 1 St ep 2
St e p 3
St ep 4
STI CK ER
Tapping Screw
Dia 3 mm.x12 mm.l.
1. Look for the yellow sticker on the casing for location of branch duct or fresh air intake connections.
2. The sticker is at the center of a knock out hole underneath the casing insulation. Use a cutter and follow along the pre-cut circular marking as shown and trim off the insulation.
3. Knock out the pre-cut hole.
4. Connect the flange on to the opening with Φ3 mm. x 12 mm. tapping screws.
Page 26
HYDRONIC CASSETTE 26 INTERCONNECTING WIRING
We recommend that screened cable be used in electrically noisy areas.
1. Always separate low voltage (5VDC) signal wires from power line (230 VAC) to avoid electro­magnetic disturbance of control system.
2. Do not install the unit where electromagnetic waves are directly radiated at the infra red receiver on the unit.
3. Install the unit and components as far away as is practical (at least 5 meters) from the electromagnetic wave source.
4. Where electromagnetic waves exist use shielded sensor cable.
5. Install a noise filter if any harmful noise exists in the power supply.
Important note: Please ensure the cable of the main powers supply will be > 500mm long from the
control box terminal block. This is to ensure the control box can be slide out easily during maintenance activities.
Wiring procedures:
1) Open the terminal block cover by removing 4 screws
2) Connect L & N cable to the terminal according to wiring diagram on page 63
3) Connect room temperature sensor, coil temperature sensors to the control box
4) Connect stepping motor
5) Connect receiver display
6) Connect wall pad (optional)
7) Slide in the control box to the unit casing and fixed with 2 screws.
Fig.27
Page 27
HYDRONIC CASSETTE 27 CONTORL BOX CONFIGURAITON
a) Plug-and-play control box with full functionality PCB (please refer to wiring diagram on page 60)
The PCB is a universal type with multiple configurations selectable using dipswitches. Please provide dip-switch setting according to below.
There are 2 DIP Switch sets on the PCB, one with 8 Dip-switches which named as DIP-Switch A and one with 6 Dip-switches which named as DIP-Switch B
For master-slave connection setting, please refer to Appendix I.
DIP Switch A SW1-SW6 is used for master slave address setting.
DIP switch address setting: 1 for ON, 0 for OFF.
SW7 SW8 Model setting 0 0 Cool-Heat 0 1 Cool-Heat + booster heater 1 0 Cooling only 1 1 Cool + primary heater
DIP Switch B is used for model configuration as follow:-
DIP switch setting: 1 for ON, 0 for OFF.
SW1 PR-O contact setting 0 Economy contact 1 Window contact
SW2 System setting 0 2 pipes system 1 4 pipes system
SW3 Preheat setting 0 28C 1 36C
SW4 MTV setting [applicable to 2 pipes system only] 0 Without motorized valve 1 With motorized valve
SW5 Reserved
SW6 RS485 termination setting 0 Other than below 1 Last unit on RS485 communication bus
Page 28
HYDRONIC CASSETTE 28 MOUNTING FRONT PANEL ASSEMBLY
1. Remove return grille from front panel.
2. Move the front panel to casing.
3. Tighten 4 screws as shown in Fig 28,29
FILTER REMOVAL
1. Unlock the two fasteners on the front panel.
2. Open the grille downward with care.
3. Pull the filter out along the slot.
4. Clean the filter and reassemble.
PCG-06/08
PCG-09/12/16
Fig.28 Fig.29
Page 29
HYDRONIC CASSETTE 29
PRELIMINARY CHECKS BEFORE START-UP
1. The unit should not be started up until the system piping has been cleaned and all the air has been purged.
2. Check condensate drain pipe slope.
3. After you have connected the main power supply to the cassette unit, it is necessary to check the good function of the condensate water pump which is installed inside. Due to transport vibration, it might be possible that the float switch is hung up and the pump might not work in the correct way. For this reason, you have to do the following, to ensure good functioning of the unit:
4. Install the cassette unit in an absolute horizontal position.
5. Fill the internal drain pan (manually) with enough water to ensure the drain pump is working.
6. You can fill the drain pan by pouring water through the external drain pan. If everything is correct, the water will be pushed out into the pipe work you have installed. If the valve does not open, you have to make sure the float switch is not hung up inside the unit and you will have to loosen it by hand.
7. Make sure that air filter is clean and properly installed.
8. Ensure that voltage and current values correspond with the unit nameplate values; check electrical connections.
9. Verify that air outlets are not closed.
MAINTENANCE
1. Before performing any service or maintenance operations, turn off the main power switch.
2. The air filter is made of acrylic fiber and is washable in water. To remove filter simply open the intake grille by releasing the two catches. See Fig.19 and the section filter removal.
3. Check the filter periodically and before the operating season; clean or replace as necessary.
PROLONGED UNIT SHUT-DOWN
1. Prior to restarting the unit:
2. Clean or replace the air filters.
3. Check and remove any obstruction from the external drain pan and the internal drain pan.
EXTRA MAINTENANCE
1. The electrical panel is easily accessible by removing the cover panel.
2. The inspection or replacement of internal components such as; heat exchanger coil, condensate
3. Drain pump, float switch, involves the removal of the condensate drain pan. See Fig.20-25.
4. During the removal of the condensate drain pan protect the floor under the unit with a plastic sheet from condensate water that could be spilled.
5. Remove fixing screws of the drain pan fixture and remove condensate drain pan with care.
The appliance is intended to be maintained by qualified service personnel and located at a height of not less than 2.5m.
Page 30
HYDRONIC CASSETTE 30
HOW TO ACCESS AIR VENT AND WATER PURGE
2
nd
STEP: release the air vent / water purge
by loosen the screws.
HOW TO CONNECT NON-DEFAULT FAN SPEED
1
st
STEP: remove the grill. 2
nd
STEP: remove the finger guard by removing 4 screws.
