Faber TEND30BSV, TEND36SSV, TEND30SSV INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

0 (0)

TENDER

Installation Instructions

Use and Care Information

Instructions d'installation

Utilisez et d'entretien

Instrucciones de instalación Información de uso y cuidado

TEND30SSV

TEND36SSV

TEND30BSV

TEND36BSV

READ AND SAVE THESE INSTRUCTIONS BEFORE YOU START

INSTALLING THIS RANGEHOOD

WARNING: - TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:

a)Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium setting.

b)Always turn hood ON when cooking at high heat or when flambeing food (i.e. Crepes

Suzette, Cherries Jubilee, Peppercorn Beef Flambé).

c)Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.

d)Useproperpansize. Alwaysusecookwareappropriateforthesizeofthesurfaceelement.

WARNING: - TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING*:

a)SMOTHERFLAMESwithaclose-fittinglid,cookiesheet,ormetaltray,thenturnofftheburner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately EVACUATE

AND CALL THE FIRE DEPARTMENT.

b)NEVER PICK UP A FLAMING PAN - You may be burned.

c)DO NOT USE WATER, including wet dishcloths or towels - a violent steam explosion will result.

d)Use an extinguisher ONLY if:

1.You know you have a Class ABC extinguisher, and you already know how to operate it.

2.Thefireissmallandcontainedintheareawhereitstarted.

3.Thefiredepartmentisbeingcalled.

4.Youcanfightthefirewithyourbacktoanexit.

* Based on "Kitchen Firesafety Tips" published by NFPA

WARNING - TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, do not use this fan with any solid-state speed control device.

WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1.Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.

2.Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.

CAUTION: For General Ventilating Use Only. Do Not Use To Exhaust Hazardous or Explosive Materials and Vapors.

WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1.InstallationWorkAndElectricalWiringMustBeDoneByQualifiedPerson(s)InAccordance With All Applicable Codes And Standards, Including Fire-Rated Construction.

2.Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer's guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.

2

3.When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

4.Ducted fans must always be vented to the outdoors.

ALL WALL AND FLOOR OPENINGS WHERE THE RANGEHOOD IS INSTALLED MUST

BE SEALED.

This rangehood requires at least 24" of clearance between the bottom of the rangehood and the cooking surface or countertop. This hood has been approved by UL at this distance from the cooktop.

This minimum clearance may be higher depending on local building codes. For gas cooktops and combination ranges, a minimum of 30" is recommended and may be required.

Overhead cabinets on both sides of this unit must be a minimum of 18" above the cooking surface or countertop. Consult the cooktop or range installation instructions given by the manufacturer before making any cutouts.

MOBILEHOMEINSTALLATIONTheinstallationofthisrangehoodmustconformtotheManufactured Home Construction and Safety Standards, Title 24 CFR, Part 3280 (formerly Federal Standard for Mobile Home Construction and Safety, Title 24, HUD, Part 280). See Electrical Requirements.

VENTING REQUIREMENTS

Determine which venting method is best for your application. Ductwork can extend either through the wall or the roof.

Thelengthoftheductworkandthenumberofelbowsshouldbekepttoaminimumtoprovideefficient performance. The size of the ductwork should be uniform. Do not install two elbows together. Use duct tape to seal all joints in the ductwork system. Use caulking to seal exterior wall or floor opening around the cap.

Flexible ductwork is not recommended. Flexible ductwork creates back pressure and air turbulence that greatly reduces performance.

Make sure there is proper clearance within the wall or floor for exhaust duct before making cutouts.

Do not cut a joist or stud unless absolutely necessary. If a joist or stud must be cut, then a supporting frame must be constructed.

WARNING - To Reduce The Risk Of Fire, Use Only Metal Ductwork.

CAUTION-Toreduceriskoffireandtoproperlyexhaustair,besuretoductairoutside–Do notventexhaustairintospaceswithinwallsorceilingsorintoattics,crawlspaces,orgarages.

! WARNING

Venting system MUST terminate outside the home.

DO NOT terminate the ductwork in an attic or other enclosed space.

DO NOT use 4" laundry-type wall caps.

Flexible-type ductwork is not recommended.

DO NOT obstruct the flow of combustion and ventilation air.

Failure to follow venting requirements may result in a fire.

3

! WARNING

Electrical ground is required on this rangehood.

If cold water pipe is interrupted by plastic, nonmetallic gaskets or other materials, DO NOT use for grounding.

DO NOT ground to a gas pipe.

DO NOT have a fuse in the neutral or grounding circuit. A fuse in the neutral or grounding circuit could result in electrical shock.

Check with a qualified electrician if you are in doubt as to whether the rangehood is properly grounded.

Failure to follow electrical requirements may result in a fire.

State of California Proposition 65 Warning (US only)

WARNING

This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.

