• Make sure the document is stored in a safe place such that it is always available when
working on or with the device.
• To avoid danger to individuals or the facility, read the "Basic safety instructions" section
carefully, as well as all other safety instructions in the document that are specific to
working procedures.
• The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser Sales Center will supply you with current information and updates to
these instructions.
2Endress+Hauser
Page 3
Proline Promag P 500 HARTTable of contents
Table of contents
1About this document ................ 6
1.1Document function ..................... 6
1.2Symbols used .......................... 6
1.2.1Safety symbols .................. 6
1.2.2Electrical symbols ................ 6
1.2.3Communication symbols ........... 6
1.2.4Tool symbols .................... 7
1.2.5Symbols for
certain types of information ......... 7
1.2.6Symbols in graphics ............... 7
1.3Documentation ........................ 8
1.3.1Standard documentation ........... 8
1.3.2Supplementary device-dependent
documentation .................. 8
1.4Registered trademarks ................... 8
2Basic safety instructions ............ 9
2.1Requirements for the personnel ............ 9
2.2Designated use ........................ 9
2.3Workplace safety ...................... 10
2.4Operational safety ..................... 10
2.5Product safety ........................ 10
2.6IT security ........................... 11
2.7Device-specific IT security ................ 11
These Operating Instructions contain all the information that is required in various phases
of the life cycle of the device: from product identification, incoming acceptance and
storage, to mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal.
1.2 Symbols used
1.2.1 Safety symbols
SymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will
result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.2.2 Electrical symbols
SymbolMeaning
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
1.2.3 Communication symbols
SymbolMeaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
LED
Light emitting diode is off.
6Endress+Hauser
Page 7
Proline Promag P 500 HARTAbout this document
A
1.
1.
-
SymbolMeaning
LED
Light emitting diode is on.
LED
Light emitting diode is flashing.
1.2.4 Tool symbols
SymbolMeaning
Torx screwdriver
Phillips head screwdriver
Open-ended wrench
1.2.5 Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Notice or individual step to be observed.
, 2., 3.…Series of steps.
Result of a step.
Help in the event of a problem.
Visual inspection.
1.2.6 Symbols in graphics
SymbolMeaning
1, 2, 3, ...Item numbers
, 2., 3., …Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Hazardous area
Endress+Hauser7
Page 8
About this documentProline Promag P 500 HART
.
SymbolMeaning
Safe area (non-hazardous area)
Flow direction
1.3 Documentation
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate
or scan the 2-D matrix code (QR code) on the nameplate.
For a detailed list of the individual documents along with the documentation code
→ 202
1.3.1 Standard documentation
Document typePurpose and content of the document
Technical InformationPlanning aid for your device
The document contains all the technical data on the device and provides
an overview of the accessories and other products that can be ordered for
the device.
Sensor Brief Operating Instructions Guides you quickly to the 1st measured value - Part 1
The Sensor Brief Operating Instructions are aimed at specialists with
responsibility for installing the measuring device.
• Incoming acceptance and product identification
• Storage and transport
• Installation
Transmitter Brief Operating
Instructions
Description of Device ParametersReference for your parameters
Guides you quickly to the 1st measured value - Part 2
The Transmitter Brief Operating Instructions are aimed at specialists with
responsibility for commissioning, configuring and parameterizing the
measuring device (until the first measured value).
• Product description
• Installation
• Electrical connection
• Operation options
• System integration
• Commissioning
• Diagnostic information
The document provides a detailed explanation of each individual
parameter in the Expert operating menu. The description is aimed at
those who work with the device over the entire life cycle and perform
specific configurations.
Additional documents are supplied depending on the device version ordered: Always
comply strictly with the instructions in the supplementary documentation. The
supplementary documentation is an integral part of the device documentation.
1.4 Registered trademarks
HART®
Registered trademark of the FieldComm Group, Austin, Texas, USA
8Endress+Hauser
Page 9
Proline Promag P 500 HARTBasic safety instructions
2 Basic safety instructions
2.1 Requirements for the personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill
the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function
‣
and task.
Are authorized by the plant owner/operator.
‣
Are familiar with federal/national regulations.
‣
Before starting work, read and understand the instructions in the manual and
‣
supplementary documentation as well as the certificates (depending on the
application).
Follow instructions and comply with basic conditions.
‣
The operating personnel must fulfill the following requirements:
Are instructed and authorized according to the requirements of the task by the facility's
‣
owner-operator.
Follow the instructions in this manual.
‣
2.2 Designated use
Application and media
The measuring device described in these Brief Operating Instructions is intended only for
flow measurement of liquids with a minimum conductivity of 5 µS/cm.
Depending on the version ordered, the measuring device can also measure potentially
explosive, flammable, poisonous and oxidizing media.
Measuring devices for use in hazardous areas, in hygienic applications or where there is an
increased risk due to process pressure, are labeled accordingly on the nameplate.
To ensure that the measuring device remains in proper condition for the operation time:
Keep within the specified pressure and temperature range.
‣
Only use the measuring device in full compliance with the data on the nameplate and
‣
the general conditions listed in the Operating Instructions and supplementary
documentation.
Based on the nameplate, check whether the ordered device is permitted for the
‣
intended use in the hazardous area (e.g. explosion protection, pressure vessel safety).
Use the measuring device only for media to which the process-wetted materials are
‣
sufficiently resistant.
If the measuring device is not operated at atmospheric temperature, compliance with
‣
the relevant basic conditions specified in the associated device documentation is
absolutely essential: "Documentation" section→ 8.
Protect the measuring device permanently against corrosion from environmental
‣
influences.
Incorrect use
Non-designated use can compromise safety. The manufacturer is not liable for damage
caused by improper or non-designated use.
WARNING
L
Danger of breakage due to corrosive or abrasive fluids!
Verify the compatibility of the process fluid with the sensor material.
‣
Ensure the resistance of all fluid-wetted materials in the process.
‣
Keep within the specified pressure and temperature range.
‣
Endress+Hauser9
Page 10
Basic safety instructionsProline Promag P 500 HART
NOTICE
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance
‣
in verifying the corrosion resistance of fluid-wetted materials, but does not accept any
warranty or liability as minute changes in the temperature, concentration or level of
contamination in the process can alter the corrosion resistance properties.
Residual risks
WARNING
L
The electronics and the medium may cause the surfaces to heat up. This presents a
burn hazard!
For elevated fluid temperatures, ensure protection against contact to prevent burns.
‣
2.3 Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national
‣
regulations.
For welding work on the piping:
Do not ground the welding unit via the measuring device.
‣
If working on and with the device with wet hands:
Due to the increased risk of electric shock, gloves must be worn.
‣
2.4 Operational safety
Risk of injury.
Operate the device in proper technical condition and fail-safe condition only.
‣
The operator is responsible for interference-free operation of the device.
‣
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
‣
Repair
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
‣
Observe federal/national regulations pertaining to repair of an electrical device.
‣
Use original spare parts and accessories from Endress+Hauser only.
‣
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet
state-of-the-art safety requirements, has been tested, and left the factory in a condition in
which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EU
directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser
confirms this by affixing the CE mark to the device.
10Endress+Hauser
Page 11
Proline Promag P 500 HARTBasic safety instructions
2.6 IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
2.7 Device-specific IT security
The device offers a range of specific functions to support protective measures on the
operator's side. These functions can be configured by the user and guarantee greater inoperation safety if used correctly. An overview of the most important functions is provided
in the following section.
Function/interfaceFactory settingRecommendation
Write protection via hardware write
protection switch → 11
Access code
(also applies for Web server login or
FieldCare connection) → 12
WLAN
(order option in display module)
WLAN security modeEnabled (WPA2-
WLAN passphrase
(password) → 12
WLAN modeAccess PointIndividually following risk assessment.
Web server→ 12Enabled.Individually following risk assessment.
CDI-RJ45 service interface → 12–Individually following risk assessment.
Not enabled.Individually following risk assessment.
Not enabled
(0000).
Enabled.Individually following risk assessment.
PSK)
Serial numberAssign an individual access code during
Assign an individual access code during
commissioning.
Do not change.
commissioning.
2.7.1 Protecting access via hardware write protection
Write access to the device parameters via the local display, Web browser or operating tool
(e.g. FieldCare, DeviceCare) can be disabled via a write protection switch (DIP switch on
the motherboard). When hardware write protection is enabled, only read access to the
parameters is possible.
Hardware write protection is disabled when the device is delivered → 134.
2.7.2 Protecting access via a password
Different passwords are available to protect write access to the device parameters or access
to the device via the WLAN interface.
• User-specific access code
Protect write access to the device parameters via the local display, Web browser or
operating tool (e.g. FieldCare, DeviceCare). Access authorization is clearly regulated
through the use of a user-specific access code.
• WLAN passphrase
The network key protects a connection between an operating unit (e.g. notebook or
tablet) and the device via the WLAN interface which can be ordered as an option.
Endress+Hauser11
Page 12
Basic safety instructionsProline Promag P 500 HART
User-specific access code
Write access to the device parameters via the local display, Web browser or operating tool
(e.g. FieldCare, DeviceCare) can be protected by the modifiable, user-specific access code
(→ 132).
When the device is delivered, the device does not have an access code and is equivalent to
0000 (open).
WLAN passphrase
A connection between an operating unit (e.g. notebook or tablet) and the device via the
WLAN interface (→ 84) which can be ordered as an option is protected by the
network key. The WLAN authentication of the network key complies with the IEEE 802.11
standard.
When the device is delivered, the network key is pre-defined depending on the device. It
can be changed via the WLAN settings submenu in the WLAN passphrase parameter
(→ 126).
General notes on the use of passwords
• The access code and network key supplied with the device should be changed during
commissioning.
• Follow the general rules for generating a secure password when defining and managing
the access code or network key.
• The user is responsible for the management and careful handling of the access code and
network key.
• For information on configuring the access code or on what to do if you lose the
password, see the "Write protection via access code" section → 132
2.7.3 Access via fieldbus
When communicating via fieldbus, access to the device parameters can be restricted to
"Read only" access. The option can be changed in the Fieldbus writing access parameter.
This does not affect cyclic measured value transmission to the higher-order system, which
is always guaranteed.
For detailed information, see the "Description of Device Parameters" document
pertaining to the device → 202
2.7.4 Access via Web server
The device can be operated and configured via a Web browser with the integrated Web
server (→ 76). The connection is via the service interface (CDI-RJ45) or the WLAN
interface.
The Web server is enabled when the device is delivered. The Web server can be disabled if
necessary (e.g. after commissioning) via the Web server functionality parameter.
The device and status information can be hidden on the login page. This prevents
unauthorized access to the information.
For detailed information, see the "Description of Device Parameters" document
pertaining to the device → 202
2.7.5 Access via CDI-RJ45 service interface
The device can be connected to a network via the CDI-RJ45 service interface. Devicespecific functions guarantee the secure operation of the device in a network.
It is advisable to take relevant security concepts into consideration, such as those issued by
the Federal Office for Information Security. This includes organizational security measures
12Endress+Hauser
Page 13
Proline Promag P 500 HARTBasic safety instructions
such as the assignment of access authorization as well as technical measures such as
network segmentation.
Endress+Hauser13
Page 14
Product descriptionProline Promag P 500 HART
5
2
-
+
-
ESC
1
4
3
3 Product description
The measuring system consists of a transmitter and a sensor. The transmitter and sensor
are mounted in physically separate locations. They are interconnected by one or two
connecting cable(s).
3.1 Product design
Two versions of the transmitter are available.
3.1.1 Proline 500 – digital
Signal transmission: digital
Order code for "Integrated ISEM electronics", option A "Sensor"
For use in applications not required to meet special requirements due to ambient or
operating conditions.
As the electronics are located in the sensor, the device is ideal:
For simple transmitter replacement.
• A standard cable can be used as the connecting cable.
• Not sensitive to external EMC interference.