3
rd
STEP: remove the finger guard and venturi 4th STEP: Fan speed terminal is located in the area
inside the red rectangle.
1
s
t
STEP: remove the grill, air vent and water purge
are located at the pointed area.
Page 31
HYDRONIC CASSETTE 31
5th STEP: change the fan speed wiring according to below wiring diagram
Page 32
HYDRONIC CASSETTE 32
HOW TO FIX THE MOTOR AND FAN BLOWER
1
st
STEP: remove the grill. 2
nd
STEP: remove the finger guard by removing 4
screws.
3
rd
STEP: remove the finger guard and Venturi 4
th
STEP: remove fan blower using a spanner
5
th
STEP: remove the motor by removing 4 bolts and disconnect fan motor wire connector.
Page 33
HYDRONIC CASSETTE 33
HOW TO FIX CONDENSATE PUMP AND INTERNAL VALVE
1
st
STEP: remove the grill. 2nd STEP: remove the front panel by removing 4
screws.
3
r
d
STEP: remove the front panel by disconnecting
stepping motor and IR receiver.
4th STEP: removing the drain pan fixture by
removing 8 screws.
5th STEP: remove the drain pan fixture and
internal drain pan
6th STEP: remove the drain pump or valve
Page 34
HYDRONIC CASSETTE 34
HOW TO FIX CONTROL BOX
1
st
STEP: remove the grill. 2
nd
STEP: remove the front panel by removing 4
screws.
3
r
d
STEP: remove the front panel by disconnecting
stepping motor and IR receiver.
4th STEP: remove 2 screws on the control box.
5
th
STEP: sliding out the control box.
6th STEP: Remove the terminal cover by removing 4
screws and unplug the wiring on the terminal. And replace with a new control box
Page 35
HYDRONIC CASSETTE 35
HOW TO INSTALL ELECTRIC HEATER
1
st
STEP: remove the grill. 2nd STEP: remove the front panel by removing 4 screws.
3
r
d
STEP: remove the front panel by
disconnecting stepping motor and IR receiver.
4th STEP: remove the drain pan fixture by removing 8
screws.
5th STEP: remove internal drain pan fixture and
internal drain pan
6th STEP: slide in the insulated ring of the electric
heater to the electric heater mounting shown above
Page 36
HYDRONIC CASSETTE 36
7th STEP: slide in the rest insulated rings of the
electric heater to the electric heater mounting shown above
8th STEP: Plug in the electric heater wiring to the
connector shown above.
Page 37
HYDRONIC CASSETTE 37
EXPLODED VIEW DRAWING
PCG-06/08-PS
01---casing 08-05---main PCB 02---3-way 4-ports valve (optional) G3/4 08-05-01---chilled water coil temperature sensor 03---mounting brackets 08-05-02---hot water coil temperature sensor 04---fresh air flange (optional) 08-05-03---room temperature sensor 05---Condensate water pump 09---motor with capacitor 05-01---pump body 10---electrical heater (optional) 05-02---float switch 11---fan blower 05-03---flexible hose 1 12---drain pan with 3mm insulation 05-04---non-return valve 13---drain pan fixture 05-05--- flexible hose 2 14---finger guard 05-06---drainage head 15---Venturi 05-07---pump fixture 16---returned air grill 06--- coil 17---filter 07---coil and EH’s fixture 18---front panel 08---control system 18-01---stepping motor (2-corotation) 08-01---back of control box 18-02---stepping motor (2-reversion) 08-02---front of control box 18-03---IR receiver 08-03---cover of control box 19---external drain pan 08-04---terminal block 20--- remote handset and wired wall pad (optional)
Page 38
HYDRONIC CASSETTE 38 PCG-09/12/16-PS
01---casing 08-05---main PCB 02---3-way 4-ports valve (optional) G3/4 08-05-01---chilled water coil temperature sensor 03---mounting brackets 08-05-02---hot water coil temperature sensor 04---fresh air flange (optional) 08-05-03---room temperature sensor 05---Condensate water pump 09---motor with capacitor 05-01---pump body 10---electrical heater (optional) 05-02---float switch 11---fan blower 05-03---flexible hose 1 12---drain pan with 3mm insulation 05-04---non-return valve 13---drain pan fixture 05-05--- flexible hose 2 14---finger guard 05-06---drainage head 15---Venturi 05-07---pump fixture 16---returned air grill 06--- coil 17---filter 07---coil and EH’s fixture 18---front panel 08---control system 18-01---stepping motor (2-corotation) 08-01---back of control box 18-02---stepping motor (2-reversion) 08-02---front of control box 18-03---IR receiver 08-03---cover of control box 19---external drain pan 08-04---terminal block 20--- remote handset and wired wall pad (optional)
Page 39
HYDRONIC CASSETTE 39
DIMENSIONAL DRAWINGS
PCG-06-08-PS
Page 40
HYDRONIC CASSETTE 40
PCG-09-PS
Page 41
HYDRONIC CASSETTE 41
PCG-12/16-PS
Page 42
HYDRONIC CASSETTE 42
VALVE INFORMATION
Page 43
HYDRONIC CASSETTE 43
Page 44
HYDRONIC CASSETTE 44
REMOTE CONTROL HANDSET
WIRELESS LCD HANDSET DISPLAY
Page 45
HYDRONIC CASSETTE 45
***When unit with handset is master, settings are automatically sent to slaves; ***Auto Cool-Heat operation will be applicable in 4-pipe system only. ***Swing is not applicable to PCG models.
Page 46
HYDRONIC CASSETTE 46
***Wall pad will recognize the main board model automatically whether it is 2 pipes or 4 pipes. Auto Cool-Heat operation will be applicable in 4 pipe system only. ***When the wall pad is connected to the main board, air sensor inside the wall pad will be automatically set as primary source and the return air sensor from the unit will be disabled.
