• Make sure the document is stored in a safe place such that it is always available when
working on or with the device.
• To avoid danger to individuals or the facility, read the "Basic safety instructions" section
carefully, as well as all other safety instructions in the document that are specific to
working procedures.
• The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser Sales Center will supply you with current information and updates to
these Instructions.
16.12 Certificates and approvals .............. 132
16.13 Application packages .................. 133
16.14 Accessories ......................... 134
16.15 Documentation ...................... 134
Index ................................. 136
Endress+Hauser5
Page 6
Document informationProline Promag H 200 HART
DANGER
WARNING
CAUTION
NOTICE
1 Document information
1.1 Document function
These Operating Instructions contain all the information that is required in various phases
of the life cycle of the device: from product identification, incoming acceptance and
storage, to mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal.
1.2 Symbols used
1.2.1 Safety symbols
SymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.2.2 Electrical symbols
SymbolMeaningSymbolMeaning
Direct currentAlternating current
Direct current and alternating currentGround connection
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
1.2.3 Tool symbols
SymbolMeaning
Flat blade screwdriver
Allen key
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
Open-ended wrench
6Endress+Hauser
Page 7
Proline Promag H 200 HARTDocument information
,…,
,…,
-
.
1.2.4 Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Series of steps
Result of a sequence of actions
Help in the event of a problem
Visual inspection
1.2.5 Symbols in graphics
SymbolMeaningSymbolMeaning
1, 2, 3,...Item numbers
A, B, C, ...ViewsA-A, B-B, C-C, ... Sections
Hazardous area
Flow direction
Series of steps
Safe area (non-hazardous area)
1.3 Documentation
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The CD-ROM provided for the device (depending on the device version, the CD-ROM
might not be part of the delivery!)
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate
or scan the 2-D matrix code (QR code) on the nameplate.
For a detailed list of the individual documents along with the documentation code
Endress+Hauser7
Page 8
Document informationProline Promag H 200 HART
1.3.1 Standard documentation
Document typePurpose and content of the document
Technical InformationPlanning aid for your device
The document contains all the technical data on the device and provides
an overview of the accessories and other products that can be ordered for
the device.
Brief Operating InstructionsGuide that takes you quickly to the 1st measured value
The Brief Operating Instructions contain all the essential information
from incoming acceptance to initial commissioning.
Additional documents are supplied depending on the device version ordered: Always
comply strictly with the instructions in the supplementary documentation. The
supplementary documentation is an integral part of the device documentation.
1.4 Registered trademarks
®
HART
Registered trademark of the HART Communication Foundation, Austin, USA
Applicator®, FieldCare®, Field XpertTM, HistoROM®, Heartbeat Technology
Registered or registration-pending trademarks of the Endress+Hauser Group
TM
8Endress+Hauser
Page 9
Proline Promag H 200 HARTBasic safety instructions
2 Basic safety instructions
2.1 Requirements for the personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill
the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function
‣
and task
Are authorized by the plant owner/operator
‣
Are familiar with federal/national regulations
‣
Before beginning work, the specialist staff must have read and understood the
‣
instructions in the Operating Instructions and supplementary documentation as well as
in the certificates (depending on the application)
Following instructions and basic conditions
‣
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the
‣
facility's owner-operator
Following the instructions in these Operating Instructions
‣
2.2 Designated use
Application and media
The measuring device is only suitable for flow measurement of liquids with a minimum
conductivity of 20 μS/cm.
Depending on the version ordered, the measuring device can also measure potentially
explosive, flammable, poisonous and oxidizing media.
Measuring devices for use in hazardous areas, in hygienic applications or in applications
where there is an increased risk due to process pressure, are labeled accordingly on the
nameplate.
To ensure that the measuring device remains in proper condition for the operation time:
Only use the measuring device in full compliance with the data on the nameplate and
‣
the general conditions listed in the Operating Instructions and supplementary
documentation.
Check the nameplate to verify if the device ordered can be put to its intended use in the
‣
approval-related area (e.g. explosion protection, pressure vessel safety).
Use the measuring device only for media against which the process-wetted materials
‣
are adequately resistant.
If the measuring device is not operated at atmospheric temperature, compliance with
‣
the relevant basic conditions specified in the associated device documentation is
absolutely essential: "Documentation" section → 7.
Protect the measuring device permanently against corrosion from environmental
‣
influences.
Incorrect use
Non-designated use can compromise safety. The manufacturer is not liable for damage
caused by improper or non-designated use.
WARNING
L
Danger of breakage of the sensor due to corrosive or abrasive fluids or from
environmental conditions!
Verify the compatibility of the process fluid with the sensor material.
‣
Ensure the resistance of all fluid-wetted materials in the process.
‣
Keep within the specified pressure and temperature range.
‣
Endress+Hauser9
Page 10
Basic safety instructionsProline Promag H 200 HART
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance
‣
in verifying the corrosion resistance of fluid-wetted materials, but does not accept any
warranty or liability as minute changes in the temperature, concentration or level of
contamination in the process can alter the corrosion resistance properties.
Residual risks
The external surface temperature of the housing can increase by max. 10 K due to the
power consumption of the electronic components. Hot process fluids passing through the
measuring device will further increase the surface temperature of the housing. The surface
of the sensor, in particular, can reach temperatures which are close to the fluid
temperature.
Possible burn hazard due to fluid temperatures!
For elevated fluid temperature, ensure protection against contact to prevent burns.
‣
2.3 Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national
‣
regulations.
For welding work on the piping:
Do not ground the welding unit via the measuring device.
‣
If working on and with the device with wet hands:
It is recommended to wear gloves on account of the higher risk of electric shock.
‣
2.4 Operational safety
Risk of injury.
Operate the device in proper technical condition and fail-safe condition only.
‣
The operator is responsible for interference-free operation of the device.
‣
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
‣
Repair
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
‣
Observe federal/national regulations pertaining to repair of an electrical device.
‣
Use original spare parts and accessories from Endress+Hauser only.
‣
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet
state-of-the-art safety requirements, has been tested, and left the factory in a condition in
which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EC
directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser
confirms this by affixing the CE mark to the device.
10Endress+Hauser
Page 11
Proline Promag H 200 HARTBasic safety instructions
2.6 IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
Endress+Hauser11
Page 12
Product descriptionProline Promag H 200 HART
12
3
4
56
7
8
9
+
E
–
3 Product description
The device consists of a transmitter and a sensor.
One device version is available: compact version - transmitter and sensor form a
Proline Promag H 200 HARTIncoming acceptance and product identification
1
+
2
1
+
2
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
Are the order codes on the
delivery note (1) and the
product sticker (2)
identical?
Are the goods undamaged?
Do the nameplate data
match the ordering
information on the delivery
note?
Is the CD-ROM with the
Technical Documentation
(depends on device
version) and documents
present?
• If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center.
• Depending on the device version, the CD-ROM might not be part of the delivery!
The Technical Documentation is available via the Internet or via the Endress+HauserOperations App, see the "Product identification" section → 14.
4.2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is
displayed.
• Enter the serial number from the nameplates into the Endress+Hauser Operations App
or scan the 2-D matrix code (QR code) on the nameplate with the Endress+HauserOperations App: all the information for the measuring device is displayed.
Endress+Hauser13
Page 14
Incoming acceptance and product identificationProline Promag H 200 HART
Ordercode:
Ext.ord.cd.:
Ser.no.:
Date:
i
i
Patents
322540-0001
1
2
3 4 5
6
7
8
9
1011
12
14
15
16
17
13
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The chapters "Additional standard documentation on the device" → 8 and
"Supplementary device-dependent documentation" → 8
• The W@M Device Viewer: Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or
scan the 2-D matrix code (QR code) on the nameplate.
4.2.1 Transmitter nameplate
A0013906
2Example of a transmitter nameplate
1Manufacturing location
2Name of the transmitter
3Order code
4Serial number (Ser. no.)
5Extended order code (Ext. ord. cd.)
6Electrical connection data, e.g. available inputs and outputs, supply voltage
7Type of cable glands
8Permitted ambient temperature (Ta)
9Firmware version (FW) and device revision (Dev.Rev.) from the factory
10 CE mark, C-Tick
11 Additional information on version: certificates, approvals
12 Permitted temperature range for cable
13 Manufacturing date: year-month
14 Degree of protection
15 Approval information for explosion protection
16 Document number of safety-related supplementary documentation
17 2-D matrix code
14Endress+Hauser
Page 15
Proline Promag H 200 HARTIncoming acceptance and product identification
i
Patents
i
Material:
Tm:
Ext. ord. cd.:
Order Code:
Ser.No.:
Date:
21
3
4
5
67
8
9
10
11
13
12
14
15
4.2.2 Sensor nameplate
3Example of sensor nameplate
1Name of the sensor
2Manufacturing location
3Order code
4Serial number (ser. no.)
5Extended order code (ext. ord. cd.)
6Nominal diameter of sensor
7Test pressure of the sensor
8Fluid temperature range
9Material of lining and electrodes
10 Degree of protection: e.g. IP, NEMA
11 Permitted ambient temperature (Ta)
12 2-D matrix code
13 CE mark, C-Tick
14 Flow direction
15 Manufacturing date: year-month
Order code
The measuring device is reordered using the order code.
Extended order code
• The device type (product root) and basic specifications (mandatory features) are
always listed.
• Of the optional specifications (optional features), only the safety and approvalrelated specifications are listed (e.g. LA). If other optional specifications are also
ordered, these are indicated collectively using the # placeholder symbol (e.g. #LA#).
• If the ordered optional specifications do not include any safety and approval-related
specifications, they are indicated by the + placeholder symbol (e.g. XXXXXX-ABCDE
+).
A0017186
Endress+Hauser15
Page 16
Incoming acceptance and product identificationProline Promag H 200 HART
4.2.3 Symbols on measuring device
SymbolMeaning
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious
or fatal injury.
Reference to documentation
Refers to the corresponding device documentation.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
16Endress+Hauser
Page 17
Proline Promag H 200 HARTStorage and transport
5 Storage and transport
5.1 Storage conditions
Observe the following notes for storage:
• Store in the original packaging to ensure protection from shock.
• Do not remove protective covers or protective caps installed on process connections.
They prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
• Protect from direct sunlight to avoid unacceptably high surface temperatures.
• Select a storage location where moisture cannot collect in the measuring device as
fungus and bacteria infestation can damage the lining.
• Store in a dry and dust-free place.
• Do not store outdoors.
• Storage temperature→ 125
5.2 Transporting the product
Transport the measuring device to the measuring point in the original packaging.
A0015604
Do not remove protective covers or caps installed on process connections. They
prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
5.2.1 Measuring devices without lifting lugs
WARNING
L
Center of gravity of the measuring device is higher than the suspension points of the
webbing slings.
Risk of injury if the measuring device slips.
Secure the measuring device against slipping or turning.
‣
Observe the weight specified on the packaging (stick-on label).
‣
A0015606
Endress+Hauser17
Page 18
Storage and transportProline Promag H 200 HART
5.2.2 Measuring devices with lifting lugs
CAUTION
L
Special transportation instructions for devices with lifting lugs
Only use the lifting lugs fitted on the device or flanges to transport the device.
‣
The device must always be secured at two lifting lugs at least.
‣
5.2.3 Transporting with a fork lift
If transporting in wood crates, the floor structure enables the crates to be lifted lengthwise
or at both sides using a forklift.
CAUTION
L
Risk of damaging the magnetic coil
If transporting by forklift, do not lift the sensor by the metal casing.
‣
This would buckle the casing and damage the internal magnetic coils.
‣
5.3 Packaging disposal
All packaging materials are environmentally friendly and 100% recyclable:
• Measuring device secondary packaging: polymer stretch film that conforms to EC
Directive 2002/95/EC (RoHS).
• Packaging:
– Wood crate, treated in accordance with ISPM 15 standard, which is confirmed by the
affixed IPPC logo.
or
– Carton in accordance with European Packaging Directive 94/62EC; recyclability is
confirmed by the affixed RESY symbol.
• Seaworthy packaging (optional): Wood crate, treated in accordance with ISPM 15
standard, which is confirmed by the affixed IPPC logo.
Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the
next pipe elbow: h ≥ 2 × DN
To prevent measuring errors arising from accumulation of gas bubbles in the measuring
tube, avoid the following mounting locations in the pipe:
• Highest point of a pipeline.
• Directly upstream of a free pipe outlet in a down pipe.
Installation in down pipes
Install a siphon with a vent valve downstream of the sensor in down pipes whose length h
≥ 5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of
damage to the measuring tube. This measure also prevents the system losing prime.
For information on the liner's resistance to partial vacuum
A0017064
4Installation in a down pipe
1Vent valve
2Pipe siphon
hLength of down pipe
Installation in partially filled pipes
A partially filled pipe with a gradient necessitates a drain-type configuration.
Endress+Hauser19
Page 20
InstallationProline Promag H 200 HART
³ 5 × DN
³ 2 × DN
1
22
A0017063
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor
according to the flow direction (direction of medium flow through the piping).
An optimum orientation position helps avoid gas and air accumulations and deposits in
the measuring tube.
The measuring device also offers the empty pipe detection function to detect partially filled
measuring pipes in the event of outgassing fluids or variable process pressures.
