11.6Software history and overview of compatibility ... 39
12Technical data ..................... 40
13Operating menu and parameter
description ........................ 51
13.1"Display/operation" menu ................. 57
13.2"Setup" menu .......................... 61
13.3"Diagnostics" menu ...................... 72
13.4"Expert" menu ......................... 80
Index .................................. 96
6Operating options .................. 20
6.1Overview of operation options .............. 20
6.2Structure and function of the operating menu .... 21
6.3Measured value display and operating elements .. 23
6.4Access to the operating menu via the operating
tool ................................ 25
7
Integrating the transmitter via HART
®
protocol ........................... 28
7.1HART device variables and measured values ..... 28
7.2Device variables and measured values ......... 29
8Commissioning .................... 30
8.1Function check ........................ 30
8.2Switching on the transmitter ............... 30
8.3Enabling configuration .................... 30
9Maintenance ...................... 30
10Accessories ........................ 30
10.1Optional accessories ..................... 31
Endress+Hauser3
Page 4
Important document information
DANGER
CAUTION
NOTICE
iTEMP® TMT82
1 Important document information
1.1
About this document
1.1.1 Document function
These Operating Instructions contain all the information that is required in various phases of the
life cycle of the device: from product identification, incoming acceptance and storage, to
mounting, connection, operation and commissioning through to troubleshooting, maintenance
and disposal.
1.1.2 Additional standard documentation on the device
DocumentPurpose and content of the document
Technical Information
TI01010T/09/en
Brief Operating Instructions
KA01095T/09/en
The document types listed are available:
On the CD supplied with the device
•
•
In the Download Area of the Endress+Hauser Internet site: www.endress.com ®
Download
Planning aid for your device
The document contains all the technical data on the device and provides an
overview of the accessories and other products that can be ordered for the
device.
Guide that takes you quickly to the 1st measured value
The Brief Operating Instructions contain all the essential information from
incoming acceptance to initial commissioning.
1.1.3 Safety Instructions (XA)
When using in hazardous areas, the national safety requirements must be met. Separate Ex
documentation is contained in these Operating Instructions for measurement systems that are to
mounted in hazardous areas. Strict compliance with the installation instructions, ratings and
safety instructions as listed in this supplementary documentation is mandatory. Ensure you are
using the correct Ex documentation for the relevant Ex-approved device. The number of the
related Ex documentation (XA...) is indicated on the nameplate. You can use this Ex
documentation if the two numbers (i.e. in the Ex documentation and on the nameplate) are
identical.
1.2 Document conventions
1.2.1 Safety symbols
SymbolMeaning
DANGER!
A0011189-EN
A0011191-EN
A0011192-EN
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result
in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result
in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
4Endress+Hauser
Page 5
iTEMP® TMT82
)
*
-
.
Important document information
1.2.2 Electrical symbols
SymbolMeaning
Direct current
A terminal to which DC voltage is applied or through which direct current flows.
A0011197
Alternating current
A0011198
A terminal to which alternating voltage (sine-wave) is applied or through which alternating current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
A0011200
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0011199
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
A0011201
equalization line or a star grounding system depending on national or company codes of practice.
1.2.3 Symbols and notation for certain types of information
SymbolMeaning
Allowed
Indicates procedures, processes or actions that are allowed.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
1., 2., 3.Series of steps
Result of a sequence of actions
Ã
1.2.4 Symbols and notation in graphics
SymbolMeaning
1,2,3 ...
A, B, C, ...
A-A, B-B, C-C, ...
Endress+Hauser5
Item numbers
Views
Sections
Hazardous area
Indicates a hazardous area.
A0011187
Safe area (non-hazardous area)
Indicates a non-hazardous area.
A0011188
Page 6
Basic safety instructions
iTEMP® TMT82
2 Basic safety instructions
2.1
Requirements for the personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill the
following requirements:
►
Trained, qualified specialists must have a relevant qualification for this specific function and
task
►
Are authorized by the plant owner/operator
►
Are familiar with federal/national regulations
►
Before beginning work, the specialist staff must have read and understood the instructions in
the Operating Instructions and supplementary documentation as well as in the certificates
(depending on the application)
►
Following instructions and basic conditions
The operating personnel must fulfill the following requirements:
►
Being instructed and authorized according to the requirements of the task by the facility's
owner-operator
►
Following the instructions in these Operating Instructions
2.2 Designated use
The device is a universal and user-configurable temperature transmitter with either one or two
sensor inputs for a resistance thermometer (RT), thermocouples (TC), resistance and voltage
transmitters. The head transmitter version of the device is intended for mounting in a flat-face
terminal head as per DIN EN 50446. It is also possible to mount the device on a DIN rail using
the optional DIN rail clip. The device is also optionally available in a version suitable for DIN rail
mounting as per IEC 60715 (TH35).
The manufacturer is not liable for damage caused by improper or non-designated use.
2.3 Operational safety
►
Operate the device in proper technical condition and fail-safe condition only.
►
The operator is responsible for interference-free operation of the device.
Hazardous area
To eliminate a danger for persons or for the facility when the device is used in the hazardous area
(e.g. explosion protection or safety equipment):
►
Based on the technical data on the nameplate, check whether the ordered device is permitted
for the intended use in the hazardous area. The nameplate can be found on the side of the
transmitter housing.
►
Observe the specifications in the separate supplementary documentation that is an integral
part of these Instructions.
Electromagnetic compatibility
The measuring system complies with the general safety requirements in accordance with EN
61010, the EMC requirements of IEC/EN 61326 and NAMUR Recommendation NE 21 and NE
89.
NOTICE
►
The unit must only be powered by a power supply that operates using an energy-limited
electric circuit that is compliant with IEC 61010-1, "SELV or Class 2 circuit".
6Endress+Hauser
Page 7
iTEMP® TMT82
1
2
3
4
5
11-42V
012345678910
xx.yy
.zz
TMT82- XXXXX/XX
iTEMP
®
Made in Germany 2011
D-87484 Nesselwang
Ser
.no.:
FW:
Input:
12345678ABCDEFGH
12345678ABCDEFGH
Current consum.: 23,6 mA
Dev.Rev: 1
Ext. ord. cd.:
XXXXXXXXXXXXX#
II3G Ex nA II T6/T5/T4 Ta= -40 ...+ 55/70/85°C
II3G Ex nL IIC T6/T5/T4 Ta= -40 ... +55/70/85°C
EH 08.001X
Install per XA00102R/09/a3/xx.xx
6
0044
Identification
3 Identification
3.1
Device designation
The following options are available for identification of the device:
• Nameplate specifications
•
Enter the serial number from the nameplate in W@M Device Viewer (www.endress.com/deviceviewer): All data relating to the device and an overview of the technical documentation
supplied with the device are displayed.
3.1.1 Nameplate
The right device?
Compare and check the data on the nameplate of the device against the requirements of the
measuring point:
A0014561
å 1
Nameplate of the head transmitter (example, Ex version)
1Power supply, current consumption and extended order code
2Serial number, device revision and firmware version
3Approvals with symbols
42 lines for the TAG name
5Approval in hazardous area with number of the relevant Ex documentation (XA...)
6Order code and manufacturer ID
Endress+Hauser7
Page 8
Identification
1
2
3
4
5
6
0044
iTEMP®TMT82
Made in Germany 2012 D-87484 Nesselwang
TAGXXXXXXXXXXX
TAGXXXXXXXXXXX
FW: XX.XX.XX Dev. Rev.: X
Order code: TMT82-xxx/xx
Ext. ord. cd.: XXXXXXXXXXX
Ser
. no.: XXXXXXXXX
Input: 12-42 V
Current cunsum.: 23,0 mA
1
II3G Ex nAII T6/T5/T4 Ta= -40 ...+ 55/70/85°C
II3G Ex nLIIC T6/T5/T4 Ta= -40 ... +55/70/85°C
EH 08.001X
Install per XA0xxxxT/09/a3/xx.xx
7
Nameplate of DIN rail transmitter (example, Ex version)
å 2
1Product description and manufacturer ID
2Order code, extended order code and serial number
3Power supply and current consumption
4Approval in hazardous area with number of the relevant Ex documentation (XA...)
5Firmware version and device version
6Approval logos
72 lines for the TAG name
iTEMP® TMT82
A0017924
3.2 Scope of delivery
The scope of delivery of the device comprises:
•
Temperature transmitter
• Mounting material (head transmitter)
• Hard copy of multi-language Brief Operating Instructions
• Operating Instructions and additional documentation on CD-ROM
•
Additional documentation for devices which are suitable for use in hazardous areas (0
such as Safety Instructions (XA), Control or Installation Drawings (ZD).
3.3
Certificates and approvals
The device left the factory in a safe operating condition. The device complies with the standards
EN 61 010-1 "Protection Measures for Electrical Equipment for Measurement, Control,
Regulation and Laboratory Procedures" and with the EMC requirements of IEC/EN 61326.
3.3.1 CE mark, Declaration of Conformity
The device therefore meets the legal requirements of the EC guidelines. The manufacturer
confirms that the device is compliant with the relevant guidelines by applying the CE mark.
3.3.2
The temperature transmitter is registered by HART® Communication. The device meets the
requirements of the HART Communication Protocol Specifications, April 2001, Revision 6.0.
HART® protocol certification
1),
3.3.3 Registered trademarks
• HART
• iTEMP
®
Registered trademark of the HART® Communication Foundation
Registered trademark of Endress+Hauser Wetzer GmbH + Co. KG, Nesselwang, D
8Endress+Hauser
®
Page 9
iTEMP® TMT82
Identification
An overview of other approvals and certifications is provided in the "Technical data"
section(®ä 50).
Endress+Hauser9
Page 10
Installation instructions
iTEMP® TMT82
4 Installation instructions
4.1
Incoming acceptance, transport, storage
4.1.1 Incoming acceptance
• Is the packaging or content damaged?
• Is the delivery complete? Compare the scope of delivery against the information on your order
form.
4.1.2 Transport and storage
• Pack the device in such a way as to protect it reliably against impact for storage (and
transportation). The original packaging provides optimum protection.
• Permitted storage temperature:
– Head transmitter: –50 to +100 °C (–58 to +212 °F)
– DIN rail transmitter: –40 to +100 °C (–40 to +212 °F)
4.2 Installation conditions
4.2.1 Dimensions
The dimensions of the device are provided in the "Technical data" section. (®ä 40).
4.2.2 Mounting location
• Head transmitter:
– In the terminal head, flat face, as per DIN EN 50446, direct mounting on insert with cable
entry (middle hole 7 mm)
–
In the field housing, separated from the process(®ä 30)
• DIN rail transmitter:
Designed for mounting on DIN rail (IEC 60715 TH35).
It is also possible to mount the device on a DIN rail as per IEC 60715 using the DIN rail clip
accessory (®ä 30).
Information about the conditions (such as the ambient temperature, degree of protection, climate
class etc.) that must be present at the installation point so that the device can be mounted
correctly, is provided in the "Technical data" section(®ä 40).
When using in hazardous areas, the limit values of the certificates and approvals must be
observed (see Ex Safety Instructions).
4.3
A Phillips head screwdriver is required to mount the head transmitter.
NOTICE
Do not overtighten the mounting screws as this could damage the head transmitter.
►
Maximum torque = 1 Nm (¾ pound-feet).
Installation instructions
10Endress+Hauser
Page 11
iTEMP® TMT82
1
2
3
4
5
6
7
9
8
123 45
1
2
34
Item A
Item B
Item C
Installation instructions
4.3.1 Mounting the head transmitter
A0014269-EN
å 3
Head transmitter mounting (three versions)
Item AMounting in a terminal head (terminal head flat face as per DIN 43729)
1Terminal head
2Circlips
3Insert
4Connection wires
5Head transmitter
6Mounting springs
7Mounting screws
8Terminal head cover
9Cable entry
Procedure for mounting in a terminal head, pos. A:
1. Open the terminal head cover (8) on the terminal head.
2. Guide the connection wires (4) of the insert (3) through the center hole in the head
transmitter (5).
3. Fit the mounting springs (6) on the mounting screws (7).
4. Guide the mounting screws (7) through the side boreholes of the head transmitter and the
insert (3). Then fix both mounting screws with the snap rings (2).
5. Then tighten the head transmitter (5) along with the insert (3) in the terminal head.
6.
After wiring, close the terminal head cover again (8) tightly.(®ä 15)
Endress+Hauser11
Item BMounting in a field housing
1Field housing cover
2Mounting screws with springs
Page 12
Installation instructions
1
2
345
6
5
6
iTEMP® TMT82
Item BMounting in a field housing
3Head transmitter
5Field housing
Procedure for mounting in a field housing, pos. B:
1. Open the cover (1) of the field housing (4).
2. Guide the mounting screws (2) through the lateral bores of the head transmitter (3).
3. Screw the head transmitter to the field housing.
4.
After wiring, close the field housing cover (1) again. (®ä 15)
Item CMounting on DIN rail (DIN rail as per IEC 60715)
1Mounting screws with springs
2Head transmitter
3Circlips
4DIN rail clip
5DIN rail
Procedure for mounting on a DIN rail, pos. C:
1. Press the DIN rail clip (4) onto the DIN rail (5) until it engages with a click.
2. Fit the mounting springs on the mounting screws (1) and guide the screws through the side
boreholes of the head transmitter (2). Then fix both mounting screws with the snap rings
(3).
3. Screw the head transmitter (2) onto the DIN rail clip (4).
Thermometer design with thermocouples or RTD sensors and head transmitter:
12Endress+Hauser
Page 13
iTEMP® TMT82
Installation instructions
1. Fit the thermowell (1) on the process pipe or the container wall. Secure the thermowell
according to the instructions before the process pressure is applied.