1Important components of a measuring device
1Electronics compartment cover
2Display module
3Transmitter housing
4Sensor connection housing with integrated ISEM electronics: connecting cable connection
5Sensor
A0029593
14Endress+Hauser
Page 15
Proline Promag P 500 HARTProduct description
N
i
c
h
t
u
n
t
e
r
c
i
r
c
u
i
t
s
a
r
e
a
l
i
v
e
4
7
Nicht unter
Spannung öffnen
Do not open when
energized
Ne pas ouvrir
sous tension
Power
I/O
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
D
i
s
p
l
a
y
+
E
ESC
–
1
2
3
5
6
3.1.2 Proline 500
Signal transmission: analog
Order code for "Integrated ISEM electronics", option B "Transmitter"
For use in applications required to meet special requirements due to ambient or operating
conditions.
As the electronics are located in the transmitter, the device is ideal in the event of:
Incoming acceptance and product identificationProline Promag P 500 HART
1
2
1
2
Order code:
Ser. no.:
Ext. ord. cd.:
i
i
Date:
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
Are the order codes on the
A0028673
delivery note (1) and the
product sticker (2) identical?
Are the goods undamaged?
A0028673
Do the nameplate data
A0028673
A0028673
match the ordering
information on the delivery
note?
Is the CD-ROM with the
Technical Documentation
(depends on device version)
and documents present?
• If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center.
• Depending on the device version, the CD-ROM might not be part of the delivery!
The Technical Documentation is available via the Internet or via the Endress+HauserOperations App, see the "Product identification" section → 17.
4.2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is
displayed.
• Enter the serial number from the nameplates into the Endress+Hauser Operations App
or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser
16Endress+Hauser
Operations App: all the information for the measuring device is displayed.
Page 17
Proline Promag P 500 HARTIncoming acceptance and product identification
Order code:
Ser. no.:
Ext. ord. cd.:
i
i
Date:
1
4
5
6
7
891012
2
13
11
3
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The chapters "Additional standard documentation on the device" → 8 and
"Supplementary device-dependent documentation" → 8
• The W@M Device Viewer: Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or
scan the 2-D matrix code (QR code) on the nameplate.
4.2.1 Transmitter nameplate
Proline 500 – digital
3Example of a transmitter nameplate
1Name of the transmitter
2Manufacturing location
3Space for approvals: use in hazardous areas
4Degree of protection
5Electrical connection data: available inputs and outputs
6Permitted ambient temperature (Ta)
72-D matrix code
8Space for approvals and certificates: e.g. CE mark, C-Tick
9Permitted temperature range for cable
10 Manufacturing date: year-month
11 Firmware version (FW) and device revision (Dev.Rev.) from the factory
12 Document number of safety-related supplementary documentation
13 Space for additional information in the case of special products
14 Available inputs and outputs, supply voltage
15 Electrical connection data: supply voltage
16 Extended order code (Ext. ord. cd.)
17 Serial number (ser. no.)
18 Order code
A0029194
Endress+Hauser17
Page 18
Incoming acceptance and product identificationProline Promag P 500 HART
Order code:
Ser. no.:
Ext. ord. cd.:
i
i
Date:
1 23 4 5
6
7
8
9
13121011
Proline 500
4Example of a transmitter nameplate
1Manufacturing location
2Name of the transmitter
3Order code
4Serial number (ser. no.)
5Extended order code (Ext. ord. cd.)
6Degree of protection
7Space for approvals: use in hazardous areas
8Electrical connection data: available inputs and outputs
92-D matrix code
10 Manufacturing date: year-month
11 Document number of safety-related supplementary documentation
12 Space for approvals and certificates: e.g. CE mark, C-Tick
13 Space for degree of protection of connection and electronics compartment when used in hazardous areas
14 Firmware version (FW) and device revision (Dev.Rev.) from the factory
15 Space for additional information in the case of special products
16 Permitted temperature range for cable
17 Permitted ambient temperature (Ta)
18 Information on cable gland
19 Available inputs and outputs, supply voltage
20 Electrical connection data: supply voltage
A0029192
18Endress+Hauser
Page 19
Proline Promag P 500 HARTIncoming acceptance and product identification
Order code:
Ser. no.:
Ext. ord. cd.:
i
i
Date:
1
3
4
5
6
2
7
8
9
12
10
11
4.2.2 Sensor nameplate
A0029205
5Example of sensor nameplate
1Name of the sensor
2Manufacturing location
3Order code
4Serial number (ser. no.)
5Extended order code (Ext. ord. cd.)
6Flow; nominal diameter of the sensor; pressure rating; nominal pressure; system pressure; fluid temperature
range; material of liner and electrodes
7Approval information for explosion protection, Pressure Equipment Directive and degree of protection
8Document number of safety-related supplementary documentation → 202
92-D matrix code
10 Manufacturing date: year-month
11 Flow direction
12 CE mark, C-Tick
13 Permitted ambient temperature (Ta)
Order code
The measuring device is reordered using the order code.
Extended order code
• The device type (product root) and basic specifications (mandatory features) are
always listed.
• Of the optional specifications (optional features), only the safety and approvalrelated specifications are listed (e.g. LA). If other optional specifications are also
ordered, these are indicated collectively using the # placeholder symbol (e.g. #LA#).
• If the ordered optional specifications do not include any safety and approval-related
specifications, they are indicated by the + placeholder symbol (e.g. XXXXXX-ABCDE
+).
Endress+Hauser19
Page 20
Incoming acceptance and product identificationProline Promag P 500 HART
4.2.3 Symbols on measuring device
SymbolMeaning
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious
or fatal injury.
Reference to documentation
Refers to the corresponding device documentation.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
20Endress+Hauser
Page 21
Proline Promag P 500 HARTStorage and transport
5 Storage and transport
5.1 Storage conditions
Observe the following notes for storage:
Store in the original packaging to ensure protection from shock.
‣
Do not remove protective covers or protective caps installed on process connections.
‣
They prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
Protect from direct sunlight to avoid unacceptably high surface temperatures.
‣
Select a storage location where moisture cannot collect in the measuring device as
‣
fungus and bacteria infestation can damage the lining.
Store in a dry and dust-free place.
‣
Do not store outdoors.
‣
Storage temperature→ 186
5.2 Transporting the product
Transport the measuring device to the measuring point in the original packaging.
A0029252
Do not remove protective covers or caps installed on process connections. They
prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
5.2.1 Measuring devices without lifting lugs
WARNING
L
Center of gravity of the measuring device is higher than the suspension points of the
webbing slings.
Risk of injury if the measuring device slips.
Secure the measuring device against slipping or turning.
‣
Observe the weight specified on the packaging (stick-on label).
‣
A0029214
Endress+Hauser21
Page 22
Storage and transportProline Promag P 500 HART
5.2.2 Measuring devices with lifting lugs
CAUTION
L
Special transportation instructions for devices with lifting lugs
Only use the lifting lugs fitted on the device or flanges to transport the device.
‣
The device must always be secured at two lifting lugs at least.
‣
5.2.3 Transporting with a fork lift
If transporting in wood crates, the floor structure enables the crates to be lifted lengthwise
or at both sides using a forklift.
CAUTION
L
Risk of damaging the magnetic coil
If transporting by forklift, do not lift the sensor by the metal casing.
‣
This would buckle the casing and damage the internal magnetic coils.
‣
5.3 Packaging disposal
All packaging materials are environmentally friendly and 100% recyclable:
• Measuring device secondary packaging: polymer stretch film that conforms to EC
Directive 2002/95/EC (RoHS).
• Packaging:
– Wood crate, treated in accordance with ISPM 15 standard, which is confirmed by the
affixed IPPC logo.
or
– Carton in accordance with European Packaging Directive 94/62EC; recyclability is
confirmed by the affixed RESY symbol.
• Seaworthy packaging (optional): Wood crate, treated in accordance with ISPM 15
standard, which is confirmed by the affixed IPPC logo.
Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the
next pipe elbow: h ≥ 2 × DN
Installation in down pipes
Install a siphon with a vent valve downstream of the sensor in down pipes whose length h
≥ 5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of
damage to the measuring tube. This measure also prevents the system losing prime.
A0028981
6Installation in a down pipe
1Vent valve
2Pipe siphon
hLength of down pipe
Installation in partially filled pipes
A partially filled pipe with a gradient necessitates a drain-type configuration.
Endress+Hauser23
A0029257
Page 24
InstallationProline Promag P 500 HART
For heavy sensors DN ≥ 350 (14")
A0016276
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor
according to the flow direction (direction of medium flow through the piping).
OrientationRecommendation
AVertical orientation
A0015591
BHorizontal orientation, transmitter at
1)
top
A0015589
CHorizontal orientation, transmitter at
2) 3)
bottom
A0015590
DHorizontal orientation, transmitter at
side
A0015592
1)Applications with low process temperatures may decrease the ambient temperature. To maintain the
minimum ambient temperature for the transmitter, this orientation is recommended.
2)Applications with high process temperatures may increase the ambient temperature. To maintain the
maximum ambient temperature for the transmitter, this orientation is recommended.
3)To prevent the electronics module from overheating in the case of a sharp rise in temperature (e.g. CIP- or
SIP processes), install the device with the transmitter component pointing downwards.
Horizontal
• Ideally, the measuring electrode plane should be horizontal. This prevents brief
insulation of the two measuring electrodes by entrained air bubbles.
• Empty pipe detection only works if the transmitter housing is pointing upwards as
otherwise there is no guarantee that the empty pipe detection function will actually
respond to a partially filled or empty measuring tube.
24Endress+Hauser
Page 25
Proline Promag P 500 HARTInstallation
1
2
3
≥ 5 × DN
≥ 2 × DN
≥ 0 × DN
A0029344
1EPD electrode for empty pipe detection
2Measuring electrodes for signal detection
3Reference electrode for potential equalization
Measuring devices with tantalum or platinum electrodes can be ordered without an
EPD electrode. In this case, empty pipe detection is performed via the measuring
electrodes.
Inlet and outlet runs
If possible, install the sensor upstream from fittings such as valves, T-pieces or elbows.
Observe the following inlet and outlet runs to comply with accuracy specifications:
A0028997
7Order code for "Design", option A "Insertion length short, ISO/DVGW until DN400, DN450-2000 1:1" and
order code for "Design", option B "Insertion length long, ISO/DVGW until DN400, DN450-2000 1:1.3"
A0032859
8Order code for "Design", option C "Insertion length short ISO/DVGW until DN300, w/o inlet and outlet
runs, constricted meas.tube"
Installation dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section.
Endress+Hauser25
Page 26
InstallationProline Promag P 500 HART
L
6.1.2 Requirements from environment and process
Ambient temperature range
Transmitter• Standard: –40 to +60 °C (–40 to +140 °F)
• Optional: –50 to +60 °C (–58 to +140 °F) (order code for "Test,
certificate", option JN "Ambient temperature of transmitter –50 °C (–
58 °F)")
Local display–20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.
Sensor• Process connection material, carbon steel:
–10 to +60 °C (+14 to +140 °F)
• Process connection material, stainless steel:
–40 to +60 °C (–40 to +140 °F)
LinerDo not exceed or fall below the permitted temperature range of the liner .
If operating outdoors:
• Install the measuring device in a shady location.
• Avoid direct sunlight, particularly in warm climatic regions.
• Avoid direct exposure to weather conditions.
System pressure
A0028777
Never install the sensor on the pump suction side in order to avoid the risk of low pressure,
and thus damage to the liner.
Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps
are used.
• Information on the liner's resistance to partial vacuum → 188
• Information on the shock resistance of the measuring system → 187
• Information on the vibration resistance of the measuring system → 186
Vibrations
A0029004
9Measures to avoid device vibrations (L > 10 m (33 ft))
In the event of very strong vibrations, the pipe and sensor must be supported and fixed.
• Information on the shock resistance of the measuring system → 187
• Information on the vibration resistance of the measuring system → 186
26Endress+Hauser
Page 27
Proline Promag P 500 HARTInstallation
max.
100
10
0.5
d / D
[mbar]
0.60.70.80.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
Thermal insulation
Pipes generally have to be insulated if they carry very hot fluids to avoid energy losses and
prevent accidental contact with pipes at temperatures that could cause injury. Guidelines
regulating the insulation of pipes have to be taken into account.