Page 47
HYDRONIC CASSETTE 47
WALL PAD OPERATION
1) Clock display and setting
System has an accurate internal real time clock used for time indication and timer ON/OFF function.
Real time clock display area indicates internal time clock which can be set by
TIME
or
TIME
button.
2) Day display and setting
The wall pad has day display function which is used for day indication and timer ON/OFF function.
Day display icon indicates current day. Press
D
A
Y
button to set day.
3) Timer ON/OFF setting
If master unit is in global control mode and on/off timer setting is reached, master unit will command the whole network to be on or off. Otherwise timer on/off is effective to the local unit only. The system
supports 7 days on/off timer setting.
a) Press
TIMER
button once, and ON symbol blinking indicates on timer programming mode,
day display area indicates the day for setting timer on. If on timer for this day is null, timer
display area shows
, otherwise the on timer setting will be shown. Press
TIME
or
TIME
button to change the on timer setting. Press
CANCEL
key to cancel the current on timer selected
and the timer display area will show
. Press
D
A
Y
button to change the day the on
timer is to be programmed.
b) Press
TIMER
button again, and
OFF
symbol blinking indicates off timer programming
mode. The setting method is the same as on timer setting above.
c) Press
TIMER
button again, to exit timer on/off setting function.
d) Should there be any on or off timer being programmed,
will light up. Should there be any
unexecuted on or off timer for the current day, its corresponding
ON
or
OFF
icon will light up.
e) Hold down
CANCEL
button for 3 seconds to cancel all timer settings.
Timer set by master unit is as follows:-
1. Press
NET
button to enter into networking control mode. Unit area blinking indicates the
slave unit under control. Press
TIME
or
TIME
to select the desired slave unit. Units that are off
will be skipped automatically.
2. Press
TIMER
button once to enter into on timer programming mode. Press
D
A
Y
button to select the required day of the week. Master unit will then retrieve the setting from the selected slave unit and timer display area will show “rEAd”. The on timer setting will be
shown upon reading the data successfully. Press
TIME
or
TIME
button to change the on timer
setting.
Page 48
HYDRONIC CASSETTE 48
3. Press
TIMER
button again to enter into off timer programming mode. Press
D
A
Y
button to select the required day of the week. Master unit will then retrieve the setting from the selected slave unit and timer display area will show “rEAd”. The off timer setting will be
shown upon reading the data successfully. Press
TIME
or
TIME
button to change the off timer
setting.
4. Upon completion of changing timer settings for the selected day, press
TIMER
button again to exit timer programming mode. The settings will then upload to the selected slave unit. The next day of the week settings can be done only upon completion of sending data to the slave units. (Repeat steps 1~4 if setting is required for the next day of the week).
5. In Global control mode:
Pressing Master
CANCEL
button for 3 seconds will cancel all timer settings in all slave
units.
Timer settings will be broadcast to all slave units.
Clock synchronization by master unit is as follows:
1. Press
TIME
and
TIME
buttons for 3 seconds to activate clock synchronization to all slave
units. Master wall pad will respond with a beeping sound.
4) Key lock
In order to prevent unauthorized access to the system setting, a key lock function is provided to prevent mischief. Hold down
and for 3 seconds to activate key lock, symbol lights up.
Repeat the same to exit key lock. Only
button is applicable in key lock mode.
5) Swing
Press
S
W
I
N
G
to activate or deactivate swing function.
6) Sleep
Press
SLEEP
button to activate or deactivate sleep setting. Sleep is valid in cool or heat modes only.
7) Temperature setting
Press
or to enter into temperature setting mode, temperature display area blinks indicating
the current set temperature. Press the above buttons to adjust the set temperature.
8) Mode setting
Press
MODE
button to change the operation mode.
9) Fan speed setting
Press
FAN
button to change the fan speed. Only low speed is available for dehumidification mode.
10) On/Off control
Press
to start or stop the air conditioner.
Page 49
HYDRONIC CASSETTE 49
11) Networking Master - Slave control (only master unit wall pad can control other units on the network)
Press
NET
button to enter into networking control mode. Unit area blinking indicates the slave unit
under control. Press
TIME
or
TIME
to select the desired slave unit; Units that are off will be bypassed automatically. Parameters that can be controlled are on/off, timer weekly program, set temperature, mode, fan speed, swing and sleep. Parameter operation methods are the same as above. Press
NET
button again to exit networking control mode.
Hold down
S
W
I
N
G
and
FRESH
buttons for 3 seconds to enter into global control mode, lights up. Repeat the same to exit global control mode. In global control mode, the settings of the master unit will be broadcast to all the slave units.
12) Unit operation parameters browsing
Hold down
CANCEL
and
FAN
buttons for 3 seconds to enter into operation parameters browsing
mode. Unit display area shows the slave unit under browsing. Slave unit selection method is the
same as in networking control above. Press
HUMIDIFY
or
HUMIDIFY
to browse various
parameters as follow:
Wall pad display temperature area Wall pad display time area C0 Return air temperature displayed C1 Indoor coil temperature displayed C2 DIP switch setting displayed C3 Indoor coil 2 temperature
Press
CANCEL
button to exit.
13) Error indication
When faulty slave unit is detected, Master unit display area shows the faulty unit address, time area shows the error code and wall pad backlight changes to red color. Should there be multiple units having problems, addresses and error codes will be shown one after another.
Error code definition:
Error Error code Electrical heater faulty E1 Indoor coil sensor 2 faulty E2 Return air sensor faulty E3 Indoor coil sensor 1 faulty E4 Indoor coil low temperature protection E5 Indoor coil over heat protection E6 Water pump faulty E7 Local communication error E8
For system without master-slave settings, wall pad will indicate unit error codes as above.