2. Fit the necessary neck tube nipples and adapter (3) on the thermowell.
3. Make sure sealing rings are installed if such rings are needed for harsh environmental
conditions or special regulations.
4. Guide the mounting screws (6) through the lateral bores of the head transmitter (5).
5. Position the head transmitter (5) in the terminal head (4) in such a way that the bus cable
(terminals 1 and 2) point to the cable entry.
6. Using a screwdriver, screw down the head transmitter (5) in the terminal head (4).
7. Guide the connection wires of the insert (3) through the lower cable entry of the terminal
head (4) and through the middle hole in the head transmitter (5). Wire the connection wires
and transmitter with one another (®ä 15).
8. Screw the terminal head (4), with the integrated and wired head transmitter, onto the readymounted nipple and adapter (3).
NOTICE
The terminal head cover must be secured properly to meet the requirements for
explosion protection.
►
After wiring, securely screw the terminal head cover back on.
Mounting the display on the head transmitter
å 5
Mounting the display
A0009852
1. Loosen the screw on the terminal head cover. Flip back the terminal head cover.
2. Remove the cover of the display connection area.
3. Fit the display module onto the mounted and wired head transmitter. The fastening pins
must click securely into place on the head transmitter. After mounting, securely tighten the
terminal head cover.
The display can only be used with the appropriate terminal heads - cover with viewing
window (e.g. TA30 from Endress+Hauser).
Endress+Hauser13
Page 14
Installation instructions
4.3.2 Mounting the DIN rail transmitter
Mounting the DIN rail transmitter
å 6
iTEMP® TMT82
A0017821
1. Slide the upper DIN rail clip upwards and the lower clip downwards until they click into
place.
2. Fit the device on the DIN rail from the front.
3. Slide the two DIN rail clips back together until they click into place.
4.4
Post-installation check
After installing the device, always run the following final checks:
Device condition and specificationsNotes
Is the device undamaged (visual inspection)?-
Do the ambient conditions match the device specification (e.g. ambient temperature, measuring
range, etc.)?
See 'Technical data'
section(®ä 40)
14Endress+Hauser
Page 15
iTEMP® TMT82
-
+
+
1
-
2
7
6
5
4
3
1
2
7
6
5
4
3
Sensor input 2
Sensor input 1
Bus connection
and supply voltage
Display connection/
service interface
TC, mV
RTD,4-, 3- and 2-wire:Ω
RTD,3- and 2-wire:Ω
TC, mV
white
red
red
white
white
red
red
Wiring
5 Wiring
CAUTION
!
►
Switch off power supply before installing or connecting the device. Failure to observe this may
result in destruction of parts of the electronics.
►
When installing Ex-approved devices in a hazardous area please take special note of the
instructions and connection schematics in the respective Ex documentation added to these
Operating Instructions. Your supplier is available for assistance if required.
►
Do not occupy the display connection. An incorrect connection can destroy the electronics.
A Phillips head screwdriver is required to wire the head transmitter with screw terminals. A flatbladed screwdriver must be used for the version with spring terminals and for the DIN rail
transmitter.
NOTICE
Do not overtighten the screw terminals, as this could damage the transmitter.
►
Maximum torque = 1 Nm (¾ pound-feet).
For wiring a mounted head transmitter, proceed as follows:
1. Open the cable gland and the housing cover on the terminal head or the field housing.
2. Feed the cables through the opening in the cable gland.
3.
Connect the cables as shown in (®ä 15). If the head transmitter is fitted with spring
terminals, pay particular attention to the information in the "Connecting to spring terminals"
section" (®ä 17).
4. Retighten the cable gland and close the housing cover.
In order to avoid connection errors always take note of the hints given in the section "connection
check"!
5.1
Quick wiring guide
Terminal assignment of head transmitter
Wiring the head transmitter
å 7
Endress+Hauser15
A0007285-EN
Page 16
Wiring
-
+
A
TMT82
ON
63748
5
1/+
2/- Test
8
7
6
5
6
4
3
1
2
Sensor input 2
Sensor input 1
Supply voltage
4...20 mA
HART
connection
®
Test
RTD,3- and 2-wire:Ω
RTD,4-, 3- and 2-wire:Ω
white
red
red
white
white
red
red
TC, mV
TC, mV
Terminal assignment of DIN rail transmitter
Assignment of terminal connections for DIN rail device
å 8
ATo check the output current, an amperemeter (DC measurement) can be connected between the "Test" and "-" terminals.
iTEMP® TMT82
A0017807-EN
To operate the device via the HART® protocol (terminals 1 and 2), a minimum load of 250 W is
required in the signal circuit.
NOTICE
►
ESD - electrostatic discharge. Protect the terminals from electrostatic discharge. Failure to
observe this may result in destruction or malfunction of parts of the electronics.
5.2 Connecting the sensor cables
Terminal assignment of the sensor terminals(®å 7, ä 15).
NOTICE
When connecting 2 sensors ensure that there is no galvanic connection between the
sensors (e.g. caused by sensor elements that are not isolated from the thermowell). The
resulting equalizing currents distort the measurements considerably.
►
The sensors must remain galvanically isolated from one another by connecting each sensor
separately to a transmitter. The transmitter provides sufficient galvanic isolation (> 2 kV AC)
between the input and output.
The following connection combinations are possible when both sensor inputs are assigned:
Sensor input 1
Sensor input 2
RTD or resistance
transmitter, 2-wire
RTD or resistance
transmitter, 3-wire
RTD or resistance
transmitter, 4-wire
Thermocouple (TC),
voltage transmitter
RTD or
resistance
transmitter, 2-
wire
ÂÂ
ÂÂ
ÂÂÂÂ
----
RTD or
resistance
transmitter, 3-
wire
RTD or
resistance
transmitter, 4-
wire
-
-
Thermocouple
(TC), voltage
transmitter
Â
Â
16Endress+Hauser
Page 17
iTEMP® TMT82
ABCD
5.2.1 Connecting to spring terminals
A flat-bladed screwdriver, size 3 mm is required.
å 9
Pos. A, solid wire:
Spring terminal connection
1. Strip wire end. Min. stripping length 10 mm (0.39 in).
2. Insert the wire end into the terminal (A).
3. Pull the wire gently to ensure it is connected correctly. Repeat from step 1 if necessary.
Wiring
A0008322
Pos. B, fine-strand wire without ferrule:
1. Strip wire end. Min. stripping length 10 mm (0.39 in).
2. Operate lever opener with tool (B).
3. Insert the wire end into the terminal (B).
4. Release lever opener.
5. Pull the wire gently to ensure it is connected correctly. Repeat from step 1 if necessary.
Pos. C and D, releasing the connection:
1. Operate lever opener with tool (C).
2. Remove wire from terminal (D).
3. Release lever opener.
When connecting flexible cables and spring terminals, it is not recommended to use ferrules.
5.3
CAUTION
!
►
Switch off power supply before installing or connecting the transmitter. Failure to observe this
Connecting the power supply and signal cables
may result in destruction of parts of the electronics.
Cable specification
•
A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended for HART® communication. Observe grounding concept
of the plant.
Please also observe the general procedure on (®ä 15).
Endress+Hauser17
Page 18
Wiring
*
*
123
4
2-
1+
21+
*
2-1+
5
6
7
4
5
7
Connecting the signal cables and power supply
å 10
1Head transmitter installed in field housing
2Head transmitter installed in terminal head
3DIN rail transmitter mounted on DIN rail
4
Terminals for HART® protocol and power supply
5Internal ground connection
6External ground connection
7
Shielded signal cable (recommended for HART® protocol)
iTEMP® TMT82
A0017841
• The terminals for connecting the signal cable (1+ and 2-) are protected against reverse
polarity.
Conductor cross-section:
•
– Max. 2.5 mm2 for screw terminals
– max. 1.5 mm2 for spring terminals. Min. stripping length of wire 10 mm (0.39 in).
5.4 Shielding and grounding
Optimum electromagnetic compatibility (EMC) can only be guaranteed if the system components
and, in particular, the lines are shielded and the shield forms as complete a cover as possible. A
shield coverage of 90% is ideal.
• To ensure an optimum EMC protective effect when communicating with HART®, connect the
shield as often as possible to the reference ground.
• For reasons of explosion protection, you should refrain from grounding however.
To comply with both requirements, three different types of shielding are possible when
communicating with HART®:
• Shielding at both ends
• Shielding at one end on the feed side with capacitance termination at the field device
• Shielding at one end on the feed side
Experience shows that the best results with regard to EMC are achieved in most cases in
installations with one-sided shielding on the feed side (without capacitance termination at the
field device). Appropriate measures with regard to input wiring must be taken to allow
unrestricted operation when EMC interference is present. These measures have been taken into
account for this device. Operation in the event of disturbance variables as per NAMUR NE21 is
18Endress+Hauser
thus guaranteed. Where applicable, national installation regulations and guidelines must be
observed during the installation! Where there are large differences in potential between the
individual grounding points, only one point of the shielding is connected directly with the
reference ground. In systems without potential equalization, therefore, cable shielding of fieldbus
systems should only be grounded on one side, for example at the supply unit or at safety barriers.
Page 19
iTEMP® TMT82
-
.
1
2
3
4
Wiring
A0014463
å 11
1Optional grounding of the field device, isolated from cable shielding
2Grounding of the cable shield at one end
3Supply unit
4
Shielding and grounding the signal cable at one end with HART® communication
Grounding point for HART® communication cable shield
NOTICE
If the shielding of the cable is grounded at more than one point in systems without
potential matching, power supply frequency equalizing currents can occur that damage
the signal cable or have a serious effect on signal transmission.
►
In such cases the shielding of the signal cable is to be grounded on only one side, i.e. it must
not be connected to the ground terminal of the housing (terminal head, field housing). The
shield that is not connected should be insulated!
5.5
Device condition and specificationsNotes
Is the device or cable undamaged (visual check)?--
Electrical connectionNotes
Does the supply voltage match the specifications on the
nameplate?
Do the cables have adequate strain relief?--
Are the power supply and signal cables correctly
connected?
Are all the screw terminals well tightened and have the
connections of the spring terminals been checked?
Are all the cable entries installed, tightened and sealed?--
Are all housing covers installed and firmly tightened?--
Post-connection check
Head transmitter: U = 11 to 42 V
DIN rail transmitter: U = 12 to 42 V
(®ä 15)
--
DC
DC
Endress+Hauser19
Page 20
Operating options
1
2
4
5
7
6
3
ON
OFF
1
2
4
8
16
32
64
HW
SW
ADDR
SIM
WRITE LOCK
DISPL. 180°
8
iTEMP® TMT82
6 Operating options
6.1
å 12
Overview of operation options
A0014460
Operating options of the head transmitter
1PLC (programmable logic control)
2Transmitter power supply unit, e.g. RN221N (with communication resistor)
3
HART® modem Commubox FXA191 (RS232) or FXA195 (USB)
7Commubox FXA291 (USB) or TXU10 (USB) for connecting to the CDI interface
8Temperature transmitter as head transmitter or DIN rail device, onsite operation via DIP switches on the rear of
the optional display possible only for head transmitter
For the head transmitter, display and operating elements are available locally only if the head
transmitter was ordered with a display unit!
20Endress+Hauser
Page 21
iTEMP® TMT82
Expert
System
Sensor
Communication
Diagnostics
Operating menu for experts
Display/operat.
Display interval
Format display
Decimal places 1
Setup
Advanced setup
Device tag
Diagnostics
Operating menu for operators and maintenances
Value 1 display
Operator
Maintenance
Expert
Output
Unit
Sensor type
Lower range value
Upper range value
Enter access code
Locking status
SensorSensor offset
Current output
Output current
Actual diagnostics
Operating time
Diagnostics listActual diagnostics count
Device resetDevice reset
Enter access code
Unit
Mains filter
DisplayDisplay interval
SensorSensor type
Output current
Current trimming
HART config.
HART info
HART output
Burst mode
Device type
Assign PV
Actual diagnostics
Diagnostics listActual diagnostics count
Event logbook
Device information
Simulation
Device reset
Previous diagnostics
Device tag
Min/max values
Sensor 1 min v.
Simulation current output
Device reset
Sensor value
Sensor value
Operating options
6.2 Structure and function of the operating menu
6.2.1
Structure of the operating menu
Endress+Hauser21
A0014757-EN
Page 22
Operating options
6.2.2 Submenus and user roles
Certain parts of the menu are assigned to certain user roles. Each user role corresponds to typical
tasks within the lifecycle of the device.
User roleTypical tasksMenuContent/meaning
OperatorTasks during operation:
MaintenanceCommissioning:
ExpertTasks that require detailed knowledge of the function of
Configuration of the display.
•
• Reading measured values.
• Configuration of the measurement.
• Configuration of data processing (scaling, linearization,
etc.).
• Configuration of the analog measured value output.
Fault elimination:
• Diagnosing and eliminating process errors.
• Interpretation of device error messages and correcting
associated errors.
the device:
• Commissioning measurements under difficult
conditions.
• Optimal adaptation of the measurement to difficult
conditions.
• Detailed configuration of the communication interface.
• Error diagnostics in difficult cases.
"Display/operation" Contains all the parameters that are required in ongoing
operation: configuration of the measured value display
(displayed values, display format, etc.).
"Setup"Contains all parameters for commissioning:.
"Diagnostics"Contains all parameters for detecting and analyzing errors:
"Expert"Contains all parameters of the device (including those that
Setup parameters
•
Once values have been set for these parameters, the
measurement should generally be completely configured.
"Extended Setup" submenu
•
Contains additional submenus and parameters:
– For more accurate configuration of the measurement
(adaptation to special measuring conditions).
– For converting the measured value (scaling,
linearization).
– For scaling the output signal.
Diagnostics list
•
Contains up to 3 currently pending error messages.
Event logbook
•
Contains the last 5 error messages (no longer pending).
