Endress+Hauser iTEMP TMT82 Operating Instructions Manual

Operating Instructions
iTEMP® TMT82
Dual-input temperature transmitter
BA01028T/09/EN/14.12 71198558
Valid as of version
Brief overview
For quick and straightforward commissioning:
iTEMP® TMT82
Safety instructions
t
Installation instructions
t
Wiring
t
Display and operating elements
t
Commissioning
Commissioning using the HART® communication interface - Quick start for device
configuration for standard operation
Customer-specific configuration
Complex measurement tasks require the configuration of additional functions, which the
user can select, set and adapt to his/her process conditions by setting the appropriate device
parameters. A detailed description of all functions and device parameters.
(® ä 6)
(® ä 10)
(® ä 15)
(® ä 20)
(® ä 30)
(® ä 51)
2 Endress+Hauser
iTEMP® TMT82

Table of contents

Table of contents
1 Important document information ..... 4
About this document ..................... 4
1.1
1.2 Document conventions .................... 4
2 Basic safety instructions .............. 6
2.1 Requirements for the personnel .............. 6
2.2 Designated use .......................... 6
2.3 Operational safety ........................ 6
3 Identification ....................... 7
3.1 Device designation ....................... 7
3.2 Scope of delivery ........................ 8
3.3 Certificates and approvals .................. 8
4 Installation instructions ............. 10
4.1 Incoming acceptance, transport, storage ........ 10
4.2 Installation conditions .................... 10
4.3 Installation instructions ................... 10
4.4 Post-installation check .................... 14
5 Wiring ............................ 15
5.1 Quick wiring guide ...................... 15
5.2 Connecting the sensor cables ............... 16
5.3 Connecting the power supply and signal cables .. 17
5.4 Shielding and grounding .................. 18
5.5 Post-connection check ................... 19
10.2 Communication-specific accessories .......... 31
10.3
System components and data manager ......... 32
11 Diagnostics and troubleshooting ..... 33
11.1 Troubleshooting ........................ 33
11.2 Diagnostics events ...................... 35
11.3 Spare parts ............................ 38
11.4 Return .............................. 38
11.5 Disposal ............................. 38
11.6 Software history and overview of compatibility ... 39
12 Technical data ..................... 40
13 Operating menu and parameter
description ........................ 51
13.1 "Display/operation" menu ................. 57
13.2 "Setup" menu .......................... 61
13.3 "Diagnostics" menu ...................... 72
13.4 "Expert" menu ......................... 80
Index .................................. 96
6 Operating options .................. 20
6.1 Overview of operation options .............. 20
6.2 Structure and function of the operating menu .... 21
6.3 Measured value display and operating elements .. 23
6.4 Access to the operating menu via the operating
tool ................................ 25
7
Integrating the transmitter via HART
®
protocol ........................... 28
7.1 HART device variables and measured values ..... 28
7.2 Device variables and measured values ......... 29
8 Commissioning .................... 30
8.1 Function check ........................ 30
8.2 Switching on the transmitter ............... 30
8.3 Enabling configuration .................... 30
9 Maintenance ...................... 30
10 Accessories ........................ 30
10.1 Optional accessories ..................... 31
Endress+Hauser 3
Important document information
DANGER
CAUTION
NOTICE
iTEMP® TMT82

1 Important document information

1.1

About this document

1.1.1 Document function

These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.

1.1.2 Additional standard documentation on the device

Document Purpose and content of the document
Technical Information TI01010T/09/en
Brief Operating Instructions KA01095T/09/en
The document types listed are available:
On the CD supplied with the device
In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download
Planning aid for your device
The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
Guide that takes you quickly to the 1st measured value
The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning.

1.1.3 Safety Instructions (XA)

When using in hazardous areas, the national safety requirements must be met. Separate Ex documentation is contained in these Operating Instructions for measurement systems that are to mounted in hazardous areas. Strict compliance with the installation instructions, ratings and safety instructions as listed in this supplementary documentation is mandatory. Ensure you are using the correct Ex documentation for the relevant Ex-approved device. The number of the related Ex documentation (XA...) is indicated on the nameplate. You can use this Ex documentation if the two numbers (i.e. in the Ex documentation and on the nameplate) are identical.

1.2 Document conventions

1.2.1 Safety symbols

Symbol Meaning
DANGER!
A0011189-EN
A0011191-EN
A0011192-EN
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in personal injury.
4 Endress+Hauser
iTEMP® TMT82
)
*
-
.
Important document information

1.2.2 Electrical symbols

Symbol Meaning
Direct current
A terminal to which DC voltage is applied or through which direct current flows.
A0011197
Alternating current
A0011198
A terminal to which alternating voltage (sine-wave) is applied or through which alternating current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
A0011200
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0011199
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
A0011201
equalization line or a star grounding system depending on national or company codes of practice.