PARAMETER
PARAMETER
Page 50
HYDRONIC CASSETTE 50
CONTROL SPECIFICATIONS
HOT AND CHILLED WATER CASSETTE
WITH MASTER-SLAVE CONTROL
1. ABBREVIATIONS AND DEFINITION OF INPUT & OUTPUT PORT S
Ts = Setting temperature Tr = Room air temperature Ti1 = Indoor coil temperature, ID1 Ti2 = Indoor coil temperature, ID2 MTV1 = Cool Motorized valve MTV2 = Heat Motorized valve AUX1 = Hot water free contact AUX2 = Cold water free contact
I/O
Code
2-Pipe 4-Pipe
Room Sensor CN8 Return air Return air
Chilled water Sensor CN7 Indoor coil Chilled water coil
Analogue Input
Hot water Sensor CN6 Reserved Hot water coil
IR receiver CN9 Used Used
Input
Wired wall pad CN5 Used Used
Occupancy contact PR-O
DIP-SWITCH IS ON. (Window contact)
The contact is normally open. If the contact has been closed for 10 minutes, the unit will go to stand­by mode (all output signals will be disabled). When the contact is open again, the unit will resume running normally.
DIP-SWITCH IS OFF. (Economy contact)
Cooling operation will only be activated when Tr - Ts >= 4 ºC. If Tr < Ts, cool operation will be terminated. Heating operation will only be activated when Tr – Ts <= -4 ºC. If Tr > Ts, heating operation will be terminated.
Float switch Float Voltage-free (NC)
Digital input
Electrical heater safety switch
EH
Voltage-free (NC). The contact is closed before the EH is turned on.
Phase L
Power supply to the PCB and all the loads connected to the voltage outputs. Max length: 5 m.
Neutral N
Power supply to the PCB and all the loads connected to the voltage outputs. Max length: 5 m.
Power input
Earth GND
Power supply to the PCB and all the loads connected to the voltage outputs. Max length: 5 m.
Page 51
HYDRONIC CASSETTE 51
High fan speed HF Max length: 5 m. Voltage output (L)
Medium fan speed MF Max length: 5 m. Voltage output (L)
Low fan speed LF Max length: 5 m. Voltage output (L)
Valve1 MTV1
Water valve Voltage output (L)
Chilled water valve Voltage output (L)
Valve2 MTV2 Reserved
Hot water valve Voltage output (L)
Water pump WP Voltage output (L)
Voltage output
Voltage of electrical heater (Live)
L-EH Voltage output (L), maximum 30A
Stepping motor CN1-4
Cold water free contact. AUX2
Voltage free contact. To ensure the sensitivity of the connection, please make sure Max wiring length < 30 m.
Hot water free contact. AUX1
Voltage free contact. To ensure the sensitivity of the connection, please make sure Max wiring length < 30 m.
In Modbus signal CN10
Output
Out Modbus signal CN11
Terminals for local network serial connection
2. CONTROL SYSTEM OPERATION 4-PIPES SYSTEM
System always with Motorized Valve
COOL MODE
1. MTV2, AUX1 and heater always off.
2. If Tr >= Ts+1ºC (or +4 ºC if economy contact is activated), cool operation is activated, MTV1 and AUX2 are turned on. Indoor fan runs at set speed.
3. If Tr < Ts, cool operation is terminated, MTV1 and AUX2 are turned off. Indoor fan runs at set speed.
4. The range of Ts is 16-30 ºC
5. Indoor fan speed can be adjusted for low, medium, high and auto.
6. When turned on, MTV1 requires 30 seconds before it is fully open.
7. When turned off, MTV1 requires 120 seconds before it is fully closed.
8. When the unit is turned off, indoor fan will delay for 5 seconds before it is turned off.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
1. If Ti1 ≦ 2 ºC for 2 minutes, MTV1 and AUX2 are turned off. If indoor fan is set for low speed, it will run at medium speed. If it is set at medium or high speed, it will keep running at the same speed.
2. If Ti1 ≧ 5ºC for 2 minutes, MTV1 and AUX2 are turned on. Indoor fun runs at set speed.
FAN MODE
1. Indoor fan runs at the set speed while heater, MTV1, MTV2, AUX1 and AUX2 are turned off.
2. Indoor fan speed can be adjusted for low, medium and high.
Page 52
HYDRONIC CASSETTE 52
HEAT MODE i. HEAT MODE--- WITHOUT ELECTRICAL HEATER
1. MTV1, AUX2 and heater always off.
2. If Tr <= Ts1 ºC (or -4 ºC if economy contact is activated), heat operation is activated, MTV2 and
AUX1 are turned on. Indoor fan runs at the set speed.
3. If Tr >Ts, heat operation is terminated, MTV2 and AUX1 are turned off. Indoor fan repeatedly runs at
low fan speed for 30 seconds and stops for 3 minutes.
4. The range of Ts is 16~30 ºC
5. Indoor fan speed can be adjusted for low, medium, high and auto.
6. MTV2 will delay for 30 seconds before it is turned on.
7. MTV2 will delay for 120 seconds before it is turned off.
ii. HEAT MODE---WITH ELECTRICAL HEATER AS BOOSTER
1. MTV1 and AUX2 are always off.
2. If Tr <= Ts1 ºC (or -4 ºC if economy contact is activated), heat operation is activated, MTV2 and
AUX1 are turned on. Indoor fan runs at the set speed.
3. If Tr >Ts, heat operation is terminated, MTV2 and AUX1 are turned off. Indoor fan repeatedly runs at
low fan speed for 30 seconds and stops for 3 minutes.
4. If Ti1<40 ºC, the electrical heater is turned on. If 40<= Ti1<45 ºC, the electrical heater is kept original
state. If Ti1>=45 ºC, the electrical heater is turned off.