"Device information" submenu
•
Contains information for identifying the device.
"Measured values" submenu
•
Contains all current measured values.
"Simulation" submenu
•
Is used to simulate measured values or output values.
"Device reset" submenu
•
are already in one of the other menus). The structure of this
menu is based on the function blocks of the device:
"System" submenu
•
Contains all higher-order device parameters that do not
pertain either to measurement or the measured value
communication.
"Sensor" submenu
•
Contains all parameters for configuring the
measurement.
"Output" submenu
•
Contains all parameters for configuring the analog
current output.
"Communication" submenu
•
Contains all parameters for configuring the digital
communication interface.
"Diagnostics" submenu
•
Contains all parameters for detecting and analyzing
errors.
iTEMP® TMT82
22Endress+Hauser
Page 23
iTEMP® TMT82
1
2
3
4
5
6
7
Operating options
6.3 Measured value display and operating elements
6.3.1
Display elements
Head transmitter
å 13
Optional LC display TID10 for head transmitter
Item No. FunctionDescription
1Displays the TAGTAG, 32 characters long.
2'Communication' symbolThe communication symbol appears when read and write-accessing via the
fieldbus protocol.
3Unit displayUnit display for the measured value displayed.
4Measured value displayDisplays the current measured value.
5Value/channel display S1,
S2, DT, PV, I, %
6'Configuration locked'
symbol
7Status signals
SymbolsMeaning
e.g. S1 for a measured value from channel 1 or DT for the device
temperature
The 'configuration locked' symbol appears when configuration is locked via
the hardware.
Error message "Failure detected"
An operating error has occurred. The measured value is no longer valid.
The display alternates between the error message and "- - - -" (no valid
measured value present), see "Diagnostics events" (®ä 35) section.
"Service mode"
The device is in service mode (e.g. during a simulation).
"Out of specification"
The device is being operated outside its technical specifications (e.g. during
warm-up or cleaning processes).
"Maintenance required"
Maintenance is required. The measured value is still valid.
The display alternates between the measured value and the status message.
A0008549
DIN rail transmitter
Endress+Hauser23
Page 24
Operating options
ON
OFF
1
2
4
8
16
32
64
HW
SW
ADDR ACTIVE
SIM
WRITE LOCK
DISPL. 180°
1
2
3
iTEMP® TMT82
The DIN rail transmitter version does not have an interface to the LC display TID10 and
therefore does not have a local display either.
Two LEDs on the front indicate the device status in accordance with NAMUR NE44.
TypeFunction and characteristic
Status LED (red)When the device is operating without errors, the device status is displayed. This
function can no longer be guaranteed in the event of an error.
LED off: without diagnostic message
•
• LED is lit: diagnostic display, category F
• LED flashing: diagnostic display of categories C, S or M
Power LED (green) 'ON'When the device is operating without errors, the operating status is displayed.
This function can no longer be guaranteed in the event of an error.
• LED off: Power failure or insufficient supply voltage
• LED is lit: Supply voltage is OK (either via CDI or via supply voltage,
terminals 1+, 2-)
6.3.2 Local operation
You can make hardware settings for the fieldbus interface using miniature switches (DIP
switches) on the rear of the optional display .
The user has the option of ordering the display with the head transmitter, or as an accessory
for subsequent mounting. (®ä 30)
NOTICE
►
ESD - electrostatic discharge. Protect the terminals from electrostatic discharge. Failure to
observe this may result in destruction or malfunction of parts of the electronics.
1: Connection to head transmitter
2: DIP switch (1 - 64, SW/HW, ADDR and SIM = simulation mode) no
1. Open the cover of the terminal head or field housing.
2. Remove the attached display from the head transmitter.
3. Configure the DIP switch on the rear of the display accordingly. In general: switch to ON =
function enabled, switch to OFF = function disabled.
4. Fit the display onto the head transmitter in the correct position. The head transmitter accepts
the settings within one second.
5. Secure the cover back onto the terminal head or field housing.
Switching write protection on/off
Write protection is switched on and off via a DIP switch on the rear of the optional attachable
display. When write protection is active, parameters cannot be modified. A key symbol on the
display indicates that the write protection is on. Write protection prevents any write access to the
24Endress+Hauser
parameters. The write protection remains active even when the display is removed. To deactivate
the write protection, the device must be restarted with the display attached and the DIP switch
deactivated (WRITE LOCK = OFF).
Page 25
iTEMP® TMT82
Operating options
Turning the display
The display can be rotated 180° using the "DISPL. 180°" DIP switch. The setting is retained
when the display is removed.
6.4
Access to the operating menu via the operating tool
6.4.1 FieldCare
Function scope
FDT/DTM-based plant asset management tool from Endress+Hauser. It can configure all smart
field units in a system and help you manage them. By using the status information, it is also a
simple but effective way of checking their status and condition. Access takes place via the HART
protocol or CDI (= Endress+Hauser Common Data Interface).
Typical functions:
• Configuring parameters of transmitters
• Loading and saving device data (upload/download)
• Documentation of the measuring point
• Visualization of the measured value memory (line recorder) and event logbook
For details, see Operating Instructions BA027S/04/xx and BA059AS/04/xx
NOTICE
For use in hazardous areas: Before accessing the device with the Commubox FXA291
via the CDI (= Endress+Hauser Common Data Interface), disconnect the transmitter
from the power supply, terminals (1+) and (2-).
►
Failure to comply with this instruction can result in damage to parts of the electronics.
®
Source for device description files
See data (®ä 28)
Endress+Hauser25
Page 26
Operating options
iTEMP® TMT82
User interface
A0014485-EN
6.4.2
AMS Device Manager
Function scope
Program from Emerson Process Management for operating and configuring measuring devices via
the HART® protocol.
Source for device description files
See data (®ä 28).
6.4.3 SIMATIC PDM
Function scope
SIMATIC PDM is a standardized, manufacturer-independent program from Siemens for the
operation, configuration, maintenance and diagnosis of intelligent field devices via the HART
protocol.
Source for device description files
See data (®ä 28).
®
6.4.4 Field Communicator 375/475
Function scope
Industrial handheld terminal from Emerson Process Management for remote configuration and
measured value display via the HART ® protocol.
26Endress+Hauser
Page 27
iTEMP® TMT82
Operating options
Source for device description files
See data (®ä 28).
Endress+Hauser27
Page 28
Integrating the transmitter via HART® protocoliTEMP® TMT82
7
Integrating the transmitter via HART® protocol
Version data for the device
Firmware version01.00.zz• On the title page of the Operating instructions
•
On nameplate (®å 1, ä 7)
•
Parameter firmware version
Diagnostics ® Device info® Firmware version
Manufacturer ID0x11Manufacturer ID parameter
Diagnostics ® Device info® Manufacturer ID
Device type ID0xCCDevice type parameter
Diagnostics ® Device info ® Device type
HART protocol revision6.0---
Device revision1•
On transmitter nameplate (®å 1, ä 7)
• Device revision parameter
Diagnostics ® Device info ® Device revision
The suitable device description file (DD) for the individual operating tools is listed in the table
below, along with information on where the file can be acquired.
Operating tools
Operating toolSources for obtaining device descriptions (DD)
FieldCare•
AMS Device Manager
(Emerson Process Management)
SIMATIC PDM
(Siemens)
Field Communicator 375, 475
(Emerson Process Management)
www.endress.com ® Download Area
CD–ROM (contact Endress+Hauser)
•
• DVD (contact Endress+Hauser)
www.endress.com ® Download Area
www.endress.com ® Download Area
Use update function of handheld terminal
7.1 HART device variables and measured values
The following measured values are assigned to the device variables at the factory:
Device variables for temperature measurement
Device variableMeasured value
Primary device variable (PV)Sensor 1
Secondary device variable (SV)Device temperature
Tertiary device variable (TV)Sensor 1
Quaternary device variable (QV)Sensor 1
It is possible to change the assignment of device variables to process variables in the Expert® Communication ® HART output menu.
28Endress+Hauser
Page 29
iTEMP® TMT82Integrating the transmitter via HART® protocol
7.2 Device variables and measured values
The following measured values are assigned to the individual device variables:
Device variable codeMeasured value
0Sensor 1
1Sensor 2
2Device temperature
3Average of sensor 1 and sensor 2
4Difference between sensor 1 and sensor 2
5Sensor 1 (backup sensor 2)
6Sensor 1 with switchover to sensor 2 if a limit value is exceeded
7Average of sensor 1 and sensor 2 with backup
The device variables can be queried from a HART® master using HART® command 9 or 33.
Endress+Hauser29
Page 30
Commissioning
iTEMP® TMT82
8 Commissioning
8.1
Before commissioning the measuring point make sure that all final checks have been carried out:
•
Checklist “Post-installation check”, (®ä 14)
•
Checklist “Post-connection check”, (®ä 19)
Function check
8.2 Switching on the transmitter
Once the final checks have been successfully completed, it is time to switch on the supply
voltage. The transmitter performs a number of internal test functions after power-up. As this
procedure progresses, the following sequence of messages appears on the display:
Step Display
1"Display" text and firmware version of the display
2Firm logo
3Device name with firmware and hardware versions
4Information on the sensor configuration (sensor element and type of connection)
5Set measuring range
6aCurrent measured value or
6bCurrent status message
If the switch-on procedure is not successful, the relevant diagnostics event, depending on the cause, is
displayed. A detailed list of diagnostic events and the corresponding troubleshooting instructions can be
found in the "Diagnostics and troubleshooting" section (®ä 33).
The device is operational after approx. 8 seconds, and the plug-in display after approx. 12 seconds
in normal operating mode! Normal measuring mode commences as soon as the switch-on
procedure is completed. Measured values and status values appear on the display.
8.3
If the device is locked and the parameter settings cannot be changed, it must first be enabled via
the hardware lock. The device is locked using the hardware if the keyhole symbol appears in the
header of the measured value display. To unlock the device, switch the write protection switch
on the back of the display to the "OFF" position (®ä 24).
Enabling configuration
9 Maintenance
In general, no specific maintenance is required for this device.
10 Accessories
Different accessories are available for the device. These may be ordered separately from your
supplier. Contact your service organization for detailed information on the relevant order code.
When ordering accessories, please quote the serial number of the device!
30Endress+Hauser
Page 31
iTEMP® TMT82
Accessories
Currently available accessories and spare parts for the product can be found online at:
http://www.products.endress.com/spareparts_consumables; HART® temperature transmitter:
TMT82
Accessories included in the scope of delivery:
Multilingual Brief Operating Instructions as hard copy
Commubox FXA195 HARTFor intrinsically safe HART® communication with FieldCare via the USB interface.
For details, see Technical Information TI404F/00
Commubox FXA191 HARTFor intrinsically safe HART® communication with FieldCare via the RS232C interface.
For details, see Technical Information TI237F/00
Commubox FXA291Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
Common Data Interface) and the USB port of a computer or laptop.
For details, see Technical Information TI405C/07
WirelessHART adapterIs used for the wireless connection of field devices.
The WirelessHART® adapter can be easily integrated into field devices and existing
infrastructures, offers data protection and transmission safety and can be operated in
parallel with other wireless networks.
For details, see Operating Instructions BA061S/04
Fieldgate FXA320Gateway for accessing connected 4-20 mA measuring devices via a web browser.
For details, see Technical Information TI025S/04
Fieldgate FXA520Gateway for accessing connected HART® measuring devices via a web browser.
For details, see Technical Information TI025S/04
Endress+Hauser31
Page 32
Accessories
10.3 System components and data manager
AccessoriesDescription
Graphic Data Manager
Memograph M
The Memograph M graphic data manager provides information on all the relevant process
variables. Measured values are recorded correctly, limit values are monitored and
measuring points analyzed. The data are stored in the 256 MB internal memory and also
on a SD card or USB stick.
For details, see Technical Information TI133R/09
iTEMP® TMT82
Paperless recorder
Ecograph T
RN221NActive barrier with power supply for safe separation of 4 to 20 mA standard signal
RNS221Supply unit for powering two 2-wire measuring devices solely in the non-Ex area.
RB223One- or two-channel, loop-powered barrier for safe separation of 4 to 20 mA standard
RIA14, RIA16Loop-powered field indicator for 4 to 20 mA circuit, RIA14 in flameproof metal enclosure
RIA15Process display, digital loop-powered display for 4 to 20 mA circuit, panel mounting
Multi-channel data recording system with LC color graphic display (120 mm / 4,7"
screen size), galvanically isolated universal inputs (U, I, TC, RTD), digital input,
transmitter power supply, limit relay, communication interfaces (USB, Ethernet,
RS232/485), Internal flash memory and compact flash card.
Bidirectional communication is possible via the HART® communication jacks.
For details, see Technical Information TI081R/09
signal circuits. Bidirectional communication is possible via the HART communication
jacks.
For details, see Technical Information TI132R/09
For details, see Technical Information TI143R/09 and TI144R/09
For details, see Technical Information TI01043K/09
32Endress+Hauser
Page 33
iTEMP® TMT82
Diagnostics and troubleshooting
11 Diagnostics and troubleshooting
11.1
Troubleshooting
Always start troubleshooting with the checklists below if faults occur after start up or during
operation. This takes you directly (via various queries) to the cause of the problem and the
appropriate remedial measures.
Due to its design, the device cannot be repaired. However, it is possible to send the device in
for examination. See the information in the "Return" section. (®ä 38)
General errors
ProblemPossible causeRemedy
Device is not responding.Supply voltage does not match that
specified on the nameplate.
Connecting cables are not in contact
with the terminals.
Output current < 3.6 mASignal line is not wired correctly.Check wiring.
Electronics unit is defective.Replace the device.
HART communication is not
working.
Status LED is lit or flashing red
(DIN rail transmitter only).
Power LED is not lit green (DIN
rail transmitter only).