WARNING
L
Electronics overheating on account of thermal insulation!
The housing support dissipates heat and its entire surface area must remain uncovered.
‣
Make sure that the sensor insulation does not extend past the top of the two sensor
half-shells.
A0031216
Adapters
Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor
in larger-diameter pipes. The resultant increase in the rate of flow improves measuring
accuracy with very slow-moving fluids. The nomogram shown here can be used to
calculate the pressure loss caused by reducers and expanders.
The nomogram only applies to liquids with a viscosity similar to that of water.
1.Calculate the ratio of the diameters d/D.
2.From the nomogram read off the pressure loss as a function of flow velocity
(downstream from the reduction) and the d/D ratio.
A0029002
Endress+Hauser27
Page 28
InstallationProline Promag P 500 HART
213 (8.4)
39 (1.5)
243 (9.6)
203 (8.0)
146 (5.75)
48 (1.9)
12 (0.47)
280 (11.0)255 (10.0)
134 (5.3)
30 (1.18)
6.1.3 Special mounting instructions
Protective cover
A0029552
10Weather protection cover for Proline 500 – digital
11Weather protection cover for Proline 500
6.2 Mounting the measuring device
6.2.1 Required tools
For transmitter
For mounting on a post:
• Proline 500 – digital transmitter
– Open-ended wrench AF 10
– Torx screwdriver TX 25
• Proline 500 transmitter
Open-ended wrench AF 13
For wall mounting:
Drill with drill bit ⌀ 6.0 mm
For sensor
For flanges and other process connections: Corresponding mounting tools
A0029553
28Endress+Hauser
Page 29
Proline Promag P 500 HARTInstallation
6.2.2 Preparing the measuring device
1.Remove all remaining transport packaging.
2.Remove any protective covers or protective caps present from the sensor.
3.Remove stick-on label on the electronics compartment cover.
6.2.3 Mounting the sensor
WARNING
L
Danger due to improper process sealing!
Ensure that the inside diameters of the gaskets are greater than or equal to that of the
‣
process connections and piping.
Ensure that the gaskets are clean and undamaged.
‣
Install the gaskets correctly.
‣
1.Ensure that the direction of the arrow on the sensor matches the flow direction of
the medium.
2.To ensure compliance with device specifications, install the measuring device
between the pipe flanges in a way that it is centered in the measurement section.
3.If using ground disks, comply with the Installation Instructions provided.
Screw tightening torques for EN 1092-1 (DIN 2501), PN 10/16/25, P245GH/stainless;
calculated according to EN 1591-1:2014 for flanges as per EN 1092-1:2013
6.2.4 Mounting the transmitter housing: Proline 500 – digital
CAUTION
L
Ambient temperature too high!
Danger of electronics overheating and housing deformation.
Do not exceed the permitted maximum ambient temperature → 26.
‣
If operating outdoors: Avoid direct sunlight and exposure to weathering, particularly in
‣
warm climatic regions.
CAUTION
L
Excessive force can damage the housing!
Avoid excessive mechanical stress.
‣
The transmitter can be mounted in the following ways:
• Post mounting
• Wall mounting
Endress+Hauser33
Page 34
InstallationProline Promag P 500 HART
ø 20…70
( 0.79…2.75)ø
~102 (~ 4.0)
4 x
SW 10
3 x
TX 25
149 (5.85)
211 (8.31)
=
5.8 (0.23)
17 (0.67)=
L
5.8 (0.23)
Post mounting
WARNING
L
Excessive tightening torque applied to the fixing screws!
Risk of damaging the plastic transmitter.
Tighten the fixing screws as per the tightening torque: 2 Nm (1.5 lbf ft)
‣
12Engineering unit mm (in)
Wall mounting
13Engineering unit mm (in)
LDepends on order code for "Transmitter housing"
A0029051
A0029054
Order code for "Transmitter housing"
• Option A, aluminum coated: L =14 mm (0.55 in)
• Option D, polycarbonate: L = 13 mm (0.51 in)
1.Drill the holes.
34Endress+Hauser
Page 35
Proline Promag P 500 HARTInstallation
20 (0.79)
100 (3.94)
100 (3.94)
! 8.6 (0.39)
! 18 (0.71)
! 10 (0.39)
2.Insert wall plugs into the drilled holes.
3.Screw in the securing screws slightly at first.
4.Fit the transmitter housing over the securing screws and mount in place.
5.Tighten the securing screws.
6.2.5 Mounting the transmitter housing: Proline 500
CAUTION
L
Ambient temperature too high!
Danger of electronics overheating and housing deformation.
Do not exceed the permitted maximum ambient temperature → 26.
‣
If operating outdoors: Avoid direct sunlight and exposure to weathering, particularly in
‣
warm climatic regions.
CAUTION
L
Excessive force can damage the housing!
Avoid excessive mechanical stress.
‣
The transmitter can be mounted in the following ways:
• Post mounting
• Wall mounting
Wall mounting
14Engineering unit mm (in)
1.Drill the holes.
2.Insert wall plugs into the drilled holes.
3.Screw in the securing screws slightly at first.
4.Fit the transmitter housing over the securing screws and mount in place.
5.Tighten the securing screws.
A0029068
Endress+Hauser35
Page 36
InstallationProline Promag P 500 HART
4 x
SW 13
!…(! 0.79 to 2.75)20 70
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
1.
2.
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
3.
3 mm4 mm
4.
Post mounting
WARNING
L
Order code for "Transmitter housing", option L "Cast, stainless": cast transmitters are
very heavy.
They are unstable if they are not mounted on a secure, fixed post.
Only mount the transmitter on a secure, fixed post on a stable surface.
‣
15Engineering unit mm (in)
6.2.6 Turning the transmitter housing: Proline 500
To provide easier access to the connection compartment or display module, the transmitter
housing can be turned.
1.Depending on the device version: Loosen the securing clamp of the connection
compartment cover.
36Endress+Hauser
2.Unscrew the connection compartment cover.
3.Release the fixing screw.
4.Turn the housing to the desired position.
5.Firmly tighten the securing screw.
6.Screw on the connection compartment cover
A0029057
A0029993
Page 37
Proline Promag P 500 HARTInstallation
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
1.
2.
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
3.
3 mm
+
E
ESC
–
7.Depending on the device version: Attach the securing clamp of the connection
compartment cover.
6.2.7 Turning the display module: Proline 500
The display module can be turned to optimize display readability and operability.
A0030035
1.Depending on the device version: Loosen the securing clamp of the connection
compartment cover.
2.Unscrew the connection compartment cover.
3.Turn the display module to the desired position: max. 8 × 45° in each direction.
4.Screw on the connection compartment cover.
5.Depending on the device version: Attach the securing clamp of the connection
compartment cover.
6.3 Post-installation check
Is the device undamaged (visual inspection)?
Does the measuring device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure (refer to the section on "Pressure-temperature ratings" in the "Technical
Information" document)
• Ambient temperature
• Measuring range
Has the correct orientation for the sensor been selected ?
• According to sensor type
• According to medium temperature
• According to medium properties (outgassing, with entrained solids)
Does the arrow on the sensor nameplate match the direction of flow of the fluid through the
piping ?
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected from precipitation and direct sunlight?
Have the fixing screws been tightened with the correct tightening torque?
Endress+Hauser37
Page 38
Electrical connectionProline Promag P 500 HART
7 Electrical connection
NOTICE
The measuring device does not have an internal circuit breaker.
For this reason, assign the measuring device a switch or power-circuit breaker so that
‣
the power supply line can be easily disconnected from the mains.
Although the measuring device is equipped with a fuse, additional overcurrent
‣
protection (maximum 10 A) should be integrated into the system installation.
7.1 Connection conditions
7.1.1 Required tools
• For cable entries: Use corresponding tools
• For securing clamp: Allen key 3 mm
• Wire stripper
• When using stranded cables: crimper for wire end ferrule
• For removing cables from terminal: Flat blade screwdriver ≤ 3 mm (0.12 in)
7.1.2 Requirements for connecting cable
The connecting cables provided by the customer must fulfill the following requirements.
Electrical safety
In accordance with applicable federal/national regulations.
Protective ground cable
Cable: 2.1 mm2 (14 AWG)
The grounding impedance must be less than 1 Ω.
Permitted temperature range
• The installation guidelines that apply in the country of installation must be observed.
• The cables must be suitable for the minimum and maximum temperatures to be
expected.
Power supply cable
Standard installation cable is sufficient.
Signal cable
Current output 4 to 20 mA HART
A shielded cable is recommended. Observe grounding concept of the plant.
Current output 0/4 to 20 mA
Standard installation cable is sufficient.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Double pulse output
Standard installation cable is sufficient.
38Endress+Hauser
Page 39
Proline Promag P 500 HARTElectrical connection
2
3
B
1
3
A
1
3
A
1
3
A
1
3
A
2
3
B
4
5
6
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm2 (24 to 12 AWG).
Choice of connecting cable between the transmitter and sensor
Depends on the type of transmitter and the installation zones
A0032477
1Proline 500 digital transmitter
2Proline 500 transmitter
3Promag sensor
4Non-hazardous area
5Hazardous area: Zone 2; Class I, Division 2
6Hazardous area: Zone 1; Class I, Division 1
AStandard cable to 500 digital transmitter → 39
Transmitter installed in the non-hazardous area or hazardous area: Zone 2; Class I, Division 2 / sensor
installed in the hazardous area: Zone 2; Class I, Division 2 or Zone 1; Class I, Division 1
BSignal cable to 500 transmitter → 40
Transmitter and sensor installed in the hazardous area: Zone 2; Class I, Division 2 oder Zone 1;
Class I, Division 1
A: Connecting cable between sensor and transmitter: Proline 500 – digital
Standard cable
Endress+Hauser39
A standard cable with the following specifications can be used as the connecting cable.
Page 40
Electrical connectionProline Promag P 500 HART
Design4 cores (2 pairs); uninsulated stranded CU wires; pair-stranded with common
5 m (15 ft), 10 m (32 ft), 20 m (65 ft) or variable length up to max.
200 m (656 ft)
≤ AC 1433 V rms 50/60 Hz or ≥ DC 2026 V
A0029151
Reinforced connecting cables
Reinforced connecting cables with an additional, reinforcing metal braid should be used
for:
• When laying the cable directly in the ground
• Where there is a risk of damage from rodents
Operation in zones of severe electrical interference
The measuring system meets the general safety requirements → 200 and EMC
specifications → 187.
Grounding is by means of the ground terminal provided for the purpose inside the
connection housing. The stripped and twisted lengths of cable shield to the ground
terminal must be as short as possible.
7.1.3 Terminal assignment
Transmitter: supply voltage, input/outputs
The terminal assignment of the inputs and outputs depends on the individual order
version of the device. The device-specific terminal assignment is documented on an
adhesive label in the terminal cover.
Device-specific terminal assignment: adhesive label in terminal cover.
Endress+Hauser41
Input/output
2
Input/output
3
Input/output
4
Page 42
Electrical connectionProline Promag P 500 HART
Transmitter and sensor connection housing: connecting cable
The sensor and transmitter, which are mounted in separate locations, are interconnected
by a connecting cable. The cable is connected via the sensor connection housing and the
transmitter housing.
Terminal assignment and connection of the connecting cable:
4.Transmitter: Connect signal cable and cable for supply voltage.
NOTICE
Insufficient sealing of the housing!
Operational reliability of the measuring device could be compromised.
Use suitable cable glands corresponding to the degree of protection.
‣
1.Remove dummy plug if present.
2.If the measuring device is supplied without cable glands:
Provide suitable cable gland for corresponding connecting cable.
3.If the measuring device is supplied with cable glands:
Observe requirements for connecting cables → 38.