Vertical
Optimum for self-emptying pipe systems and for use in conjunction with empty pipe
detection.
Horizontal
1EPD electrode for empty pipe detection
2Measuring electrodes for signal detection
• The measuring electrode plane must be horizontal. This prevents brief insulation of
the two measuring electrodes by entrained air bubbles.
• Empty pipe detection only works if the transmitter housing is pointing upwards as
otherwise there is no guarantee that the empty pipe detection function will actually
respond to a partially filled or empty measuring tube.
A0015591
A0019602
Inlet and outlet runs
If possible, install the sensor upstream from fittings such as valves, T-pieces or elbows.
Observe the following inlet and outlet runs to comply with accuracy specifications:
20Endress+Hauser
Page 21
Proline Promag H 200 HARTInstallation
5 × DN≥
2 × DN≥
A0016275
Installation dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section
6.1.2 Requirements from environment and process
Ambient temperature range
Transmitter–40 to +60 °C (–40 to +140 °F)
Local display–20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.
Sensor–20 to +60 °C (–4 to +140 °F)
LinerDo not exceed or fall below the permitted temperature range of the liner .
If operating outdoors:
• Install the measuring device in a shady location.
• Avoid direct sunlight, particularly in warm climatic regions.
• Avoid direct exposure to weather conditions.
Temperature tables
Observe the interdependencies between the permitted ambient and fluid
temperatures when operating the device in hazardous areas.
For detailed information on the temperature tables, see the separate document
entitled "Safety Instructions" (XA) for the device.
System pressure
A0015594
Never install the sensor on the pump suction side in order to avoid the risk of low pressure,
and thus damage to the liner.
Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps
are used.
• For information on the liner's resistance to partial vacuum → 127
• For information on the shock resistance of the measuring system → 126
• For information on the vibration resistance of the measuring system → 126
Endress+Hauser21
Page 22
InstallationProline Promag H 200 HART
L
100
10
0.5
d / D
[mbar]
0.60.70.80.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
Vibrations
In the event of very strong vibrations, the pipe and sensor must be supported and fixed.
• For information on the shock resistance of the measuring system → 126
• For information on the vibration resistance of the measuring system → 126
A0016266
5Measures to avoid device vibrations (L > 10 m (33 ft))
Adapters
Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor
in larger-diameter pipes. The resultant increase in the rate of flow improves measuring
accuracy with very slow-moving fluids. The nomogram shown here can be used to
calculate the pressure loss caused by reducers and expanders.
The nomogram only applies to liquids with a viscosity similar to that of water.
1.Calculate the ratio of the diameters d/D.
2.From the nomogram read off the pressure loss as a function of flow velocity
(downstream from the reduction) and the d/D ratio.
6.1.3 Special mounting instructions
Display protection
To ensure that the optional display protection can be easily opened, maintain the
‣
following minimum head clearance: 350 mm (13.8 in)
A0016359
22Endress+Hauser
Page 23
Proline Promag H 200 HARTInstallation
6.2 Mounting the measuring device
6.2.1 Required tools
For transmitter
• For turning the transmitter housing: Open-ended wrench8 mm
• For opening the securing clamps: Allen key3 mm
For sensor
For flanges and other process connections:
• Screws, nuts, seals etc. are not included in the scope of supply and must be provided by
the customer.
• Appropriate mounting tools
6.2.2 Preparing the measuring device
1.Remove all remaining transport packaging.
2.Remove any protective covers or protective caps present from the sensor.
3.Remove stick-on label on the electronics compartment cover.
6.2.3 Mounting the sensor
WARNING
L
Danger due to improper process sealing!
Ensure that the inside diameters of the gaskets are greater than or equal to that of the
‣
process connections and piping.
Ensure that the gaskets are clean and undamaged.
‣
Install the gaskets correctly.
‣
1.Ensure that the direction of the arrow on the sensor matches the flow direction of
the medium.
2.To ensure compliance with device specifications, install the measuring device
between the pipe flanges in a way that it is centered in the measurement section.
3.Install the measuring device or turn the transmitter housing so that the cable entries
do not point upwards.
A0013964
The sensor is supplied to order, with or without pre-installed process connections. Preinstalled process connections are firmly secured to the sensor by 4 or 6 hexagonal-headed
bolts.
The sensor may need to be supported or additionally secured depending on the
application and pipe length. In particular, it is absolutely essential to secure the sensor
additionally if plastic process connections are used. An appropriate wall mounting kit
can be ordered separately as an accessory from Endress+Hauser → 134.
Endress+Hauser23
Page 24
InstallationProline Promag H 200 HART
A
B
DN 2…25
(1/12…1 )"
A0018782
6Process connection seals
AProcess connections with O-ring seal
BProcess connections with aseptic molded seal
Welding the sensor into the pipe (welding connections)
WARNING
L
Risk of destroying the electronics!
Make sure that the welding system is not grounded via the sensor or transmitter.
‣
1.Tack-weld the sensor to secure it in the pipe. A suitable welding aid can be ordered
separately as an accessory → 134.
2.Release the screws on the process connection flange and remove the sensor, along
with the seal, from the pipe.
3.Weld the process connection into the pipe.
4.Reinstall the sensor in the pipe, and in doing so make sure that the seal is clean and
in the right position.
• If thin-walled pipes carrying food are welded correctly, the seal is not damaged by
the heat even when mounted. However, it is recommended to disassemble the
sensor and seal.
• It must be possible to open the pipe by approx. 8 mm (0.31 in) in total to permit
disassembly.
Cleaning with pigs
It is essential to take the internal diameters of the measuring tube and process connection
into account when cleaning with pigs. All the dimensions and lengths of the sensor and
transmitter are provided in the separate "Technical Information" document.
Mounting the seals
CAUTION
L
An electrically conductive layer could form on the inside of the measuring tube!
Risk of measuring signal short circuit.
Do not use electrically conductive sealing compounds such as graphite.
‣
24Endress+Hauser
Page 25
Proline Promag H 200 HARTInstallation
Comply with the following instructions when installing seals:
• Make sure that the seals do not protrude into the piping cross-section.
• In the case of metal process connections, the screws must be tightened securely. The
process connection forms a metal connection with the sensor, which ensures a defined
compression of the seal.
• In the case of plastic process connections, comply with the max. screw tightening torques
for lubricated threads: 7 Nm (5.2 lbf ft). In the case of plastic flanges, always insert a
seal between the connection and the counterflange.
• For "PFA" lining: additional seals are always required.
• Depending on the application the seals should be replaced periodically, particularly if
molded seals are used (aseptic version)! The interval between changes depends on the
frequency of the cleaning cycles, the cleaning temperature and the medium temperature.
Replacement seals can be ordered as an accessory → 134.
Mounting grounding rings (DN 2 to 25 (1/12 to 1"))
Pay attention to the information on potential equalization → 32.
In the case of plastic process connections (e.g. flange connections or adhesive fittings),
additional ground rings must be used to ensure potential matching between the sensor
and the fluid. If grounding rings are not installed, this can affect the measuring accuracy or
cause the destruction of the sensor as a result of the electrochemical decomposition of the
electrodes.
• Depending on the option ordered, plastic disks are used instead of grounding rings
on some process connections. These plastic disks only act as "spacers" and do not
have any potential matching function. Furthermore, they also perform a significant
sealing function at the sensor/process connection interface. Therefore, in the case
of process connections without metal grounding rings, these plastic disks/seals
should never be removed and should always be installed!
• Grounding rings can be ordered separately as an accessory from Endress+Hauser
→ 134. When ordering make sure that the grounding rings are compatible with
the material used for the electrodes, as otherwise there is the danger that the
electrodes could be destroyed by electrochemical corrosion!
Material specifications → 129.
• Grounding rings, including seals, are mounted inside the process connections.
Therefore the installation length is not affected.
Endress+Hauser25
Page 26
InstallationProline Promag H 200 HART
1
3
2
4
2
max.350°
8mm
8mm
A0002651
7Installing grounding rings
1Hexagonal-headed bolts of process connection
2O-ring seals
3Grounding ring or plastic disk (spacer)
4Sensor
1.Release the 4 or 6 hexagonal-headed bolts (1) and remove the process connection
from the sensor (4).
2.Remove the plastic disk (3), along with the two O-ring seals (2), from the process
connection.
3.Place the first O-ring seal (2) back into the groove of the process connection.
4.Fit the metal grounding ring (3) in the process connection as illustrated.
5.Place the second O-ring seal (2) into the groove of the grounding ring.
6.Mount the process connection back on the sensor. In doing so, make sure to observe
the maximum screw tightening torques for lubricated threads: 7 Nm (5.2 lbf ft)
6.2.4 Turning the transmitter housing
To provide easier access to the connection compartment or display module, the transmitter
housing can be turned.
A0013713
1.Release the fixing screw.
2.Turn the housing to the desired position.
26Endress+Hauser
Page 27
Proline Promag H 200 HARTInstallation
+
E
–
1
3mm
3.Firmly tighten the securing screw.
6.2.5 Turning the display module
The display module can be turned to optimize display readability and operability.
A0013905
1.Loosen the securing clamp of the electronics compartment cover using an Allen key.
2.Unscrew cover of the electronics compartment from the transmitter housing.
3.Optional: pull out the display module with a gentle rotational movement.
4.Rotate the display module into the desired position: Max. 8 × 45° in each direction.
5.Without display module pulled out:
Allow display module to engage at desired position.
6.With display module pulled out:
Feed the cable into the gap between the housing and main electronics module and
plug the display module into the electronics compartment until it engages.
7.Reverse the removal procedure to reassemble the transmitter.
6.3 Post-installation check
Is the device undamaged (visual inspection)?
Does the measuring device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure (refer to the section on "Pressure-temperature ratings" in the "Technical
Information" document)
• Ambient temperature
• Measuring range
Has the correct orientation for the sensor been selected ?
• According to sensor type
• According to medium temperature
• According to medium properties (outgassing, with entrained solids)
Does the arrow on the sensor nameplate match the direction of flow of the fluid through the
piping ?
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected from precipitation and direct sunlight?
Have the fixing screws been tightened with the correct tightening torque?
Endress+Hauser27
Page 28
Electrical connectionProline Promag H 200 HART
7 Electrical connection
The measuring device does not have an internal circuit breaker. For this reason,
assign the measuring device a switch or power-circuit breaker so that the power
supply line can be easily disconnected from the mains.
7.1 Connection conditions
7.1.1 Required tools
• For cable entries: Use corresponding tools
• For securing clamp: Allen key 3 mm
• Wire stripper
• When using stranded cables: crimping tool for ferrule
• For removing cables from terminal: flat blade screwdriver ≤3 mm (0.12 in)
7.1.2 Requirements for connecting cable
The connecting cables provided by the customer must fulfill the following requirements.
Electrical safety
In accordance with applicable federal/national regulations.
Permitted temperature range
• –40 °C (–40 °F) to +80 °C (+176 °F)
• Minimum requirement: cable temperature range ≥ ambient temperature +20 K
Signal cable
Current output
For 4-20 mA HART: Shielded cable recommended. Observe grounding concept of the
plant.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Plug-in spring terminals for device version without integrated overvoltage protection:
wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Screw terminals for device version with integrated overvoltage protection: wire crosssections 0.2 to 2.5 mm2 (24 to 14 AWG)
28Endress+Hauser
Page 29
Proline Promag H 200 HARTElectrical connection
–
4
+
1
–
2
+
3
1
2
3
+
1
–
2
–
4
+
3
1
2
3
7.1.3 Terminal assignment
Transmitter
4-20 mA HART connection version with additional outputs
A0013570
Maximum number of terminals, without integrated
overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Ground terminal for cable shield
Order code for "Output"Terminal numbers
Output 1Output 2
1 (+)2 (-)3 (+)4 (-)
Option A4-20 mA HART (passive)-
1)
Option B
1)Output 1 must always be used; output 2 is optional.
4-20 mA HART (passive)
Maximum number of terminals, with integrated
overvoltage protection
Pulse/frequency/switch output
(passive)
A0018161
7.1.4 Requirements for the supply unit
Supply voltage
Transmitter
An external power supply is required for each output. The following supply voltage values
apply for the 4-20 mA HART current output:
Order code for "Output"
Option A
Option B
switch output
1)External supply voltage of the power supply unit with load.
2)For device versions with SD03 local display: The terminal voltage must be increased by DC 2 V if
1) 2)
: 4-20 mA HARTFor 4 mA: ≥ DC 18 V
1) 2)
: 4-20 mA HART, pulse/frequency/
backlighting is used.
Minimum terminal
voltage
For 20 mA: ≥ DC 14 V
For 4 mA: ≥ DC 18 V
For 20 mA: ≥ DC 14 V
Maximum terminal
voltage
DC 35 V
DC 35 V
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power
supply unit
Endress+Hauser29
Page 30
Electrical connectionProline Promag H 200 HART
0
100
200
300
400
500
14
161820
2224
26283032
U [V]
s
R [ ]bW
1.11.21
3436
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB)
including line resistance must be observed to ensure adequate terminal voltage at the
device. In doing so, observe the minimum terminal voltage
• For US = 18 to 18.9 V: RB ≤ (US - 18 V): 0.0036 A
• For US = 18.9 to 24.5 V: RB ≤ (US - 13.5 V): 0.022 A
• For US = 24.5 to 30 V: RB ≤ 500 Ω
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with non-Ex and Ex d
Sample calculation
Supply voltage of the power supply unit: US = 19 V
Maximum load: RB ≤ (19 V - 13.5 V): 0.022 A = 250 Ω
7.1.5 Preparing the measuring device
1.Remove dummy plug if present.