Missing or incorrectly installed
communication resistor.
Commubox is not properly connected.Connect Commubox correctly .
Commubox is not set to "HART".Set Commubox selector switch to "HART".
Diagnostics events as per NAMUR
NE107 (®ä 35)
Power failure or insufficient supply
voltage
Apply correct voltage.
Check the contacting of the cables and
correct if necessary.
Install the communication resistor (250 W)
correctly.
Check diagnostics events:
LED is lit: diagnostic display, category F
•
• LED flashing: diagnostic display of
categories C, S or M
Check the supply voltage and check if
wiring is correct.
Check display (optional in conjunction with head transmitter)
ProblemPossible causeRemedy
No supply voltage• Check the supply voltage at the head
transmitter, terminals + and -.
Ensure that the display module holders
•
are correctly seated and that the display
module is properly connected to the
head transmitter. (®ä 10).
No display visible
The display module is defective.Replace the module.
The electronics of the head transmitter
are defective.
• If possible, test the display module with
other suitable head transmitters e.g.
Endress+Hauser head transmitter.
Replace the head transmitter.
Application errors without status messages for RTD sensor connection
ProblemPossible causeRemedy
Incorrect sensor orientation.Install the sensor correctly.
Measured value is incorrect/
inaccurate
Heat conducted by sensor.Observe the face-to-face length of the
sensor.
Device programming is incorrect
(number of wires).
Change the Connection type device
function.
Endress+Hauser33
Page 34
Diagnostics and troubleshooting
ProblemPossible causeRemedy
Failure current (≤ 3.6 mA or
≥ 21 mA)
Device programming is incorrect
(scaling).
Incorrect RTD configured.Change the Sensor type device function.
Sensor connection.Check that the sensor is connected
The cable resistance of the sensor (twowire) was not compensated.
Offset incorrectly set.Check offset.
Faulty sensor.Check the sensor.
RTD connected incorrectly.Connect the connecting cables correctly
Incorrect device programming (e.g.
number of wires).
Incorrect programming.Incorrect sensor type set in the Sensor
Change scaling.
correctly.
Compensate the cable resistance.
(terminal diagram).
Change the Connection type device
function.
type device function. Set the correct sensor
type.
iTEMP® TMT82
Application errors without status messages for TC sensor connection
ProblemPossible causeRemedy
Incorrect sensor orientation.Install the sensor correctly.
Heat conducted by sensor.Observe the face-to-face length of the
sensor.
Measured value is incorrect/
inaccurate
Failure current (≤ 3.6 mA or
≥ 21 mA)
Device programming is incorrect
(scaling).
Incorrect thermocouple type (TC)
configured.
Incorrect comparison measuring point
set.
Interference via the thermocouple wire
welded in the thermowell (interference
voltage coupling).
Offset incorrectly set.Check offset.
Faulty sensor.Check the sensor.
Sensor is connected incorrectly.Connect the connecting cables correctly
Incorrect programming.Incorrect sensor type set in the Sensor
Change scaling.
Change the Sensor type device function.
Set the correct comparison measuring
point(®ä 62).
Use a sensor where the thermocouple wire
is not welded.
(terminal diagram).
type device function. Set the correct sensor
type.
34Endress+Hauser
Page 35
iTEMP® TMT82
1
2
1
3
A
B
Diagnostics and troubleshooting
11.2 Diagnostics events
11.2.1
ADisplay in the event of a warning
BDisplay in the event of an alarm
1Status signal in the header
2The display alternates between the primary measured value and the status - indicated by the appropriate letter (M,
C or S) - plus the defined error number.
3The display alternates between "- - - -" (no valid measured value) and the status - indicated by the appropriate
letter (F) - plus the defined error number.
Displaying diagnostics events
A0014837
Status signals
SymbolEvent
category
Operating error An operating error has occurred. The measured value is no longer valid.
Service modeThe device is in service mode (e.g. during a simulation).
Out of
specification
Maintenance
required
Meaning
The device is being operated outside its technical specifications (e.g. during warm-up or
cleaning processes).
Maintenance is required. The measured value is still valid.
Diagnostic behavior
Alarm
Warning
Measurement is interrupted. The signal outputs assume the defined alarm condition. A
diagnostic message is generated (status signal F).
The device continues to measure. A diagnostic message is generated (status signals M, C
or S).
Endress+Hauser35
Page 36
Diagnostics and troubleshooting
iTEMP® TMT82
Diagnostics event and event text
The fault can be identified by means of the diagnostics event. The event text helps you by
providing information about the fault.
Diagnostics event
Status signalEvent numberEvent text
¯¯¯
Example
042Sensor corroded
3-digit number
If two or more diagnostics events are pending simultaneously, only the message with the highest
priority is shown. Additional pending diagnostic messages are shown in the Diagnostics list
submenu (®ä 73).
Past diagnostic messages that are no longer pending are shown in the Event logbook
submenu (®ä 74).
11.2.2
Overview of diagnostics events
Each diagnostics event is assigned a certain event level at the factory. The user can change this
assignment for certain diagnostics events.
Valid for diagnostics numbers 006, 041, 042, 043, 101 and 102.
The relevant sensor input for these diagnostics events can be identified by the Actual diag.
channel parameter or on the optional attachable display.
Status
signal
Diagno
stic
number
001Device malfunction Replace electronics.FAlarm
006Redundancy active 1. Check electrical wiring.
041Sensor broken1. Check electrical wiring.
042Sensor corroded1. Check electrical wiring of sensor.
043Short circuit1. Check electronic wiring.
044Sensor drift1. Check sensors.
045Working area1. Check ambient temperature.
101Sensor value too
Short textCorrective measure
Diagnostics for the sensor
2. Replace sensor.
3. Check connection type.
2. Replace sensor.
3. Check connection type.
2. Replace sensor.
2. Replace sensor.
2. Check process temperatures.
2. Check external reference measuring point.
1. Check process temperatures.
low
2. Inspect sensor.
3. Check sensor type.
from the
factory
Can be
changed
MWarning
FAlarm
MWarning
F
FAlarm
MWarning
F, S
FAlarm
FAlarm
Diagnostic
behavior
from the
factory
to
1)
1)
36Endress+Hauser
Page 37
iTEMP® TMT82
Diagnostics and troubleshooting
Status
signal
Diagno
stic
number
102Sensor value too
104Backup active1. Check electrical wiring of sensor 1.
105Calibration interval 1. Execute calibration and reset calibration interval.
106Backup not
201Device malfunction Replace electronics.FAlarm
221Reference
241Software1. Restart device.
261Electronic modules Replace electronics.FAlarm
262Module connection
283Memory contentReplace electronics.FAlarm
301Supply voltage1. Increase supply voltage.
401Factory resetPlease wait until the reset procedure is complete.CWarning
402InitializationPlease wait until the start-up procedure is complete.CWarning
411Up-/downloadPlease wait until the up-/download is complete.CWarning
431Factory
435Linearization1. Check configuration of sensor parameters.
437Configuration1. Check configuration of sensor parameters.
451Data processingPlease wait until data processing is complete.CWarning
483Simulation input
485Measured value
491Simulation current
Short textCorrective measure
1. Check process temperatures.
high
available
measurement
short circuit
calibration
simulation
output
2)
2. Inspect sensor.
3. Check sensor type.
2. Replace sensor 1.
3. Check connection type.
2. Switch off calibration counter.
1. Check electrical wiring of sensor 2.
2. Replace sensor 2.
3. Check connection type.
Diagnostics for the electronics
Replace electronics.FAlarm
2. Perform device reset.
3. Replace device.
1. Ensure that display module is correctly seated on the head
transmitter.
2. Test the display module using other suitable head
transmitters.
3. Display module defective? Replace module.
2. Check connection wires for corrosion.
Diagnostics for the configuration
Replace electronics.FAlarm
2. Check configuration of special sensor linearizion.
3. Contact service.
4. Replace electronics.
2. Check configuration of special sensor linearizion.
3. Check configuration of transmitter settings.
4. Contact service.
Deactivate simulation.CWarning
from the
factory
Can be
changed
FAlarm
MWarning
MWarning
F
MWarning
FAlarm
MWarning
FAlarm
FAlarm
FAlarm
Diagnostic
behavior
from the
factory
to
1)
Endress+Hauser37
Page 38
Diagnostics and troubleshooting
iTEMP® TMT82
Status
signal
Diagno
stic
number
803Current loop1. Check wiring.
842Process limit value Check scaling of analog output.MWarning
925Device
1)Diagnostic behavior can be changed in: "Alarm" or "Warning"
2)
Short textCorrective measure
Diagnostics for the process
2. Replace electronics.
Observe ambient temperature in accordance with
temperature
In the case of this diagnostics event, the device always issues a "low" alarm status (output current £ 3.6 mA).
specification.
from the
factory
Can be
changed
FAlarm
F, S
SWarning
F
Diagnostic
behavior
from the
factory
to
1)
11.3 Spare parts
Currently available spare parts for your product can be found online at:
http://www.products.endress.com/spareparts_consumables, HART® Temperature transmitter:
TMT82. When ordering spare parts, please quote the serial number of the device!
TypeOrder number
Standard - DIN securing set (2 screws and springs, 4 shaft lock-down rings, 1 plug for the display
interface)
US - M4 securing set (2 screws and 1 plug for the display interface)71044062
TID10 service cable; connecting cable for service interface, 40 cm71086650
Commubox FXA195 HART®, for intrinsically safe HART communication with FieldCare via the USB
interface.
Spare parts kit for DIN rail transmitter (terminals and DIN rail clips)71203361
71044061
FXA195-.......
11.4 Return
The measuring device must be returned if repairs or a factory calibration are required, or if the
wrong measuring device has been ordered or delivered. According to legal regulations, Endress
+Hauser, as an ISO-certified company, is required to follow certain procedures when handling
returned products that are in contact with medium.
To ensure swift, safe and professional device returns, please read the return procedures and
conditions on the Endress+Hauser website at www.services.endress.com/return-material
11.5
Disposal
The device contains electronic components and must therefore be disposed of as electronic waste.
Please pay particular attention to the national disposal regulations in your country.
38Endress+Hauser
Page 39
iTEMP® TMT82
Diagnostics and troubleshooting
11.6 Software history and overview of compatibility
Revision history
The firmware version (FW) on the nameplate and in the Operating Instructions indicates the
device release: XX.YY.ZZ (example 01.02.01).
XXChange to main version. No longer compatible. The device and Operating
Instructions change.
YYChange to functions and operation. Compatible. The Operating Instructions
change.
ZZFixes and internal changes. No changes to the Operating Instructions.
DateFirmware VersionModificationsDocumentation
01/111.00.zzOriginal firmwareBA01028T/09/en/13.10
10/121.00.zzNo changes to functions and operation.BA01028T/09/en/14.12
Endress+Hauser39
Page 40
Technical data
iTEMP® TMT82
12 Technical data
12.1
Input
Measured variableTemperature (temperature-linear transmission behavior), resistance and voltage.
Type of inputTwo independent sensors can be connected. The measuring inputs are not galvanically isolated
from each other.
Type of inputDesignationMeasuring range limitsMin. span
Resistance
thermometer (RTD)
as per IEC
60751:2008
(a = 0.003851)
as per JIS
C1604:1984
(a = 0.003916)
as per DIN 43760
IPTS-68
(a = 0.006180)
as per GOST 6651-94
(a = 0.003910) (for
Cu: a = 0.004280)
as per OIML R84:
2003
and GOST 6651-94
(a = 0.006170) (for
Cu: a = 0.004260)
as per OIML R84:
2003 (a = 0.004280)
Resistance
transmitter
Thermocouples
(TC)
to IEC 584 part 1
As per ASTM E988Type C (W5Re-W26Re)
to DIN 43710Type L (Fe-CuNi)
Pt100
Pt200
Pt500
Pt1000
Pt100–200 to +510 °C (–328 to +950 °F)10 K
Ni100
Ni120
Pt100
Pt50
Cu50
Cu50
Ni100
Ni120
Cu50–180 to +200 °C (–292 to +392 °F)10 K
Pt100 (Callendar van
Dusen)
Nickel polynomial
Copper polynomial
•
Type of connection: 2-wire, 3-wire or 4-wire connection, sensor current: £ 0.3 mA
•
With 2-wire circuit, compensation of wire resistance possible (0 to 30 W)
•
With 3-wire and 4-wire connection, sensor wire resistance up to max. 50 W per wire
Resistance W10 to 400 W
Type B (PtRh30-PtRh6)
Type E (NiCr-CuNi)
Type J (Fe-CuNi)
Type K (NiCr-Ni)
Type N (NiCrSi-NiSi)
Type R (PtRh13-Pt)
Type S (PtRh10-Pt)
Type T (Cu-CuNi)
Type D (W3Re-W25Re)
Type U (Cu-CuNi)
–200 to +850 °C (–328 to +1562 °F)
–200 to +850 °C (–328 to +1562 °F)
–200 to +500 °C (–328 to +932 °F)
–200 to +250 °C (–328 to +482 °F)
–60 to +250 °C (–76 to +482 °F)
–60 to +250 °C (–76 to +482 °F)
–200 to +850 °C (–328 to +1562 °F)
–185 to +1100 °C (–301 to +2012 °F)
–175 to +200 °C (–283 to +392 °F)
–50 to +200 °C (–58 to +392 °F)
–60 to +180 °C (–76 to +356 °F)
–60 to +180 °C (–76 to +356 °F)
The measuring range limits are specified by entering the limit values that depend on the
coefficients A to C and R0.