1.2.3 Symbols and notation for certain types of information

Symbol Meaning
Allowed
Indicates procedures, processes or actions that are allowed.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
1., 2., 3. Series of steps
Result of a sequence of actions
Ã

1.2.4 Symbols and notation in graphics

Symbol Meaning
1,2,3 ...
A, B, C, ...
A-A, B-B, C-C, ...
Endress+Hauser 5
Item numbers
Views
Sections
Hazardous area
Indicates a hazardous area.
A0011187
Safe area (non-hazardous area)
Indicates a non-hazardous area.
A0011188
Basic safety instructions
iTEMP® TMT82

2 Basic safety instructions

2.1

Requirements for the personnel

The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function and task
Are authorized by the plant owner/operator
Are familiar with federal/national regulations
Before beginning work, the specialist staff must have read and understood the instructions in the Operating Instructions and supplementary documentation as well as in the certificates (depending on the application)
Following instructions and basic conditions
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the facility's owner-operator
Following the instructions in these Operating Instructions

2.2 Designated use

The device is a universal and user-configurable temperature transmitter with either one or two sensor inputs for a resistance thermometer (RT), thermocouples (TC), resistance and voltage transmitters. The head transmitter version of the device is intended for mounting in a flat-face terminal head as per DIN EN 50446. It is also possible to mount the device on a DIN rail using the optional DIN rail clip. The device is also optionally available in a version suitable for DIN rail mounting as per IEC 60715 (TH35).
The manufacturer is not liable for damage caused by improper or non-designated use.

2.3 Operational safety

Operate the device in proper technical condition and fail-safe condition only.
The operator is responsible for interference-free operation of the device.
Hazardous area
To eliminate a danger for persons or for the facility when the device is used in the hazardous area (e.g. explosion protection or safety equipment):
Based on the technical data on the nameplate, check whether the ordered device is permitted for the intended use in the hazardous area. The nameplate can be found on the side of the transmitter housing.
Observe the specifications in the separate supplementary documentation that is an integral part of these Instructions.
Electromagnetic compatibility
The measuring system complies with the general safety requirements in accordance with EN 61010, the EMC requirements of IEC/EN 61326 and NAMUR Recommendation NE 21 and NE
89.
NOTICE
The unit must only be powered by a power supply that operates using an energy-limited electric circuit that is compliant with IEC 61010-1, "SELV or Class 2 circuit".
6 Endress+Hauser
iTEMP® TMT82
1
2
3
4
5
11-42V
012345678910
xx.yy
.zz
TMT82- XXXXX/XX
iTEMP
®
Made in Germany 2011 D-87484 Nesselwang
Ser
.no.:
FW:
Input:
12345678ABCDEFGH 12345678ABCDEFGH
Current consum.: 23,6 mA
Dev.Rev: 1
Ext. ord. cd.: XXXXXXXXXXXXX#
II3G Ex nA II T6/T5/T4 Ta= -40 ...+ 55/70/85°C II3G Ex nL IIC T6/T5/T4 Ta= -40 ... +55/70/85°C
EH 08.001X
Install per XA00102R/09/a3/xx.xx
6
0044
Identification

3 Identification

3.1

Device designation

The following options are available for identification of the device:
• Nameplate specifications
Enter the serial number from the nameplate in W@M Device Viewer (www.endress.com/ deviceviewer): All data relating to the device and an overview of the technical documentation supplied with the device are displayed.

3.1.1 Nameplate

The right device?
Compare and check the data on the nameplate of the device against the requirements of the measuring point:
A0014561
å 1
Nameplate of the head transmitter (example, Ex version)
1 Power supply, current consumption and extended order code 2 Serial number, device revision and firmware version 3 Approvals with symbols 4 2 lines for the TAG name 5 Approval in hazardous area with number of the relevant Ex documentation (XA...) 6 Order code and manufacturer ID
Endress+Hauser 7
Identification
1
2
3
4
5
6
0044
iTEMP®TMT82
Made in Germany 2012 D-87484 Nesselwang
TAGXXXXXXXXXXX
TAGXXXXXXXXXXX
FW: XX.XX.XX Dev. Rev.: X
Order code: TMT82-xxx/xx Ext. ord. cd.: XXXXXXXXXXX Ser
. no.: XXXXXXXXX Input: 12-42 V Current cunsum.: 23,0 mA
1
II3G Ex nAII T6/T5/T4 Ta= -40 ...+ 55/70/85°C II3G Ex nLIIC T6/T5/T4 Ta= -40 ... +55/70/85°C
EH 08.001X
Install per XA0xxxxT/09/a3/xx.xx
7
Nameplate of DIN rail transmitter (example, Ex version)
å 2
1 Product description and manufacturer ID 2 Order code, extended order code and serial number 3 Power supply and current consumption 4 Approval in hazardous area with number of the relevant Ex documentation (XA...) 5 Firmware version and device version 6 Approval logos 7 2 lines for the TAG name
iTEMP® TMT82
A0017924

3.2 Scope of delivery

The scope of delivery of the device comprises:
Temperature transmitter
• Mounting material (head transmitter)
• Hard copy of multi-language Brief Operating Instructions
• Operating Instructions and additional documentation on CD-ROM
Additional documentation for devices which are suitable for use in hazardous areas (0 such as Safety Instructions (XA), Control or Installation Drawings (ZD).
3.3

Certificates and approvals

The device left the factory in a safe operating condition. The device complies with the standards EN 61 010-1 "Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures" and with the EMC requirements of IEC/EN 61326.