42Endress+Hauser
Page 43
Proline Promag P 500 HARTElectrical connection
A
90 (3.54)*
70 (2.76)
50 (1.97)
10 (0.4)
8 (0.3)
B
A
80 (3.15)
50 (1.97)6 (0.24)
170 (6.7)*
20 (0.8)*
B
1
2
7.1.5 Preparing the connecting cable: Proline 500 – digital
When terminating the connecting cable, pay attention to the following points:
For cables with fine-wire cores (stranded cables):
‣
Fit the cores with ferrules.
TransmitterSensor
A0029330
A0029443
Engineering unit mm (in)
A = Terminate the cable
B = Fit ferrules on cables with fine-wire cores (stranded cables)
1 = Red ferrules, 1.0 mm (0.04 in)
2 = White ferrules, 0.5 mm (0.02 in)
* = Stripping only for reinforced cables
7.1.6 Preparing the connecting cable: Proline 500
When terminating the connecting cable, pay attention to the following points:
1.In the case of the electrode cable:
Make sure that the ferrules do not touch the core shields on the sensor side.
Minimum distance = 1 mm (exception: green “GND” cable)
2.In the case of the coil current cable:
Insulate one core of the three-core cable at the level of the core reinforcement. You
only require two cores for the connection.
3.For cables with fine-wire cores (stranded cables):
Fit the cores with ferrules.
Endress+Hauser43
Page 44
Electrical connectionProline Promag P 500 HART
A
80 (3.15)
50 (1.97)
8 (0.3)
100 (3.94)*
B
GND
1
2
1
2
1
2
2
A
90*(3.54)
70 (2.76)
50 (1.97)
10 (0.4)
8 (0.3)
B
A
80 (3.15)
50 (1.97)
6 (0.24)
170 (6.7)*
20 (0.8)*
18.5 (0.73)
B
GND
³1 (0.04)
1
2
2
2
1
A
70 (2.76)
50 (1.97)
10 (0.4)
8 (0.3)
160 (6.30)*20 (0.8)*
B
1
1
1
Transmitter
Electrode cableCoil current cable
A0029326
Sensor
Electrode cableCoil current cable
A0029329
Engineering unit mm (in)
A = Terminate the cable
B = Fit ferrules on cables with fine-wire cores (stranded cables)
1 = Red ferrules, 1.0 mm (0.04 in)
2 = White ferrules, 0.5 mm (0.02 in)
* = Stripping only for reinforced cables
44Endress+Hauser
A0029336
A0029337
Page 45
Proline Promag P 500 HARTElectrical connection
+–AB
61 62 63 64
+–AB
61 62 63 64
4
2
1
4
3
5
6
7.2 Connecting the measuring device: Proline 500 digital
NOTICE
Limitation of electrical safety due to incorrect connection!
Have electrical connection work carried out by appropriately trained specialists only.
‣
Observe applicable federal/national installation codes and regulations.
‣
Comply with local workplace safety regulations.
‣
Always connect the protective ground cable before connecting additional cables.
‣
For use in potentially explosive atmospheres, observe the information in the device-
‣
specific Ex documentation.
7.2.1 Connecting the connecting cable
WARNING
L
Risk of damaging the electronic components!
Connect the sensor and transmitter to the same potential equalization.
‣
Only connect the sensor to a transmitter with the same serial number.
‣
Ground the connection housing of the sensor via the external screw terminal.
‣
Connecting cable terminal assignment
1Cable entry for cable on transmitter housing
2Protective earth (PE)
3Connecting cable ISEM communication
4Grounding via ground connection; on device plug versions grounding is through the plug itself
5Cable entry for cable or connection of device plug on sensor connection housing
6Protective earth (PE)
Connecting the connecting cable to the sensor connection housing
Connection via terminals with order code for "Sensor connection housing":
– Option A "Aluminum, coated"→ 46
– Option L "Cast, stainless"→ 46
A0028198
The cable is connected to the transmitter via terminals → 47.
Endress+Hauser45
Connecting the connecting cable to the transmitter
Page 46
Electrical connectionProline Promag P 500 HART
2.
1.
3.
6.
5.
3 mm
10 (0.4)
TX 20TX 20
22 mm
7.
24 mm
Connecting the sensor connection housing via terminals
For the device version with the order code for "Sensor connection housing":
• Option A "Aluminum coated"
• Option L "Cast, stainless"
1.Loosen the securing clamp of the housing cover.
2.Unscrew the housing cover.
3.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4.Strip the cable and cable ends. In the case of stranded cables, fit ferrules.
5.Connect the protective ground.
6.Connect the cable in accordance with the connecting cable terminal assignment.
7.Firmly tighten the cable glands.
This concludes the process for connecting the connecting cable.
WARNING
L
Housing degree of protection voided due to insufficient sealing of the housing.
Screw in the thread on the cover without using any lubricant. The thread on the cover is
‣
coated with a dry lubricant.
8.Screw on the housing cover.
9.Tighten the securing clamp of the housing cover.
A0029616
46Endress+Hauser
Page 47
Proline Promag P 500 HARTElectrical connection
1.
3.
2.
4.
4 x
5.
7.
TX 20TX 20
6.
10 (0.4)
22 mm
8.
24 mm
Connecting the connecting cable to the transmitter
A0029597
1.Loosen the 4 fixing screws on the housing cover.
2.Open the housing cover.
3.Fold open the terminal cover.
4.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
5.Strip the cable and cable ends. In the case of stranded cables, fit ferrules.
6.Connect the protective ground.
7.Connect the cable in accordance with the connecting cable terminal assignment
→ 45.
8.Firmly tighten the cable glands.
This concludes the process for connecting the connecting cable.
9.Close the housing cover.
10. Tighten the securing screw of the housing cover.
11. After connecting the connecting cable:
Connect the signal cable and the supply voltage cable → 48.
Endress+Hauser47
Page 48
Electrical connectionProline Promag P 500 HART
12 3456
1.
3.
2.
4.
4 x
5.
7.
TX 20TX 20
6.
10 (0.4)
22 mm
8.
24 mm
7.2.2 Connecting the signal cable and the supply voltage cable
A0028200
1Terminal connection for supply voltage
2Terminal connection for signal transmission, input/output
3Terminal connection for signal transmission, input/output
4Terminal connection for connecting cable between sensor and transmitter
5Terminal connection for signal transmission, input/output; optional: connection for external WLAN antenna
6Protective earth (PE)
1.Loosen the 4 fixing screws on the housing cover.
2.Open the housing cover.
3.Fold open the terminal cover.
4.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
5.Strip the cable and cable ends. In the case of stranded cables, fit ferrules.
6.Connect the protective ground.
7.Connect the cable in accordance with the terminal assignment .
Signal cable terminal assignment: The device-specific terminal assignment is
documented on an adhesive label in the terminal cover.
Supply voltage terminal assignment: Adhesive label in the terminal cover or
→ 41.
8.Firmly tighten the cable glands.
This concludes the cable connection process.
9.Close the terminal cover.
10. Close the housing cover.
48Endress+Hauser
A0029597
Page 49
Proline Promag P 500 HARTElectrical connection
3 (0.12)
2.
1.
WARNING
L
Housing degree of protection may be voided due to insufficient sealing of the housing.
Screw in the screw without using any lubricant.
‣
WARNING
L
Excessive tightening torque applied to the fixing screws!
Risk of damaging the plastic transmitter.
Tighten the fixing screws as per the tightening torque: 2 Nm (1.5 lbf ft)
‣
11. Tighten the 4 fixing screws on the housing cover.
Removing a cable
A0029598
17Engineering unit mm (in)
1.To remove a cable from the terminal, use a flat-blade screwdriver to push the slot
between the two terminal holes
2.while simultaneously pulling the cable end out of the terminal.
Endress+Hauser49
Page 50
Electrical connectionProline Promag P 500 HART
42
41
GNDE1S1E2 S2SE
GNDE1 E2E
ER
+
+
ERERER
4567836 3742 41
4
5
7
37
n.c.n.c.
5
3
2
8
1
3
7
4
5
6
n.c.
7.3 Connecting the measuring device: Proline 500
NOTICE
Limitation of electrical safety due to incorrect connection!
Have electrical connection work carried out by appropriately trained specialists only.
‣
Observe applicable federal/national installation codes and regulations.
‣
Comply with local workplace safety regulations.
‣
Always connect the protective ground cable before connecting additional cables.
‣
For use in potentially explosive atmospheres, observe the information in the device-
‣
specific Ex documentation.
7.3.1 Connecting the connecting cable
WARNING
L
Risk of damaging the electronic components!
Connect the sensor and transmitter to the same potential equalization.
‣
Only connect the sensor to a transmitter with the same serial number.
‣
Ground the connection housing of the sensor via the external screw terminal.
‣
Connecting cable terminal assignment
1Protective earth (PE)
2Cable entry for coil current cable on transmitter connection housing
3Coil current cable
4Cable entry for signal cable on transmitter connection housing
5Signal cable
6Cable entry for signal cable on sensor connection housing
7Cable entry for coil current cable on sensor connection housing
8Protective earth (PE)
Connecting the connecting cable to the sensor connection housing
Connection via terminals with order code for "Housing":
Option A "Aluminum coated"→ 51
Connecting the connecting cable to the transmitter
The cable is connected to the transmitter via terminals → 52.
50Endress+Hauser
A0029145
Page 51
Proline Promag P 500 HARTElectrical connection
2.
1.
3.
6.
5.
3 mm
10 (0.4)
22 mm
7.
24 mm
Connecting the sensor connection housing via terminals
For the device version with the order code for "Housing":
• Option A "Aluminum coated"
• Option L "Cast, stainless"
1.Loosen the securing clamp of the housing cover.
2.Unscrew the housing cover.
3.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4.Strip the cable and cable ends. In the case of stranded cables, fit ferrules.
5.Connect the protective ground.
6.Connect the cable in accordance with the connecting cable terminal assignment.
7.Firmly tighten the cable glands.
This concludes the process for connecting the connecting cables.
WARNING
L
Housing degree of protection voided due to insufficient sealing of the housing.
Screw in the thread on the cover without using any lubricant. The thread on the cover is
‣
coated with a dry lubricant.
8.Screw on the housing cover.
9.Tighten the securing clamp of the housing cover.
A0029612
Endress+Hauser51
Page 52
Electrical connectionProline Promag P 500 HART
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
N
i
c
h
t
u
n
t
e
r
c
i
r
c
u
i
t
s
a
r
e
a
l
i
v
e
1.
2.
3.
6.
5.
10 (0.4)
3 mm
22 mm
7.
24 mm
Connecting the connecting cable to the transmitter
A0029592
1.Loosen the securing clamp of the connection compartment cover.
2.Unscrew the connection compartment cover.
3.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4.Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5.Connect the protective ground.
6.Connect the cable in accordance with the connecting cable terminal assignment
→ 50.
7.Firmly tighten the cable glands.
This concludes the process for connecting the connecting cables.
8.Screw on the connection compartment cover.
9.Tighten the securing clamp of the connection compartment cover.
10. After connecting the connecting cables:
Connect the signal cable and the supply voltage cable → 53.
52Endress+Hauser
Page 53
Proline Promag P 500 HARTElectrical connection
1
2
3
4
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
1.
2.
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
+
E
ESC
–
3.
3.
4.
3 mm
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
Nicht unter
Spannungöffnen
Do not open when
energized
Ne pas ouvrir
sous tension
Power
I/O
+
E
ESC
–
5.
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
Nicht unter
Spannung öffnen
Do not open when
energized
Ne pas ouvrir
sous tension
Power
I/O
+
E
ESC
–
Power
Nicht unter
Spannung öffnen
Do not open when
energized
Ne pas ouvrir
sous tension
I/O
6.
7.3.2 Connecting the signal cable and the supply voltage cable
A0026781
1Terminal connection for supply voltage
2Terminal connection for signal transmission, input/output
3Terminal connection for signal transmission, input/output or terminal connection for network connection via
service interface (CDI-RJ45)
4Protective earth (PE)
1.Loosen the securing clamp of the connection compartment cover.
2.Unscrew the connection compartment cover.
3.Squeeze the tabs of the display module holder together.
4.Remove the display module holder.
5.Attach the holder to the edge of the electronics compartment.
6.Open the terminal cover.