5. The range of Ts is 16~30 ºC
6. Indoor fan speed can be adjusted for low, medium, high and auto.
7. MTV2 will delay for 30 seconds before it is turned on.
8. MTV2 will delay for 120 seconds before it is turned off.
iii. PRE-HEAT---WITHOUT ELECTRICAL HEATER
1. If Ti1<36 ºC [or 28C depends on DIP setting], when MTV2 and AUX1 are on, indoor fan remains off.
2. If Ti1>=38 ºC [or30C depends on DIP setting], when MTV2 and AUX1 are on, indoor fan runs at set
speed.
3. If indoor coil temperature sensor is damaged, pre-heat time is set for 2 minutes and indoor fan runs
at set speed.
iv. PRE-HEAT---WITH ELECTRICAL HEATER
1. MTV2 and AUX2 turn on.
2. Indoor fan will turn on after the electrical heater is turned on for 10 seconds.
v. POST-HEAT---WITHOUT ELECTRICAL HEATER
1. If Ti238ºC, when MTV2 and AUX 1 are off, indoor fan continues to run at set speed.
2. If 36 C <= Ti2< =38 C, when MTV2 and AUX1 are off. Indoor fan keeps original state.
3. If Ti2<36ºC, when MTV2 and AUX1 are off. Indoor fan runs 30 seconds and stop 3 minutes
repeatedly.
4. If indoor coil temperature coil is damaged, post-heat time is set for 3 minutes with indoor fan running
at set speed.
vi. POST-HEAT---WITH ELECTRICAL HEATER
1. Indoor fan will turn off after the unit off for 20 seconds.
vii. OVER HEAT PROTECTION OF INDOOR COIL
1. If Ti2 >= 75 ºC, MTV2 and AUX1 are turned off, indoor fan remains on and runs at high speed.
2. If Ti2<70 ºC, MTV2 and AUX1 are turned on, indoor fan remains on and runs at set speed.
3. If indoor coil temperature sensor is damaged, the protection mode will become obsolete and the unit
will work as the Pre-heat and Post-heat set times.
Page 53
HYDRONIC CASSETTE 53
DEHUMIDIFICATION MODE
1. MTV2, AUX1 and heater always off.
2. If Tr >= 25 ºC, MTV1 and AUX2 will be ON for 3 minutes, and OFF for 4 minutes.
3. If 16 ºC < =Tr < 25 ºC, MTV1 and AUX2 will be ON for 3 minutes, and OFF for 6 minutes.
4. If Tr <16 ºC, MTV1 and AUX2 will be turned off for 4 minutes.
At the end of the above dehumidification cycle, system will decide the next dehumidification control option. Indoor fan will run at low speed throughout the dehumidification process.
AUTOMODE
1. If current running mode is auto cool mode, it will change over to auto heat mode upon satisfy all the
conditions below:
Ts-Tr1.0°C(or -4 ºC if economy contact is activated) MTV1 has stop10 min.
2. If current running mode is auto heat mode, it will change over to auto cool mode upon satisfy all the
conditions below:
Tr-Ts1.0°C(or +4 ºC if economy contact is activated) MTV2 has stop10 min.
Note: Auto cool or auto heat operation are the same as cool or heat mode respectively.
SLEEP MODE
a) Sleep mode can only be set in cool or heat modes only. b) In cool mode, after sleep mode is set, the indoor fan will run at low speed and Ts will increase 2 ºC during 2 hours. c) In heat mode, after sleep mode is set, the indoor fan will run at set speed and Ts will decrease 2 ºC during 2 hours. d) Changing of operation mode will cancel sleep mode.
The cool mode sleep profile is:
The heat mode sleep profile is:
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts+0.5
Ts+1.0
Ts+2.0
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts-2.0
Ts-1.0
Ts-0.5
Page 54
HYDRONIC CASSETTE 54
AUTO FAN SPEED
In cool mode, the fan speed cannot change until it has run at this speed for more then 30 seconds. Fan speed is regulated according to the profile below.
In heat mode, the fan speed cannot change until it has run at this speed for more then 30 seconds.
SWING / LOUVER
For remote handset Whenever indoor fan is running, louver can swing or stop at the desired position. Louver angle: 0~100 º, opens clockwise with largest angle at 100 º. Swing angle: 35~100 º, opens clockwise to 68º. Below are the 4 fixed positions which can be set from wireless LCD handset.
Position Angle
1 35 º 2 57 º 3 83 º 4 100 º
For wired wall pad Louver angle: 0~100 º, opens clockwise, and with biggest angle at 100 º. Swing angle: 35~100 º, opens clockwise to 68º. User may stop louver at any desired poison between 35~100 º.
High
Tr
Lo
w
Lo
w
Medium
Ts
Ts-1C
Ts-2C
Ts-3C
Lo
w
Medium
High
High
Tr
Medium
Lo
w
Lo
w
Ts+3C
Ts+2C
Ts+1C
Ts
High
Medium
Lo
w
Page 55
HYDRONIC CASSETTE 55
BUZZER
If a command is received by the air conditioner, the master unit will respond with 2 beeps for each setting, and the slave unit will respond with 1 beep.
AUTO RESTART
The system uses non-volatile memory to save the present operation parameters when system is turned
off or in case of system failure or cessation of power supply. Operation parameters are mode, set
temperature, swing louver’s position, and the fan speed. When power supply resumes or the system is
switched on again, the same operations as previously set will function.
OPERATION OF CONTROL PANEL ON HIGH WALL UNIT ON/OFF SWITCH
i. This is a tact switch to select Cool→Heat→Off operation mode.
ii. In cool mode, the set temperature of the system is 24ºC with auto fan speed and swing. There are
no timer and sleep modes.
iii. In heat mode, the set temperature of the system is 24ºC with auto fan speed and swing. There are
no timer and sleep modes.
iv. Master unit that does not use LCD wall pad will globally broadcast.
v. Master unit that does not use LCD wall pad will globally broadcast.