3.3.1 CE mark, Declaration of Conformity

The device therefore meets the legal requirements of the EC guidelines. The manufacturer confirms that the device is compliant with the relevant guidelines by applying the CE mark.
3.3.2
The temperature transmitter is registered by HART® Communication. The device meets the requirements of the HART Communication Protocol Specifications, April 2001, Revision 6.0.

HART® protocol certification

1),

3.3.3 Registered trademarks

• HART
• iTEMP
®
Registered trademark of the HART® Communication Foundation
Registered trademark of Endress+Hauser Wetzer GmbH + Co. KG, Nesselwang, D
8 Endress+Hauser
®
iTEMP® TMT82
Identification
An overview of other approvals and certifications is provided in the "Technical data" section(® ä 50).
Endress+Hauser 9

Installation instructions

iTEMP® TMT82

4 Installation instructions

4.1

Incoming acceptance, transport, storage

4.1.1 Incoming acceptance

• Is the packaging or content damaged?
• Is the delivery complete? Compare the scope of delivery against the information on your order form.

4.1.2 Transport and storage

• Pack the device in such a way as to protect it reliably against impact for storage (and transportation). The original packaging provides optimum protection.
• Permitted storage temperature: – Head transmitter: –50 to +100 °C (–58 to +212 °F) – DIN rail transmitter: –40 to +100 °C (–40 to +212 °F)

4.2 Installation conditions

4.2.1 Dimensions

The dimensions of the device are provided in the "Technical data" section. (® ä 40).

4.2.2 Mounting location

• Head transmitter: – In the terminal head, flat face, as per DIN EN 50446, direct mounting on insert with cable
entry (middle hole 7 mm)
In the field housing, separated from the process(® ä 30)
• DIN rail transmitter: Designed for mounting on DIN rail (IEC 60715 TH35).
It is also possible to mount the device on a DIN rail as per IEC 60715 using the DIN rail clip accessory (® ä 30).
Information about the conditions (such as the ambient temperature, degree of protection, climate class etc.) that must be present at the installation point so that the device can be mounted
correctly, is provided in the "Technical data" section(® ä 40).
When using in hazardous areas, the limit values of the certificates and approvals must be observed (see Ex Safety Instructions).
4.3
A Phillips head screwdriver is required to mount the head transmitter.
NOTICE
Do not overtighten the mounting screws as this could damage the head transmitter.
Maximum torque = 1 Nm (¾ pound-feet).
Installation instructions
10 Endress+Hauser
iTEMP® TMT82
1
2
3
4
5
6
7
9
8
1 2 3 4 5
1
2
3 4
Item A
Item B
Item C
Installation instructions