A0029813
A0029814
Endress+Hauser53
Page 54
Electrical connectionProline Promag P 500 HART
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
10 (0.4)
mm (in)
7.
8.
9.
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
+
E
ESC
–
10.
11.
22 mm
24 mm
A0029815
7.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
8.Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
9.Connect the protective ground.
10. Connect the cable in accordance with the terminal assignment .
Signal cable terminal assignment: The device-specific terminal assignment is
documented on an adhesive label in the terminal cover.
Supply voltage terminal assignment: Adhesive label in the terminal cover or
→ 41.
11. Firmly tighten the cable glands.
This concludes the cable connection process.
12. Close the terminal cover.
13. Fit the display module holder in the electronics compartment.
14. Screw on the connection compartment cover.
15. Secure the securing clamp of the connection compartment cover.
A0029816
54Endress+Hauser
Page 55
Proline Promag P 500 HARTElectrical connection
3 (0.12)
2.
1.
Removing a cable
A0029598
18Engineering unit mm (in)
1.To remove a cable from the terminal, use a flat-blade screwdriver to push the slot
between the two terminal holes
2.while simultaneously pulling the cable end out of the terminal.
7.4 Ensure potential equalization
7.4.1 Requirements
CAUTION
L
Electrode damage can result in the complete failure of the device!
Same electrical potential for the medium and sensor
‣
Company-internal grounding concepts
‣
Pipe material and grounding
‣
7.4.2 Connection example, standard scenario
Metal, grounded pipe
19Potential equalization via measuring tube
A0016315
7.4.3 Connection example in special situations
Unlined and ungrounded metal pipe
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present
Endress+Hauser55
Page 56
Electrical connectionProline Promag P 500 HART
DN 300≤DN 350≥
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
A0029338
20Potential equalization via ground terminal and pipe flanges
1.Connect both sensor flanges to the pipe flange via a ground cable and ground them.
2.If DN ≤ 300 (12"): Mount the ground cable directly on the conductive flange coating
of the sensor with the flange screws.
3.If DN ≥ 350 (14"): Mount the ground cable directly on the metal transport bracket.
Observe screw tightening torques: see the Sensor Brief Operating Instructions.
4.Connect the connection housing of the transmitter or sensor to ground potential by
means of the ground terminal provided for the purpose.
Plastic pipe or pipe with insulating liner
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
21Potential equalization via ground terminal and ground disks
1.Connect the ground disks to the ground terminal via the ground cable.
2.Connect the ground disks to ground potential.
Pipe with a cathodic protection unit
This connection method is only used if the following two conditions are met:
• Metal pipe without liner or pipe with electrically conductive liner
• Cathodic protection is integrated in the personal protection equipment
A0029339
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
56Endress+Hauser
Page 57
Proline Promag P 500 HARTElectrical connection
+
–
4
4...20 mA
5
2
1
3
6
A0029340
Prerequisite: The sensor is installed in the pipe in a way that provides electrical insulation.
1.Connect the two flanges of the pipe to one another via a ground cable.
2.Guide the shield of the signal lines through a capacitor.
3.Connect the measuring device to the power supply such that it is floating in relation
to the protective ground (isolation transformer).
7.5 Special connection instructions
7.5.1 Connection examples
Current output 4 to 20 mA HART
A0029055
22Connection example for 4 to 20 mA HART current output (active)
1Automation system with current input (e.g. PLC)
2Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
3Connection for HART operating devices → 83
4Resistor for HART communication (≥ 250 Ω): observe maximum load → 179
5Analog display unit: observe maximum load → 179
6Transmitter
Endress+Hauser57
Page 58
Electrical connectionProline Promag P 500 HART
2
3
4...20 mA
41
5
2
4...20 mA
4
1
2
3
3
6
5
4...20 mA
2
1
3
A0028762
23Connection example for 4 to 20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Power supply
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
24Connection example for HART input with a common negative (passive)
1Automation system with HART output (e.g. PLC)
2Active barrier for power supply (e.g. RN221N)
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
4Analog display unit: observe maximum load
5Pressure transmitter (e.g. Cerabar M, Cerabar S): see requirements
6Transmitter
Current output 4-20 mA
25Connection example for 4-20 mA current output (active)
1Automation system with current input (e.g. PLC)
2Analog display unit: observe maximum load
3Transmitter
A0028758
58Endress+Hauser
Page 59
Proline Promag P 500 HARTElectrical connection
2
4...20 mA
3
1
4
1
2
3
12345
1
2
3
A0028759
26Connection example for 4-20 mA current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply (e.g. RN221N)
3Analog display unit: observe maximum load
4Transmitter
Pulse/frequency output
27Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 180
Switch output
28Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 180
A0028761
A0028760
Endress+Hauser59
Page 60
Electrical connectionProline Promag P 500 HART
1
2
3
4
1
3
2
4
5
1
2
3
Double pulse output
A0029280
29Connection example for double pulse output (active)
1Automation system with relay input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 181
60Endress+Hauser
Page 61
Proline Promag P 500 HARTElectrical connection
31
4
2
1
2
3
Current input
A0028915
32Connection example for 4 to 20 mA current input
1Power supply
2External measuring device (for reading in pressure or temperature, for instance)
3Transmitter: Observe input values
Status input
33Connection example for status input
1Automation system with status output (e.g. PLC)
2Power supply
3Transmitter: Observe input values
7.6 Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection,
Type 4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following
steps after the electrical connection:
1.Check that the housing seals are clean and fitted correctly.
2.Dry, clean or replace the seals if necessary.
3.Tighten all housing screws and screw covers.
4.Firmly tighten the cable glands.
A0028764
Endress+Hauser61
Page 62
Electrical connectionProline Promag P 500 HART
5.To ensure that moisture does not enter the cable entry:
Route the cable so that it loops down before the cable entry ("water trap").
A0029278
6.Insert dummy plugs into unused cable entries.
7.7 Post-connection check
Are cables or the device undamaged (visual inspection)?
Do the cables used meet the requirements?
Do the cables have adequate strain relief?
Are all the cable glands installed, firmly tightened and leak-tight? Cable run with "water trap"
→ 61 ?
Is the potential equalization established correctly ?
62Endress+Hauser
Page 63
Proline Promag P 500 HARTOperation options
1
234
5
E+-
ESC
8 Operation options
8.1 Overview of operation options
A0034513
1Local operation via display module
2Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS
Device Manager, SIMATIC PDM)
3Field Xpert SFX350 or SFX370
5Mobile handheld terminal
6Control system (e.g. PLC)
Endress+Hauser63
Page 64
Operation optionsProline Promag P 500 HART
!
Expert
System
Sensor
Communication
Application
Diagnostics
Access status display
Output
Operating menu for experts
Language
OperatationLanguage
Parameter 1
Setup
Submenu 1
Submenu n
Device tag
Advanced setup
Enter access code
Parameter 1
Parameter n
Submenu 1
Submenu n
Diagnostics
Parameter 1
Parameter n
Submenu 1
Submenu n
Operating menu for operators and maintenances
Parameter n
Operator
Maintenance
Task-oriented
Function-oriented
Expert
Wizard 1 / Parameter 1
Wizard n / Parameter n
Parameter n
Input
8.2 Structure and function of the operating menu
8.2.1 Structure of the operating menu
For an overview of the operating menu for experts: "Description of Device Parameters"
document supplied with the device→ 202
64Endress+Hauser
34Schematic structure of the operating menu
A0018237-EN
Page 65
Proline Promag P 500 HARTOperation options
8.2.2 Operating philosophy
The individual parts of the operating menu are assigned to certain user roles (operator,
maintenance etc.). Each user role contains typical tasks within the device lifecycle.
Contains all parameters for error detection and analyzing process and device
errors:
• Diagnostic list
Contains up to 5 currently pending diagnostic messages.
• Event logbook
Contains event messages that have occurred.
• Device information
Contains information for identifying the device.
• Measured values
Contains all current measured values.
• Data logging submenu with "Extended HistoROM" order option
Storage and visualization of measured values
• Heartbeat
The functionality of the device is checked on demand and the verification
results are documented.
• Simulation
Is used to simulate measured values or output values.
Expertfunction-oriented Tasks that require detailed
knowledge of the function of the
device:
• Commissioning measurements
under difficult conditions
• Optimal adaptation of the
measurement to difficult
conditions
• Detailed configuration of the
communication interface
• Error diagnostics in difficult cases
Contains all the parameters of the device and makes it possible to access
these parameters directly using an access code. The structure of this menu is
based on the function blocks of the device:
• System
Contains all higher-order device parameters which do not concern the
measurement or the communication interface.
• Sensor
Configuration of the measurement.
• Input
Configuring the status input.
• Output
Configuring of the analog current outputs as well as the pulse/frequency
and switch output.
• Communication
Configuration of the digital communication interface and the Web server.
• Application
Configure the functions that go beyond the actual measurement (e.g.
totalizer).
• Diagnostics
Error detection and analysis of process and device errors and for device
simulation and Heartbeat Technology.
Endress+Hauser65
Page 66
Operation optionsProline Promag P 500 HART
XXXXXXXXX
1
3
l/h
1120.50
F
8.3 Access to the operating menu via the local display
8.3.1 Operational display
A0029346
1Operational display
2Device tag→ 96
3Status area
4Display area for measured values (4-line)
5Operating elements→ 71
Status area
The following symbols appear in the status area of the operational display at the top right:
• Status signals→ 152
– F: Failure
– C: Function check
– S: Out of specification
– M: Maintenance required
• Diagnostic behavior→ 153
–: Alarm
–: Warning
•: Locking (the device is locked via the hardware )
•: Communication (communication via remote operation is active)
Display area
In the display area, each measured value is prefaced by certain symbol types for further
description:
Measured variableMeasurement channel
number
↓↓↓
Example
Diagnostic behavior
Appears only if a diagnostics
event is present for this
measured variable.
Measured values
SymbolMeaning
Volume flow
Conductivity
66Endress+Hauser
Page 67
Proline Promag P 500 HARTOperation options
4
1
3
/../Operation
0091-1
Access stat.disp
Operator
Locking status
Display
S
4
2
1
5
3
/../Curr. output 1
Assign curr.
Volume flow
Mass flow
Totalizer
The measurement channel number indicates which of the three totalizers is
displayed.
Output
The measurement channel number indicates which of the outputs is displayed.
Status input
Measurement channel numbers
SymbolMeaning
Measurement channel 1 to 4
The measurement channel number is displayed only if more than one channel is present for the same measured
variable type (e.g. Totalizer 1 to 3).
Diagnostic behavior
The diagnostic behavior pertains to a diagnostic event that is relevant to the displayed measured variable.
For information on the symbols → 153
The number and display format of the measured values can be configured via the
Format display parameter (→ 110).
8.3.2 Navigation view
In the submenuIn the wizard
A0013993-EN
1
Navigation view
2
Navigation path to current position
3
Status area
4
Display area for navigation
5
Operating elements → 71
A0016327-EN
Navigation path
The navigation path - displayed at the top left in the navigation view - consists of the
following elements:
• In the submenu:
Display symbol for menu
Examples/ ../Display
• In the wizard:
Display symbol for wizard
↓↓↓
Omission symbol for
operating menu levels in
between
Name of current
• Submenu
• Wizard
• Parameters
Endress+Hauser67
Page 68
Operation optionsProline Promag P 500 HART
/ ../Display
For more information about the icons in the menu, refer to the "Display area" section
→ 68
Status area
The following appears in the status area of the navigation view in the top right corner:
• In the submenu
– The direct access code for the parameter you are navigating to (e.g. 0022-1)
– If a diagnostic event is present, the diagnostic behavior and status signal
• In the wizard
If a diagnostic event is present, the diagnostic behavior and status signal
• For information on the diagnostic behavior and status signal → 152
• For information on the function and entry of the direct access code → 73
Display area
Menus
SymbolMeaning
Operation
Appears:
• In the menu next to the "Operation" selection
• At the left in the navigation path in the Operation menu
Setup
Appears:
• In the menu next to the "Setup" selection
• At the left in the navigation path in the Setup menu
Diagnostics
Appears:
• In the menu next to the "Diagnostics" selection
• At the left in the navigation path in the Diagnostics menu
Expert
Appears:
• In the menu next to the "Expert" selection
• At the left in the navigation path in the Expert menu
Submenus, wizards, parameters
SymbolMeaning
Submenu
Wizard
Parameters within a wizard
No display symbol exists for parameters in submenus.