For more information go to www.P65Warnings.ca.gov

4

RANGEHOOD DIMENSIONS

Min. 28 3/4

 

 

 

 

Min. 28 3/4

Max. 43 5/16

22 1/16

 

 

 

Max. 43 5/16

9 7/16

 

 

13/16

 

 

 

 

 

 

 

 

 

 

 

8

1/4

8

 

 

 

7/

 

 

 

 

 

5

 

 

3 15/16

 

 

 

 

 

9 ”

 

 

 

 

 

 

 

 

 

14 13/16

18 17/8” - 19 5/8

 

 

 

 

 

 

29 15/16”

- 35 11/16”

 

 

 

 

 

Min. 24"

Min. 30''

 

 

 

 

 

5

MAIN PARTS

 

 

Components

Ref.

Qty.

Product Components

1

1

Hood Body, complete with: Con-

 

 

trols, Light, Filters, Blower.

2

1

Telescopic Chimney comprising:

2.1

1

Upper Section

2.2

1

Lower Section

10

1

Damper ø 5 7/8"

Ref.

Qty.

Installation Components

7.1

2

Hood Body Fixing Brackets

7.2.1

2

Upper Chimney Section Fixing

 

 

Bracket

12a

8

Screws 3/16" x 1 3/4"

12c

6

Screws 1/8" x 3/8"

12d

2

Screws 3/16" x 1"

 

Qty.

Documentation

 

1

Instruction Manual

 

7.3

11

15

12a

7.2.1

 

 

 

 

12e

 

 

7.2.1

 

 

12c

 

2.1

 

 

2

12c

 

 

 

2.2

 

10

 

 

 

 

12c

 

 

12a

 

1

7.1

 

 

12d

Parts needed

- 6" Round Metal ductwork .

Available Accessories

Direct Connect Wiring Box sku # WIREBOX

Activated Charcoal Filter sku # FILTER1

Long Lasting Activated Charcoal Filter sku # FILTER1LL High Ceiling Kit - One Flue -Upper to 11ft. - sku# HIGHTNDR

Ductless Kit - Includes Ductless Diverter, Two Charcoal Filters - sku# DUCTCLPL Wireless Remote Control-REMCTRL2

6

Only for Ducted Venting Installation

Install Damper that is included with the Hood

1

7.

before connecting to the ductwork.

 

12

 

Choose your ducting method

Ducted Venting Installation

Non Ducted - Recirculation

Vertical

6"

 

 

 

Horizontal

Requires

purchase of

 

 

Activated

 

Charcoal

 

Accessory

7

Installation Instructions

1

Draw a vertical line on the supporting wall as high as practical, at the center of the area in which the hood will be installed.

Draw a horizontal line at where the bottom edge of the hood will be located as indicated in the figure that is a minimum of 24" - 30" above cooking surface.

2

 

> ´

 

 

 

 

 

 

 

x8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

´

 

 

x8

<![if ! IE]>

<![endif]>´

 

<![if ! IE]>

<![endif]>´

Place a Upper bracket 7.2.1 on the wall as shown about 1 1/8" from the ceiling or upper limit, aligning the centers(notch) with the vertical reference line and mark the wall at the centers of the holes in the bracket.

Place the other bracket 7.2.1 on the wall as shown, below the first bracket, at the height of the upper chimney section supplied and aligning the centers(notch) with the vertical line.

Mark the wall at the centers of the holes in the bracket.

Place bracket 7.1 as shown 4” 5/16 from the vertical reference line and 7” 1/2 above the horizontal reference line.

Mark the centres of the holes in the bracket and repeat this operation on the other side. Drill ø 5/16" holes at all the centers points marked (point 1,2,3,4,5,6,7,8) as shown.

Fix the 2 brackets 7.2.1 using the 12a screws supplied with wall plugs (purchase separately).

8

3

Installationscrewsprovidedmustbesecured with wall plugs (purchase separately).

4

12a

Fix the brackets 7.1 using the 12a screws supplied in the hood body fixing holes as shown.

5

12.d

7.1

Screw the two screws 12d supplied onto the brackets 7.1.

Hook the hood body onto the bracket 7.1, centering it around the vertical line.

Use the adjusting screws 12d underneath the hood to level the hood body.

6

x2

Ø 85/16"mm

x2

x2

From inside the Hood body, mark the security hole, drill ø 5/16" where marked, insert 2 wall plugs in the holes and fix with 2 screws 12a.

9

7

Vertical or Horizontal

Ducting Installation

Install Roof or Wall Cap purchased separately. Connect the 6" metal ductwork to the Roof or Wall Cap and then attach ductwork.

9

12aL = 4x

Fix the bracket 7.2.1 using the screws 12a supplied.

8 Non-Ducted Recirculation Option

Only for the recirculation

 

version, put connection in

 

to the hood body air outlet.