10 to 2000 W
Recommended temperature range:
+40 to +1820 °C (+104 to +3308 °F)
–270 to +1000 °C (–454 to +1832 °F)
–210 to +1200 °C (–346 to +2192 °F)
–270 to +1372 °C (–454 to +2501 °F)
–270 to +1300 °C (–454 to +2372 °F)
–50 to +1768 °C (–58 to +3214 °F)
–50 to +1768 °C (–58 to +3214 °F)
–260 to +400 °C (–436 to +752 °F)
0 to +2315 °C (+32 to +4199 °F)
0 to +2315 °C (+32 to +4199 °F)
–200 to +900 °C (–328 to +1652 °F)
–200 to +600 °C (–328 to +1112 °F)
+100 to +1500 °C (+212 to +2732 °F)
0 to +750 °C (+32 to +1382 °F)
+20 to +700 °C (+68 to +1292 °F)
0 to +1100 °C (+32 to +2012 °F)
0 to +1100 °C (+32 to +2012 °F)
0 to +1400 °C (+32 to +2552 °F)
0 to +1400 °C (+32 to +2552 °F)
–185 to +350 °C (–301 to +662 °F)
0 to +2000 °C (+32 to +3632 °F)
0 to +2000 °C (+32 to +3632 °F)
0 to +750 °C (+32 to +1382 °F)
–185 to +400 °C (–301 to +752 °F)
10 K
10 K
10 K
10 K
10 K
10 W
100 W
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
40Endress+Hauser
Page 41
iTEMP® TMT82
Type of inputDesignationMeasuring range limitsMin. span
• Internal cold junction (Pt100)
External cold junction: configurable value –40 to +85 °C (–40 to +185 °F)
•
•
Max. sensor resistance k10 kW (if sensor resistance is greater than 10 kW, an error message as per NAMUR NE89 is output)
Voltage transmitter
(mV)
Millivolt transmitter
(mV)
–20 to 100 mV5 mV
Technical data
The following connection combinations are possible when both sensor inputs are assigned:
Sensor input 1
Sensor input 2
RTD or resistance
transmitter, 2-wire
RTD or resistance
transmitter, 3-wire
RTD or resistance
transmitter, 4-wire
Thermocouple (TC),
voltage transmitter
RTD or
resistance
transmitter, 2-
wire
ÂÂ
ÂÂ
----
ÂÂÂÂ
RTD or
resistance
transmitter, 3-
wire
RTD or
resistance
transmitter, 4-
wire
-
-
Thermocouple
(TC), voltage
transmitter
Â
Â
Output signal
Failure information
12.2 Output
Analog output4 to 20 mA, 20 to 4 mA (can be inverted)
Signal encodingFSK ±0.5 mA via current signal
Data transmission rate1200 baud
Galvanic isolationU = 2 kV AC (input/output)
Failure information as per NAMUR NE43:
Failure information is created if the measuring information is missing or not valid. A complete list
of all the errors occurring in the measuring system is created.
UnderrangingLinear drop from 4.0 to 3.8 mA
OverrangingLinear increase from 20.0 to 20.5 mA
Failure, e.g. sensor breakage, sensor short-circuit≤ 3.6 mA ("low") or ≥ 21 mA ("high"), can be selected
The "high" alarm setting can be set between 21.5 mA and 23 mA,
thus providing the flexibility needed to meet the requirements of
various control systems.
Device address in multi-drop modeSoftware setting addresses 0 to 63
Device description files (DD)Information and files are available free of charge at:
Load (communication resistor)
A0014066-EN
www.endress.com
www.hartcomm.org
min.250 W
Write protection for device
parameters
Switch-on delay
Hardware: Write protection on optional display using DIP switch
•
• Software: Write protection using password
10 s, during switch-on delay Ia £ 3.8 mA
12.3 Power supply
Supply voltage
Current consumption• 3.6 to 23 mA
Residual ripplePermanent residual ripple Uss ≤ 3 V at Ub ≥ 13.5 V, f
Values for non-hazardous areas, protected against polarity reversal:
• Head transmitter
– 11 V ≤ Vcc ≤ 42 V (standard)
– I: < 22.5 mA
• DIN rail device
– 12 V ≤ Vcc ≤ 42 V (standard)
– I: < 22.5 mA
Values for hazardous areas, see Ex documentation (®ä 50).
Minimum current consumption 3.5 mA, multidrop mode 4 mA
•
• Current limit ≤ 23 mA
max.
= 1 kHz
42Endress+Hauser
Page 43
iTEMP® TMT82
Technical data
12.4 Accuracy
Response time
The measured value update depends on the type of sensor and connection method and moves
within the following ranges:
Resistance thermometer (RTD)0.9 to 1.2 s (depends on the connection method 2/3/4-wire)
Thermocouples (TC)0.7 s
Reference temperature0.5 s
When recording step responses, it must be taken into account that the times for the
measurement of the second channel and the internal reference measuring point are added to
the specified times where applicable.
Reference conditions• Calibration temperature: +25 °C ±5 K (77 °F ±9 °F)
Supply voltage: 24 V DC
•
• 4-wire circuit for resistance adjustment
Maximum measured errorThe data concerning the various measured errors are typical values and correspond to a standard
deviation of ±3 s (normal distribution), i.e. 99.8 % of all the measured values achieve the given
values or better values.
–20 to 100 mVThermocouples type: B, C, D, E, J, K, L, N, R, S, T, U
Sensor transmitter matching
RTD sensors are one of the most linear temperature measuring elements. Nevertheless, the output
must be linearized. To significantly improve temperature measurement accuracy, the device
allows the use of two methods:
Endress+Hauser43
Page 44
Technical data
iTEMP® TMT82
• Callendar-Van-Dusen coefficients (Pt100 resistance thermometer)
The Callendar-Van-Dusen equation is described as:
The coefficients A, B and C are used to match the sensor (platinum) and transmitter in order to
improve the accuracy of the measuring system. The coefficients for a standard sensor are
specified in IEC 751. If no standard sensor is available or if greater accuracy is required, the
coefficients for each sensor can be determined specifically with the aid of sensor calibration.
Linearization for copper/nickel resistance thermometers (RTD)
•
The polynomial equation for copper/nickel is as follows:
The coefficients A and B are used for the linearization of nickel or copper resistance
thermometers (RTD). The exact values of the coefficients derive from the calibration data and
are specific to each sensor. The sensor-specific coefficients are then sent to the transmitter.
Sensor transmitter matching using one of the methods explained above significantly improves the
temperature measurement accuracy of the entire system. This is because the transmitter uses the
specific data pertaining to the connected sensor to calculate the measured temperature, instead of
using the standardized sensor curve data.
Current output adjustment
Non-repeatability
Influence of the supply
voltage
1-point adjustment (offset)
Shifts the sensor value
2-point adjustment (sensor trimming)
Correction (slope and offset) of the measured sensor value at transmitter input
Data under reference operating conditions. % refers to the set span. The larger value is valid.
Influence of ambient
Total temperature drift = input temperature drift + output temperature drift
temperature (temperature
drift)
Impact on accuracy when ambient temperature changes by 1 K (1.8 °F):
Input10 to 400WTyp. 0.001 % of the measured value, min. 1 mW
Input10 to 2000 WTyp. 0.001 % of the measured value, min. 10 mW
Input–20 to 100 mVTyp. 0.001 % of the measured value, min. 0.2 µV
Output4 to 20 mATyp. 0.0015 % of the span
44Endress+Hauser
Page 45
iTEMP® TMT82
Technical data
Typical sensitivity of resistance thermometers:
Pt: 0.00385 * R
Example Pt100: 0.00385 * 100 W/K = 0.385 W/K
Typical sensitivity of thermocouples:
Type B:
9 µV/K at
1000 °C (1832 °F)
Type L:
60 µV/K at
500 °C (932 °F)
/KCu: 0.0043 * R
nom
Type C:
18 µV/K at
1000 °C (1832 °F)
Type N:
38 µV/K at
500 °C (932 °F)
Type D:
20 µV/K at
1000 °C (1832 °F)
Type R:
13 µV/K at
1000 °C (1832 °F)
/KNi: 0.00617 * R
nom
Type E:
81 µV/K at
500 °C (932 °F)
Type S:
11 µV/K at
1000 °C (1832 °F)
Type J:
56 µV/K at
500 °C (932 °F)
Type T:
46 µV/K at
100 °C (212 °F)
nom
/K
Type K:
43 µV/K at
500 °C (932 °F)
Type U:
70 µV/K at
500 °C (932 °F)
Example of calculating the measured error with ambient temperature drift:
Input temperature drift DJ = 10 K (18 °F), Pt100, measuring range 0 to 100 °C (32 to 212 °F).
Maximum process temperature: 100 °C (212 °F)
Measured resistance value: 138.5 W (IEC 60751) at maximum process temperature
Typical temperature drift in W: (0.001 % of 138.5 W) * 10 = 0.01385 W
Conversion to Kelvin: 0.01385 W / 0.385 W/K = 0.04 K (0.072 °F)
Output temperature drift:
0.0015 % of span * 10
•
• 0.0015 % * 100 K * 10 = 0.015 K
Total temperature drift = 0.04 K + 0.015 K = 0.055 K (current output)
Influence of the reference
Pt100 DIN IEC 60751 Cl. B (internal cold junction with thermocouples TC)
junction (internal cold
junction)
12.5 Environment
Ambient temperature
Storage temperature• Head transmitter: –50 to +100 °C (–58 to +212 °F)
AltitudeUp to 4000 m (4374.5 yards) above mean sea level as per IEC 61010-1, CAN/CSA C22.2 No.
–40 to +85 °C (–40 to +185 °F), for hazardous areas see Ex documentation (®ä 50)
DIN rail device: –40 to +100 °C (–40 to +212 °F)
•
61010-1
Climate classAs per IEC 60654-1, Class C
Humidity• Condensation permitted as per IEC 60 068-2-33
Max. rel. humidity: 95% as per IEC 60068-2-30
•
Endress+Hauser45
Page 46
Technical data
iTEMP® TMT82
Degree of protection• With screw terminals: IP 20. In the installed state, it depends on the terminal head or field
housing used.
With spring terminals: IP 30
•
• When installing in field housing TA30A, TA30D or TA30H: IP 66/67 (NEMA Type 4x encl.)
• DIN rail device: IP 20
Shock and vibration
resistance
Head transmitter: 25 to 100 Hz for 4g (increased vibration stress), as per GL guideline, section
•
2, issue 3B, paragraph 9. Vibration and IEC 60068-2-27 and IEC 60068-2-6
• DIN rail device: 25 to 100 Hz for "0.7g" (increased vibration stress), as per GL guideline,
section 2, issue 3B, paragraph 9. Vibration and IEC 60068-2-27 and IEC 60068-2-6
Electromagnetic compatibility
(EMC)
CE compliance
Electromagnetic compatibility in accordance with all the relevant requirements of the EN 61326
series and NAMUR Recommendation EMC (NE21). For details refer to the Declaration of
Conformity. All tests were passed both with and without ongoing digital HART® communication.
ESD (electrostatic discharge)EN/IEC 61000-4-26 kV cont., 8 kV air
Electromagnetic fieldsEN/IEC 61000-4-30.08 to 2.7 GHz10 V/m
Burst (fast transients)EN/IEC 61000-4-42 kV
Surge (surge voltage)EN/IEC 61000-4-50.5 kV sym.
1 kV assym.
Conducted RFEN/IEC 61000-4-60.01 to 80 MHz10 V
Measuring categoryMeasuring category II as per IEC 61010-1. The measuring category is provided for measuring on
power circuits that are directly connected electrically with the low-voltage network.
Degree of contaminationPollution degree 2 as per IEC 61010-1.
46Endress+Hauser
Page 47
iTEMP® TMT82
24.1 (0.95)
33 (1.3)
Ø44 (1.73)
Ø7 (0.28)
Ø5 (0.2)
B
C
A
28.1 (1.11)
17.5 (0.69)
114.9 (4.52)
100 (3.94)
112.8 (4.44)
Technical data
12.6 Mechanical construction
Design, dimensions
Dimensions in mm (in)
Head transmitter
å 15
ASpring travel L ≥ 5 mm (not for US - M4 securing screws)
BFasteners for attachable measured value display
CInterface for contacting the measured value display
Version with screw terminals
A0007301
A0007672
å 16
Version with spring terminals. The dimensions are identical to the version with screw terminals, apart from the
housing height.
DIN rail transmitter
A0017808
Endress+Hauser47
Page 48
Technical data
107.5 (4.23)
68.5 (2.7)
28
(1.1)
78 (3.1)
15.5 (0.6)
107.5 (4.23)
91.6 (3.61)
28
(1.1)
78 (3.1)
15.5 (0.6)
125 (4.92)
89.5 (3.52)
28
(1.1)
78 (3.01)
20.5 (0.8)
iTEMP® TMT82
Field housings
All terminal heads have an internal shape and size in accordance with DIN EN 50446, flat face
and a thermometer connection of M24x1.5. Cable glands as shown in figures: M20x1.5.
TA30ASpecification
• Two cable entries
Temperature: –50 to +150 °C (–58 to +302 °F) without
• Two head transmitters can be mounted. In the standard
version, one transmitter is mounted in the terminal head
cover and an additional terminal block is installed directly on
the insert.
• Head color: blue RAL 5012
• Cap color: gray RAL 7035
• Weight: 390 g (13.75 oz)
Technical data
A0009822
Maximum ambient temperature for cable glands
TypeTemperature range
Cable gland polyamide ½" NPT, M20x1.5 (non-Ex)–40 to +100 °C (–40 to 212 °F)
Cable gland polyamide M20x1.5 (for dust ignition-proof area)–20 to +95 °C (–4 to 203 °F)
Cable gland brass ½" NPT, M20x1.5 (for dust ignition-proof area)–20 to +130 °C (–4 to +266 °F)
Weight• Head transmitter: approx. 40 to 50 g (1.4 to 1.8 oz)
Field housing: see specifications
•
• DIN rail transmitter: approx. 100 g (3.53 oz)
MaterialAll materials used are RoHS-compliant.