Locking
SymbolMeaning
Parameter locked
When displayed in front of a parameter name, indicates that the parameter is locked.
• By a user-specific access code
• By the hardware write protection switch
68Endress+Hauser
Page 69
Proline Promag P 500 HARTOperation options
+0.000 Xx
01234
+
5
67
8
9
–
Xxxxxxx
A B C D E F G HIJ K
M N O P Q RS T U V W
X YLZ
5
6
7
Wizard operation
SymbolMeaning
Switches to the previous parameter.
Confirms the parameter value and switches to the next parameter.
Opens the editing view of the parameter.
8.3.3 Editing view
Numeric editor
35For entering values in parameters (e.g. limit values)
1Entry display area
2Input screen
3Confirm, delete or reject entry
4Operating elements
Text editor
36For entering text in parameters (e.g. tag name)
1Entry display area
2Current input screen
3Change input screen
4Operating elements
5Move entry position
6Delete entry
7Reject or confirm entry
Close the editing view without accepting the changes.
Input screens
SymbolMeaning
Upper case
Lower case
Numbers
Punctuation marks and special characters: = + – * / ² ³ ¼ ½ ¾ ( ) [ ] < > { }
Punctuation marks and special characters: ' " `^. , ; : ? ! % µ ° € $ £ ¥ § @ # / \ I ~ & _
Umlauts and accents
Controlling data entries
SymbolMeaning
Move entry position
Reject entry
Confirm entry
Delete character immediately to the left of the entry position
Delete character immediately to the right of the entry position
Clear all the characters entered
70Endress+Hauser
Page 71
Proline Promag P 500 HARTOperation options
+
+
8.3.4 Operating elements
Operating key(s)Meaning
Minus key
In a menu, submenu
Moves the selection bar upwards in a choose list.
With a Wizard
Confirms the parameter value and goes to the previous parameter.
With a text and numeric editor
Move the entry position to the left.
Plus key
In a menu, submenu
Moves the selection bar downwards in a choose list.
With a Wizard
Confirms the parameter value and goes to the next parameter.
With a text and numeric editor
Move the entry position to the right.
Enter key
For operational display
• Pressing the key briefly opens the operating menu.
• Pressing the key for 2 s opens the context menu including the option for activating the
keypad lock.
In a menu, submenu
• Pressing the key briefly:
– Opens the selected menu, submenu or parameter.
– Starts the wizard.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s for parameter:
If present, opens the help text for the function of the parameter.
• Pressing the key briefly:
– Exits the current menu level and takes you to the next higher level.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s returns you to the operational display ("home position").
With a Wizard
Exits the wizard and takes you to the next higher level.
With a text and numeric editor
Close the editing view without accepting the changes.
Minus/Enter key combination (press the keys simultaneously)
Press the key for 3 s: deactivate the keypad lock.
8.3.5 Opening the context menu
Using the context menu, the user can call up the following menus quickly and directly from
the operational display:
• Setup
• Data backup
• Simulation
Endress+Hauser71
Page 72
Operation optionsProline Promag P 500 HART
XXXXXXXXXX
l/h
Setup
Conf.backup
Simulation
Keylock on
Calling up and closing the context menu
The user is in the operational display.
1.Press for 2 s.
The context menu opens.
A0034608-EN
2.Press + simultaneously.
The context menu is closed and the operational display appears.
Calling up the menu via the context menu
1.Open the context menu.
2.Press to navigate to the desired menu.
3.Press to confirm the selection.
The selected menu opens.
72Endress+Hauser
Page 73
Proline Promag P 500 HARTOperation options
X X X X X X XXX
20.50
0104-1
2 s
0091-1
0098-1
0098-1
0098-1
X X X X X X XXX
10.50
2800
Hz
mA
3.
4.
5.
6.
7.
8.
1.
2.
Display/operat.
Display/operat.
Setup
Main menu
English
Main menu
Format display
/ ../Display
Contrast display
Display intervall
1 value, max.
Setup
Access stat.disp
/ ../Display/operat.
Display
Locking status
1 value, max.
/ ../Format display
2 values
Val. large+2val.
Bargr. + 1 value
Locking status
/ ../Display/operat.
Display
1 value, max.
/ ../Format display
2 values
Val. large+2val.
Bargr. + 1 value
Operator
Language
Language
8.3.6 Navigating and selecting from list
Different operating elements are used to navigate through the operating menu. The
navigation path is displayed on the left in the header. Icons are displayed in front of the
individual menus. These icons are also shown in the header during navigation.
For an explanation of the navigation view with symbols and operating elements
→ 67
Example: Setting the number of displayed measured values to "2 values"
Endress+Hauser73
8.3.7 Calling the parameter directly
A parameter number is assigned to every parameter to be able to access a parameter
directly via the onsite display. Entering this access code in the Direct access parameter
calls up the desired parameter directly.
The direct access code consists of a 5-digit number (at maximum) and the channel
number, which identifies the channel of a process variable: e.g. 00914-2. In the navigation
view, this appears on the right-hand side in the header of the selected parameter.
A0029414
1Direct access code
Note the following when entering the direct access code:
• The leading zeros in the direct access code do not have to be entered.
Example: Enter "914" instead of "00914"
• If no channel number is entered, channel 1 is accessed automatically.
Example: Enter 00914 → Assign process variable parameter
• If a different channel is accessed: Enter the direct access code with the corresponding
channel number.
Example: Enter 00914-2 → Assign process variable parameter
For the direct access codes of the individual parameters, see the "Description of Device
Parameters" document for the device
8.3.8 Calling up help text
Help text is available for some parameters and can be called up from the navigation view.
The help text provides a brief explanation of the parameter function and thereby supports
swift and safe commissioning.
Calling up and closing the help text
The user is in the navigation view and the selection bar is on a parameter.
1.Press for 2 s.
The help text for the selected parameter opens.
A0014002-EN
37Example: Help text for parameter "Enter access code"
2.Press + simultaneously.
The help text is closed.
8.3.9 Changing the parameters
Parameters can be changed via the numeric editor or text editor.
• Numeric editor: Change values in a parameter, e.g. specifications for limit values.
• Text editor: Enter text in a parameter, e.g. tag name.
A message is displayed if the value entered is outside the permitted value range.
74Endress+Hauser
Page 75
Proline Promag P 500 HARTOperation options
Ent.accesscode
Invalidoroutofrangeinput
value
Max:9999
Min:0
A0014049-EN
For a description of the editing view - consisting of the text editor and numeric editor
- with symbols → 69, for a description of the operating elements → 71
8.3.10 User roles and related access authorization
The two user roles "Operator" and "Maintenance" have different write access to the
parameters if the customer defines a user-specific access code. This protects the device
configuration via the local display from unauthorized access → 132.
Defining access authorization for user roles
An access code is not yet defined when the device is delivered from the factory. Access
authorization (read and write access) to the device is not restricted and corresponds to the
"Maintenance" user role.
Define the access code.
‣
The "Operator" user role is redefined in addition to the "Maintenance" user role.
Access authorization differs for the two user roles.
Access authorization to parameters: "Maintenance" user role
Access code statusRead accessWrite access
An access code has not yet been defined
(factory setting).
After an access code has been defined.
1)The user only has write access after entering the access code.
1)
Access authorization to parameters: "Operator" user role
Access code statusRead accessWrite access
After an access code has been defined.––
1)Despite the defined access code, certain parameters can always be modified and thus are excepted from
the write protection, as they do not affect the measurement. Refer to the "Write protection via access code"
section
1)
The user role with which the user is currently logged on is indicated by the Access
status parameter. Navigation path: Operation → Access status
8.3.11 Disabling write protection via access code
If the -symbol appears on the local display in front of a parameter, the parameter is
write-protected by a user-specific access code and its value cannot be changed at the
moment using local operation → 132.
Endress+Hauser75
Parameter write protection via local operation can be disabled by entering the user-specific
access code in the Enter access code parameter (→ 119) via the respective access
option.
1.After you press , the input prompt for the access code appears.
Page 76
Operation optionsProline Promag P 500 HART
2.Enter the access code.
The -symbol in front of the parameters disappears; all previously write-
protected parameters are now re-enabled.
8.3.12 Enabling and disabling the keypad lock
The keypad lock makes it possible to block access to the entire operating menu via local
operation. As a result, it is no longer possible to navigate through the operating menu or
change the values of individual parameters. Users can only read the measured values on
the operational display.
The keypad lock is switched on and off via the context menu.
Switching on the keypad lock
The keypad lock is switched on automatically:
• If the device has not been operated via the display for > 1 minute.
• Each time the device is restarted.
To activate the keylock manually:
1.The device is in the measured value display.
Press for at least 2 seconds.
A context menu appears.
2.In the context menu select the Keylock on option.
The keypad lock is switched on.
If the user attempts to access the operating menu while the keypad lock is active, the
Keylock on message appears.
Switching off the keypad lock
1.The keypad lock is switched on.
Press for at least 2 seconds.
A context menu appears.
2.In the context menu select the Keylock off option.
The keypad lock is switched off.
8.4 Access to the operating menu via the Web browser
8.4.1 Function range
Thanks to the integrated Web server, the device can be operated and configured via a Web
browser and via a service interface (CDI-RJ45) or via a WLAN interface. The structure of
the operating menu is the same as for the local display. In addition to the measured values,
status information on the device is also displayed and allows the user to monitor the status
of the device. Furthermore the device data can be managed and the network parameters
can be configured.
A device that has a WLAN interface (can be ordered as an option) is required for the
WLAN connection: order code for "Display; operation", option G "4-line, illuminated; touch
control + WLAN". The device acts as an Access Point and enables communication by
computer or a mobile handheld terminal.
For additional information on the Web server, refer to the Special Documentation for
the device
76Endress+Hauser
Page 77
Proline Promag P 500 HARTOperation options
8.4.2 Prerequisites
Computer hardware
HardwareInterface
CDI-RJ45WLAN
InterfaceThe computer must have an RJ45
interface.
ConnectionStandard Ethernet cable with RJ45
connector.
ScreenRecommended size: ≥12" (depends on the screen resolution)
Computer software
SoftwareInterface
CDI-RJ45WLAN
Recommended operating
systems
• Microsoft Windows 7 or higher.
• Mobile operating systems:
– iOS
– Android
Microsoft Windows XP is supported.
The operating unit must have a
WLAN interface.
Connection via Wireless LAN.
Web browsers supported• Microsoft Internet Explorer 8 or higher
• Microsoft Edge
• Mozilla Firefox
• Google Chrome
• Safari
Computer settings
SettingsInterface
CDI-RJ45WLAN
User rightsAppropriate user rights (e.g. administrator rights) for TCP/IP and proxy server
settings are necessary (for adjusting the IP address, subnet mask etc.).
Proxy server settings of the
Web browser
JavaScriptJavaScript must be enabled.
Network connectionsOnly the active network connections to the measuring device should be used.
The Web browser setting Use a Proxy Server for Your LAN must be
deselected .
If JavaScript cannot be enabled:
enter http://192.168.1.212/basic.html in the address line of the Web
browser. A fully functional but simplified version of the operating menu
structure starts in the Web browser.
When installing a new firmware version: To enable correct data display,
clear the temporary memory (cache) of the Web browser under Internetoptions.
Switch off all other network
connections such as WLAN.
Switch off all other network
connections.
In the event of connection problems: → 147
Endress+Hauser77
Page 78
Operation optionsProline Promag P 500 HART
Measuring device: Via CDI-RJ45 service interface
DeviceCDI-RJ45 service interface
Measuring deviceThe measuring device has an RJ45 interface.