Note: When button pressing is effective, master unit buzzer will beep twice and slave unit beeps once.
DRAIN PUMP
Drain pump turns on if thermostat cut in during cooling or dehumidification cooling cycle. It will remain on for at least 5 minutes after thermostat cut out. During mode change from cooling to non cooling mode, water pump will on for minimum 5 minutes.
Warning! If turn off the system by circuit breaker (or main power supply) the drain pump does not work after turn off.
FLOAT SWITCH Float-switch open before turning on.
If float switch (N/C) is opened before the unit is turned on. MTV1 is off. Drain pump and indoor fan will operate. After float switch is closed, MTV1 is on.
Float switch is opened, when unit is on.
If float switch is opened continuously 5sec, drain pump will work and MTV1 cut off. When the float switch is closed, the drain pump will run for additional 5 minutes. If the float switch is opened for 10
minutes continuously, MTV1 will remain off. Indoor fan runs at set speed and system report error.
Float switch is opened, when unit is off.
If the float switch is opened, the drain pump will work. When the float switch is closed, the drain pump will
run for additional 5 minutes. If the float switch is opened for 10 minutes continuously, system report error.
ELECTRIC HEATER SAFETY SWITCH
Before the electrical heater is turned on, the EH safety switch must be closed. If this contact is opened continuously 1sec, heater must be cut off immediately and report error. Once the contact is returned to close position 60sec, reset the error and heater is allowed to cut in again. Should EH safety switch be opened 3 times within 60 minutes, heater is not allowed to cut in anymore. Turn off the unit to reset the fault provided that the switch has returned to close position.
Page 56
HYDRONIC CASSETTE 56
ERROR DESCRIPTION
LED lights Indication - with Master-Slave Connection
For unit with handset only Error message can be found in LED lights on unit body. Table below indicate the error code for master and all slave unit.
For all units (both master and slave) High speed Red LED On For master unit indicating defect status of all slave unit Unit 2 failure Blink 2 times, stop 3 sec Unit 3 failure Blink 3 times, stop 3 sec Unit 4 failure Blink 4 times, stop 3 sec Unit 5 failure Blink 5 times, stop 3 sec Unit 6 failure Blink 6 times, stop 3 sec Unit 7 failure Blink 7 times, stop 3 sec Unit 8 failure Blink 8 times, stop 3 sec Unit 9 failure Blink 9 times, stop 3 sec Unit 10 failure Blink 10 times, stop 3 sec Unit 11 failure Blink 11 times, stop 3 sec Unit 12 failure Blink 12 times, stop 3 sec Unit 13 failure Blink 13 times, stop 3 sec Unit 14 failure Blink 14 times, stop 3 sec Unit 15 failure Blink 15 times, stop 3 sec Unit 16 failure Blink 16 times, stop 3 sec Unit 17 failure Blink 17 times, stop 3 sec Unit 18 failure Blink 18 times, stop 3 sec Unit 19 failure Blink 19 times, stop 3 sec Unit 20 failure Blink 20 times, stop 3 sec Unit 21 failure Blink 21 times, stop 3 sec Unit 22 failure Blink 22 times, stop 3 sec Unit 23 failure Blink 23 times, stop 3 sec Unit 24 failure Blink 24 times, stop 3 sec Unit 25 failure Blink 25 times, stop 3 sec Unit 26 failure Blink 26 times, stop 3 sec Unit 27 failure Blink 27 times, stop 3 sec Unit 28 failure Blink 28 times, stop 3 sec Unit 29 failure Blink 29 times, stop 3 sec Unit 30 failure Blink 30 times, stop 3 sec Unit 31 failure Blink 31 times, stop 3 sec Unit 32 failure Blink 32 times, stop 3 sec
For all units Yellow light
Medial speed Yellow Led on
For all units Green LED light Low speed Green LED ON Electrical heater failure Blink 1times, stop 3 sec Indoor coil sensor 2 failure Blink 2 times, stop 3 sec Return air sensor failure Blink 3 times, stop 3 sec Indoor coil sensor 1 failure Blink 4 times, stop 3 sec Indoor coil low temperature protection Blink 5 times, stop 3 sec Indoor coil over heat protection Blink 6 times, stop 3 sec Water pump failure Blink 7 times, stop 3 sec
Table 1
Page 57
HYDRONIC CASSETTE 57
For unit with wall pad only Error message can be found in both LED lights on unit body (please refer to table 1) and wall pad error indication. (Please refer to page 49 Error Indication)
Note: If the address of slave unit is not set (refer to appendix I) LED lights and Wall pad of the master unit will not show the status of the defective slave unit.