4.3.1 Mounting the head transmitter

A0014269-EN
å 3
Head transmitter mounting (three versions)
Item A Mounting in a terminal head (terminal head flat face as per DIN 43729)
1 Terminal head
2 Circlips
3 Insert
4 Connection wires
5 Head transmitter
6 Mounting springs
7 Mounting screws
8 Terminal head cover
9 Cable entry
Procedure for mounting in a terminal head, pos. A:
1. Open the terminal head cover (8) on the terminal head.
2. Guide the connection wires (4) of the insert (3) through the center hole in the head transmitter (5).
3. Fit the mounting springs (6) on the mounting screws (7).
4. Guide the mounting screws (7) through the side boreholes of the head transmitter and the insert (3). Then fix both mounting screws with the snap rings (2).
5. Then tighten the head transmitter (5) along with the insert (3) in the terminal head.
6.
After wiring, close the terminal head cover again (8) tightly.(® ä 15)
Endress+Hauser 11
Item B Mounting in a field housing
1 Field housing cover
2 Mounting screws with springs
Installation instructions
1
2
3 4 5
6
5
6
iTEMP® TMT82
Item B Mounting in a field housing
3 Head transmitter
5 Field housing
Procedure for mounting in a field housing, pos. B:
1. Open the cover (1) of the field housing (4).
2. Guide the mounting screws (2) through the lateral bores of the head transmitter (3).
3. Screw the head transmitter to the field housing.
4.
After wiring, close the field housing cover (1) again. (® ä 15)
Item C Mounting on DIN rail (DIN rail as per IEC 60715)
1 Mounting screws with springs
2 Head transmitter
3 Circlips
4 DIN rail clip
5 DIN rail
Procedure for mounting on a DIN rail, pos. C:
1. Press the DIN rail clip (4) onto the DIN rail (5) until it engages with a click.
2. Fit the mounting springs on the mounting screws (1) and guide the screws through the side boreholes of the head transmitter (2). Then fix both mounting screws with the snap rings (3).
3. Screw the head transmitter (2) onto the DIN rail clip (4).
Mounting typical of North America
Head transmitter mounting
å 4
1 Protection tube 2 Insert 3 Adapter, coupling 4 Terminal head 5 Head transmitter 6 Mounting screws
A0008520
Thermometer design with thermocouples or RTD sensors and head transmitter:
12 Endress+Hauser
iTEMP® TMT82
Installation instructions
1. Fit the thermowell (1) on the process pipe or the container wall. Secure the thermowell according to the instructions before the process pressure is applied.
2. Fit the necessary neck tube nipples and adapter (3) on the thermowell.
3. Make sure sealing rings are installed if such rings are needed for harsh environmental conditions or special regulations.
4. Guide the mounting screws (6) through the lateral bores of the head transmitter (5).
5. Position the head transmitter (5) in the terminal head (4) in such a way that the bus cable (terminals 1 and 2) point to the cable entry.
6. Using a screwdriver, screw down the head transmitter (5) in the terminal head (4).
7. Guide the connection wires of the insert (3) through the lower cable entry of the terminal head (4) and through the middle hole in the head transmitter (5). Wire the connection wires
and transmitter with one another (® ä 15).
8. Screw the terminal head (4), with the integrated and wired head transmitter, onto the ready­mounted nipple and adapter (3).
NOTICE
The terminal head cover must be secured properly to meet the requirements for explosion protection.
After wiring, securely screw the terminal head cover back on.
Mounting the display on the head transmitter
å 5
Mounting the display
A0009852
1. Loosen the screw on the terminal head cover. Flip back the terminal head cover.
2. Remove the cover of the display connection area.
3. Fit the display module onto the mounted and wired head transmitter. The fastening pins must click securely into place on the head transmitter. After mounting, securely tighten the terminal head cover.
The display can only be used with the appropriate terminal heads - cover with viewing window (e.g. TA30 from Endress+Hauser).
Endress+Hauser 13
Installation instructions

4.3.2 Mounting the DIN rail transmitter

Mounting the DIN rail transmitter
å 6
iTEMP® TMT82
A0017821
1. Slide the upper DIN rail clip upwards and the lower clip downwards until they click into place.
2. Fit the device on the DIN rail from the front.
3. Slide the two DIN rail clips back together until they click into place.
4.4

Post-installation check

After installing the device, always run the following final checks:
Device condition and specifications Notes
Is the device undamaged (visual inspection)? -
Do the ambient conditions match the device specification (e.g. ambient temperature, measuring range, etc.)?
See 'Technical data' section(® ä 40)
14 Endress+Hauser
iTEMP® TMT82
-
+
+
1
-
2
7
6
5
4
3
1
2
7
6
5
4
3
Sensor input 2
Sensor input 1
Bus connection
and supply voltage
Display connection/ service interface
TC, mV
RTD, 4-, 3- and 2-wire:Ω
RTD, 3- and 2-wire:Ω
TC, mV
white
red
red
white
white
red
red
Wiring

5 Wiring

CAUTION
!
Switch off power supply before installing or connecting the device. Failure to observe this may result in destruction of parts of the electronics.
When installing Ex-approved devices in a hazardous area please take special note of the instructions and connection schematics in the respective Ex documentation added to these Operating Instructions. Your supplier is available for assistance if required.
Do not occupy the display connection. An incorrect connection can destroy the electronics.
A Phillips head screwdriver is required to wire the head transmitter with screw terminals. A flat­bladed screwdriver must be used for the version with spring terminals and for the DIN rail transmitter.
NOTICE
Do not overtighten the screw terminals, as this could damage the transmitter.
Maximum torque = 1 Nm (¾ pound-feet).
For wiring a mounted head transmitter, proceed as follows:
1. Open the cable gland and the housing cover on the terminal head or the field housing.
2. Feed the cables through the opening in the cable gland.
3.
Connect the cables as shown in (® ä 15). If the head transmitter is fitted with spring terminals, pay particular attention to the information in the "Connecting to spring terminals"
section" (® ä 17).
4. Retighten the cable gland and close the housing cover.
In order to avoid connection errors always take note of the hints given in the section "connection check"!
5.1

Quick wiring guide

Terminal assignment of head transmitter
Wiring the head transmitter
å 7
Endress+Hauser 15
A0007285-EN
Wiring
-
+
A
TMT82
ON
63748
5
1/+
2/- Test
8
7
6
5
6
4
3
1
2
Sensor input 2
Sensor input 1
Supply voltage
4...20 mA
HART connection
®
Test
RTD, 3- and 2-wire:Ω
RTD, 4-, 3- and 2-wire:Ω
white
red
red
white
white
red
red
TC, mV
TC, mV
Terminal assignment of DIN rail transmitter
Assignment of terminal connections for DIN rail device
å 8
A To check the output current, an amperemeter (DC measurement) can be connected between the "Test" and "-" terminals.
iTEMP® TMT82
A0017807-EN
To operate the device via the HART® protocol (terminals 1 and 2), a minimum load of 250 W is required in the signal circuit.
NOTICE
ESD - electrostatic discharge. Protect the terminals from electrostatic discharge. Failure to
observe this may result in destruction or malfunction of parts of the electronics.