Web serverWeb server must be enabled; factory setting: ON
For information on enabling the Web server → 82
Measuring device: via WLAN interface
DeviceWLAN interface
Measuring deviceThe measuring device has a WLAN antenna:
• Transmitter with integrated WLAN antenna
• Transmitter with external WLAN antenna
Web serverWeb server and WLAN must be enabled; factory setting: ON
For information on enabling the Web server → 82
8.4.3 Establishing a connection
Via service interface (CDI-RJ45)
Preparing the measuring device
Proline 500 – digital
1.Loosen the 4 fixing screws on the housing cover.
2.Open the housing cover.
3.The location of the connection socket depends on the measuring device and the
communication protocol:
Connect the computer to the RJ45 connector via the standard Ethernet connecting
cable .
Proline 500
1.Depending on the housing version:
Release the securing clamp or securing screw of the housing cover.
2.Depending on the housing version:
Unscrew or open the housing cover.
3.The location of the connection socket depends on the measuring device and the
communication protocol:
Connect the computer to the RJ45 connector via the standard Ethernet connecting
cable .
Configuring the Internet protocol of the computer
The following information refers to the default Ethernet settings of the device.
IP address of the device: 192.168.1.212 (factory setting)
1.Switch on the measuring device.
2.Connect to the computer using a cable → 84.
3.If a 2nd network card is not used, close all the applications on the notebook.
Applications requiring Internet or a network, such as e-mail, SAP applications,
Internet or Windows Explorer.
4.Close any open Internet browsers.
5.Configure the properties of the Internet protocol (TCP/IP) as defined in the table:
78Endress+Hauser
Page 79
Proline Promag P 500 HARTOperation options
IP address192.168.1.XXX; for XXX all numerical sequences except: 0, 212 and 255 → e.g.
192.168.1.213
Subnet mask255.255.255.0
Default gateway192.168.1.212 or leave cells empty
Via WLAN interface
Configuring the Internet protocol of the mobile terminal
NOTICE
If the WLAN connection is lost during the configuration, settings made may be lost.
Make sure that the WLAN connection is not disconnected while configuring the device.
‣
NOTICE
In principle, avoid simultaneous access to the measuring device via the service
interface (CDI-RJ45) and the WLAN interface from the same mobile terminal. This
could cause a network conflict.
Only activate one service interface (CDI-RJ45 service interface or WLAN interface).
‣
If simultaneous communication is necessary: configure different IP address ranges, e.g.
‣
192.168.0.1 (WLAN interface) and 192.168.1.212 (CDI-RJ45 service interface).
Preparing the mobile terminal
Enable WLAN reception on the mobile terminal.
‣
Establishing a connection from the mobile terminal to the measuring device
1.In the WLAN settings of the mobile terminal:
Select the measuring device using the SSID (e.g. EH_Promag_500_A802000).
2.If necessary, select the WPA2 encryption method.
3.Enter the password: serial number of the measuring device ex-works (e.g.
L100A802000).
LED on display module flashes: it is now possible to operate the measuring device
with the Web browser, FieldCare or DeviceCare.
The serial number can be found on the nameplate.
To ensure the safe and swift assignment of the WLAN network to the measuring
point, it is advisable to change the SSID name. It should be possible to clearly assign
the new SSID name to the measuring point (e.g. tag name) because it is displayed as
the WLAN network.
Disconnecting
After configuring the device:
‣
Terminate the WLAN connection between the operating unit and measuring device.
Starting the Web browser
1.Start the Web browser on the computer.
Endress+Hauser79
Page 80
Operation optionsProline Promag P 500 HART
6
7
8
9
10
152 3 4
2.Enter the IP address of the Web server in the address line of the Web browser:
192.168.1.212
The login page appears.
A0029417
1Picture of device
2Device name
3Device tag (→ 96)
4Status signal
5Current measured values
6Operating language
7User role
8Access code
9Login
10 Reset access code (→ 129)
If a login page does not appear, or if the page is incomplete → 147
8.4.4 Logging on
1.Select the preferred operating language for the Web browser.
2.Enter the user-specific access code.
3.Press OK to confirm your entry.
Access code0000 (factory setting); can be changed by customer
If no action is performed for 10 minutes, the Web browser automatically returns to
the login page.
80Endress+Hauser
Page 81
Proline Promag P 500 HARTOperation options
2
1
3
8.4.5 User interface
A0029418
1Function row
2Local display language
3Navigation area
Header
The following information appears in the header:
• Device tag
• Device status with status signal → 155
• Current measured values
Function row
FunctionsMeaning
Measured valuesDisplays the measured values of the measuring device
• Access to the operating menu from the measuring device
Menu
Device statusDisplays the diagnostic messages currently pending, listed in order of priority
Data
management
Network
configuration
LogoutEnd the operation and call up the login page
• The structure of the operating menu is the same as for the local display
For detailed information on the structure of the operating menu, see the Operating
Instructions for the measuring device
Data exchange between PC and measuring device:
• Device configuration:
– Load settings from the device
(XML format, save configuration)
– Save settings to the device
(XML format, restore configuration)
• Logbook - Export Event logbook (.csv file)
• Documents - Export documents:
– Export backup data record
(.csv file, create documentation of the measuring point configuration)
– Verification report
(PDF file, only available with the "Heartbeat Verification" application package)
• Firmware update - Flashing a firmware version
Configuration and checking of all the parameters required for establishing the connection
to the measuring device:
• Network settings (e.g. IP address, MAC address)
• Device information (e.g. serial number, firmware version)
Navigation area
If a function is selected in the function bar, the submenus of the function open in the
navigation area. The user can now navigate through the menu structure.
Endress+Hauser81
Page 82
Operation optionsProline Promag P 500 HART
Working area
Depending on the selected function and the related submenus, various actions can be
performed in this area:
• Configuring parameters
• Reading measured values
• Calling up help text
• Starting an upload/download
8.4.6 Disabling the Web server
The Web server of the measuring device can be switched on and off as required using the
Web server functionality parameter.
Navigation
"Expert" menu → Communication → Web server
Parameter overview with brief description
ParameterDescriptionSelectionFactory setting
Web server functionalitySwitch the Web server on and off.• Off
• On
On
Function scope of the "Web server functionality" parameter
OptionDescription
Off• The web server is completely disabled.
• Port 80 is locked.
On• The complete functionality of the web server is available.
• JavaScript is used.
• The password is transferred in an encrypted state.
• Any change to the password is also transferred in an encrypted state.
Enabling the Web server
If the Web server is disabled it can only be re-enabled with the Web server functionality
parameter via the following operating options:
• Via local display
• Via Bedientool "FieldCare"
• Via "DeviceCare" operating tool
8.4.7 Logging out
Before logging out, perform a data backup via the Data management function
(upload configuration from device) if necessary.
1.Select the Logout entry in the function row.
The home page with the Login box appears.
2.Close the Web browser.
3.If no longer needed:
Reset modified properties of the Internet protocol (TCP/IP) → 78.
8.5 Access to the operating menu via the operating tool
The structure of the operating menu in the operating tools is the same as for operation via
the local display.
82Endress+Hauser
Page 83
Proline Promag P 500 HARTOperation options
1235
7
46
1457
9
68
3
8.5.1 Connecting the operating tool
Via HART protocol
This communication interface is available in device versions with a HART output.
A0028747
38Options for remote operation via HART protocol (active)
1Control system (e.g. PLC)
2Field Communicator 475
3Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) with COM
DTM "CDI Communication TCP/IP"
4Commubox FXA195 (USB)
5Field Xpert SFX350 or SFX370
6VIATOR Bluetooth modem with connecting cable
7Transmitter
39Options for remote operation via HART protocol (passive)
1Control system (e.g. PLC)
2Transmitter power supply unit, e.g. RN221N (with communication resistor)
3Connection for Commubox FXA195 and Field Communicator 475
4Field Communicator 475
5Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) with COM
DTM "CDI Communication TCP/IP"
6Commubox FXA195 (USB)
7Field Xpert SFX350 or SFX370
8VIATOR Bluetooth modem with connecting cable
9Transmitter
Endress+Hauser83
A0028746
Page 84
Operation optionsProline Promag P 500 HART
open
press
2
3
2
3
Service interface
Via service interface (CDI-RJ45)
A point-to-point connection can be established to configure the device onsite. With the
housing open, the connection is established directly via the service interface (CDI-RJ45) of
the device.
An adapter for RJ45 and the M12 connector is optionally available:
Order code for "Accessories", option NB: "Adapter RJ45 M12 (service interface)"
The adapter connects the service interface (CDI-RJ45) to an M12 connector mounted
in the cable entry. Therefore the connection to the service interface can be established
via an M12 connector without opening the device.
Proline 500 – digital transmitter
A0029163
40Connection via service interface (CDI-RJ45)
1Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated
device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"
2Standard Ethernet connecting cable with RJ45 connector
3Service interface (CDI-RJ45) of the measuring device with access to the integrated Web server
Proline 500 transmitter
A0027563
41Connection via service interface (CDI-RJ45)
1Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated
device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"
2Standard Ethernet connecting cable with RJ45 connector
3Service interface (CDI-RJ45) of the measuring device with access to the integrated Web server
Via WLAN interface
The optional WLAN interface is available on the following device version:
Order code for "Display; operation", option G "4-line, illuminated, graphic display; touch
control + WLAN"
84Endress+Hauser
Page 85
Proline Promag P 500 HARTOperation options
1
22
1
3
4
3
4
3
4
3
4
567
A0034569
1Transmitter with integrated WLAN antenna
2Transmitter with external WLAN antenna
3LED lit constantly: WLAN reception is enabled on measuring device
4LED flashing: WLAN connection established between operating unit and measuring device
5Computer with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for
accessing the integrated device Web server or with operating tool (e.g. FieldCare, DeviceCare)
6Mobile handheld terminal with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft
Edge) for accessing the integrated device Web server or operating tool (e.g. FieldCare, DeviceCare)
7Smartphone or tablet
FunctionWLAN: IEEE 802.11 b/g (2.4 GHz)
EncryptionWPA2-PSK/AES 128 bit
Configurable WLAN channels1 to 11
Degree of protectionIP67
Available antennas• Internal antenna
• External antenna (optional)
In the event of poor transmission/reception conditions at the place of
installation.
Only one antenna active in each case!
Max. range50 m (164 ft)
Materials:
External WLAN antenna
• Antenna: ASA plastic (acrylic ester-styrene-acrylonitrile) and nickelplated brass
• Adapter: Stainless steel and nickel-plated brass
• Cable: Polyethylene
• Connector: Nickel-plated brass
• Angle bracket: Stainless steel
Configuring the Internet protocol of the mobile terminal
NOTICE
If the WLAN connection is lost during the configuration, settings made may be lost.
Make sure that the WLAN connection is not disconnected while configuring the device.
‣
Endress+Hauser85
Page 86
Operation optionsProline Promag P 500 HART
NOTICE
In principle, avoid simultaneous access to the measuring device via the service
interface (CDI-RJ45) and the WLAN interface from the same mobile terminal. This
could cause a network conflict.
Only activate one service interface (CDI-RJ45 service interface or WLAN interface).
‣
If simultaneous communication is necessary: configure different IP address ranges, e.g.
‣
192.168.0.1 (WLAN interface) and 192.168.1.212 (CDI-RJ45 service interface).
Preparing the mobile terminal
Enable WLAN reception on the mobile terminal.
‣
Establishing a connection from the mobile terminal to the measuring device
1.In the WLAN settings of the mobile terminal:
Select the measuring device using the SSID (e.g. EH_Promag_500_A802000).
2.If necessary, select the WPA2 encryption method.
3.Enter the password: serial number of the measuring device ex-works (e.g.
L100A802000).
LED on display module flashes: it is now possible to operate the measuring device
with the Web browser, FieldCare or DeviceCare.
The serial number can be found on the nameplate.
To ensure the safe and swift assignment of the WLAN network to the measuring
point, it is advisable to change the SSID name. It should be possible to clearly assign
the new SSID name to the measuring point (e.g. tag name) because it is displayed as
the WLAN network.