Without Master-Slave connection
For unit with handset only
For all units Red LED light on the unit High speed Red LED On Medial speed Yellow LED On Low speed Green LED On
For all units Green LED light on the unit Electrical heater failure Blink 1times, stop 3 sec Return air sensor failure Blink 3 times, stop 3 sec Indoor coil sensor 1 failure Blink 4 times, stop 3 sec Indoor coil low temperature protection Blink 5 times, stop 3 sec Indoor coil over heat protection Blink 6 times, stop 3 sec
For unit with wall pad only Error message can be found in both LED lights on the unit body (please refer to table 2) and on the wall pad error indication. (Please refer to page 49 Error Indication)
Table 2
Page 58
HYDRONIC CASSETTE 58
SENSOR RESISTANCE R-T CONVERSION TABLE
R25: 10KΩ±1% B25/85: 3977±1%
T Rmin Rnom Rmax T Rmin Rnom Rmax
()
(K) (K) (K)
()
(K) (K) (K)
-30 174 182.7 191.8 4 26.11 26.9 27.71
-29 163.4 171.5 179.9 5 24.85 25.59 26.34
-28 153.6 161.1 168.9 6 23.65 24.35 25.05
-27 144.4 151.3 158.5 7 22.52 23.17 23.83
-26 135.8 142.2 148.9 8 21.45 22.06 22.68
-25 127.8 133.8 140 9 20.44 21.01 21.59
-24 120.3 125.8 131.6 10 19.48 20.02 20.55
-23 113.3 118.4 123.8 11 18.58 19.7 19.58
-22 106.7 111.5 116.5 12 17.71 18.18 18.65
-21 100.6 105.1 109.7 13 16.9 17.33 17.77
-20 94.9 99.03 103.3 14 16.12 16.53 16.94
-19 89.51 93.39 97.41 15 15.39 15.77 16.16
-18 84.5 88.11 91.85 16 14.69 15.05 15.41
-17 79.8 83.17 86.64 17 14.03 14.37 14.7
-16 75.39 78.53 81.76 18 13.41 13.72 14.03
-15 71.26 74.18 77.19 19 12.81 13.1 13.4
-14 67.37 70.1 72.9 20 12.24 12.52 12.79
-13 63.73 66.26 68.88 21 11.7 11.96 12.22
-12 60.3 62.67 65.1 22 11.19 11.43 11.67
-11 57.08 59.28 61.55 23 10.71 10.93 11.15
-10 54.05 56.1 58.22 24 10.24 10.45 10.66
-9 51.19 53.12 55.08 25 9.8 10 10.2
-8 48.51 50.3 52.14 26 9.374 9.57 9.765
-7 45.98 47.66 49.37 27 8.969 9.16 9.351
-6 43.61 45.17 46.77 28 8.584 8.77 8.957
-5 41.36 42.82 44.31 29 8.218 8.4 8.582
-4 39.25 40.61 42 30 7.869 8.047 8.225
-3 37.26 38.53 39.83 31 7.537 7.71 7.885
-2 35.38 36.56 37.78 32 7.221 7.39 7.56
-1 33.6 34.71 35.85 33 6.92 7.085 7.251 0 31.93 32.97 3402 34 6.633 6.794 6.956 1 30.35 31.32 32.3 35 6.36 6.517 6.675 2 28.85 29.76 30.68 36 6.099 6.252 6.407 3 27.44 28.29 29.15 37 5.85 6 6.151
Page 59
HYDRONIC CASSETTE 59
R25: 10KΩ±1%
B25/85: 3977±1%
T Rmin Rnom Rmax T Rmin Rnom Rmax
()
(K) (K) (K)
()
(K) (K) (K)
38 5.614 5.759 5.907 75 1.417 1.474 1.532 39 5.387 5.53 5.673 76 1.37 1.426 1.482 40 5.172 5.31 5.451 77 1.326 1.379 1.434 41 4.966 5.101 5.238 78 1.282 1.335 1.389 42 4.769 4.901 5.034 79 1.241 1.292 1.344 43 4.582 4.71 4.84 80 1.201 1.25 1.302 44 4.402 4.527 4.654 81 1.162 1.211 1.261 45 4.231 4.353 4.477 82 1.125 1.172 1.221 46 4.067 4.186 4.307 83 1.089 1.135 1.183 47 3.911 4.027 4.144 84 1.055 1.1 1.146 48 3.761 3.874 3.989 85 1.021 1.065 1.111 49 3.618 3.728 3.84 86 0.9891 1.032 1.077 50 3.481 3.588 3.697 87 0.9582 1 1.044 51 3.35 3.454 3.561 88 0.9284 0.9697 1.012 52 3.225 3.326 3.43 89 0.8998 0.9401 0.9818 53 3.105 3.204 3.305 90 0.8721 0.9115 0.9522 54 2.99 3.086 3.185 91 0.8455 0.8839 0.9237 55 2.88 2.974 3.07 92 0.8198 0.8573 0.8961 56 2.774 2.866 2.959 93 0.795 0.8316 0.8696 57 2.673 2.762 2.854 94 0.7711 0.8069 0.8439 58 2.576 2.663 2.752 95 0.748 0.783 0.8192 59 2.483 2.568 2.655 96 0.7258 0.7599 0.7953 60 2.394 2.477 2.562 97 0.7043 0.7376 0.7722 61 2.309 2.39 2.472 98 0.6836 0.7161 0.7499 62 2.227 2.306 2.386 99 0.6635 0.6953 0.7283 63 2.149 2.225 2.304 100 0.6442 0.6752 0.7075 64 2.073 2.148 2.224 101 0.6255 0.6558 0.6874 65 2.001 2.074 2.148 102 0.6075 0.6371 0.6679 66 1.931 2.002 2.075 103 0.59 0.619 0.6491 67 1.865 1.934 2.005 104 0.5732 0.6015 0.631 68 1.801 1.868 1.937 105 0.5569 0.5846 0.6134 69 1.739 1.805 1.872 70 1.68 1.744 1.81 71 1.623 1.686 1.75 72 1.569 1.63 1.692 73 1.516 1.576 1.637 74 1.466 1.524 1.583
Page 60
HYDRONIC CASSETTE 60
CONTROL AND POWER SUPPLY WIRING DIAGRAMS
Page 61
HYDRONIC CASSETTE 61
MASTER-SLAVE CONTROL WIRING DIAGRAM
Page 62
HYDRONIC CASSETTE 62
MALFUNCTION CAUSE REMEDY
The fan coil does not start up
No voltage
Mains switch in the “OFF
Faulty room control
Faulty fan
- Check for presence of voltage
- Place in the “ON” position
- Check the room control
- Check fan motor
Filter clogged
Air flow obstructed
Room control regulation
Incorrect water temperature
Air present
Insufficient output
- Clean the filter
- Remove obstacles
- Check
- Check
- Vent
Contact between metal parts
Loose screws
Noise and vibrations
- Check
- Tighten screws
Page 63
HYDRONIC CASSETTE 63
Appendix I
MASTER AND SLAVE UNIT FUNCTION
The control PCB can be set either as a master unit or slave unit.