Housing: polycarbonate (PC), complies with UL94, V-2 UL recognized
•
• Terminals:
– Screw terminals: nickel-plated brass and gold-plated contact
– Spring terminals (head transmitter): tin-plated brass, contact spring 1.4310, 301 (AISI)
• Potting (head transmitter): WEVO PU 403 FP / FL
Field housing: see specifications
Endress+Hauser49
Page 50
Technical data
TerminalsChoice of screw or spring terminals for sensor and fieldbus wires:
Flexible with wireend ferrules without
plastic ferrule
Flexible with wireend ferrules with
plastic ferrule
No ferrules have to be used when connecting flexible wires to spring terminals.
12.7 Certificates and approvals
iTEMP® TMT82
0.25 to 1.5 mm² (24 to 16 AWG)
0.25 to 0.75 mm² (24 to 18 AWG)
CE mark
The measuring system meets the legal requirements of the EC guidelines. The manufacturer
confirms that the device conforms to all relevant guidelines by affixing the CE mark.
Ex approvalInformation about currently available Ex versions (ATEX, FM, CSA, etc.) can be supplied by your
E+H Sales Center on request. All explosion protection data are given in separate documentation
which is available upon request.
Equipment safety ULEquipment safety as per UL61010-1, 2nd Edition
CSA GPCAN/CSA-C22.2 No. 61010-1, 2nd Edition
HART® communication
The temperature transmitter is registered by HART® Communication. The device meets the
requirements of the HART® Communication Protocol Specifications, April 2001, Revision 6.0.
12.8 Documentation
ATEX supplementary documentation:
ATEX II 1G Ex ia IIC: XA00102T/09/a3
ATEX II2G Ex d IIC: XA01007T/09/a3 (transmitter in field housing)
ATEX II2(1)G Ex ia IIC: XA01012T/09/a3 (transmitter in field housing)
50Endress+Hauser
Page 51
iTEMP® TMT82
Operating menu and parameter description
13 Operating menu and parameter description
The following table lists all parameters the menus "Display/operation, Setup, Diagnostics and
Expert" may contain. The page number refers to where a description of the parameter can be
found.
Depending on the device version and parametrization some parameters will not be available
in a given situation. For details on the conditions refer to the "Prerequisite" category in the
description of the respective parameter. All the configuration options of the menus "Display/
operation, Setup, Diagnostics" are available in the "Expert" setup mode as well as additional
parameters that are reserved for experienced users.
This symbol marks the navigation path to the parameter via an operating tool (e.g.
FieldCare).
The settings for displaying the measured value on the optional plug-in display (only for head
transmitter) are made in the "Display/Operation" menu. The following parameters can be found
in "Display/operation" and "Expert ® System ® Display".
These settings do not have any effect on the output values of the transmitter. They are only
used to configure how information is shown on the display.
Use this function to set the length of time the measured values are displayed if the values
alternate on the display. The display only alternates between values if more than one measured
value is defined.
• The Value 1 display - Value 3 display parameters are used to specify what measured
values are shown on the display (®ä 58).
The display format of the displayed measured values is specified using the Format display
•
parameter.
4 to 20 s
4 s
Display/operation ® Format display
Expert ® System ® Display ® Format display
Description
Options:
Factory settings
Endress+Hauser57
Use this function to select how the measured value is shown on the local display. The display
format Measured value or Measured value with bar graph can be configured.
• Value only
Value + Bargraph
•
Value only
Page 58
Operating menu and parameter description
iTEMP® TMT82
Additional information
Value only
A0014564
Value + Bargraph
A0014563
Value 1 display
Navigation
Description
Options:
Factory settings
Decimal places 1
Display/operation ® Value 1 display
Expert ® System ® Display ® Value 1 display
Use this function to select one of the measured values to be shown on the local display.
The Format display parameter is used to specify how the measured values are displayed
(®ä 57).
A measured value is specified in the Value 1 display parameter (®ä 58).
58Endress+Hauser
Page 59
iTEMP® TMT82
Operating menu and parameter description
Description
Options:
Factory settings
Value 2 display
Navigation
Description
Use this function to select the number of decimal places displayed for the display value. This
setting does not affect the accuracy of the device for measuring or calculating the value.
If Automatic is selected, the maximum possible number of decimal places is always shown
on the display.
• x
x.x
•
• x.xx
• x.xxx
• x.xxxx
• Automatic
Automatic
Display/operation ® Value 2 display
Expert ® System ® Display ® Value 2 display
Use this function to select one of the measured values to be shown on the local display.
The Format display parameter is used to specify how the measured values are displayed .
A measured value is specified in the Value 2 display parameter.
Use this function to select the number of decimal places displayed for the display value. This
setting does not affect the accuracy of the device for measuring or calculating the value.
If Automatic is selected, the maximum possible number of decimal places is always shown
on the display.
Endress+Hauser59
Page 60
Operating menu and parameter description
iTEMP® TMT82
Options:
Factory settings
Value 3 display
Navigation
Description
Options:
• x
x.x
•
• x.xx
• x.xxx
• x.xxxx
• Automatic
Automatic
Display/operation ® Value 3 display
Expert ® System ® Display ® Value 3 display
Use this function to select one of the measured values to be shown on the local display.
The Format display parameter is used to specify how the measured values are displayed.
A measured value is specified in the Value 3 display parameter.
Use this function to select the number of decimal places displayed for the display value. This
setting does not affect the accuracy of the device for measuring or calculating the value.
If Automatic is selected, the maximum possible number of decimal places is always shown
on the display.
• x
x.x
•
• x.xx
• x.xxx
• x.xxxx
• Automatic
Factory settings
60Endress+Hauser
Automatic
Page 61
iTEMP® TMT82
Unit
Operating menu and parameter description
13.2 "Setup" menu
This menu contains all the parameters that are needed to configure the basic settings of the
device. The transmitter can be put into operation with this limited parameter set.
n = Stands for the number of sensor inputs (1 and 2)
Navigation
Description
Options:
Factory settings
Sensor type n
Navigation
Description
Setup ® Unit
Expert ® System ® Unit
Use this function to select the engineering unit for all the measured values.
• °C
•
°F
• K
• °R
• Ohm
• mV
°C
Setup ® Sensor type n
Expert ® Sensor ® Sensor n ® Sensor type n
Use this function to select the sensor type for the sensor input in question.
Sensor type 1: settings for sensor input 1
•
• Sensor type 2: settings for sensor input 2
Please observe the terminal assignment (®å 7, ä 15) when connecting the individual
sensors. In the case of 2-channel operation, the possible connection options also have to be
observed.
Options:
Factory settings
Connection type n
Navigation
Prerequisite
Endress+Hauser61
A list of all the possible sensor types is provided in the 'Technical data' section (®ä 40).
Sensor type 1: Pt100 IEC751
Sensor type 2: No sensor
Setup ® Connection type n
Expert ® Sensor ® Sensor n ® Connection type n
An RTD sensor must be specified as the sensor type.
Page 62
Operating menu and parameter description
iTEMP® TMT82
Description
Options:
Factory settings
2-wire compensation n
Navigation
Prerequisite
Description
User input
Factory settings
Use this function to select the connection type for the sensor.
• Sensor 1 (connection type 1): 2-wire, 3-wire, 4-wire
Sensor 2 (connection type 2): 2-wire, 3-wire
•
• Sensor 1 (connection type 1): 4-wire
• Sensor 2 (connection type 2): 3-wire
Setup ® 2-wire compensation n
Expert ® Sensor ® Sensor n ® 2-wire compensation n
An RTD sensor with a 2-wire connection type must be specified as the sensor type.
Use this function to specify the resistance value for two-wire compensation in RTDs.
0 to 30 Ohm
0
Reference junction n
Navigation
Prerequisite
Description
Options:
Factory settings
Setup ® Reference junction n
Expert ® Sensor ® Sensor n ® Reference junction n
A thermocouple (TC) sensor must be selected as the sensor type.
Use this function to select reference junction measurement for temperature compensation of
thermocouples (TC).
• If Fixed value is selected, the compensation value is specified via the RJ preset value
parameter.
Temperature measurement must be configured for channel 2 if Sensor 2 value is
•
selected.
• No compensation: no temperature compensation is used.
• Internal measurement: the internal reference junction temperature is used.
• Fixed value: a fixed preset value is used.
• Sensor 2 value: the measured value of sensor 2 is used.
It is not possible to select the Sensor 2 value option for the Reference junction 2
parameter.
Internal measurement
RJ preset value n
62Endress+Hauser
Page 63
iTEMP® TMT82
Operating menu and parameter description
Navigation
Prerequisite
Description
User input
Factory settings
Assign current output (PV)
Navigation
Description
Options:
Setup ® RJ preset value
Expert ® Sensor ® Sensor n ® RJ preset value
The Fixed value parameter must be set if the Reference junction n option is selected.
Use this function to define the fixed preset value for temperature compensation.
–50 to +85 °C
0.00
Setup ® Assign current output (PV)
Expert ® Communication ® HART output ® Assign current output (PV)
Use this function to assign a measured variable to the primary HART® value (PV).
• Average of the two measured values: 0.5 x (SV1+SV2)
• Difference between sensor 1 and sensor 2: SV1-SV2
• Sensor 1 (backup sensor 2): If sensor 1 fails, the value of sensor 2 automatically becomes the
primary HART® value (PV): sensor 1 (OR sensor 2)
• Sensor switching: If the value exceeds the configured threshold value T for sensor 1, the
measured value of sensor 2 becomes the primary HART® value (PV). The system switches back
to sensor 1 when the measured value of sensor 1 is at least 2 K below T: sensor 1 (sensor 2, if
sensor 1 > T)
• Average: 0.5 x (SV1+SV2) with backup (measured value of sensor 1 or sensor 2 in the event of
a sensor error in the other sensor)
Factory settings
Lower range value
Navigation
Description
User input
Factory settings
The threshold value can be set with the Sensor switch set point (®ä 68) parameter.
With temperature-dependent switching, it is possible to combine 2 sensors that offer
advantages in different temperature ranges.
Sensor 1
Setup ® Lower range value
Expert ® Output ® Lower range value
Use this function to assign a measured value to the current value 4 mA.
The set point that can be set depends on the sensor type used in the Sensor type (®ä 61)
parameter and the measured variable assigned in the Assign current output (PV)
parameter.
Depends on the sensor type and the setting for "Assign current output (PV)."
0
Endress+Hauser63
Page 64
Operating menu and parameter description
Upper range value
iTEMP® TMT82
Navigation
Description
User input
Factory settings
Setup ® Upper range value
Expert ® Output ® Upper range value
Use this function to assign a measured value to the current value 20 mA.
The set point that can be set depends on the sensor type used in the Sensor type (®ä 61)
parameter and the measured variable assigned in the Assign current output (PV)
parameter.
Depends on the sensor type and the setting for "Assign current output (PV)."
100
13.2.1 "Advanced setup" submenu
Corrosion monitoring
Sensor connection cable corrosion can lead to false measured value readings. Therefore the unit
offers the possibility of recognizing any corrosion before a measured value is affected. Corrosion
monitoring is only possible for RTDs with a 4-wire connection and thermocouples.
Drift/difference mode
If two sensors are connected and the measured values differ by a specified value, a status signal is
generated as a diagnostic event. The drift/difference mode can be used to verify the correctness of
the measured values and for mutual monitoring of the connected sensors. The drift/difference
mode is enabled with the Drift/difference mode parameter. A distinction is made between two
specific modes. If the In band option is selected (ISV1-SV2I < drift/difference set point), a status
message is output if the value drops below the set point, or if the value exceeds the set point if the
Out band (drift) option is selected (ISV1-SV2I > drift/difference set point).
Procedure for configuring the drift/difference mode
1. Start
ß
2. For drift/difference monitoring, select Out band for drift detection and In band for difference monitoring.
ß
3. Set the alarm category for drift/difference monitoring to Out of specification (S), Maintenance required (M) or
Failure (F) as required.
ß
4. Set the set point for drift/difference monitoring to the desired value.
ß
5. End
64Endress+Hauser
Page 65
iTEMP® TMT82
D
t
0
L+
L-
D
t
0
L+
L-
AB
xx
å 17
AValue under range
BValue over range
DDrift
L+,L-Upper (+) or lower (-) set point
tTime
xDiagnostics event, status signal is generated
Drift/difference mode
Operating menu and parameter description
A0014782
Enter access code
Navigation
Description
User input
Factory settings
Access status tooling
Navigation
Setup ® Advanced setup ® Enter access code
Expert ® Enter access code
Use this function to enable the service parameters via the operating tool. If an incorrect access
code is entered, the user retains his current access authorization.
If a value is entered that is not to equal to the access code, the parameter is automatically set
to 0. The service parameters should only be modified by the service organization.
0 to 9999
0
Setup ® Advanced setup ® Access status tooling
Expert ® Access status tooling
Description
Additional information
Use this function to show access authorization to the parameters.
If additional write protection is active, this restricts the current access authorization even further.
The write protection status can be viewed via the Locking status parameter.
Options:
Factory settings
Endress+Hauser65
• Operator
•
Operator
Service
Page 66
Operating menu and parameter description
Device temperature alarm
iTEMP® TMT82
Navigation
Description
Options:
Factory settings
Device tag
Navigation
Description
Setup ® Advanced setup ® Device temperature alarm
Use this function to select the category (status signal) as to how the device reacts when the
electronics temperature of the transmitter exceeds or falls below the limit value < -40 °C (-40 °F)
or > +85 °C (+185 °F).