Disconnecting
After configuring the device:
‣
Terminate the WLAN connection between the operating unit and measuring device.
8.5.2 Field Xpert SFX350, SFX370
Function range
Field Xpert SFX350 and Field Xpert SFX370 are mobile computers for commissioning and
maintenance. They enable efficient device configuration and diagnostics for HART and
FOUNDATION Fieldbus devices in the non-hazardous area (SFX350, SFX370) and
hazardous area (SFX370).
For details, see Operating Instructions BA01202S
Source for device description files
See information → 90
8.5.3 FieldCare
Function scope
FDT-based plant asset management tool from Endress+Hauser. It can configure all smart
field devices in a system and helps you manage them. By using the status information, it is
also a simple but effective way of checking their status and condition.
86Endress+Hauser
Page 87
Proline Promag P 500 HARTOperation options
Access is via:
• HART protocol
• CDI-RJ45 service interface → 84
• WLAN interface→ 84
Typical functions:
• Configuring parameters of transmitters
• Loading and saving device data (upload/download)
• Documentation of the measuring point
• Visualization of the measured value memory (line recorder) and event logbook
For additional information about FieldCare, see Operating Instructions BA00027S
and BA00059S
Source for device description files
See information → 90
Establishing a connection
1.Start FieldCare and launch the project.
2.In the network: Add a device.
The Add device window opens.
3.Select the CDI Communication TCP/IP option from the list and press OK to confirm.
4.Right-click CDI Communication TCP/IP and select the Add device option in the
context menu that opens.
5.Select the desired device from the list and press OK to confirm.
The CDI Communication TCP/IP (Configuration) window opens.
6.Enter the device address in the IP address field: 192.168.1.212 and press Enter to
confirm.
7.Establish the online connection to the device.
For additional information, see Operating Instructions BA00027S and BA00059S
Endress+Hauser87
Page 88
Operation optionsProline Promag P 500 HART
6
5
32
1
Xxxxxx/…/…/
7
P
P
+
–
P
–
P
+
+
+
+
+
+
4
89
10
11
Xxxxxxx
GoodStatus:
Device tag:
Xxxxxxx
Device name:
Mass flow:
12.34
kg/h
Volume flow:
12.34
m /h³
Mass flow unit:
Volume flow unit:
kg/h
m /h³
Access status tooling
Operation
Setup
Xxxxxx
Mass flow unit
Volume flow unit
Select medium
Device tag
…
…
Advanced setup
Diagnostics
Expert
Maintenance
kg/h
m /h³
Xxxxxx
System units
User interface
1Header
2Picture of device
3Device name
4Tag name
5Status area with status signal→ 155
6Display area for current measured values
7Edit toolbar with additional functions such as save/restore, event list and create documentation
8Navigation area with operating menu structure
9Working area
10 Range of action
11 Status area
8.5.4 DeviceCare
Function scope
Tool to connect and configure Endress+Hauser field devices.
88Endress+Hauser
The fastest way to configure Endress+Hauser field devices is with the dedicated
"DeviceCare" tool. Together with the device type managers (DTMs) it presents a convenient,
comprehensive solution.
For details, see Innovation Brochure IN01047S
Source for device description files
See information → 90
8.5.5 AMS Device Manager
Function scope
Program from Emerson Process Management for operating and configuring measuring
devices via HART protocol.
A0021051-EN
Page 89
Proline Promag P 500 HARTOperation options
Source for device description files
See data → 90
8.5.6 SIMATIC PDM
Function scope
SIMATIC PDM is a standardized, manufacturer-independent program from Siemens for
the operation, configuration, maintenance and diagnosis of intelligent field devices via
HART protocol.
Source for device description files
See data → 90
8.5.7 Field Communicator 475
Function scope
Industrial handheld terminal from Emerson Process Management for remote
configuration and measured value display via HART protocol.
Source for device description files
See data → 90
Endress+Hauser89
Page 90
System integrationProline Promag P 500 HART
9 System integration
9.1 Overview of device description files
9.1.1 Current version data for the device
Firmware version01.01.zz• On the title page of the Operating Instructions
• On the transmitter nameplate
• Firmware version
Diagnostics → Device information → Firmware
version
Release date of firmware version10.2017---
Manufacturer ID0x11Manufacturer ID
Diagnostics → Device information → Manufacturer ID
Device type ID0x3CDevice type
Diagnostics → Device information → Device type
HART protocol revision7---
Device revision1• On the transmitter nameplate
• Device revision
Diagnostics → Device information → Device revision
For an overview of the different firmware versions for the device → 169
9.1.2 Operating tools
The suitable device description file for the individual operating tools is listed in the table
below, along with information on where the file can be acquired.
Operating tool via
HART protocol
FieldCare• www.endress.com → Download Area
DeviceCare• www.endress.com → Download Area
• Field Xpert SFX350
• Field Xpert SFX370
AMS Device Manager
(Emerson Process Management)
SIMATIC PDM
(Siemens)
Field Communicator 475
(Emerson Process Management)
Sources for obtaining device descriptions
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
Use update function of handheld terminal
www.endress.com → Download Area
www.endress.com → Download Area
Use update function of handheld terminal
9.2 Measured variables via HART protocol
The following measured variables (HART device variables) are assigned to the dynamic
variables at the factory:
90Endress+Hauser
Page 91
Proline Promag P 500 HARTSystem integration
Dynamic variablesMeasured values
(HART device variables)
Primary dynamic variable (PV)Volume flow
Secondary dynamic variable (SV)Totalizer 1
Tertiary dynamic variable (TV)Totalizer 2
Quaternary dynamic variable (QV)Totalizer 3
The assignment of the measured variables to the dynamic variables can be modified and
assigned as desired via local operation and the operating tool using the following
parameters:
• Expert → Communication → HART output → Output → Assign TV
• Expert → Communication → HART output → Output → Assign QV
The following measured variables can be assigned to the dynamic variables:
Measured variables for PV (primary dynamic variable)
• Off
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
1)
• Electronic temperature
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic
variable)
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
2)
• Electronic temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
The range of options increases if the measuring device has one or more application
packages.
Device variables
The device variables are permanently assigned. A maximum of 8 device variables can be
transmitted:
• 0 = volume flow
• 1 = mass flow
• 2 = corrected volume flow
• 3 = flow velocity
• 4 = conductivity
• 7 = electronic temperature
• 8 = totalizer 1
• 9 = totalizer 2
• 10 = totalizer 3
1)Visibility depends on order options or device settings
2)Visibility depends on order options or device settings
Endress+Hauser91
Page 92
System integrationProline Promag P 500 HART
9.3 Other settings
Burst mode functionality in accordance with HART 7 Specification:
Navigation
"Expert" menu → Communication → HART output → Burst configuration → Burst
configuration 1 to n
Burst configuration
‣
Burst configuration 1 to n
‣
Burst mode 1 to n
Burst command 1 to n
Burst variable 0
Burst variable 1
Burst variable 2
Burst variable 3
Burst variable 4
Burst variable 5
Burst variable 6
Burst variable 7
Burst trigger mode
→ 92
→ 92
→ 93
→ 93
→ 93
→ 93
→ 93
→ 93
→ 93
→ 93
→ 93
Burst trigger level
Min. update period
Max. update period
→ 93
→ 93
→ 93
Parameter overview with brief description
ParameterDescriptionSelection / User entryFactory setting
Burst mode 1 to nActivate the HART burst mode for burst
message X.
Burst command 1 to nSelect the HART command that is sent to the
HART master.
• Off
• On
• Command 1
• Command 2
• Command 3
• Command 9
• Command 33
• Command 48
Off
Command 2
92Endress+Hauser
Page 93
Proline Promag P 500 HARTSystem integration
ParameterDescriptionSelection / User entryFactory setting
Burst variable 0For HART command 9 and 33: select the
HART device variable or the process variable.
Burst variable 1For HART command 9 and 33: select the
HART device variable or the process variable.
Burst variable 2For HART command 9 and 33: select the
HART device variable or the process variable.
Burst variable 3For HART command 9 and 33: select the
HART device variable or the process variable.
Burst variable 4For HART command 9: select the HART
device variable or the process variable.
Burst variable 5For HART command 9: select the HART
device variable or the process variable.
Burst variable 6For HART command 9: select the HART
device variable or the process variable.
Burst variable 7For HART command 9: select the HART
device variable or the process variable.
Burst trigger modeSelect the event that triggers burst messageX.• Continuous
Burst trigger levelEnter the burst trigger value.
Together with the option selected in the
Burst trigger mode parameter the burst
trigger value determines the time of burst
message X.
Min. update periodEnter the minimum time span between two
burst commands of burst message X.
Max. update periodEnter the maximum time span between two
burst commands of burst message X.
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Electronic temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Density
• HART input
• Percent of range
• Measured current
• Primary variable (PV)
• Secondary variable (SV)
• Tertiary variable (TV)
• Quaternary variable (QV)
• Not used
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
• Window
• Rising
• Falling
• On change
Signed floating-point number–
Positive integer1000 ms
Positive integer2000 ms
*
Volume flow
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Continuous
*Visibility depends on order options or device settings
Endress+Hauser93
Page 94
CommissioningProline Promag P 500 HART
X X X X X X XXX
20.50
Operation
Setup
Main menu
0104-1
Display language
English
Español
Français
Display language
English
Deutsch
Ã
0104-1
Ã
Español
Français
Display language
English
Deutsch
0104-1
Betrieb
Setup
Hauptmenü
Sprache
Deutsch
0104-1
XXXX
1.
2.
3.
4.
10 Commissioning
10.1 Function check
Before commissioning the measuring device:
Make sure that the post-installation and post-connection checks have been performed.
‣
• "Post-installation check" checklist→ 37
• "Post-connection check" checklist → 62
10.2 Switching on the measuring device
After a successful function check, switch on the measuring device.
‣
After a successful startup, the local display switches automatically from the startup
display to the operational display.
If nothing appears on the local display or a diagnostic message is displayed, refer to
the section on "Diagnostics and troubleshooting" → 146.
10.3 Setting the operating language
Factory setting: English or ordered local language
94Endress+Hauser
42Taking the example of the local display
10.4 Configuring the measuring device
• The Setup menu with its guided wizards contains all the parameters needed for standard
operation.
• Navigation to the Setup menu
A0029420
Page 95
Proline Promag P 500 HARTCommissioning
X X X X X X XXX
20.50
0104-1
XXXXXXXXX
XXXXXXXXX
mA
1.
2.
3.
Display/operat.
Setup
Diagnostic
Display/operat.
Setup
Main menu
English
Main menu
Medium selection
/ ../Setup
Display language
A0032222-EN
43Taking the example of the local display
Depending on the device version, not all submenus and parameters are available in
every device. The selection can vary depending on the order code.
Setup
Device tag
System units
‣
I/O configuration
‣
Current input 1 to n
‣
Status input 1 to n
‣
Current output 1 to n
‣
Pulse/frequency/switch output
‣
1 to n
Relay output 1 to n
‣
→ 96
→ 96
→ 98
→ 99
→ 98
→ 100
→ 103
→ 114
Double pulse output
Endress+Hauser95
‣
Display
‣
Low flow cut off
‣
Empty pipe detection
‣
Advanced setup
‣
→ 116
→ 109
→ 111
→ 112
→ 118
Page 96
CommissioningProline Promag P 500 HART
XXXXXXXXX
10.4.1 Defining the tag name
To enable fast identification of the measuring point within the system, you can enter a
unique designation using the Device tag parameter and thus change the factory setting.
A0029422
44Header of the operational display with tag name
1Tag name
Enter the tag name in the "FieldCare" operating tool → 88
Navigation
"Setup" menu → Device tag
Parameter overview with brief description
ParameterDescriptionUser entryFactory setting
Device tagEnter the name for the measuring point.Max. 32 characters, such as
letters, numbers or special
characters (e.g. @, %, /).
10.4.2 Setting the system units
In the System units submenu the units of all the measured values can be set.
Depending on the device version, not all submenus and parameters are available in
every device. The selection can vary depending on the order code.