 

Ensure that the activated

 

charcoal filters have been

15

inserted.

10

Slightly widen the two sides

of the upper 2.1 chimney and

hook them behind the brackets 7.2.1, making sure that they are

well seated.

11

12bN = 4x

Secure the sides to the brackets by using the 4 screws 12b.

12

Slightly widen

2.1

the two sides of

 

the lower section

 

and hook them

 

between

2.2

the upper section

and the wall, making sure that they are properly housed.

10

13

ELECTRICAL INSTALLATION WITH CONNECTION

CABLE

GROUNDING INSTRUCTIONS This appliance must be grounded. In the event of an electrical short circuit, grounding reduces the risk of electric shock by providing an escape wire for the electric current. This appliance is equipped with a cord having a grounding wire with a grounding plug. The plug must be plugged into an outlet that is properly installed and grounded.

WARNING - Improper grounding can result in a risk of electric shock.

Consultaqualifiedelectricianifthegroundinginstructions are not completely understood, or if doubt exists as to whether the appliance is properly grounded.

Do not use an extension cord. If the power supply cord is too short, have a qualified electrician install an outlet near the appliance.

Max. 33 7/16

ELECTRICAL INSTALLATION WITH

OPTIONALWIRING BOX

For Permanent wiring Installation-Use only with Listed rangehood Wiring Box kit

sku # WIREBOX, manufactured by Faber.

Direct Connect Wiring Box Accessory sku # WIREBOX (purchased separately)

14 For Non-Ducted Recirculation

 

 

Option

 

1

7.

Attach each

 

12

charcoal

 

 

filter to the

 

 

black grid on

 

 

each side of

 

 

the blower.

 

 

Press the

 

 

charcoal

1

 

filter tightly

 

 

2

to the black

 

 

grid on the blower side and rotate the filter clockwise (towards the front of the hood) until it locks into place. Turn counterclockwise (towards the back of the hood) to remove.

Required Activated Charcoal Filter Accessory - sku # - FILTER1

Long Lasting Activated Charcoal Filter Accessory - sku # FILTER1LL (purchased separately)

15

1

7.

12

Replace the grease filters removed previously.

11

USE AND CARE INFORMATION

For Best Results

Start the rangehood several minutes before cooking to develop proper airflow. Allow the rangehood to operate for several minutes after cooking is complete to clear all smoke and odors from the kitchen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

T2

T3

T4

L

T1. Fan off button:turn the blower Off. The fan can be operated by pressing any of the fan setting buttons. Hold down this button for 2 seconds to activate Delay off function which will keep the fan on for 15 minutes and automatically shut off.

T2. Fan settings buttons: Low speed.

T3. Fan settings buttons: Medium speed.

T4. Fan settings buttons: High speed / Intensive speed.

Hold down the button for 2 seconds to activate the intensive speed, which is timed to run for 6 minutes. At the end of this time it will automatically return to the speed set before.Suitable to deal with maximum levels of cooking fumes.

L. Light button: On/Off switch for the lights.

NOTE: If your product has had a CFM adjustment, refer to the CFM adjustment manual for the information. Some motor speeds or functions may be reduced.

12

Cleaning metal grease filters

The filters must be cleaned every 2 months of operation,

 

 

or more frequently for particularly heavy usage, and can

 

 

be washed in a dishwasher.

 

 

• Remove the Filters one at a time, pushing them

1

7.

towards the back of the unit and at the same time

 

 

pulling downward.

12

 

Wash the Filters without bending them, and leave them to dry completely before replacing. (If the surface of the filter changes colour as time goes by, this will have absolutely no effect on the efficiency of the filter itself.)

• Replace, taking care to ensure that the handle faces forwards.

No water can be present in filters before installing back in hood.

 

1

7.

Replacing Activated Charcoal Filter

 

12

Thefilterisnotwashableandcannotberegenerated,andmust

 

 

bereplacedapproximatelyevery4monthsofoperation,ormore

 

 

frequently for particularly heavy usage.

 

 

• Remove the Filters one at a time, pushing them towards

 

 

the back of the unit and at the same time pulling downward.

 

 

• Remove the saturated charcoal filter by releasing the fixing

 

 

hooks.

 

 

• Fit the new filter and fasten it in its correct position.

 

 

• Replace,takingcaretoensurethatthehandlefacesforwards.

 

 

CAUTION: When used in recirculation mode, to Reduce

1

 

the Risk of Fire and Shock use only conversion kit Model

 

2

FILTER 1 or FILTER1LL.

 

 

 

LED LIGHTING UNIT

LED lights must be replaced by Faber factory authorized service.

13

Faber TEND30BSV, TEND36SSV, TEND30SSV INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

Wiring Diagram

<![if ! IE]>

<![endif]>120V

<![if ! IE]>

<![endif]>60Hz

14

Loading...
+ 30 hidden pages