• Off
•
Out of specification (S)
• Failure (F)
Out of specification (S)
Setup ® Advanced setup ® Device tag
Diagnostics ® Device information ® Device tag
Expert ® Diagnostics ® Device information ® Device tag
Use this function to enter a unique name for the measuring point so it can be identified quickly
within the plant. The name is displayed in the header of the plug-in display. (®å 13, ä 23)
User input
Factory settings
Locking status
Navigation
Description
Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /)
-none-
Setup ® Advanced setup ® Locking status
Expert ® Locking status
Use this function to view the device locking status. The DIP switch for hardware locking is fitted
on the display module. When write protection is activated, write access to the parameters is
disabled. (®ä 24)
66Endress+Hauser
Page 67
iTEMP® TMT82
Sensor offset n
Operating menu and parameter description
"Sensor" submenu
n = Stands for the number of sensor inputs (1 and 2)
Navigation
Description
User input
Factory settings
Corrosion detection
Navigation
Description
Setup ® Advanced setup ® Sensor ® Sensor offset n
Expert ® Sensor ® Sensor n ® Sensor offset n
Use this function to set the zero point correction (offset) of the sensor measured value. The value
indicated is added to the measured value.
Use this function to choose whether the device reacts to the value exceeding or dropping below
the drift/difference set point.
Can only be selected for 2-channel operation.
• If the Out band (drift) option is selected, a status signal is displayed if the absolute value for
the differential value exceeds the drift/difference set point.
•
If the In band option is selected, a status signal is displayed if the absolute value for the
differential value drops below the drift/difference set point.
The Drift/difference mode parameter must be activated with the Out band (drift) or In band
option.
Use this function to select the category (status signal) as to how the device reacts when a drift/
difference is detected between sensor 1 and sensor 2.
• Out of specification (S)
•
Maintenance required (M)
• Failure (F)
Factory settings
Drift/difference set point
Navigation
Prerequisite
Description
Options:
Factory settings
Sensor switch set point
Maintenance required (M)
Setup ® Advanced setup ® Sensor ® Drift/difference set point
Expert ® Sensor ® Diagnostic settings ® Drift/difference set point
The Drift/difference mode parameter must be activated with the Out band (drift) or In band
option.
Use this function to configure the maximum permissible measured value deviation between
sensor 1 and sensor 2 which results in drift/difference detection.
1.0...999.0
999.0
Navigation
Description
68Endress+Hauser
Setup ® Advanced setup ® Sensor ® Sensor switch set point
Expert ® Sensor ® Diagnostic settings ® Sensor switch set point
Use this function to set the threshold value for sensor switching (®ä 63).
Page 69
iTEMP® TMT82
Operating menu and parameter description
Additional information
Options:
Factory settings
The threshold value is relevant if the sensor switching function is assigned to a HART® variable
(PV, SV, TV, QV).
Depends on the sensor types selected.
0.0 °C
"Current output" submenu
Adjustment of the analog output (4 and 20 mA current trimming)
Current trimming is used to compensate the analog output (D/A conversion). Here, the output
current of the transmitter can be adapted so that it suits the value expected at the higher-order
system.
NOTICE
Current trimming does not affect the digital HART® value. This can cause the measured
value shown on the plug-in display to differ from the value displayed in the higherorder system.
►
The digital measured values can be adapted with the sensor trimming parameter in the menu
Expert ® Sensor ® Sensor trimming.
Procedure
1. Start
ß
2. Install an accurate amperemeter (more accurate than the transmitter) in the current loop.
ß
3. Switch on current output simulation and set the simulation value to 4 mA.
ß
4. Measure the loop current with the amperemeter and make a note of the value.
ß
5. Set the simulation value to 20 mA.
ß
6. Measure the loop current with the amperemeter and make a note of the value.
ß
7. Enter the current values determined as adjustment values in the Current trimming 4 mA / 20 mA parameters.
ß
8. End
Output current
Navigation
Setup ® Advanced setup ® Current output® Output current
Expert ® Output ® Output current
Description
Use this function to view the calculated output current in mA.
Use this function to select the signal on alarm level of the current output in the event of an error.
If Max. is selected, the signal on alarm level is specified using the Failure current parameter.
• Min.
•
Max.
Factory settings
70Endress+Hauser
Max.
Page 71
iTEMP® TMT82
Failure current
Operating menu and parameter description
Navigation
Prerequisite
Description
User input
Factory settings
Current trimming 4 mA
Navigation
Description
User input
Setup ® Advanced setup ® Current output® Failure current
Expert ® Output ® Failure current
The Max. option is enabled in the Failure mode parameter.
Use this function to set the value the current output adopts in an alarm condition.
21.5 to 23.0 mA
22.5
Setup ® Advanced setup ® Current output® Current trimming 4 mA
Expert ® Output ® Current trimming 4 mA
Use this function to set the correction value for the current output at the start of the measuring
range at 4 mA (®ä 69).
3.85 to 4.15 mA
Factory settings
Current trimming 20 mA
Navigation
Description
User input
Factory settings
4 mA
Setup ® Advanced setup ® Current output® Current trimming 20 mA
Expert ® Output ® Current trimming 20 mA
Use this function to set the correction value for the current output at the end of the measuring
range at 20 mA (®ä 69).
19.850 to 20.15 mA
20.000 mA
Endress+Hauser71
Page 72
Operating menu and parameter description
13.3 "Diagnostics" menu
All the information that describes the device, the device status and the process conditions can be
found in this group.
Actual diagnostics 1
iTEMP® TMT82
Navigation
Description
Display
Additional information
Remedy information
Navigation
Description
Diagnostics ® Actual diagnostics
Expert ® Diagnostics ® Actual diagnostics 1
Use this function to display the current diagnostics message. If two or more messages occur
simultaneously, the message with the highest priority is shown on the display.
Symbol for event behavior and diagnostic event.
Example for display format:
F261-Electronic modules
Diagnostics ® Remedy information
Expert ® Diagnostics ® Remedy information
Use this function to display the remedial action to be taken for the current diagnostics message.
Use this function to display the last diagnostics message with the highest priority.
Symbol for event behavior and diagnostic event.
Example for display format:
F261-Electronic modules
Diagnostics ® Operating time
Expert ® Diagnostics ® Operating time
Use this function to display the length of time the device has been in operation up to now.
72Endress+Hauser
Page 73
iTEMP® TMT82
Operating menu and parameter description
Display
Actual diagnostics count
Navigation
Description
Actual diagnostics
Hours (h)
13.3.1 "Diagnostics list" submenu
Up to 3 diagnostics messages currently pending are displayed in this submenu. If more than 3
messages are pending, the messages with the highest priority are shown on the display.
Information on diagnostics measures in the device and an overview of all the diagnostics message
(®ä 33).
Diagnostics ® Diagnostics list ® Actual diagnostics count
Expert ® Diagnostics ® Diagnostics list ® Actual diagnostics count
Use this function to display the number of diagnostics messages currently pending in the device.
Navigation
Description
Display
Additional information
Actual diag channel
Navigation
Description
Display
Diagnostics ® Diagnostics list ® Actual diagnostics
Expert ® Diagnostics ® Diagnostics list ® Actual diagnostics
Use this function to display the current diagnostics messages with the highest priority to the thirdhighest priority.
Symbol for event behavior and diagnostic event.
Example for display format:
F261-Electronic modules
Diagnostics ® Diagnostics list ® Actual diag channel
Expert ® Diagnostics ® Diagnostics list ® Actual diag channel
Use this function to display the sensor input to which the diagnostics message refers.
• Sensor 1
•
Sensor 2
• - - - - - -
Endress+Hauser73
Page 74
Operating menu and parameter description
13.3.2 "Event logbook" submenu
Previous diagnostics n
n = Number of diagnostics messages (n = 1 to 5)
iTEMP® TMT82
Navigation
Description
Display
Additional information
Previous diag channel
Navigation
Description
Display
Diagnostics ® Diagnostics list ® Previous diagnostics n
Expert ® Diagnostics ® Diagnostics list ® Previous diagnostics n
Use this function to display the diagnostics messages that occurred in the past. The last 5
messages are listed in chronological order.
Symbol for event behavior and diagnostic event.
Example for display format:
F261-Electronic modules
Diagnostics ® Diagnostics list ® Previous diag channel
Expert ® Diagnostics ® Diagnostics list ® Previous diag channel
Use this function to display the possible sensor input to which the diagnostics message refers.
• Sensor 1
Sensor 2
•
• - - - - - -
74Endress+Hauser
Page 75
iTEMP® TMT82
Device tag (®ä 66)
Serial number
Operating menu and parameter description
13.3.3 "Device information" submenu
Navigation
Description
Display
Firmware Version
Navigation
Description
Display
Diagnostics ® Device information ® Serial number
Expert ® Diagnostics ® Device information ® Serial number
Use this function to display the serial number of the device. It can also be found on the
nameplate.
Uses of the serial number
•
To identify the device quickly, e.g. when contacting Endress+Hauser.
• To obtain specific information on the device using the Device Viewer:
www.endress.com/deviceviewer
Max. 11-digit character string comprising letters and numbers
Diagnostics ® Device information® Firmware version
Expert ® Diagnostics ® Device information ® Firmware version
Use this function to view the device firmware version installed.
Max. 6-digit character string in the format xx.yy.zz
Device name
Navigation
Description
Order code
Navigation
Endress+Hauser75
Diagnostics ® Device information ® Device name
Expert ® Diagnostics ® Device information ® Device name
Use this function to display the device name. It can also be found on the nameplate.
Diagnostics ® Device information ® Order code
Expert ® Diagnostics ® Device information® Order code
Page 76
Operating menu and parameter description
iTEMP® TMT82
Description
Configuration counter
Navigation
Description
Use this function to display the order code of the device. It can also be found on the nameplate.
The order code is generated from the extended order code, which defines all the device features
of the product structure. In contrast, the device features cannot be read directly from the order
code.
Uses of the order code
To order an identical spare device.
•
• To identify the device quickly and easily, e.g. when contacting the supplier.
Diagnostics ® Device information ® Configuration counter
Expert ® Diagnostics ® Device information ® Configuration counter
Use this function to display the counter reading for changes to device parameters.
Static parameters, whose values change during optimization or configuration, cause this
parameter to increment by 1. This supports parameter version management. If several
parameters change, e. g. due to loading of parameters from FieldCare, etc. in the device, the
counter can show a higher value. The counter can never be reset and is not reset to a default
value after a device reset. If the counter overflows, (16 bit), it starts again at 1.
Sensor n value
Navigation
Description
Device temperature
Navigation
Description
13.3.4 "Measured values" submenu
n = Stands for the number of sensor inputs (1 and 2)
Diagnostics ® Measured values ® Sensor n value
Expert ® Diagnostics ® Measured values ® Sensor n value
Use this function to display the current measured value at the sensor input.
Diagnostics ® Measured values ® Device temperature
Expert ® Diagnostics ® Measured values ® Device temperature
Use this function to display the current electronics temperature.
76Endress+Hauser
Page 77
iTEMP® TMT82
Sensor n min value
Operating menu and parameter description
"Min/max values" submenu
n = Stands for the number of sensor inputs (1 and 2)
Navigation
Description
Sensor n max value
Navigation
Description
Reset sensor min/max values
Diagnostics ® Measured values ® Min/max values ® Sensor n min value
Expert ® Diagnostics ® Measured values ® Min/max values ® Sensor n min value
Use this function to display the minimum temperature measured in the past at sensor input 1 or 2
(peakhold indicator).
n = Stands for the number of sensor inputs (1 and 2)
Diagnostics ® Measured values ® Min/max values ® Sensor n max value
Expert ® Diagnostics ® Measured values ® Min/max values ® Sensor n max value
Use this function to display the maximum temperature measured in the past at sensor input 1 or
2 (maximum indicator).
Resets the maximum indicators for the minimum and maximum electronic temperatures
measured.
• No
Yes
•
No
13.3.5 "Simulation" submenu
Diagnostics ® Simulation ® Simulation current output
Expert ® Diagnostics ® Simulation ® Simulation current output
Use this function to switch simulation of the current output on and off. The display alternates
between the measured value and a diagnostics message of the "function check" category (C) while
simulation is in progress.
Measured value display « C491 (simulation current output)
Options:
Factory settings
78Endress+Hauser
• Off
On
•
Off
Page 79
iTEMP® TMT82
Operating menu and parameter description
Additional information
Value current output
Navigation
Additional information
Description
User input
Factory settings
The simulation value is defined in the Value current output parameter.
Diagnostics ® Simulation ® Value current output
Expert ® Diagnostics ® Simulation ® Value current output
The Simulation current output parameter must be set to On.
Use this function to set a current value for the simulation. In this way, users can verify the correct
adjustment of the current output and the correct function of downstream switching units.
Use this function to reset the device configuration - either entirely or in part - to a defined state.
Not active
•
No action is executed and the user exits the parameter.
To factory defaults
•
All the parameters are reset to the factory setting.
To delivery settings
•
All the parameters are reset to the order configuration.The order configuration can differ from
the factory setting if customer-specific parameter values were defined when the device was
ordered.
Restart device
•
The device is restarted but the device configuration remains unchanged.
Not active
Endress+Hauser79
Page 80
Operating menu and parameter description
13.4 "Expert" menu
The parameter groups for the Expert setup contain all the parameters of the "Display/operation",
"Setup" and "Diagnostics" operating menus, as well as other parameters that are solely reserved
for experts.
iTEMP® TMT82
Damping
Navigation
Description
User input
Factory settings
Additional information
Alarm delay
13.4.1
Use this function to set the time constant for current output damping.
0 to 120 s
0.00 s
The current output reacts with an exponential delay to fluctuations in the measured value. The
time constant of this delay is specified by this parameter. If a low time constant is entered, the
current output reacts quickly to the measured value. On the other hand, if a high time constant is
entered, the current output reaction is delayed.
"System" submenu
Expert ® System ® Damping
Navigation
Description
User input
Factory settings
Mains filter
Navigation
Description
Options:
Factory setting
Expert ® System ® Alarm delay
Use this function to set the delay time during which a diagnostics signal is suppressed before it is
output.