5.2 Connecting the sensor cables

Terminal assignment of the sensor terminals(® å 7, ä 15).
NOTICE
When connecting 2 sensors ensure that there is no galvanic connection between the sensors (e.g. caused by sensor elements that are not isolated from the thermowell). The resulting equalizing currents distort the measurements considerably.
The sensors must remain galvanically isolated from one another by connecting each sensor separately to a transmitter. The transmitter provides sufficient galvanic isolation (> 2 kV AC) between the input and output.
The following connection combinations are possible when both sensor inputs are assigned:
Sensor input 1
Sensor input 2
RTD or resistance transmitter, 2-wire
RTD or resistance transmitter, 3-wire
RTD or resistance transmitter, 4-wire
Thermocouple (TC), voltage transmitter
RTD or
resistance
transmitter, 2-
wire
 Â
 Â
   Â
- - - -
RTD or
resistance
transmitter, 3-
wire
RTD or
resistance
transmitter, 4-
wire
-
-
Thermocouple
(TC), voltage
transmitter
Â
Â
16 Endress+Hauser
iTEMP® TMT82
A B C D

5.2.1 Connecting to spring terminals

A flat-bladed screwdriver, size 3 mm is required.
å 9
Pos. A, solid wire:
Spring terminal connection
1. Strip wire end. Min. stripping length 10 mm (0.39 in).
2. Insert the wire end into the terminal (A).
3. Pull the wire gently to ensure it is connected correctly. Repeat from step 1 if necessary.
Wiring
A0008322
Pos. B, fine-strand wire without ferrule:
1. Strip wire end. Min. stripping length 10 mm (0.39 in).
2. Operate lever opener with tool (B).
3. Insert the wire end into the terminal (B).
4. Release lever opener.
5. Pull the wire gently to ensure it is connected correctly. Repeat from step 1 if necessary.
Pos. C and D, releasing the connection:
1. Operate lever opener with tool (C).
2. Remove wire from terminal (D).
3. Release lever opener.
When connecting flexible cables and spring terminals, it is not recommended to use ferrules.
5.3
CAUTION
!
Switch off power supply before installing or connecting the transmitter. Failure to observe this

Connecting the power supply and signal cables

may result in destruction of parts of the electronics.
Cable specification
A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended for HART® communication. Observe grounding concept of the plant.
Please also observe the general procedure on (® ä 15).
Endress+Hauser 17
Wiring
*
*
1 2 3
4
2-
1+
2­1+
*
2-1+
5
6
7
4
5
7
Connecting the signal cables and power supply
å 10
1 Head transmitter installed in field housing 2 Head transmitter installed in terminal head 3 DIN rail transmitter mounted on DIN rail 4
Terminals for HART® protocol and power supply 5 Internal ground connection 6 External ground connection 7
Shielded signal cable (recommended for HART® protocol)
iTEMP® TMT82
A0017841
• The terminals for connecting the signal cable (1+ and 2-) are protected against reverse polarity. Conductor cross-section:
• – Max. 2.5 mm2 for screw terminals – max. 1.5 mm2 for spring terminals. Min. stripping length of wire 10 mm (0.39 in).

5.4 Shielding and grounding

Optimum electromagnetic compatibility (EMC) can only be guaranteed if the system components and, in particular, the lines are shielded and the shield forms as complete a cover as possible. A shield coverage of 90% is ideal.
• To ensure an optimum EMC protective effect when communicating with HART®, connect the shield as often as possible to the reference ground.
• For reasons of explosion protection, you should refrain from grounding however.
To comply with both requirements, three different types of shielding are possible when communicating with HART®:
• Shielding at both ends
• Shielding at one end on the feed side with capacitance termination at the field device
• Shielding at one end on the feed side
Experience shows that the best results with regard to EMC are achieved in most cases in installations with one-sided shielding on the feed side (without capacitance termination at the field device). Appropriate measures with regard to input wiring must be taken to allow unrestricted operation when EMC interference is present. These measures have been taken into account for this device. Operation in the event of disturbance variables as per NAMUR NE21 is
18 Endress+Hauser
thus guaranteed. Where applicable, national installation regulations and guidelines must be observed during the installation! Where there are large differences in potential between the individual grounding points, only one point of the shielding is connected directly with the reference ground. In systems without potential equalization, therefore, cable shielding of fieldbus systems should only be grounded on one side, for example at the supply unit or at safety barriers.
iTEMP® TMT82
-
.
1
2
3
4
Wiring
A0014463
å 11
1 Optional grounding of the field device, isolated from cable shielding 2 Grounding of the cable shield at one end 3 Supply unit 4
Shielding and grounding the signal cable at one end with HART® communication
Grounding point for HART® communication cable shield
NOTICE
If the shielding of the cable is grounded at more than one point in systems without potential matching, power supply frequency equalizing currents can occur that damage the signal cable or have a serious effect on signal transmission.
In such cases the shielding of the signal cable is to be grounded on only one side, i.e. it must not be connected to the ground terminal of the housing (terminal head, field housing). The shield that is not connected should be insulated!
5.5
Device condition and specifications Notes
Is the device or cable undamaged (visual check)? --
Electrical connection Notes
Does the supply voltage match the specifications on the nameplate?
Do the cables have adequate strain relief? --
Are the power supply and signal cables correctly connected?
Are all the screw terminals well tightened and have the connections of the spring terminals been checked?
Are all the cable entries installed, tightened and sealed? --
Are all housing covers installed and firmly tightened? --