2.NOTICE! Insufficient sealing of the housing! Operational reliability of the measuring
device could be compromised. Use suitable cable glands corresponding to the degree
of protection.
If measuring device is delivered without cable glands:
Provide suitable cable gland for corresponding connecting cable .
3.If measuring device is delivered with cable glands:
Observe cable specification .
A0013563
7.2 Connecting the measuring device
NOTICE
Limitation of electrical safety due to incorrect connection!
Have electrical connection work carried out by correspondingly trained specialists only.
‣
Observe applicable federal/national installation codes and regulations.
‣
30Endress+Hauser
Comply with local workplace safety regulations.
‣
For use in potentially explosive atmospheres, observe the information in the device-
‣
specific Ex documentation.
7.2.1 Connecting the transmitter
Page 31
Proline Promag H 200 HARTElectrical connection
10(0.4)
mm(in)
20 mm3mm
mm (in)
213 4
3 (0.12)
Connection via terminals
A0013836
1.Loosen the securing clamp of the connection compartment cover.
2.Unscrew the connection compartment cover.
3.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4.Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5.Connect the cable in accordance with the terminal assignment . For HART
communication: when connecting the cable shielding to the ground terminal, observe
the grounding concept of the facility.
6.Firmly tighten the cable glands.
7.WARNING! Housing degree of protection may be voided due to insufficient sealing of
the housing. Screw in the screw without using any lubricant. The threads on the
cover are coated with a dry lubricant.
Reverse the removal procedure to reassemble the transmitter.
Removing a cable
A0013835
To remove a cable from the terminal, use a flat-blade screwdriver to push the slot
‣
between the two terminal holes while simultaneously pulling the cable end out of the
terminal.
Endress+Hauser31
Page 32
Electrical connectionProline Promag H 200 HART
7.2.2 Ensuring potential equalization
Requirements
CAUTION
L
Electrode damage can result in the complete failure of the device!
Same electrical potential for the fluid and sensor
‣
Company-internal grounding concepts
‣
Pipe material and grounding
‣
For devices intended for use in hazardous locations, please observe the guidelines in
the Ex documentation (XA).
Connection examples for standard situations
Metal process connections
Potential matching usually takes place via the metallic process connections in contact with
medium which are directly mounted on the measuring transmitter. This usually means
that additional potential matching measures are unnecessary.
Connection example in special situations
Plastic process connections
In the case of plastic process connections, additional grounding rings or process
connections with an integrated grounding electrode must be used to ensure potential
matching between the sensor and the fluid. If there is no potential matching, this can
affect the measuring accuracy or cause the destruction of the sensor as a result of the
electrochemical decomposition of the electrodes.
Note the following when using grounding rings:
• Depending on the option ordered, plastic disks are used instead of grounding rings on
some process connections. These plastic disks only act as "spacers" and do not have any
potential matching function. Furthermore, they also perform a significant sealing
function at the sensor/connection interface. Therefore, in the case of process
connections without metal grounding rings, these plastic disks/seals should never be
removed and should always be installed!
• Grounding rings can be ordered separately as an accessory from Endress+Hauser . When
ordering make sure that the grounding rings are compatible with the material used for
the electrodes, as otherwise there is the danger that the electrodes could be destroyed by
electrochemical corrosion!
• Grounding rings, including seals, are mounted inside the process connections. Therefore
the installation length is not affected.
32Endress+Hauser
Page 33
Proline Promag H 200 HARTElectrical connection
1
3
2
4
2
2
1
3
4
Potential equalization via additional grounding ring
A0002651
1Hexagonal-headed bolts of process connection
2O-ring seals
3Plastic disk (spacer) or grounding ring
4Sensor
Potential equalization via grounding electrodes on process connection
1Hexagonal-headed bolts of process connection
2Integrated grounding electrodes
3O-ring seal
4Sensor
A0017293
Endress+Hauser33
Page 34
Electrical connectionProline Promag H 200 HART
2
3
4...20 mA
41
+
-
5
+
-
1
+
_
12345
2
+
–
+
–
3
7.3 Special connection instructions
7.3.1 Connection examples
Current output 4-20 mA HART
A0015511
8Connection example for 4-20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply with integrated resistor for HART communication (≥ 250 Ω)(e.g. RN221N)
Connection for HART operating devices → 131
Observe the maximum load → 29
3Cable shield, observe cable specifications
4Analog display unit: observe maximum load → 29
5Transmitter
Pulse/frequency output
9Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: observe input values
A0016801
34Endress+Hauser
Page 35
Proline Promag H 200 HARTElectrical connection
1
+
_
+
_
2
+
_
3
3
4...20 mA
5
1
+
-
3
6
+
–
+
+
–
+
–
+
–
+
–
–
2
4
4
7
+
-
Switch output
A0016802
10Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
2Power supply
3Transmitter: observe input values
HART input
A0016029
11Connection example for HART input with a common negative
1Automation system with HART output (e.g. PLC)
2Resistor for HART communication (≥ 250 Ω): observe maximum load → 30
3Active barrier for power supply (e.g. RN221N)
4Cable shield, observe cable specifications
5Analog display unit: observe maximum load → 30
6Pressure transmitter (e.g. Cerabar M, Cerabar S): see requirements
7Transmitter
7.4 Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection,
Type 4X enclosure.
Endress+Hauser35
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following
steps after the electrical connection:
1.Check that the housing seals are clean and fitted correctly. Dry, clean or replace the
2.Tighten all housing screws and screw covers.
3.Firmly tighten the cable glands.
seals if necessary.
Page 36
Electrical connectionProline Promag H 200 HART
4.To ensure that moisture does not enter the cable entry, route the cable so that it
loops down before the cable entry ("water trap").
A0013960
5.Insert dummy plugs into unused cable entries.
7.5 Post-connection check
Are cables or the device undamaged (visual inspection)?
Do the cables comply with the requirements ?
Do the cables have adequate strain relief?
Are all the cable glands installed, firmly tightened and leak-tight? Cable run with "water trap"
→ 35 ?
Depending on the device version: are all the device plugs firmly tightened ?
Does the supply voltage match the specifications on the transmitter nameplate ?
Is the terminal assignment correct ?
If supply voltage is present, do values appear on the display module?
Is the potential equalization established correctly → 32?
Are all housing covers installed and firmly tightened?
Is the securing clamp tightened correctly?
36Endress+Hauser
Page 37
Proline Promag H 200 HARTOperation options
1
23
45
S
C
8 Operation options
8.1 Overview of operation options
A0015607
1Local operation via display module
2Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
3Field Xpert SFX350 or SFX370
4Field Communicator 475
5Control system (e.g. PLC)
Endress+Hauser37
Page 38
Operation optionsProline Promag H 200 HART
!
Expert
System
Sensor
Communication
Application
Diagnostics
Access status display
Output
Operating menu for experts
Language
OperatationLanguage
Parameter 1
Setup
Submenu 1
Submenu n
Device tag
Advanced setup
Enter access code
Parameter 1
Parameter n
Submenu 1
Submenu n
Diagnostics
Parameter 1
Parameter n
Submenu 1
Submenu n
Operating menu for operators and maintenances
Parameter n
Operator
Maintenance
Task-oriented
Function-oriented
Expert
Wizard 1 / Parameter 1
Wizard n / Parameter n
Parameter n
Intput
8.2 Structure and function of the operating menu
8.2.1 Structure of the operating menu
For an overview of the operating menu with menus and parameters
38Endress+Hauser
12Schematic structure of the operating menu
A0018237-EN
Page 39
Proline Promag H 200 HARTOperation options
8.2.2 Operating philosophy
The individual parts of the operating menu are assigned to certain user roles (operator,
maintenance etc.). Each user role contains typical tasks within the device lifecycle.
Contains all parameters for error detection and analyzing
process and device errors:
• "Diagnostic list" submenu
Contains up to 5 currently pending diagnostic messages.
• "Event logbook" submenu
Contains up to 20 or 100 (order option " Extended
HistoROM") event messages that have occurred.
• "Device information" submenu
Contains information for identifying the device.
• "Measured values" submenu
Contains all current measured values.
• "Data logging" submenu (order option "Extended
HistoROM")
Storage and visualization of up to 1000 measured values
• "Heartbeat Technology" submenu
The functionality of the device is checked on demand and the
verification results are documented.
• "Simulation" submenu
Is used to simulate measured values or output values.
Expertfunction-oriented Tasks that require detailed knowledge
of the function of the device:
• Commissioning measurements under
difficult conditions
• Optimal adaptation of the
measurement to difficult conditions
• Detailed configuration of the
communication interface
• Error diagnostics in difficult cases
Contains all the parameters of the device and makes it possible
to access these parameters directly using an access code. The
structure of this menu is based on the function blocks of the
device:
• "System" submenu
Contains all higher-order device parameters that do not
pertain either to measurement or the measured value
communication.
• "Sensor" submenu
Configuration of the measurement.
• "Input" submenu
Configuration of the input.
• "Output" submenu
Configuration of the outputs.
• "Communication" submenu
Configuration of the digital communication interface.
• "Application" submenu
Configuration of the functions that go beyond the actual
measurement (e.g. totalizer).
• "Diagnostics" submenu
Error detection and analysis of process and device errors and
for device simulation and Heartbeat Technology.
Endress+Hauser39
Page 40
Operation optionsProline Promag H 200 HART
X X X X X X XXX
4
2
1
3
5
l/h
1120.50
F
8.3 Access to the operating menu via the local display
8.3.1 Operational display
A0016502
1
Operational display
2
Device tag
3
Status area
4
Display area for measured values (4-line)
5
Operating elements → 45
Status area
The following symbols appear in the status area of the operational display at the top right:
• Status signals→ 98
– F: Failure
– C: Function check
– S: Out of specification
– M: Maintenance required
• Diagnostic behavior→ 99
–: Alarm
–: Warning
•: Locking (the device is locked via the hardware )
•: Communication (communication via remote operation is active)
Display area
In the display area, each measured value is prefaced by certain symbol types for further
description:
Measured variableMeasurement channel
number
↓↓↓
Example
Diagnostic behavior
Appears only if a diagnostics
event is present for this
measured variable.
Measured variables
SymbolMeaning
Volume flow
Mass flow
40Endress+Hauser
Page 41
Proline Promag H 200 HARTOperation options
4
2
1
3
5
/../Operation
0091-1
Access stat.disp
Operator
Locking status
Display
S
4
2
1
5
3
/../Curr. output 1
Assign curr.
Volume flow
Totalizer
The measurement channel number indicates which of the three totalizers is
displayed.
Output
The measurement channel number indicates which of the two current outputs is
displayed.
Measurement channel numbers
SymbolMeaning
Measurement channel 1 to 4
The measurement channel number is displayed only if more than one channel is present for the same measured
variable type (e.g. totalizer 1-3).
Diagnostic behavior
The diagnostic behavior pertains to a diagnostic event that is relevant to the displayed measured variable.
For information on the symbols → 99
The number and display format of the measured values can be configured via the
"Format display" parameter → 72. "Operation" menu → Display → Format
display
8.3.2 Navigation view
In the submenuIn the wizard
A0013993-EN
1
Navigation view
2
Navigation path to current position
3
Status area
4
Display area for navigation
5
Operating elements → 45
Navigation path
The navigation path - displayed at the top left in the navigation view - consists of the
following elements:
A0016327-EN
• In the submenu:
Display symbol for menu
• In the wizard:
Display symbol for wizard
↓↓↓
Examples/ ../Display
Omission symbol for
operating menu levels in
between
/ ../Display
Name of current
• Submenu
• Wizard
• Parameter
Endress+Hauser41
Page 42
Operation optionsProline Promag H 200 HART
For more information about the menu icons, refer to the "Display area" section
→ 42
Status area
The following appears in the status area of the navigation view in the top right corner:
• Of the submenu
– The direct access code for the parameter you are navigating to (e.g. 0022-1)
– If a diagnostic event is present, the diagnostic behavior and status signal
• In the wizard
If a diagnostic event is present, the diagnostic behavior and status signal
• For information on the diagnostic behavior and status signal → 98
• For information on the function and entry of the direct access code → 47
Display area
Menus
SymbolMeaning
Operation
Appears:
• In the menu next to the "Operation" selection
• At the left in the navigation path in the "Operation" menu
Setup
Appears:
• In the menu next to the "Setup" selection
• At the left in the navigation path in the "Setup" menu
Diagnostics
Appears:
• In the menu next to the "Diagnostics" selection
• At the left in the navigation path in the "Diagnostics" menu
Expert
Appears:
• In the menu next to the "Expert" selection
• At the left in the navigation path in the "Expert" menu
Submenus, wizards, parameters
SymbolMeaning
Submenu
Wizard
Parameters within a wizard
No display symbol exists for parameters in submenus.
Locking
SymbolMeaning
Parameter locked
When displayed in front of a parameter name, indicates that the parameter is locked.