0 to 5 s
2 s
Expert ® System ® Mains filter
Use this function to select the mains filter for A/D conversion.
• 50Hz
60Hz
•
50Hz
80Endress+Hauser
Page 81
iTEMP® TMT82
Device temperature alarm (®ä 66)
Operating menu and parameter description
Navigation
Serial no. sensor
Navigation
Description
User input
Factory settings
Expert ® System ® Device temperature alarm (parameter)
"Display" submenu
(®ä 57)
13.4.2
Use this function to enter the serial number of the connected sensor.
String with up to 12 characters consisting of numbers and/or text
" " (no text)
"Sensor" submenu
Expert ® Sensor ® Sensor n ® Serial no. sensor
Sensor n lower limit
Navigation
Description
Sensor n upper limit
Navigation
Description
"Sensor 1/2" submenu
n = Stands for the number of sensor inputs (1 and 2)
Expert ® Sensor ® Sensor n ® Sensor n lower limit
Displays the minimum physical full scale value.
Expert ® Sensor ® Sensor n ® Sensor n upper limit
Displays the maximum physical full scale value.
"Sensor trimming" submenu
Sensor error adjustment (sensor trimming)
Sensor trimming is used to adapt the actual sensor signal to the linearization of the selected sensor
type stored in the transmitter. Compared to sensor transmitter matching, sensor trimming only
takes place at the start and end value and does not achieve the same level of accuracy.
Endress+Hauser81
Page 82
Operating menu and parameter description
Sensor trimming does not adapt the measuring range. It is used to adapt the sensor signal to
the linearization stored in the transmitter.
Procedure
3. Using a water/oil bath or a furnace, bring the sensor connected to the transmitter to a known and stable temperature.
4. Enter the reference temperature for the value at the start of the measuring range for the Sensor trimming lower
value parameter. Based on the difference between the predefined reference temperature and the temperature actually
measured at the input, the transmitter internally calculates a correction factor which is now used to linearize the input
5. Using a water/oil bath or furnace, bring the sensor connected to the transmitter to a known and stable temperature
6. Enter the reference temperature for the value at the end of the measuring range for the Sensor trimming upper
iTEMP® TMT82
1. Start
ß
2. Set the Sensor trimming parameter to the User trim settings setting.
ß
A temperature which is close to the set start of the measuring range is recommended.
• Reset + run: Resets to the set start value and starts the calibration counter
Off
Use this function to select the category (status signal) as to how the device reacts to the set
calibration countdown.
• Maintenance required (M)
•
Failure (F)
• The countdown duration (in days) is specified with the Calibration counter start value
parameter.
The status signal issued when the limit value is reached is defined with the Calibration
Use this function to view the time remaining until the next calibration.
The countdown of the calibration counter is only running if the device is switched on.
Example: The calibration counter is set to 365 days on January 1st, 2011. If the device will
be switched off for 100 days, the calibration counter alarm is displayed on April 10th, 2012.
Page 87
iTEMP® TMT82
Measuring mode
Operating menu and parameter description
13.4.3 "Output" submenu
Navigation
Description
Additional information
Options:
Factory settings
Device tag (®ä 66)
Expert ® Output ® Measuring mode
Enables the inversion of the output signal.
Standard
•
The output current increases with increasing temperatures
Inverse
•
The output current decreases with increasing temperatures
• Standard
•
Inverse
Standard
13.4.4 "Communication" submenu
"HART configuration" submenu
Navigation
HART short tag
Navigation
Description
User input
Factory settings
HART address
Navigation
Expert ® Communication ® HART configuration ® Device tag
Expert ® Communication ® HART configuration ® HART short tag
Use this function to define a short tag for the measuring point.
Up to 8 alphanumeric characters (letters, numbers and special characters)
SHORTTAG
Expert ® Communication ® HART configuration ® HART address
Description
Endress+Hauser87
Use this function to define the HART address of the device.
Page 88
Operating menu and parameter description
iTEMP® TMT82
User input
Factory settings
Additional information
No. of preambles
Navigation
Description
User input
Factory settings
• For a system in accordance with HART 5.0:
0 to 15
For a system in accordance with HART 6.0:
•
0 to 63
0
The measured value can only be transmitted via the current value is the address is set to "0". The
current is fixed at 4.0 mA for all other addresses (Multidrop mode).
Expert ® Communication ® HART configuration ® No. of preambles
Use this function to define the number of preambles in the HART telegram.
2 ... 20
5
Burst mode
Navigation
Description
Options:
Factory settings
Burst command
Navigation
Prerequisite
Expert ® Communication ® HART configuration ® Burst mode
Use this function to switch the HART burst mode on or off.
Off
•
The device only sends data to the bus at the request of a HART master.
On
•
The device regularly sends data to the bus without being requested to do so.
Off
Expert ® Communication ® HART configuration ® Burst command
This parameter can only be selected if the Burst mode option is enabled.
Description
88Endress+Hauser
Use this function to select the command whose response is sent to the HART master in the burst
mode.
Page 89
iTEMP® TMT82
Operating menu and parameter description
Options:
Factory settings
Additional information
Burst variable slot n
• Command 1
Read out the primary variable
Command 2
•
Read out the current and the main measured value as a percentage
• Command 3
Read out the dynamic HART variables and the current
• Command 9
Read out the dynamic HART variables including the related status
• Command 33
Read out the dynamic HART variables including the related unit
Command 2
Commands 1, 2, 3 and 9 are universal HART commands.
Command 33 is a "Common-Practice" HART command.
More details on this are provided in the HART specifications.
n = Number of burst variable slots (0 to 3)
Navigation
Prerequisite
Description
Options:
Expert ® Communication ® HART configuration ® Burst variable slot n
This parameter can only be selected if the Burst mode option is enabled.
Use this function to assign a measured variable to slots 0 to 3.
This assignment is only relevant for the burst mode. The measured variables are assigned to
the 4 HART variables (PV, SV, TV, QV) in the HART output (®ä 92) menu.
• Sensor 1 (measured value)
•
Sensor 2 (measured value)
• Device temperature
• Average of the two measured values: 0.5 x (SV1+SV2)
• Difference between sensor 1 and sensor 2: SV1-SV2
• Sensor 1 (backup sensor 2): If sensor 1 fails, the value of sensor 2 automatically becomes the
primary HART® value (PV): sensor 1 (OR sensor 2)
• Sensor switching: If the value exceeds the configured threshold value T for sensor 1, the
measured value of sensor 2 becomes the primary HART® value (PV). The system switches back
to sensor 1 when the measured value of sensor 1 is at least 2 K below T: sensor 1 (sensor 2, if
sensor 1 > T)
The threshold value can be set with the Sensor switch set point parameter. With
temperature-dependent switching, it is possible to combine 2 sensors that offer advantages in
different temperature ranges.
Average: 0.5 x (SV1+SV2) with backup (measured value of sensor 1 or sensor 2 in the event of a
sensor error in the other sensor)
Factory settings
Endress+Hauser89
• Burst variable slot 0: sensor 1
•
Burst variable slot 1: device temperature
• Burst variable slot 2: sensor 1
• Burst variable slot 3: sensor 1
Page 90
Operating menu and parameter description
Configuration changed
iTEMP® TMT82
Navigation
Description
Indicates the change of configuration via a primary or a secondary master.
Reset Configuration Changed Flag
Navigation
Description
Reset of the information Configuration changed via a primary or secondary master.
"HART info" submenu
Device type
Navigation
Expert ® Communication ® HART configuration ® Configuration changed
Expert ® Communication ® HART configuration ® Reset Configuration Changed Flag
Expert ® Communication ® HART info ® Device type
Description
Display
Factory settings
Device revision
Navigation
Description
HART revision
Use this function to view the device type with which the device is registered with the HART
Communication Foundation. The device type is specified by the manufacturer. It is needed to
assign the appropriate device description file (DD) to the device.
2-digit hexadecimal number
0xcc
Expert ® Communication ® HART info ® Device revision
Use this function to view the device revision with which the device is registered with the HART
Communication Foundation. It is needed to assign the appropriate device description file (DD) to
the device.
®
Navigation
Description
Expert ® Communication ® HART info ® HART revision
Use this function to display the HART revision of the device.
90Endress+Hauser
Page 91
iTEMP® TMT82
HART descriptor
Operating menu and parameter description
Navigation
Description
User input
Factory settings
HART message
Navigation
Description
User input
Factory settings
Expert ® Communication ® HART info ® HART descriptor
Use this function to define a description for the measuring point.
Up to 32 alphanumeric characters (letters, numbers and special characters)
The device name
Expert ® Communication ® HART info ® HART message
Use this function to define a HART message which is sent via the HART protocol when requested
by the master.
Up to 32 alphanumeric characters (letters, numbers and special characters)
The device name
RevSW
Navigation
Description
HART date code
Navigation
Description
User input
Factory settings
Expert ® Communication ® HART info ® RevSW
Use this function to display the software revision of the device.
Expert ® Communication ® HART info ® HART date code
Use this function to define date information for individual use.
Date in the format year-month-day (YYYY-MM-DD)
2010-01-01
Endress+Hauser91
Page 92
Operating menu and parameter description
"HART output" submenu
Assign current output (PV)
iTEMP® TMT82
Navigation
Description
Options:
Factory settings
Expert ® Communication ® HART output ® Assign current output (PV)
Use this function to assign a measured variable to the primary HART value (PV).
• Sensor 1 (measured value)
•
Sensor 2 (measured value)
• Device temperature
• Average of the two measured values: 0.5 x (SV1+SV2)
• Difference between sensor 1 and sensor 2: SV1-SV2
• Sensor 1 (backup sensor 2): If sensor 1 fails, the value of sensor 2 automatically becomes the
primary HART® value (PV): sensor 1 (OR sensor 2)
• Sensor switching: If the value exceeds the configured threshold value T for sensor 1, the
measured value of sensor 2 becomes the primary HART® value (PV). The system switches back
to sensor 1 when the measured value of sensor 1 is at least 2 K below T: sensor 1 (sensor 2, if
sensor 1 > T)
• Average: 0.5 x (SV1+SV2) with backup (measured value of sensor 1 or sensor 2 in the event of
a sensor error in the other sensor)
The threshold value can be set with the Sensor switch set point parameter. With
temperature-dependent switching, it is possible to combine 2 sensors that offer advantages in
different temperature ranges.
Sensor 1
PV
Navigation
Description
Assign SV
Navigation
Description
Options:
Factory settings
Expert ® Communication ® HART output ® PV
Use this function to display the primary HART value.
Expert ® Communication ® HART output ® Assign SV
Use this function to assign a measured variable to the secondary HART value (SV).
See Assign current output (PV) parameter, (®ä 92)
Device temperature
SV
92Endress+Hauser
Page 93
iTEMP® TMT82
Operating menu and parameter description
Navigation
Description
Assign TV
Navigation
Description
Options:
Factory settings
TV
Expert ® Communication ® HART output ® SV
Use this function to display the secondary HART value.
Expert ® Communication ® HART output ® Assign TV
Use this function to assign a measured variable to the tertiary HART value (TV).
See Assign current output (PV) parameter, (®ä 92)
Sensor 1
Navigation
Description
Assign QV
Navigation
Description
Options:
Factory settings
QV
Expert ® Communication ® HART output ® TV
Use this function to display the tertiary HART value.
Expert ® Communication ® HART output ® Assign QV
Use this function to assign a measured variable to the quaternary (fourth) HART value (QV).
See Assign current output (PV) parameter, (®ä 92)
Sensor 1
Navigation
Description
Endress+Hauser93
Expert ® Communication ® HART output ® QV
Use this function to display the quaternary (fourth) HART value.
Page 94
Operating menu and parameter description
13.4.5 "Diagnostics" submenu
"Device information" submenu
Extended order code 1-3
iTEMP® TMT82
Navigation
Description
ENP-version
Navigation
Description
Display
Expert ® Diagnostics ® Device information ® Extended order code 1-3
Use this function to display the first, second and/or third part of the extended order code. On
account of length restrictions, the extended order code is split into a maximum of 3 parameters.
The extended order code indicates the version of all the features of the product structure for the
device and thus uniquely identifies the device. It can also be found on the nameplate.
Uses of the extended order code
•
To order an identical spare device.
• To check the ordered device features against the shipping note.
Expert ® Diagnostics ® Device information ® ENP version
Use this function to display the version of the electronic nameplate (ENP).
6-digit number in the format xx.yy.zz
Device revision
Navigation
Description
Display
Manufacturer ID
Navigation
Description
Display
Expert ® Diagnostics ® Device information ® Device revision
Expert ® Communication ® HART info ® Device revision
Use this function to view the device revision with which the device is registered with the HART
Communication Foundation. It is needed to assign the appropriate device description file (DD) to
the device.
2-digit hexadecimal number
Expert ® Diagnostics ® Device information ® Manufacturer ID
Use this function to view the manufacturer ID with which the device is registered with the HART
Communication Foundation.
2-digit hexadecimal number
94Endress+Hauser
Page 95
iTEMP® TMT82
Operating menu and parameter description
Factory settings
Manufacturer
Navigation
Description
Hardware revision
Navigation
Description
17
Expert ® Diagnostics ® Device information ® Manufacturer
Use this function to display the name of the manufacturer.
Expert ® Diagnostics ® Device information ® Hardware revision
Expert ® Communication ® HART info ® Hardware revision
Use this function to display the hardware revision of the device.
Sensor n raw value
Navigation
Description
"Measured values" submenu
n = Stands for the number of sensor inputs (1 and 2)
Expert ® Diagnostics ® Measured values ® Sensor n raw value
Use this function to display the non-linearized mV/Ohm value at the specific sensor input.