Post-connection check

Head transmitter: U = 11 to 42 V DIN rail transmitter: U = 12 to 42 V
(® ä 15)
--
DC
DC
Endress+Hauser 19
Operating options
1
2
4
5
7
6
3
ON
OFF
1 2 4 8 16 32 64
HW
SW ADDR SIM WRITE LOCK DISPL. 180°
8
iTEMP® TMT82

6 Operating options

6.1
å 12

Overview of operation options

A0014460
Operating options of the head transmitter
1 PLC (programmable logic control) 2 Transmitter power supply unit, e.g. RN221N (with communication resistor) 3
Connection for HART® modem Commubox FXA191, FXA195 4 Field Communicator 375, 475 5 Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM) 6
HART® modem Commubox FXA191 (RS232) or FXA195 (USB) 7 Commubox FXA291 (USB) or TXU10 (USB) for connecting to the CDI interface 8 Temperature transmitter as head transmitter or DIN rail device, onsite operation via DIP switches on the rear of
the optional display possible only for head transmitter
For the head transmitter, display and operating elements are available locally only if the head transmitter was ordered with a display unit!
20 Endress+Hauser
iTEMP® TMT82
Expert
System
Sensor
Communication
Diagnostics
Operating menu for experts
Display/operat.
Display interval
Format display
Decimal places 1
Setup
Advanced setup
Device tag
Diagnostics
Operating menu for operators and maintenances
Value 1 display
Operator
Maintenance
Expert
Output
Unit
Sensor type
Lower range value
Upper range value
Enter access code
Locking status
Sensor Sensor offset
Current output
Output current
Actual diagnostics
Operating time
Diagnostics list Actual diagnostics count
Device reset Device reset
Enter access code
Unit
Mains filter
Display Display interval
Sensor Sensor type
Output current
Current trimming
HART config.
HART info
HART output
Burst mode
Device type
Assign PV
Actual diagnostics
Diagnostics list Actual diagnostics count
Event logbook
Device information
Simulation
Device reset
Previous diagnostics
Device tag
Min/max values
Sensor 1 min v.
Simulation current output
Device reset
Sensor value
Sensor value
Operating options

6.2 Structure and function of the operating menu

6.2.1

Structure of the operating menu

Endress+Hauser 21
A0014757-EN
Operating options

6.2.2 Submenus and user roles

Certain parts of the menu are assigned to certain user roles. Each user role corresponds to typical tasks within the lifecycle of the device.
User role Typical tasks Menu Content/meaning
Operator Tasks during operation:
Maintenance Commissioning:
Expert Tasks that require detailed knowledge of the function of
Configuration of the display.
• Reading measured values.
• Configuration of the measurement.
• Configuration of data processing (scaling, linearization, etc.).
• Configuration of the analog measured value output.
Fault elimination:
• Diagnosing and eliminating process errors.
• Interpretation of device error messages and correcting associated errors.
the device:
• Commissioning measurements under difficult conditions.
• Optimal adaptation of the measurement to difficult conditions.
• Detailed configuration of the communication interface.
• Error diagnostics in difficult cases.
"Display/operation" Contains all the parameters that are required in ongoing
operation: configuration of the measured value display (displayed values, display format, etc.).
"Setup" Contains all parameters for commissioning:.
"Diagnostics" Contains all parameters for detecting and analyzing errors:
"Expert" Contains all parameters of the device (including those that
Setup parameters
• Once values have been set for these parameters, the measurement should generally be completely configured.
"Extended Setup" submenu
• Contains additional submenus and parameters: – For more accurate configuration of the measurement
(adaptation to special measuring conditions).
– For converting the measured value (scaling,
linearization).
– For scaling the output signal.
Diagnostics list
• Contains up to 3 currently pending error messages.
Event logbook
• Contains the last 5 error messages (no longer pending).
"Device information" submenu
• Contains information for identifying the device.
"Measured values" submenu
• Contains all current measured values.
"Simulation" submenu
• Is used to simulate measured values or output values.
"Device reset" submenu
are already in one of the other menus). The structure of this menu is based on the function blocks of the device:
"System" submenu
• Contains all higher-order device parameters that do not pertain either to measurement or the measured value communication.
"Sensor" submenu
• Contains all parameters for configuring the measurement.
"Output" submenu
• Contains all parameters for configuring the analog current output.
"Communication" submenu
• Contains all parameters for configuring the digital communication interface.
"Diagnostics" submenu
• Contains all parameters for detecting and analyzing errors.
iTEMP® TMT82
22 Endress+Hauser
iTEMP® TMT82
1
2
3 4 5
6
7
Operating options