• By a user-specific access code
• By the hardware write protection switch
42Endress+Hauser
Page 43
Proline Promag H 200 HARTOperation options
3
2
1
4
3
4
0
12
9
5
6
8
7
20
…
0
9
.
–
Wizard operation
SymbolMeaning
Switches to the previous parameter.
Confirms the parameter value and switches to the next parameter.
Opens the editing view of the parameter.
8.3.3 Editing view
Numeric editorText editor
A0013941 A0013999
1
Editing view
2
Display area of the entered values
3
Input mask
4
Operating elements → 45
Input mask
The following input symbols are available in the input mask of the numeric and text editor:
Numeric editor
SymbolMeaning
Selection of numbers from 0 to 9.
Inserts decimal separator at the input position.
Inserts minus sign at the input position.
Confirms selection.
Moves the input position one position to the left.
Exits the input without applying the changes.
Clears all entered characters.
Endress+Hauser43
Page 44
Operation optionsProline Promag H 200 HART
Aa1
XYZ
ABC
_
…
xyz
abc
_
…
~&
"'^
_
…
_
Text editor
SymbolMeaning
Toggle
• Between upper-case and lower-case letters
• For entering numbers
• For entering special characters
Selection of letters from A to Z.
Selection of letters from a to z.
Selection of special characters.
Confirms selection.
Switches to the selection of the correction tools.
Exits the input without applying the changes.
Clears all entered characters.
Correction symbols under
SymbolMeaning
Clears all entered characters.
Moves the input position one position to the right.
Moves the input position one position to the left.
Deletes one character immediately to the left of the input position.
44Endress+Hauser
Page 45
Proline Promag H 200 HARTOperation options
+
+
+
++
8.3.4 Operating elements
KeyMeaning
Minus key
In a menu, submenu
Moves the selection bar upwards in a choose list.
With a Wizard
Confirms the parameter value and goes to the previous parameter.
With a text and numeric editor
In the input mask, moves the selection bar to the left (backwards).
Plus key
In a menu, submenu
Moves the selection bar downwards in a choose list.
With a Wizard
Confirms the parameter value and goes to the next parameter.
With a text and numeric editor
Moves the selection bar to the right (forwards) in an input screen.
Enter key
For operational display
• Pressing the key briefly opens the operating menu.
• Pressing the key for 2 s opens the context menu.
In a menu, submenu
• Pressing the key briefly:
– Opens the selected menu, submenu or parameter.
– Starts the wizard.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s for parameter:
If present, opens the help text for the function of the parameter.
With a Wizard
Opens the editing view of the parameter.
With a text and numeric editor
• Pressing the key briefly:
– Opens the selected group.
– Carries out the selected action.
• Pressing the key for 2 s confirms the edited parameter value.
• Pressing the key briefly:
– Exits the current menu level and takes you to the next higher level.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s returns you to the operational display ("home position").
With a Wizard
Exits the wizard and takes you to the next higher level.
With a text and numeric editor
Closes the text or numeric editor without applying changes.
Minus/Enter key combination (press the keys simultaneously)
Reduces the contrast (brighter setting).
Plus/Enter key combination (press and hold down the keys simultaneously)
Increases the contrast (darker setting).
Minus/Plus/Enter key combination (press the keys simultaneously)
For operational display
Enables or disables the keypad lock (only SD02 display module).
8.3.5 Opening the context menu
Using the context menu, the user can call up the following menus quickly and directly from
the operational display:
Endress+Hauser45
Page 46
Operation optionsProline Promag H 200 HART
• Setup
• Conf. backup disp.
• Simulation
Calling up and closing the context menu
The user is in the operational display.
1.Press for 2 s.
The context menu opens.
A0016326-EN
2.Press + simultaneously.
The context menu is closed and the operational display appears.
Calling up the menu via the context menu
1.Open the context menu.
2.Press to navigate to the desired menu.
3.Press to confirm the selection.
The selected menu opens.
46Endress+Hauser
Page 47
Proline Promag H 200 HARTOperation options
X X X X X XXXX
20.50
0104-1
2 s
0091-1
0098-1
0098-1
0098-1
X X X X X XXXX
10.50
19.00
XX
XX
XXXX
Operation
Operation
Setup
Main menu
English
Main menu
Format display
/ ../Display
Contrast display
Display intervall
1 value, max.
Setup
Access stat.disp
/ ../Operation
Display
Locking status
1 value, max.
/ ../Format display
2 values
Val. large+2val.
Bargr. + 1 value
Locking status
/ ../Operation
Display
1 value, max.
/ ../Format display
2 values
Val. large+2val.
Bargr. + 1 value
Operator
Language
Language
8.3.6 Navigating and selecting from list
Different operating elements are used to navigate through the operating menu. The
navigation path is displayed on the left in the header. Icons are displayed in front of the
individual menus. These icons are also shown in the header during navigation.
For an explanation of the navigation view with symbols and operating elements
→ 41
Example: Setting the number of displayed measured values to "2 values"
Endress+Hauser47
8.3.7 Calling the parameter directly
A parameter number is assigned to every parameter to be able to access a parameter
directly via the onsite display. Entering this access code in the Direct access parameter
calls up the desired parameter directly.
The direct access code consists of a 4-digit number and the channel number, which
identifies the channel of a process variable: e.g. 0914-1. In the navigation view, this
appears on the right-hand side in the header of the selected parameter.
A0017223
1Direct access code
Note the following when entering the direct access code:
• The leading zeros in the direct access code do not have to be entered.
Example: Input of "914" instead of "0914"
• If no channel number is entered, channel 1 is jumped to automatically.
Example: Input of "0914" → Parameter Totalizer 1
• If a different channel is jumped to: Enter the direct access code with the corresponding
channel number.
Example: Input of "0914-2" → Parameter Totalizer 2
For the direct access codes of the individual parameters
8.3.8 Calling up help text
For some parameters, help texts exist, which the user can call up from the navigation view.
These briefly describe the function of the parameter and thus support fast and reliable
commissioning.
Calling up and closing the help text
The user is in the navigation view and the selection bar is on a parameter.
1.Press for 2 s.
The help text for the selected parameter opens.
A0014002-EN
13Example: Help text for parameter "Enter access code"
2.Press + simultaneously.
The help text is closed.
48Endress+Hauser
Page 49
Proline Promag H 200 HARTOperation options
3x
001-FT-101
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-101
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-101
DEFGHIJK
ABC
001-FT-10
DEFGHIJK
ABC
001-FT-10
DEFGHIJK
ABC
1x
001-FT-10
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-10
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-10
DEFGHIJK
ABC
A a 1
@
001-FT-10
DEFGHIJK
ABC
A a 1
@
001-FT-10
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-10
3456789
012
0 1 2
001-FT-10
3456789
012
0 1 2
001-FT-102
3456789
012
012
001-FT-102
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-102
3456789
012
012
001-FT-102
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-102
3456789
012
012
001-FT-102
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-102
1496-1
1x
2x
4x
2x
1x
001-FT-101
1496-1
Max.
Tag description
Ent. access code
Def. access code
/../Advanced setup
Tag description
/../Advanced setup
Ent. access code
Def. access code
8.3.9 Changing the parameters
For a description of the editing display - consisting of text editor and numeric editor with symbols → 43, for a description of the operating elements → 45
Example: Changing the tag name in the "Tag description" parameter from 001-FT-101 to
001-FT-102
Endress+Hauser49
A message is displayed if the value entered is outside the permitted value range.
A0014020-EN
Page 50
Operation optionsProline Promag H 200 HART
Ent.accesscode
Invalidoroutofrangeinput
value
Max:9999
Min:0
A0014049-EN
8.3.10 User roles and related access authorization
The two user roles "Operator" and "Maintenance" have different write access to the
parameters if the customer defines a user-specific access code. This protects the device
configuration via the local display from unauthorized access .
Access authorization to parameters
User roleRead accessWrite access
Without access code
(from the factory)
Operator--
Maintenance
With access codeWithout access code
(from the factory)
With access code
1)
1)Despite the defined access code, certain parameters can always be modified and thus are excepted from
the write protection, as they do not affect the measurement. Refer to the "Write protection via access code"
section
If an incorrect access code is entered, the user obtains the access rights of the "Operator"
role.
The user role with which the user is currently logged on is indicated by the Access
status display parameter. Navigation path: Operation → Access status display
8.3.11 Disabling write protection via access code
If the -symbol appears on the local display in front of a parameter, the parameter is
write-protected by a user-specific access code and its value cannot be changed at the
moment using the local display .
The locking of the write access via local operation can be disabled by entering the
customer-defined access code via the respective access option.
1.After you press , the input prompt for the access code appears.
2.Enter the access code.
The -symbol in front of the parameters disappears; all previously write-
protected parameters are now re-enabled.
8.3.12 Enabling and disabling the keypad lock
The keypad lock makes it possible to block access to the entire operating menu via local
operation. As a result, it is no longer possible to navigate through the operating menu or
change the values of individual parameters. Users can only read the measured values on
the operational display.
Local operation with mechanical push buttons (display module SD02)
Display module SD02: order characteristic "Display; Operation", option C
The keypad lock is switched on and off in the same way:
50Endress+Hauser
Page 51
Proline Promag H 200 HARTOperation options
Switching on the keypad lock
The device is in the measured value display.
‣
Press the + + keys simultaneously.
The message Keylock on appears on the display: The keypad lock is switched on.
If the user attempts to access the operating menu while the keypad lock is active, the
message Keylock on appears.
Switching off the keypad lock
The keypad lock is switched on.
‣
Press the + + keys simultaneously.
The message Keylock off appears on the display: The keypad lock is switched off.
Local operation with touch control (display module SD03)
Display module SD03: Order characteristic "Display; Operation", option E
The keypad lock is switched on and off via the context menu.
Switching on the keypad lock
The keypad lock is switched on automatically:
• Each time the device is restarted.
• If the device has not been operated for longer than one minute in the measured value
display.
1.The device is in the measured value display.
Press the key for longer than 2 seconds.
A context menu appears.
2.In the context menu, select the Keylock on option.
The keypad lock is switched on.
If the user attempts to access the operating menu while the keypad lock is active, the
message Keylock on appears.
Switching off the keypad lock
1.The keypad lock is switched on.
Press the key for longer than 2 seconds.
A context menu appears.
2.In the context menu, select the Keylock off option.
The keypad lock is switched off.
8.4 Access to the operating menu via the operating tool
The structure of the operating menu in the operating tools is the same as for operation via
the local display.
Endress+Hauser51
Page 52
Operation optionsProline Promag H 200 HART
1
2
457
9
68
3
+
E
–
12
3
8.4.1 Connecting the operating tool
Via HART protocol
A0013764
14Options for remote operation via HART protocol
1Control system (e.g. PLC)
2Transmitter power supply unit, e.g. RN221N (with communication resistor)
3Connection for Commubox FXA195 and Field Communicator 475
4Field Communicator 475
5Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
6Commubox FXA195 (USB)
7Field Xpert SFX350 or SFX370
8VIATOR Bluetooth modem with connecting cable
9Transmitter
Via service interface (CDI)
1Service interface (CDI = Endress+Hauser Common Data Interface) of the measuring device
2Commubox FXA291
3Computer with "FieldCare" operating tool with COM DTM "CDI Communication FXA291"
A0014019
52Endress+Hauser
Page 53
Proline Promag H 200 HARTOperation options
8.4.2 Field Xpert SFX350, SFX370
Function scope
Field Xpert SFX350 and Field Xpert SFX370 are mobile computers for commissioning and
maintenance. They enable efficient device configuration and diagnostics for HART and
FOUNDATION fieldbus devices in the non-Ex area (SFX350, SFX370) and the Ex area
(SFX370).
For details, see Operating Instructions BA01202S
Source for device description files
See data → 56
8.4.3 FieldCare
Function scope
FDT-based plant asset management tool from Endress+Hauser. It can configure all smart
field devices in a system and helps you manage them. By using the status information, it is
also a simple but effective way of checking their status and condition.
Access takes place via:
• HART protocol → 52
• Service interface CDI → 52
Typical functions:
• Configuring parameters of transmitters
• Loading and saving device data (upload/download)
• Documentation of the measuring point
• Visualization of the measured value memory (line recorder) and event logbook
For details, see Operating Instructions BA00027S and BA00059S
Source for device description files
See data → 56
Endress+Hauser53
Page 54
Operation optionsProline Promag H 200 HART
6
5
32
1
Xxxxxx/…/…/
7
P
P
+
–
P
–
P
+
+
+
+
+
+
4
89
10
11
Xxxxxxx
GoodStatus:
Device tag:
Xxxxxxx
Device name:
Mass flow:
12.34
kg/h
Volume flow:
12.34
m /h³
Mass flow unit:
Volume flow unit:
kg/h
m /h³
Access status tooling
Operation
Setup
Xxxxxx
Mass flow unit
Volume flow unit
Select medium
Device tag
…
…
Advanced setup
Diagnostics
Expert
Maintenance
kg/h
m /h³
Xxxxxx
System units
User interface
A0021051-EN
1Header
2Picture of device
3Device name
4Device tag
5Status area with status signal
6Display area for current measured values
7Event list with additional functions such as save/load, events list and document creation
8Navigation area with operating menu structure
9Operating range
10 Range of action
11 Status area
8.4.4 AMS Device Manager
Function scope
Program from Emerson Process Management for operating and configuring measuring
devices via HART protocol.