2.A.1 MASTER UNIT FUNCTION
a) The master unit sends data on its setting to the slave unit.
b) The master unit settings are Unit ON/OFF, Mode, Fan Speed, Set Temperature, Swing Function, and Sleep Function for handset operation.
c) The master unit settings are Unit ON/OFF, Mode, Fan Speed, Set Temperature, Swing Function, Sleep Function and Weekly Timer ON/OFF program for wall pad operation.
2.A.2 SLAVE UNIT FUNCTION
a) The slave unit receives data on its settings from the master unit.
b) The slave unit is allowed to change to a locally desired setting by local controller as long as there are no subsequent changes to the settings of the master unit. c) The slave units can be set individually for timer on and off function by handset or wall pad. The handset cannot override wall pad timer and clock setting.
When unit is power on, buzzer responds as below:
With MTV: The master unit will beep 3 times, and the slave unit will beep once. Without MTV: The master unit will beep 4 times, and the slave unit will beep twice
2.A.3 MASTER – SLAVE INSTALLATION
HANDSET AS MASTER CONTROL UNIT:
a) Connect all the units PCBs according to the wire color and type of connector. b) Select the master unit by closing the SW6 DIP switch on the main PCB c) Ensure the SW6 DIP switch in the PCB of the slave unit is opened. d) Switch on the units by connecting the main power supply. e) Using handset set the operation parameters for the Master unit which will automatically send the settings to the slave unit. f) Master unit will beep twice confirming receipt of commands while Slave unit will beep once.
WALLPAD AS MASTER CONTROL UNIT:
a) Connect all the units PCBs according to the wire color and type of connector. b) Select the master unit by closing the SW6 DIP switch on the main PCB c) Ensure the SW6 DIP switch in the PCB of the slave unit is opened. d) Provide each slave unit an addressable code by closing SW1 – SW5 DIP switch according to the DIP switch chart. e) Switch on the units by connecting the main power supply. f) Using the wall pad set the operation parameters for the Master unit which will send the setting to the slave units based on Global-control communication or Addressable communication methods. For detail
please see 2.A.6 MASTER-SLAVE COMMUNICATION METHOD & Wall pad operation item 11 Networking Master – Slave control on page 49.
g) Master unit will beep twice confirming receipt of commands while Slave unit will beep once.
Page 64
HYDRONIC CASSETTE 64
2.A.4 MASTER-SLAVE CONFIGURATION
Master unit: close SW6 [DIP switch] before power on. Master will beep twice to the LCD wireless handset or LCD wall pad confirming receipt of commands. Each master can command up to 31 slave units. Slave unit: open SW6 [DIP switch] before power on. Slave unit will beep once to the LCD wireless handset or LCD wall pad confirming receipt of commands.
Important note: Data loggers are not applicable to Master-Slave System.
2.A.5 MASTER-SLAVE CONTROL
Above control PCB can receive data from both wireless LCD handset and wired wall pad. Once wall pad is connected to the PCB, receiver from the unit will stop receiving signal from wireless LCD handset. LCD handset can only provide signal to Wall Pad receiver. When wall pad is disconnected from the PCB for 5 seconds, it will revert to wireless LCD handset reception automatically.
2.A.6 MASTER-SLAVE COMMUNICATION METHOD
There are two modes for Master-slave structure.
Global Control communication Master will broadcast the settings to all slave units. During normal operation, slave units can receive commands from its wireless handset and wall pad control panel. Upon reception of master global commands, all slave unit settings will be replaced by the master settings.
Addressable communication Master controller must be LCD wall pad. Slave unit parameters are set as usual. Upon receiving the control commands from a master, the addressed slave unit settings will be replaced by the master settings.
If master unit is equipped with wireless LCD handset only, it can only use Global-Control communication method. If it is equipped with LCD wall pad, it can use both communication methods.
DIP1 used for master slave address setting. DIP switch address setting: 1 for ON, 0 for OFF.
SW6 SW5 SW4 SW3 SW2 SW1 Unit No. Remark 1 0 0 0 0 0 01 Master 0 0 0 0 0 0 01 Slave
- 0 0 0 0 1 02 Slave
- 0 0 0 1 0 03 Slave
- 0 0 0 1 1 04 Slave
- 0 0 1 0 0 05 Slave
- 0 0 1 0 1 06 Slave
- 0 0 1 1 0 07 Slave
- 0 0 1 1 1 08 Slave
- 0 1 0 0 0 09 Slave
- 0 1 0 0 1 10 Slave
- 0 1 0 1 0 11 Slave
- 0 1 0 1 1 12 Slave
- 0 1 1 0 0 13 Slave
- 0 1 1 0 1 14 Slave
- 0 1 1 1 0 15 Slave
- 0 1 1 1 1 16 Slave
- 1 0 0 0 0 17 Slave
Page 65
HYDRONIC CASSETTE 65
- 1 0 0 0 1 18 Slave
- 1 0 0 1 0 19 Slave
- 1 0 0 1 1 20 Slave
- 1 0 1 0 0 21 Slave
- 1 0 1 0 1 22 Slave
- 1 0 1 1 0 23 Slave
- 1 0 1 1 1 24 Slave
- 1 1 0 0 0 25 Slave
- 1 1 0 0 1 26 Slave
- 1 1 0 1 0 27 Slave
- 1 1 0 1 1 28 Slave
- 1 1 1 0 0 29 Slave
- 1 1 1 0 1 30 Slave
- 1 1 1 1 0 31 Slave
- 1 1 1 1 1 32 Slave
Page 66