6.3 Measured value display and operating elements

6.3.1

Display elements

Head transmitter
å 13
Optional LC display TID10 for head transmitter
Item No. Function Description
1 Displays the TAG TAG, 32 characters long.
2 'Communication' symbol The communication symbol appears when read and write-accessing via the
fieldbus protocol.
3 Unit display Unit display for the measured value displayed.
4 Measured value display Displays the current measured value.
5 Value/channel display S1,
S2, DT, PV, I, %
6 'Configuration locked'
symbol
7 Status signals
Symbols Meaning
e.g. S1 for a measured value from channel 1 or DT for the device temperature
The 'configuration locked' symbol appears when configuration is locked via the hardware.
Error message "Failure detected"
An operating error has occurred. The measured value is no longer valid.
The display alternates between the error message and "- - - -" (no valid measured value present), see "Diagnostics events" (® ä 35) section.
"Service mode"
The device is in service mode (e.g. during a simulation).
"Out of specification"
The device is being operated outside its technical specifications (e.g. during warm-up or cleaning processes).
"Maintenance required"
Maintenance is required. The measured value is still valid.
The display alternates between the measured value and the status message.
A0008549
DIN rail transmitter
Endress+Hauser 23
Operating options
ON
OFF
1 2 4 8 16 32 64
HW
SW ADDR ACTIVE SIM WRITE LOCK DISPL. 180°
1
2
3
iTEMP® TMT82
The DIN rail transmitter version does not have an interface to the LC display TID10 and therefore does not have a local display either.
Two LEDs on the front indicate the device status in accordance with NAMUR NE44.
Type Function and characteristic
Status LED (red) When the device is operating without errors, the device status is displayed. This
function can no longer be guaranteed in the event of an error.
LED off: without diagnostic message
• LED is lit: diagnostic display, category F
• LED flashing: diagnostic display of categories C, S or M
Power LED (green) 'ON' When the device is operating without errors, the operating status is displayed.
This function can no longer be guaranteed in the event of an error.
• LED off: Power failure or insufficient supply voltage
• LED is lit: Supply voltage is OK (either via CDI or via supply voltage, terminals 1+, 2-)

6.3.2 Local operation

You can make hardware settings for the fieldbus interface using miniature switches (DIP switches) on the rear of the optional display .
The user has the option of ordering the display with the head transmitter, or as an accessory for subsequent mounting. (® ä 30)
NOTICE
ESD - electrostatic discharge. Protect the terminals from electrostatic discharge. Failure to
observe this may result in destruction or malfunction of parts of the electronics.
1: Connection to head transmitter
2: DIP switch (1 - 64, SW/HW, ADDR and SIM = simulation mode) no
function for this head transmitter
3: DIP switch (WRITE LOCK = write protection; DISPL. 180° = switch,
turn the display monitor 180°)
A0014562
Hardware settings via DIP switches
å 14
Procedure for setting the DIP switch:
1. Open the cover of the terminal head or field housing.
2. Remove the attached display from the head transmitter.
3. Configure the DIP switch on the rear of the display accordingly. In general: switch to ON = function enabled, switch to OFF = function disabled.
4. Fit the display onto the head transmitter in the correct position. The head transmitter accepts the settings within one second.
5. Secure the cover back onto the terminal head or field housing.
Switching write protection on/off
Write protection is switched on and off via a DIP switch on the rear of the optional attachable display. When write protection is active, parameters cannot be modified. A key symbol on the display indicates that the write protection is on. Write protection prevents any write access to the
24 Endress+Hauser
parameters. The write protection remains active even when the display is removed. To deactivate the write protection, the device must be restarted with the display attached and the DIP switch deactivated (WRITE LOCK = OFF).
iTEMP® TMT82
Operating options
Turning the display
The display can be rotated 180° using the "DISPL. 180°" DIP switch. The setting is retained when the display is removed.
6.4

Access to the operating menu via the operating tool

6.4.1 FieldCare

Function scope
FDT/DTM-based plant asset management tool from Endress+Hauser. It can configure all smart field units in a system and help you manage them. By using the status information, it is also a simple but effective way of checking their status and condition. Access takes place via the HART protocol or CDI (= Endress+Hauser Common Data Interface).
Typical functions:
• Configuring parameters of transmitters
• Loading and saving device data (upload/download)
• Documentation of the measuring point
• Visualization of the measured value memory (line recorder) and event logbook
For details, see Operating Instructions BA027S/04/xx and BA059AS/04/xx
NOTICE
For use in hazardous areas: Before accessing the device with the Commubox FXA291 via the CDI (= Endress+Hauser Common Data Interface), disconnect the transmitter from the power supply, terminals (1+) and (2-).
Failure to comply with this instruction can result in damage to parts of the electronics.
®
Source for device description files
See data (® ä 28)
Endress+Hauser 25
Operating options
iTEMP® TMT82
User interface
A0014485-EN
6.4.2

AMS Device Manager

Function scope
Program from Emerson Process Management for operating and configuring measuring devices via the HART® protocol.
Source for device description files
See data (® ä 28).