Source for device description files
See data → 56
8.4.5 SIMATIC PDM
Function scope
SIMATIC PDM is a standardized, manufacturer-independent program from Siemens for
the operation, configuration, maintenance and diagnosis of intelligent field devices via
HART protocol.
Source for device description files
See data → 56
54Endress+Hauser
Page 55
Proline Promag H 200 HARTOperation options
8.4.6 Field Communicator 475
Function scope
Industrial handheld terminal from Emerson Process Management for remote
configuration and measured value display via HART protocol.
Source for device description files
See data → 56
Endress+Hauser55
Page 56
System integrationProline Promag H 200 HART
9 System integration
9.1 Overview of device description files
9.1.1 Current version data for the device
Firmware version01.01.zz• On the title page of the Operating instructions
• On the transmitter nameplate → 13
• Firmware version
"Diagnostics" menu → Device information
→ Firmware version
Release date of firmware version04.2015---
Manufacturer ID0x11Manufacturer ID
"Diagnostics" menu → Device information
→ Manufacturer ID
Device type ID0x48Device type
"Diagnostics" menu → Device information → Device
type
HART protocol revision7---
Device revision2• On the transmitter nameplate → 13
• Device revision
"Diagnostics" menu → Device information → Device
revision
9.1.2 Operating tools
Operating tool via
HART protocol
• Field Xpert SFX350
• Field Xpert SFX370
FieldCare• www.endress.com → Download Area
AMS Device Manager
(Emerson Process Management)
SIMATIC PDM
(Siemens)
Field Communicator 475
(Emerson Process Management)
Sources for obtaining device descriptions
Use update function of handheld terminal
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
www.endress.com → Download Area
www.endress.com → Download Area
Use update function of handheld terminal
9.2 Measured variables via HART protocol
The following measured variables (HART device variables) are assigned to the dynamic
variables at the factory:
Dynamic variablesMeasured variables
(HART device variables)
Primary dynamic variable (PV)Volume flow
Secondary dynamic variable (SV)Totalizer 1
Tertiary dynamic variable (TV)Totalizer 2
Quaternary dynamic variable (QV)Totalizer 3
56Endress+Hauser
Page 57
Proline Promag H 200 HARTSystem integration
The assignment of the measured variables to the dynamic variables can be modified and
assigned as desired via local operation and the operating tool using the following
parameters:
The following measured variables can be assigned to the dynamic variables:
Measured variables for PV (primary dynamic variable)
• Volume flow
• Mass flow
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic
variable)
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
9.3 Other settings
9.3.1 Burst mode functionality in accordance with HART 7
Specification
Navigation
"Expert" menu → Communication → HART output → Burst configuration → Burst
configuration 1 to 3
Burst configuration
‣
Burst configuration 1 to 3
‣
Burst mode 1 to 3
Burst command 1 to 3
Burst variable 0
Burst variable 1
Burst variable 2
Burst variable 3
Burst variable 4
Burst variable 5
Endress+Hauser57
Page 58
System integrationProline Promag H 200 HART
Burst variable 6
Burst variable 7
Burst trigger mode
Burst trigger level
Min. update period
Max. update period
Parameter overview with brief description
ParameterDescriptionSelection / User entryFactory setting
Burst mode 1 to 3Activate the HART burst mode for burst
message X.
Burst command 1 to 3Select the HART command that is sent to the
HART master.
Burst variable 0For HART command 9 and 33, assign a
HART device variable or process variable to
burst variable.
Burst variable 1For HART command 9 and 33, assign a
HART device variable or process variable to
burst variable.
Burst variable 2For HART command 9 and 33, assign a
HART device variable or process variable to
burst variable.
Burst variable 3For HART command 9 and 33, assign a
HART device variable or process variable to
burst variable.
Burst variable 4For HART command 33, assign a HART
device variable or process variable to burst
variable.
Burst variable 5For HART command 33, assign a HART
device variable or process variable to burst
variable.
Burst variable 6For HART command 33, assign a HART
device variable or process variable to burst
variable.
Burst variable 7For HART command 33, assign a HART
device variable or process variable to burst
variable.
• Off
• On
• Command 1
• Command 2
• Command 3
• Command 9
• Command 33
• Command 48
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Percent Of Range
• Measured current
• Primary variable (PV)
• Secondary variable (SV)
• Tertiary variable (TV)
• Quaternary variable (QV)
• Not used
See Burst variable 0
parameter.
See Burst variable 0
parameter.
See Burst variable 0
parameter.
See Burst variable 0
parameter.
See Burst variable 0
parameter.
See Burst variable 0
parameter.
See Burst variable 0
parameter.
Off
Command 2
Volume flow
Not used
Not used
Not used
Not used
Not used
Not used
Not used
58Endress+Hauser
Page 59
Proline Promag H 200 HARTSystem integration
ParameterDescriptionSelection / User entryFactory setting
Burst trigger modeSelect the event that triggers burst messageX.• Continuous
• Window
• Rising
• Falling
• On change
Burst trigger levelEnter the burst trigger value.
Together with the option selected in the
Burst trigger mode parameter the burst
trigger value determines the time of burst
message X.
Min. update periodEnter the minimum time span between two
burst responses of one burst message.
Max. update periodEnter the maximum time span between two
burst responses of one burst message.
Positive floating-point number 2.0E-38
Positive integer1000 ms
Positive integer2000 ms
Continuous
Endress+Hauser59
Page 60
CommissioningProline Promag H 200 HART
X X X X X XXXX
20.50
Operation
Setup
Main menu
0104-1
Language
English
Español
Français
Language
English
Deutsch
Ã
0104-1
Ã
Español
Français
Language
English
Deutsch
0104-1
Betrieb
Setup
Hauptmenü
Sprache
Deutsch
0104-1
XXXX
10 Commissioning
10.1 Function check
Before commissioning the measuring device:
Make sure that the post-installation and post-connection checks have been performed.
‣
• "Post-installation check" checklist → 27
• "Post-connection check" checklist → 36
10.2 Switching on the measuring device
After a successful function check, switch on the measuring device.
‣
After a successful startup, the local display switches automatically from the startup
display to the operational display.
If nothing appears on the local display or a diagnostic message is displayed, refer to
the section on "Diagnostics and troubleshooting" → 96.
10.3 Setting the operating language
Factory setting: English or ordered local language
60Endress+Hauser
A0013996
15Taking the example of the local display
10.4 Configuring the measuring device
The Setup menu with its guided wizards contains all the parameters needed for standard
operation.
Navigation to the Setup menu
Page 61
Proline Promag H 200 HARTCommissioning
X X X X X XXXX
20.50
0104-1
XXXXXXXXX
XXXXXXXXX
mA
Display/operat.
Setup
Diagnostic
Display/operat.
Setup
Main menu
English
Main menu
Curr.output 1
/ ../Setup
Language
A0018774-EN
16Using the example of the local display
Navigation
"Setup" menu
Setup
Device tag
System units
‣
Current output 1
‣
Pulse/frequency/switch output
‣
Display
‣
Output conditioning
‣
Low flow cut off
‣
Empty pipe detection
‣
Advanced setup
‣
→ 62
→ 62
→ 64
→ 66
→ 72
→ 74
→ 75
→ 77
→ 78
Endress+Hauser61
10.4.1 Defining the tag name
To enable fast identification of the measuring point within the system, you can enter a
unique designation using the Device tag parameter and thus change the factory setting.
Page 62
CommissioningProline Promag H 200 HART
1
XXXXXXXXX
A0013375
17Header of the operational display with tag name
1Device tag
The number of characters displayed depends on the characters used.
Entry of the tag name in the "FieldCare" operating tool → 54
Navigation
"Setup" menu → Device tag
Parameter overview with brief description
ParameterDescriptionUser entryFactory setting
Device tagEnter the name for the measuring point.Max. 32 characters, such as
letters, numbers or special
characters (e.g. @, %, /).
Promag
10.4.2 Setting the system units
In the System units submenu the units of all the measured values can be set.
Navigation
"Setup" menu → Advanced setup → System units
System units
‣
Volume flow unit
Volume unit
Mass flow unit
Mass unit
Density unit
Temperature unit
62Endress+Hauser
Page 63
Proline Promag H 200 HARTCommissioning
Parameter overview with brief description
ParameterDescriptionSelectionFactory setting
Volume flow unitSelect volume flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Volume unitSelect volume unit.
Result
The selected unit is taken from: Volume
flow unit parameter
Temperature unitSelect temperature unit.
Result
The selected unit applies for:
• Output
• Reference temperature
• Simulation process variable
Mass flow unitSelect mass flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Mass unitSelect mass unit.
Result
The selected unit is taken from: Mass flow
unit parameter
Density unitSelect density unit.
Result
The selected unit applies for:
• Output
• Simulation process variable
Unit choose listCountry-specific:
• l/h
• gal/min (us)
Unit choose listCountry-specific:
• l
• gal (us)
Unit choose listCountry-specific:
• °C (Celsius)
• °F (Fahrenheit)
Unit choose listCountry-specific:
• kg/h
• lb/min
Unit choose listCountry-specific:
• kg
• lb
Unit choose listCountry-specific:
• kg/l
• lb/ft³
Endress+Hauser63
Page 64
CommissioningProline Promag H 200 HART
Volume flow
Assign curr.
Mass flow
Volume flow unit
4...20 mA NAMUR4...20 mA US4...20 mA
Fixed current
4 mA value
20 mA value
Failure mode
Defined value
Min.…
Failure current
End of wizard
Mass flow unit
Density unit
Fixed density
Current span
10.4.3 Configuring the current output
The "Current output 1" wizard guides you systematically through all the parameters that
have to be set for configuring the specific current output.
Navigation
"Setup" menu → Current output 1
Structure of the wizard
18"Current output 1" wizard in the "Setup" menu
A0018498-EN
64Endress+Hauser
Page 65
Proline Promag H 200 HARTCommissioning
Parameter overview with brief description
ParameterPrerequsiteDescriptionSelection / User
Assign current output–Select process variable for
current output.
Mass flow unit–Select mass flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Volume flow unit–Select volume flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Current span–Select current range for
process value output and
upper/lower level for alarm
signal.
4 mA valueOne of the following options is
selected in the Current span
parameter (→ 65):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
20 mA valueOne of the following options is
selected in the Current span
parameter (→ 65):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Failure modeOne of the following options is
selected in the Assign currentoutput parameter (→ 65):
• Volume flow
• Mass flow
One of the following options is
selected in the Current span
parameter (→ 65):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Failure currentThe Defined value option is
selected in the Failure mode
parameter.
Enter 4 mA value.Signed floating-point
Enter 20 mA value.Signed floating-point
Define output behavior in
alarm condition.
Enter current output value in
alarm condition.
Factory setting
entry
• Off
• Volume flow
• Mass flow
Unit choose listCountry-specific:
Unit choose listCountry-specific:
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• Fixed current
number
number
• Min.
• Max.
• Last valid value
• Actual value
• Defined value
3.59 to 22.5 mA22.5 mA
Volume flow
• kg/h
• lb/min
• l/h
• gal/min (us)
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
Country-specific:
• 0 m3/h
• 0 ft3/min
Depends on country
and nominal
diameter
Max.
10.4.4 Configuring the pulse/frequency/switch output
The Pulse/frequency/switch output wizard guides you systematically through all the
parameters that can be set for configuring the selected output type.
Endress+Hauser65
Page 66
CommissioningProline Promag H 200 HART
Failure mode
End of wizard
Invert outp.sig.
Operating mode
Pulse
Volume flow
Assign pulse
Mass flow
Off
Mass unit
Density unit
Fixed density
Volume unit
Pulse width
Value per pulse
Configuring the pulse output
Navigation
"Setup" menu → Pulse/frequency/switch output
Structure of the wizard for the pulse output
19"Pulse/frequency/switch output" wizard in the "Setup" menu: "Operating mode" parameter"Pulse" option
Parameter overview with brief description
Operating modeDefine the output as a pulse, frequency or
Assign pulse outputSelect process variable for pulse output.• Off
Mass unitSelect mass unit.
Volume unitSelect volume unit.
ParameterDescriptionSelection / User entryFactory setting
switch output.
Result
The selected unit is taken from: Mass flow
unit parameter
Result
The selected unit is taken from: Volume
flow unit parameter
• Pulse
• Frequency
• Switch
• Mass flow
• Volume flow
Unit choose listCountry-specific:
Unit choose listCountry-specific:
A0018551-EN
Pulse
Off
• kg
• lb
• l
• gal (us)
66Endress+Hauser
Page 67
Proline Promag H 200 HARTCommissioning
ParameterDescriptionSelection / User entryFactory setting
Density unitSelect density unit.
Result
The selected unit applies for:
• Output
• Simulation process variable
Value per pulseEnter measured value at which a pulse is
output.
Pulse widthDefine time width of the output pulse.5 to 2000 ms100 ms
Failure modeDefine output behavior in alarm condition.• Actual value
Invert output signalInvert the output signal.• No
Unit choose listCountry-specific:
• kg/l
• lb/ft³
Signed floating-point number0
No pulses
• No pulses
No
• Yes
Endress+Hauser67
Page 68
CommissioningProline Promag H 200 HART
Val. at min.freq
End of wizard
Invert outp.sig.
Operating mode
Frequency
Volume flow
Assign freq.
Mass flow
Off
Mass flow unit
Density unit
Fixed density
Volume flow unit
Max. freq. value
Min. freq. value
Val. at max.freq
Failure mode
Failure freq.
Defined valueActual value
0 Hz
Configuring the frequency output
Navigation
"Setup" menu → Pulse/frequency/switch output
Structure of the wizard for the frequency output
A0018557-EN
20"Pulse/frequency/switch output" wizard in the "Setup" menu: "Operating mode" parameter"Frequency" option
68Endress+Hauser
Page 69
Proline Promag H 200 HARTCommissioning
Parameter overview with brief description
ParameterDescriptionSelection / User entryFactory setting
Operating modeDefine the output as a pulse, frequency or
switch output.
Assign frequency outputSelect process variable for frequency output. • Off
Mass flow unitSelect mass flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Volume flow unitSelect volume flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Density unitSelect density unit.
Result
The selected unit applies for:
• Output
• Simulation process variable
Minimum frequency valueEnter minimum frequency.0.0 to 1000.0 Hz0.0 Hz
Maximum frequency valueEnter maximum frequency.0.0 to 1000.0 Hz1000.0 Hz
Measuring value at minimum
frequency
Measuring value at maximum
frequency
Failure modeDefine output behavior in alarm condition.• Actual value
Failure frequencyEnter frequency output value in alarm
Invert output signalInvert the output signal.• No
Enter measured value for minmum
frequency.
Enter measured value for maximum
frequency.
condition.
• Pulse
• Frequency
• Switch
• Volume flow
• Mass flow
Unit choose listCountry-specific:
Unit choose listCountry-specific:
Unit choose listCountry-specific:
Signed floating-point number0
Signed floating-point number0
• Defined value
• 0 Hz
0.0 to 1250.0 Hz0.0 Hz
• Yes
Pulse
Off
• kg/h
• lb/min
• l/h
• gal/min (us)
• kg/l
• lb/ft³
0 Hz
No
Endress+Hauser69
Page 70
CommissioningProline Promag H 200 HART
End of wizard
Operating
mode
Switch
Switch
out funct
Diag.
behavior
Off
On
Assign
diag. beh
Alarm
Alarm or
warning
Warning
Invert outp.sig.
Configuring the switch output
Navigation
"Setup" menu → Pulse/frequency/switch output
Structure of the wizard for the switch output
A0018575-EN
21"Pulse/frequency/switch output" wizard in the "Setup" menu: "Operating mode" parameter"Switch" option
(part 1)
70Endress+Hauser
Page 71
Proline Promag H 200 HARTCommissioning
Limit
Fl. direct.
check
Status
Assign
limit
Assign
dir.check
Assign
status
End of wizard
Operating
mode
Switch
Switch
out funct
Unit
Totalizer
1/2/3
Mass
flow
Volume
flow
Low flow
cut off
Empty
pipe det.
Mass
flow
Volume
flow
Switch-on value
Switch-off
value
Switch-on
delay
Switch-off
delay
Failure mode
Invert
outp.sig.
Volume
flow unit
Mass
flow unit
22"Pulse/frequency/switch output" wizard in the "Setup" menu: "Operating mode" parameter"Switch" option
ParameterDescriptionSelection / User entryFactory setting
Operating modeDefine the output as a pulse, frequency or
(part 2)
Parameter overview with brief description
switch output.
Switch output functionSelect function for switch output.• Off
Assign diagnostic behaviorSelect diagnostic behavior for switch output. • Alarm
Assign limitSelect process variable for limit function.• Volume flow
• Pulse
• Frequency
• Switch
• On
• Diagnostic behavior
• Limit
• Flow direction check
• Status
• Alarm or warning
• Warning
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
A0018576-EN
Pulse
Off
Alarm
Volume flow
Endress+Hauser71
Page 72
CommissioningProline Promag H 200 HART
ParameterDescriptionSelection / User entryFactory setting
Assign flow direction checkSelect process variable for flow direction
monitoring.
Assign statusSelect device status for switch output.• Empty pipe detection
Volume flow unitSelect volume flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Mass flow unitSelect mass flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Unit totalizerSelect process variable totalizer unit.Unit choose listl
Switch-on valueEnter measured value for the switch-on
point.
Switch-off valueEnter measured value for the switch-off
point.
Switch-on delayDefine delay for the switch-on of status
output.
Switch-off delayDefine delay for the switch-off of status
output.
Failure modeDefine output behavior in alarm condition.• Actual status
Invert output signalInvert the output signal.• No
• Volume flow
• Mass flow
• Low flow cut off
Unit choose listCountry-specific:
Unit choose listCountry-specific:
Signed floating-point number0 l/h
Signed floating-point number0 l/h
0.0 to 100.0 s0.0 s
0.0 to 100.0 s0.0 s
• Open
• Closed
• Yes
Volume flow
Empty pipe detection
• l/h
• gal/min (us)
• kg/h
• lb/min
Open
No
10.4.5 Configuring the local display
The Display wizard guides you systematically through all the parameters that can
configured for configuring the local display.
72Endress+Hauser
Page 73
Proline Promag H 200 HARTCommissioning
Formatdisplay
Value1display
0%bargraph
value1
100%bargraph
value1
Value2display
Value3display
0%bargraph
value3
100%bargraph
value3
Value4display
Endofwizard
Navigation
"Setup" menu → Display
Structure of the wizard
23"Display" wizard in the "Setup" menu
Parameter overview with brief description
ParameterPrerequsiteDescriptionSelection / User
Format displayA local display is provided.Select how measured values
are shown on the display.
Value 1 displayA local display is provided.Select the measured value that
is shown on the local display.
entry
• 1 value, max. size
• 1 bargraph + 1
value
• 2 values
• 1 value large + 2
values
• 4 values
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Current output 1
A0013797-EN
Factory setting
1 value, max. size
Volume flow
Endress+Hauser73
Page 74
CommissioningProline Promag H 200 HART
Reverse flow*Forward flow
Forward/Reverse
End of wizard
Display damping
Damping out. 1
Mode output 2
Rev. flow comp.
Damping out. 2
Mode output 1
ParameterPrerequsiteDescriptionSelection / User
0% bargraph value 1A local display is provided.Enter 0% value for bar graph
display.
100% bargraph value 1A local display is provided.Enter 100% value for bar
graph display.
Value 2 displayA local display is provided.Select the measured value that
is shown on the local display.
Value 3 displayA local display is provided.Select the measured value that
is shown on the local display.
0% bargraph value 3An option was selected in the
Value 3 display parameter.
100% bargraph value 3An option was selected in the
Value 3 display parameter.
Value 4 displayA local display is provided.Select the measured value that
Enter 0% value for bar graph
display.
Enter 100% value for bar
graph display.
is shown on the local display.
10.4.6 Configuring the output conditioning
The Output conditioning wizard guides you systematically through all the parameters
that have to be set for configuring the output conditioning.
entry
Signed floating-point
number
Signed floating-point
number
Picklist (see Value 1
display)
Picklist (see Value 1
display)
Signed floating-point
number
Signed floating-point
number
Picklist (see Value 1
display)
Factory setting
0 l/h
Depends on country
and nominal
diameter
None
None
0
Depends on country
and nominal
diameter
None
Navigation
"Setup" menu → Output conditioning
Structure of the "Output conditioning" wizard
24"Output conditioning" wizard in the "Setup" menu
A0018583-EN
Reverse flow* = option only for pulse and frequency output
74Endress+Hauser
Page 75
Proline Promag H 200 HARTCommissioning
Parameter overview with brief description
ParameterPrerequsiteDescriptionUser entry /
Display damping–Set display reaction time to
fluctuations in the measured
value.
Damping output 1–Set the reaction time of the
output signal of the current
output to fluctuations in the
measured value.
Damping output 2The measuring device has a
second current output.
Damping output 2The measuring device has a
pulse/frequency/switch
output.
Measuring mode output 1–Select measuring mode for
Measuring mode output 2–Select measuring mode for
Measuring mode output 2–Select measuring mode for
Measuring mode output 2–Select measuring mode for
Set the reaction time of the
output signal of the second
current output to fluctuations
in the measured value.
Set the reaction time of the
output signal of the frequency
output to fluctuations in the
measured value.
output.
output.
output.
output.
Selection
0.0 to 999.9 s0.0 s
0 to 999.9 s1 s
0 to 999.9 s1 s
0 to 999.9 s1 s
• Forward flow
• Forward/Reverse
flow
• Reverse flow
compensation
• Forward flow
• Forward/Reverse
flow
• Reverse flow
compensation
• Forward flow
• Forward/Reverse
flow
• Reverse flow
• Reverse flow
compensation
• Forward flow
• Forward/Reverse
flow
• Reverse flow
• Reverse flow
compensation
Forward flow
Forward flow
Forward flow
Forward flow
Factory setting
10.4.7 Configuring the low flow cut off
The Low flow cut off wizard guides you systematically through all the parameters that
have to be set for configuring the low flow cut off.
Endress+Hauser75
Page 76
CommissioningProline Promag H 200 HART
Volume flow
Assign variable
Off value
End of wizard
Off
On value
Mass flow
Pres. shock sup.
Navigation
"Setup" menu → Low flow cut off
Structure of the wizard
25"Low flow cut off" wizard in the "Setup" menu
Parameter overview with brief description
ParameterDescriptionSelection / User entryFactory setting
Assign process variableSelect process variable for low flow cut off.• Off
• Volume flow
• Mass flow
On value low flow cutoffEnter on value for low flow cut off.Signed floating-point number0 l/h
Off value low flow cutoffEnter off value for low flow cut off.0 to 100.0 %50 %
Pressure shock suppressionEnter time frame for signal suppression (=
active pressure shock suppression).
0 to 100 s0 s
Volume flow
A0017209-EN
76Endress+Hauser
Page 77
Proline Promag H 200 HARTCommissioning
Empty pipe det.
Response time
End of wizard
New adjustment
Cancel
Empty pipe adj.
Progress
Full pipe adjust.
Ok
Busy
Not ok
On
Switch point EPD
Off
10.4.8 Configuring empty pipe detection
The Empty pipe detection wizard guides you systematically through all the parameters
that have to be set for configuring empty pipe detection.
Navigation
"Setup" menu → Empty pipe detection
Structure of the wizard
26"Empty pipe detection" wizard in the "Setup" menu
Parameter overview with brief description
ParameterPrerequsiteDescriptionSelection / User
Empty pipe detection–Switch empty pipe detection on
New adjustment–Select type of adjustment.• Cancel
ProgressThe On option is selected in
Switch point empty pipe detection–Enter hysteresis in %, below
Response time empty pipe detection –Enter the time before
the Empty pipe detection
parameter.
and off.
Shows the progress.• Ok
this value the measuring tube
will detected as empty.
diagnostic message S862 ''Pipe
empty'' is displayed for empty
pipe detection.
interface / User
entry
• Off
• On
• Empty pipe adjust
• Full pipe adjust
• Busy
• Not ok
1 to 99 %10 %
0 to 100 s1 s
Off
Cancel
–
A0017210-EN
Factory setting
Endress+Hauser77
Page 78
CommissioningProline Promag H 200 HART
X X X X X XXXX
20.50
0104-1
0092-1
✱✱✱✱
XXXXXXXXX
XXXXXXXXX
XXXXXXXXX
XXXXXXXXX
mA
Display/operat.
Setup
Diagnostic
Display/operat.
Setup
Main menu
English
Main menu
/ ../Setup
/ ../Setup
Advanced setup
Ent. access code
/ ../Advanced setup
Def. access code
Device tag
Language
Curr.output 1
10.5 Advanced settings
The Advanced setup submenu with its submenus contains parameters for specific
settings.
Navigation to the "Advanced setup" submenu
Functional Safety Manual with information on the SIL device → 135
For detailed information on the parameter descriptions of the Heartbeat Verification
application package, see the Special Documentation for the device
Navigation
"Setup" menu → Advanced setup
Advanced setup
‣
Enter access code
Sensor adjustment
‣
Totalizer 1 to 3
‣
SIL confirmation
‣
→ 79
→ 79
A0018745-EN
78Endress+Hauser
Page 79
Proline Promag H 200 HARTCommissioning
Deactivate SIL
‣
Display
‣
Heartbeat setup
‣
Configuration backup display
‣
Administration
‣
→ 81
→ 84
→ 83
10.5.1 Carrying out a sensor adjustment
The Sensor adjustment submenu contains parameters that pertain to the functionality of
the sensor.
Navigation
"Setup" menu → Advanced setup → Sensor adjustment
Sensor adjustment
‣
Installation direction
Parameter overview with brief description
ParameterDescriptionSelectionFactory setting
Installation directionSet sign of flow direction to match the
direction of the arrow on the sensor.
10.5.2 Configuring the totalizer
In the "Totalizer 1 to 3" submenu the individual totalizer can be configured.