6.4.3 SIMATIC PDM

Function scope
SIMATIC PDM is a standardized, manufacturer-independent program from Siemens for the operation, configuration, maintenance and diagnosis of intelligent field devices via the HART protocol.
Source for device description files
See data (® ä 28).
®

6.4.4 Field Communicator 375/475

Function scope
Industrial handheld terminal from Emerson Process Management for remote configuration and measured value display via the HART ® protocol.
26 Endress+Hauser
iTEMP® TMT82
Operating options
Source for device description files
See data (® ä 28).
Endress+Hauser 27
Integrating the transmitter via HART® protocol iTEMP® TMT82
7

Integrating the transmitter via HART® protocol

Version data for the device
Firmware version 01.00.zz • On the title page of the Operating instructions
On nameplate (® å 1, ä 7)
Parameter firmware version Diagnostics ® Device info® Firmware version
Manufacturer ID 0x11 Manufacturer ID parameter
Diagnostics ® Device info® Manufacturer ID
Device type ID 0xCC Device type parameter
Diagnostics ® Device info ® Device type
HART protocol revision 6.0 ---
Device revision 1
On transmitter nameplate (® å 1, ä 7)
Device revision parameter
Diagnostics ® Device info ® Device revision
The suitable device description file (DD) for the individual operating tools is listed in the table below, along with information on where the file can be acquired.
Operating tools
Operating tool Sources for obtaining device descriptions (DD)
FieldCare
AMS Device Manager (Emerson Process Management)
SIMATIC PDM (Siemens)
Field Communicator 375, 475 (Emerson Process Management)
www.endress.com ® Download Area
CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
www.endress.com ® Download Area
www.endress.com ® Download Area
Use update function of handheld terminal

7.1 HART device variables and measured values

The following measured values are assigned to the device variables at the factory:
Device variables for temperature measurement
Device variable Measured value
Primary device variable (PV) Sensor 1
Secondary device variable (SV) Device temperature
Tertiary device variable (TV) Sensor 1
Quaternary device variable (QV) Sensor 1
It is possible to change the assignment of device variables to process variables in the Expert ® Communication ® HART output menu.
28 Endress+Hauser
iTEMP® TMT82 Integrating the transmitter via HART® protocol

7.2 Device variables and measured values

The following measured values are assigned to the individual device variables:
Device variable code Measured value
0 Sensor 1
1 Sensor 2
2 Device temperature
3 Average of sensor 1 and sensor 2
4 Difference between sensor 1 and sensor 2
5 Sensor 1 (backup sensor 2)
6 Sensor 1 with switchover to sensor 2 if a limit value is exceeded
7 Average of sensor 1 and sensor 2 with backup
The device variables can be queried from a HART® master using HART® command 9 or 33.
Endress+Hauser 29
Commissioning
iTEMP® TMT82

8 Commissioning

8.1
Before commissioning the measuring point make sure that all final checks have been carried out:
Checklist “Post-installation check”, (® ä 14)
Checklist “Post-connection check”, (® ä 19)

Function check

8.2 Switching on the transmitter

Once the final checks have been successfully completed, it is time to switch on the supply voltage. The transmitter performs a number of internal test functions after power-up. As this procedure progresses, the following sequence of messages appears on the display:
Step Display
1 "Display" text and firmware version of the display
2 Firm logo
3 Device name with firmware and hardware versions
4 Information on the sensor configuration (sensor element and type of connection)
5 Set measuring range
6a Current measured value or
6b Current status message
If the switch-on procedure is not successful, the relevant diagnostics event, depending on the cause, is displayed. A detailed list of diagnostic events and the corresponding troubleshooting instructions can be
found in the "Diagnostics and troubleshooting" section (® ä 33).
The device is operational after approx. 8 seconds, and the plug-in display after approx. 12 seconds in normal operating mode! Normal measuring mode commences as soon as the switch-on procedure is completed. Measured values and status values appear on the display.
8.3
If the device is locked and the parameter settings cannot be changed, it must first be enabled via the hardware lock. The device is locked using the hardware if the keyhole symbol appears in the header of the measured value display. To unlock the device, switch the write protection switch
on the back of the display to the "OFF" position (® ä 24).

Enabling configuration

9 Maintenance

In general, no specific maintenance is required for this device.

10 Accessories

Different accessories are available for the device. These may be ordered separately from your supplier. Contact your service organization for detailed information on the relevant order code. When ordering accessories, please quote the serial number of the device!
30 Endress+Hauser
Loading...
+ 70 hidden pages