Navigation
"Setup" menu → Advanced setup → Totalizer 1 to 3
Totalizer 1 to 3
‣
Assign process variable
Unit totalizer
Totalizer operation mode
• Flow in arrow direction
• Flow against arrow direction
Flow in arrow direction
Failure mode
Endress+Hauser79
Page 80
CommissioningProline Promag H 200 HART
Parameter overview with brief description
ParameterDescriptionSelectionFactory setting
Assign process variableSelect process variable for totalizer.• Off
• Volume flow
• Mass flow
Unit totalizerSelect process variable totalizer unit.Unit choose listl
Totalizer operation modeSelect totalizer calculation mode.• Net flow total
• Forward flow total
• Reverse flow total
Failure modeDefine totalizer behavior in alarm condition. • Stop
• Actual value
• Last valid value
Volume flow
Net flow total
Stop
80Endress+Hauser
Page 81
Proline Promag H 200 HARTCommissioning
10.5.3 Carrying out additional display configurations
In the Display submenu you can set all the parameters associated with the configuration
of the local display.
Navigation
"Setup" menu → Advanced setup → Display
Display
‣
Format display
Value 1 display
0% bargraph value 1
100% bargraph value 1
Decimal places 1
Value 2 display
Decimal places 2
Value 3 display
0% bargraph value 3
100% bargraph value 3
Decimal places 3
Value 4 display
Decimal places 4
Language
Display interval
Display damping
Header
Header text
Separator
Backlight
Endress+Hauser81
Page 82
CommissioningProline Promag H 200 HART
Parameter overview with brief description
ParameterPrerequsiteDescriptionSelection / User
Format displayA local display is provided.Select how measured values
are shown on the display.
Value 1 displayA local display is provided.Select the measured value that
is shown on the local display.
0% bargraph value 1A local display is provided.Enter 0% value for bar graph
display.
100% bargraph value 1A local display is provided.Enter 100% value for bar
graph display.
Decimal places 1A measured value is specified
in the Value 1 display
parameter.
Value 2 displayA local display is provided.Select the measured value that
Decimal places 2A measured value is specified
in the Value 2 display
parameter.
Value 3 displayA local display is provided.Select the measured value that
0% bargraph value 3An option was selected in the
Value 3 display parameter.
100% bargraph value 3An option was selected in the
Value 3 display parameter.
Decimal places 3A measured value is specified
in the Value 3 display
parameter.
Value 4 displayA local display is provided.Select the measured value that
Decimal places 4A measured value is specified
in the Value 4 display
parameter.
Select the number of decimal
places for the display value.
is shown on the local display.
Select the number of decimal
places for the display value.
is shown on the local display.
Enter 0% value for bar graph
display.
Enter 100% value for bar
graph display.
Select the number of decimal
places for the display value.
is shown on the local display.
Select the number of decimal
places for the display value.
entry
• 1 value, max. size
• 1 bargraph + 1
value
• 2 values
• 1 value large + 2
values
• 4 values
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Current output 1
Signed floating-point
number
Signed floating-point
number
• x
• x.x
• x.xx
• x.xxx
• x.xxxx
Picklist (see Value 1
display)
• x
• x.x
• x.xx
• x.xxx
• x.xxxx
Picklist (see Value 1
display)
Signed floating-point
number
Signed floating-point
number
• x
• x.x
• x.xx
• x.xxx
• x.xxxx
Picklist (see Value 1
display)
• x
• x.x
• x.xx
• x.xxx
• x.xxxx
Factory setting
1 value, max. size
Volume flow
0 l/h
Depends on country
and nominal
diameter
x.xx
None
x.xx
None
0
Depends on country
and nominal
diameter
x.xx
None
x.xx
82Endress+Hauser
Page 83
Proline Promag H 200 HARTCommissioning
ParameterPrerequsiteDescriptionSelection / User
LanguageA local display is provided.Set display language.• English
• Deutsch
• Français
• Español
• Italiano
• Nederlands
• Portuguesa
• Polski
• русский язык
(Russian)
• Svenska
• Türkçe
• 中文 (Chinese)
• 日本語
(Japanese)
• 한국어 (Korean)
• ةّيبَرَعْلا (Arabic)
• Bahasa Indonesia
• ภาษาไทย (Thai)
• tiếng Việt
(Vietnamese)
• čeština (Czech)
Display intervalA local display is provided.Set time measured values are
1 to 10 s5 s
shown on display if display
alternates between values.
Display dampingA local display is provided.Set display reaction time to
0.0 to 999.9 s0.0 s
fluctuations in the measured
value.
HeaderA local display is provided.Select header contents on local
display.
Header textThe Free text option is
Enter display header text.Max. 12 characters
selected in the Header
parameter.
• Device tag
• Free text
such as letters,
numbers or special
characters (e.g. @,
%, /)
SeparatorA local display is provided.Select decimal separator for
displaying numerical values.
Backlight–Switch the local display
backlight on and off.
Only for device version
with onsite display SD03
• .
• ,
• Disable
• Enable
(touch control)
entry
*
*
*
*
*
*
*
Factory setting
English
(alternatively, the
ordered language is
preset in the device)
*
*
*
*
*
*
*
*
*
*
*
Device tag
------------
.
Disable
*Visibility depends on order options or device settings
10.5.4 Administration configuration
The Administration submenu contains administrative parameters.
Define access codeRestrict write-access to parameters to
protect the configuration of the device
against unintentional changes via the local
display.
Device resetRestart or reset device manually.• Cancel
0 to 99990
Cancel
• To factory defaults
• To delivery settings
• Restart device
10.6 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration.
You can do so using the Configuration management parameter and the related options
found in the Configuration backup display submenu.
Navigation
"Setup" menu → Advanced setup → Configuration backup display
Configuration backup display
‣
Operating time
Last backup
Configuration management
Comparison result
Parameter overview with brief description
ParameterPrerequsiteDescriptionUser interface /
Operating time–Indicates how long the device
has been in operation.
Last backup–Indicates when the last data
backup was saved to the
display module.
Selection
Days (d), hours (h),
minutes (m), seconds
(s)
Days (d), hours (h),
minutes (m), seconds
(s)
Factory setting
–
–
84Endress+Hauser
Page 85
Proline Promag H 200 HARTCommissioning
ParameterPrerequsiteDescriptionUser interface /
Configuration managementA local display is provided.Select action for managing the
device data in the display
module.
Comparison result–Comparison between present
device data and display
backup.
10.6.1 Function range of "Configuration management" parameter
OptionsDescription
Execute backupThe current device configuration is backed up from the integrated HistoROM to the
device's display module. The backup copy includes the transmitter data of the
device.
RestoreThe last backup copy of the device configuration is restored from the display
module to the device's integrated HistoROM. The backup copy includes the
transmitter data of the device.
DuplicateThe transmitter configuration from another device is duplicated to the device using
the display module.
CompareThe device configuration saved in the display module is compared with the current
device configuration of the integrated HistoROM.
Clear backup dataThe backup copy of the device configuration is deleted from the display module of
the device.
Selection
• Cancel
• Execute backup
• Restore
• Duplicate
• Compare
• Clear backup data
• Settings identical
• Settings not
identical
• No backup
available
• Backup settings
corrupt
• Check not done
• Dataset
incompatible
Factory setting
Cancel
Check not done
Integrated HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
While this action is in progress, the configuration cannot be edited via the local
display and a message on the processing status appears on the display.
10.7 Simulation
The Simulation submenu enables you to simulate, without a real flow situation, various
process variables in the process and the device alarm mode and to verify downstream
signal chains (switching valves or closed-control loops).
Navigation
"Diagnostics" menu → Simulation
Simulation
‣
Assign simulation process variable
Process variable value
→ 86
→ 86
Endress+Hauser85
Page 86
CommissioningProline Promag H 200 HART
Simulation current output 1
Value current output 1
Frequency output simulation
Frequency value
Pulse output simulation
Pulse value
Switch output simulation
Switch status
Simulation device alarm
Diagnostic event category
Diagnostic event simulation
→ 86
→ 86
→ 86
→ 86
→ 86
→ 86
→ 87
→ 87
→ 87
→ 87
→ 87
Parameter overview with brief description
ParameterPrerequsiteDescriptionSelection / User
Assign simulation process variable–Select a process variable for
the simulation process that is
activated.
Process variable valueA process variable is selected
in the Assign simulationprocess variable parameter.
Simulation current output 1–Switch the simulation of the
Value current output 1The On option is selected in
the Simulation currentoutput 1 parameter
(→ 86).
Frequency output simulation–Switch simulation of the
Frequency valueThe On option is selected in
the Frequency outputsimulation parameter.
Pulse output simulationThe Down-count. val. option
is selected in the Simulationpulse output parameter.
Pulse valueThe Down-count. val. option
is selected in the Simulationpulse output parameter.
Enter the simulation value for
the selected process variable.
current output on and off.
Enter the current value for
simulation.
frequency output on and off.
Enter the frequency value for
simulation.
Switch simulation of the pulse
output on and off.
If the Fixed value option
is selected, the Pulsewidth parameter defines
the pulse width of the
pulses output.
Enter the number of pulses for
simulation.
Factory setting
entry
• Off
• Volume flow
• Mass flow
Signed floating-point
number
• Off
• On
3.59 to 22.5 mA–
• Off
• On
0.0 to 1250.0 Hz0.0 Hz
• Off
• Fixed value
• Down-counting
value
0 to 655350
Off
0
Off
Off
Off
86Endress+Hauser
Page 87
Proline Promag H 200 HARTCommissioning
ParameterPrerequsiteDescriptionSelection / User
Switch output simulation–Switch simulation of switch
output on and off.
Switch statusThe On option is selected in
the Switch output simulation
parameter.
Simulation device alarm–Switch the device alarm on and
Diagnostic event category–Select the category of the
Diagnostic event simulation–Switch simulation of the
Select the status of the status
output for the simulation.
off.
diagnostic event.
diagnostic event on and off.
For the simulation, you can
choose from the diagnostic
events of the category selected
in the Diagnostic event
category parameter.
10.8 Protecting settings from unauthorized access
The following options exist for protecting the configuration of the measuring device from
unintentional modification after commissioning:
• Write protection via access code
• Write protection via write protection switch
• Write protection via keypad lock → 50
entry
• Off
• On
• Open
• Closed
• Off
• On
• Sensor
• Electronics
• Configuration
• Process
• Off
• Picklist
Diagnostic events
(depends on the
selected category)
Factory setting
Off
Open
Off
Process
Off
10.8.1 Write protection via access code
With the customer-specific access code, the parameters for the measuring device
configuration are write-protected and their values can no longer be changed via local
operation.
2.Max. Define a max. 4-digit numeric code as an access code.
3.Enter the access code again to confirm the code.
The -symbol appears in front of all write-protected parameters.
The device automatically locks the write-protected parameters again if a key is not pressed
for 10 minutes in the navigation and editing view. The device locks the write-protected
Endress+Hauser87
Page 88
CommissioningProline Promag H 200 HART
+
E
–
3mm
XXXXXXXXXXXXX
WPCDISIM
ON
OFF
parameters automatically after 60 s if the user skips back to the operational display mode
from the navigation and editing view.
• If write access is activated via access code, it can be also be deactivated only via the
access code → 50.
• The user role with which the user is currently logged on via the local display
→ 50 is indicated by the Access status display parameter. Navigation path:
"Operation" menu → Access status display
Parameters which can always be modified via the local display
Certain parameters that do not affect the measurement are excepted from write protection
via the local display. Despite the defined access code, these parameters can always be
modified even if the other parameters are locked.
Parameters for configuring
the local display
↓↓
LanguageFormat displayControl Totalizer
Contrast displayPreset value
Display intervalReset all totalizers
Parameters for configuring
the totalizer
10.8.2 Write protection via write protection switch
Unlike write protection via a user-specific access code, this allows write access to the entire
operating menu - other than the "Contrast display" parameter - to be locked.
The parameter values are now read only and cannot be edited any more (exception
"Contrast display" parameter):
• Via local display
• Via service interface (CDI)
• Via HART protocol
A0013768
1.Loosen the securing clamp.
2.Unscrew the electronics compartment cover.
88Endress+Hauser
Page 89
Proline Promag H 200 HARTCommissioning
X X X X X XXXX
20.50
XX
XX
3.Pull out the display module with a gentle rotational movement. To make it easier to
access the lock switch, attach the display module to the edge of the electronics
compartment.
Display module is attached to the edge of the electronics compartment.
A0013909
4.Setting the write protection switch (WP) on the main electronics module to the ON
position enables hardware write protection. Setting the write protection switch (WP)
on the main electronics module to the OFF position (factory setting) disables
hardware write protection.
If hardware write protection is enabled, the Locking status parameter displays
the Hardware locked option . In addition, on the local display the -symbol
appears in front of the parameters in the header of the operational display and in
the navigation view.
Endress+Hauser89
A0015870
If hardware write protection is disabled, no option is displayed in the Lockingstatus parameter . On the local display, the -symbol disappears from in front
of the parameters in the header of the operational display and in the navigation
view.
5.Feed the cable into the gap between the housing and main electronics module and
plug the display module into the electronics compartment in the desired direction
until it engages.
6.Reverse the removal procedure to reassemble the transmitter.
Page 90
OperationProline Promag H 200 HART
11 Operation
11.1 Reading the device locking status
The write protection types that are currently active can be determined using the Locking
status parameter.
Navigation
"Operation" menu → Locking status
Function scope of "Locking status" parameter
OptionsDescription
NoneThe access status displayed in "Access status display" parameter applies → 50.
Only appears on local display.
Hardware lockedThe DIP switch for hardware locking is activated on the main electronics module.
This locks write access to the parameters .
Temporarily lockedWrite access to the parameters is temporarily lock due to device-internal
processing (e.g. data upload/download, reset). Once the internal processing has
been completed, the parameters can be changed once again.
11.2 Adjusting the operating language
Information → 60
For information on the operating languages supported by the measuring device
→ 132
11.3 Configuring the display
• Basic settings for local display → 72
• Advanced settings for local display → 81
11.4 Reading measured values
With the Measured values submenu, it is possible to read all the measured values.
11.4.1 Process variables
The Process variables submenu contains all the parameters needed to display the current
measured values for every process variable.
Navigation
"Diagnostics" menu → Measured values → Process variables
Process variables
‣
Volume flow
Mass flow
90Endress+Hauser
Page 91
Proline Promag H 200 HARTOperation
Parameter overview with brief description
ParameterDescriptionUser interface
Volume flowDisplays the volume flow currently measured.Signed floating-point number
Mass flowDisplays the mass flow currently calculated.Signed floating-point number
11.4.2 Totalizer
The Totalizer submenu contains all the parameters needed to display the current
measured values for every totalizer.
Totalizer value 1 to 3In the Assign process variable
parameter in the Totalizer 1to 3 submenu, one of the
following options is selected:
• Volume flow
• Mass flow
Totalizer overflow 1 to 3In the Assign process variable
parameter in the Totalizer 1to 3 submenu, one of the
following options is selected:
• Volume flow
• Mass flow
11.4.3 Output values
The Output values submenu contains all the parameters needed to display the current
measured values for every output.
Navigation
"Diagnostics" menu → Measured values → Output values
Displays the current totalizer
counter value.
Displays the current totalizer
overflow.
Signed floating-point
number
Integer with sign0
0 l
Output values
‣
Output current 1
Measured current 1
Terminal voltage 1
Endress+Hauser91
Page 92
OperationProline Promag H 200 HART
Output current 2
Pulse output
Output frequency
Switch status
Parameter overview with brief description
ParameterDescriptionUser interfaceFactory setting
Output current 1Displays the current value currently
calculated for the current output.
Measured current 1Displays the current value currently
measured for the current output.
Terminal voltage 1Displays the current terminal voltage that is
applied at the current output.
Output current 2Displays the current value currently
calculated for the current output.
Pulse outputDisplays the value currently measured for
the pulse output.
Output frequencyDisplays the value currently measured for
the frequency output.
Switch statusDisplays the current switch output status.• Open
3.59 to 22.5 mA3.59 mA
0 to 30 mA0 mA
0.0 to 50.0 V0 V
3.59 to 22.5 mA3.59 mA
Positive floating-point number 0 Hz
0.0 to 1250.0 Hz0.0 Hz
Open
• Closed
11.5 Adapting the measuring device to the process
conditions
The following are available for this purpose:
• Basic settings using the Setup menu
• Advanced settings using the Advanced setup submenu
11.6 Performing a totalizer reset
In the Operation submenu the totalizers are reset:
• Control Totalizer
• Reset all totalizers
Function scope of "Control Totalizer " parameter
OptionsDescription
TotalizeThe totalizer is started.
Reset + holdThe totaling process is stopped and the totalizer is reset to 0.
Preset + holdThe totaling process is stopped and the totalizer is set to its defined start value
from the Preset value parameter.
Reset + totalizeThe totalizer is reset to 0 and the totaling process is restarted.
Preset + totalizeThe totalizer is set to the defined start value in Preset value parameterand the
totaling process is restarted.
92Endress+Hauser
Page 93
Proline Promag H 200 HARTOperation
Function scope of "Reset all totalizers" parameter
OptionsDescription
Reset + totalizeResets all totalizers to 0 and restarts the totaling process. This deletes all the flow
values previously totalized.
Navigation
"Operation" menu → Operation
Totalizer handling
‣
Control Totalizer 1 to 3
Preset value 1 to 3
Reset all totalizers
Parameter overview with brief description
ParameterDescriptionSelection / User entryFactory setting
Control Totalizer 1 to 3Control totalizer value.• Totalize
• Reset + hold
• Preset + hold
• Reset + totalize
• Preset + totalize
Preset value 1 to 3Specify start value for totalizer.Signed floating-point number0 l
Reset all totalizersReset all totalizers to 0 and start.• Cancel
• Reset + totalize
Totalize
Cancel
11.7 Showing data logging
The Extended HistoROM application package (order option) must be enabled in the
device for the Data logging submenu to appear. This contains all the parameters for the
measured value history.
The data logging history is also available via the FieldCare plant asset management
tool → 53.
Function scope
• A total of 1000 measured values can be stored
• 4 logging channels
• Adjustable logging interval for data logging
• Display of the measured value trend for each logging channel in the form of a chart
A0016222
27Chart of a measured value trend
Endress+Hauser93
Page 94
OperationProline Promag H 200 HART
• x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
• y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
If the length of the logging interval or the assignment of the process variables to the
channels is changed, the content of the data logging is deleted.
Navigation
"Diagnostics" menu → Data logging
"Data logging" submenu
Data logging
‣
Assign channel 1
Assign channel 2
Assign channel 3
Assign channel 4
Logging interval
Clear logging data
Display channel 1
‣
Display channel 2
‣
Display channel 3
‣
Display channel 4
‣
94Endress+Hauser
Page 95
Proline Promag H 200 HARTOperation
Parameter overview with brief description
ParameterPrerequsiteDescriptionSelection / User
Assign channel 1 to 4The Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Logging intervalThe Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Clear logging dataThe Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Assign process variable to
logging channel.
Define the logging interval for
data logging. This value
defines the time interval
between the individual data
points in the memory.
Clear the entire logging data.• Cancel
• Off
• Volume flow
• Mass flow
• Electronic
temperature
• Current output 1
• Current difference
potential
1.0 to 3600.0 s10.0 s
• Clear data
Factory setting
entry
Off
Cancel
Endress+Hauser95
Page 96
Diagnostics and troubleshootingProline Promag H 200 HART
12 Diagnostics and troubleshooting
12.1 General troubleshooting
For local display
ProblemPossible causesRemedial action
Local display dark and no output
signals
Local display dark and no output
signals
Local display dark and no output
signals
Local display dark and no output
signals
Local display dark and no output
signals
Local display is dark, but signal
output is within the valid range
Local display is dark, but signal
output is within the valid range
Local display is dark, but signal
output is within the valid range
Backlighting of local display is redDiagnostic event with "Alarm"
Text on local display appears in a
foreign language and cannot be
understood.
Message on local display:
"Communication Error"
"Check Electronics"
Supply voltage does not match that
specified on the nameplate.
Supply voltage has incorrect
polarity.
No contact between connecting
cables and terminals.
Terminals are not plugged into the
I/O electronics module correctly.
I/O electronics module is defective.Order spare part → 113.
Display is set too bright or too dark. • Set the display brighter by
The cable of the display module is
not plugged in correctly.
Display module is defective.Order spare part → 113.
diagnostic behavior has occurred.
Incorrect operating language is
configured.
Communication between the
display module and the electronics
is interrupted.
Apply the correct supply voltage .
Reverse polarity of supply voltage.
Check the connection of the cables
and correct if necessary.
Check terminals.
simultaneously pressing + .
• Set the display darker by
simultaneously pressing + .
Insert the plug correctly into the
main electronics module and
display module.
Take remedial measures → 103
1. Press + for 2 s ("home
position").
2. Press .
3. Set the desired language in the
Language parameter.
• Check the cable and the
connector between the main
electronics module and display
module.
• Order spare part → 113.
For output signals
ProblemPossible causesRemedial action
Signal output outside the valid
range
Signal output outside the valid
current range
(< 3.6 mA or > 22 mA)
Device shows correct value on local
display, but signal output is
incorrect, though in the valid range.
Device measures incorrectly.Configuration error or device is
Main electronics module is
defective.
I/O electronics module is defective.Order spare part → 113.
Configuration errorCheck and correct parameter
operated outside the application.
Order spare part → 113.
configuration.
1. Check and correct parameter
configuration.
2. Observe limit values specified in
the "Technical Data".
96Endress+Hauser
Page 97
Proline Promag H 200 HARTDiagnostics and troubleshooting
For access
ProblemPossible causesRemedial action
No write access to parametersHardware write protection enabledSet the write protection switch on
the main electronics module to the
OFF position .
No write access to parametersCurrent user role has limited access
authorization
No connection via HART protocolMissing or incorrectly installed
communication resistor.
No connection via HART protocolCommubox
• Connected incorrectly
• Configured incorrectly
• Drivers not installed correctly
• USB interface on computer
configured incorrectly
No connection via service interfaceIncorrect configuration of USB
interface on PC or driver not
installed correctly.
1. Check user role → 50.
2. Enter correct customer-specific
access code → 50.
Install the communication resistor
(250 Ω) correctly. Observe the
maximum load → 29.
Observe the documentation for the
Commubox.
FXA195 HART: Document
"Technical Information"
TI00404F
Observe the documentation for the
Commubox.
FXA291: Document
"Technical Information"
TI00405C
Endress+Hauser97
Page 98
Diagnostics and troubleshootingProline Promag H 200 HART
1
4
3
X X X X X X XXXX X X X X X XXX
2
S
S
XX
20.50
5
X
i
S801
Menu
Supply voltage
12.2 Diagnostic information on local display
12.2.1 Diagnostic message
Faults detected by the self-monitoring system of the measuring device are displayed as a
diagnostic message in alternation with the operational display.
Operational display in alarm conditionDiagnostic message
A0013939-EN
1
Status signal
2
Diagnostic behavior
3
Diagnostic behavior with diagnostic code
4
Short text
5
Operating elements
If two or more diagnostic events are pending simultaneously, only the message of the
diagnostic event with the highest priority is shown.
Other diagnostic events that have occurred can be called up in the Diagnostics menu:
• Via parameters → 105
• Via submenus → 106
Status signals
The status signals provide information on the state and reliability of the device by
categorizing the cause of the diagnostic information (diagnostic event).
The status signals are categorized according to VDI/VDE 2650 and NAMUR
Recommendation NE 107: F = Failure, C = Function Check, S = Out of Specification, M
= Maintenance Required
SymbolMeaning
Failure
A device error has occurred. The measured value is no longer valid.
A0013956
Function check
The device is in service mode (e.g. during a simulation).
A0013959
Out of specification
The device is operated:
• Outside its technical specification limits (e.g. outside the process temperature range)
A0013958
• Outside of the configuration carried out by the user (e.g. maximum flow in parameter
20 mA value)
Maintenance required
Maintenance is required. The measured value remains valid.
A0013957
98Endress+Hauser
Page 99
Proline Promag H 200 HARTDiagnostics and troubleshooting
Diagnostic behavior
SymbolMeaning
Alarm
• Measurement is interrupted.
• Signal outputs and totalizers assume the defined alarm condition.
A0013961
• A diagnostic message is generated.
• For local display with touch control: the background lighting changes to red.
Warning
Measurement is resumed. The signal outputs and totalizers are not affected. A diagnostic
A0013962
message is generated.
Diagnostic information
The fault can be identified using the diagnostic information. The short text helps you by
providing information about the fault. In addition, the corresponding symbol for the
diagnostic behavior is displayed in front of the diagnostic information on the local display.
Diagnostic information
Diagnostic code
Diagnostic
behavior
Example
Operating elements
KeyMeaning
Plus key
In a menu, submenu
A0013970
Opens the message about the remedial measures.
Enter key
In a menu, submenu
A0013952
Opens the operating menu.
Status signal
↓↓↓
A0013962 A0013958
NAMUR
NE 107
Diagnostic
number
441Curr.output 1
3-digit number
Short text
Endress+Hauser99
Page 100
Diagnostics and troubleshootingProline Promag H 200 HART
X X X X X X XXXX X X X X X XXX
S
S
XX
20.50
X
i
S801
Menu
S
(ID:203)
S801 0d00h02m25s
1
2
4
6
3
5
Increase supply voltage
S801 Supply voltage
Diagnostic list
Diagnostics 1
Diagnostics 2
Diagnostics 3
Supply voltage
Supply voltage
12.2.2 Calling up remedial measures
28Message for remedial measures
1Diagnostic information
2Short text
3Service ID
4Diagnostic behavior with diagnostic code
5Operation time of occurrence
6Remedial measures
The user is in the diagnostic message.
1.Press ( symbol).
The Diagnostic list submenu opens.
2.Select the desired diagnostic event with or and press .
The message for the remedial measures for the selected diagnostic event opens.
3.Press + simultaneously.
The message for the remedial measures closes.
The user is in the Diagnostics menu at an entry for a diagnostics event, e.g. in the
Diagnostic list submenu or the Previous diagnostics parameter.
1.Press .
The message for the remedial measures for the selected diagnostic event opens.
2.Press + simultaneously.
The message for the remedial measures closes.
A0013940-EN
12.3 Diagnostic information in FieldCare
12.3.1 Diagnostic options
Any faults detected by the measuring device are displayed on the home page of the
operating tool once the connection has been established.
100Endress+Hauser
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.