Direct current and alternating currentGround connection
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
Symbols for certain types of information
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
SymbolMeaningSymbolMeaning
1, 2, 3,...Item numbers
A, B, C, ...ViewsA-A, B-B, C-C, ... Sections
Hazardous area
Series of steps
Safe area (non-hazardous area)
Flow direction
Function and system design
Measuring principle
Endress+Hauser3
Following Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a
magnetic field.
In the electromagnetic measuring principle, the flowing medium is the moving conductor. The
voltage induced (Ue) is proportional to the flow velocity (v) and is supplied to the amplifier by means
of two measuring electrodes. The flow volume (Q) is calculated via the pipe cross-section (A). The DC
magnetic field is created through a switched direct current of alternating polarity.
Formulae for calculation
• Induced voltage Ue = B · L · v
• Volume flow Q = A · v
4Endress+Hauser
Proline Promag H 200
Measuring system
The device consists of a transmitter and a sensor.
The device is available as a compact version:
The transmitter and sensor form a mechanical unit.
Transmitter
Promag 200Materials:
Aluminum, AlSi10Mg, coated
Configuration:
• External operation via four-line, illuminated local display with touch
control and guided menus ("Make-it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
A0013471
Sensor
Promag HNominal diameter range: DN 2 to 25 (1/12 to 1")
Materials:
• Sensor housing: stainless steel 1.4301 (304)
• Measuring tubes: stainless steel, 1.4301 (304)
• Liner: PFA (USP Class VI; FDA 21 CFR 177.1550; 3A)
We only provide a warranty if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any inadvertent
changes to the device settings.
IT security measures in line with operators' security standards and designed to provide additional
protection for the device and device data transfer must be implemented by the operators themselves.
Input
Measured variableDirect measured variables
Volume flow (proportional to induced voltage)
Calculated measured variables
Mass flow
Measuring range
Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Flow characteristic values in SI units
Nominal
diameter
[mm][in][dm3/min][dm3/min][dm3][dm3/min]
21/120.06 to 1.80,50.0050,01
41/80.25 to 720.0250,05
Recommended
Min./max. full scale value
(v ~ 0.3/10 m/s)
flow
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
Endress+Hauser5
Proline Promag H 200
Nominal
diameter
[mm][in][dm3/min][dm3/min][dm3][dm3/min]
83/81 to 3080.10,1
15½4 to 100250.20,5
2519 to 300750.51
Recommended
flow
Min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
Flow characteristic values in US units
Nominal
diameter
[in][mm][gal/min][gal/min][gal][gal/min]
1/1220.015 to 0.50,10,0010,002
1/840.07 to 20,50,0050,008
3/880.25 to 820,020,025
½151 to 2760,050,1
1252.5 to 80180,20,25
Recommended
flow
Min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
To calculate the measuring range, use the Applicator sizing tool → 68
Recommended measuring range
"Flow limit" section → 34
Operable flow range
Over 1000 : 1
Output
Output signalCurrent output
Current output4-20 mA HART (passive)
Resolution< 1 µA
DampingAdjustable: 0.0 to 999.9 s
Assignable measured
variables
Pulse/frequency/switch output
• Volume flow
• Mass flow
FunctionCan be set to pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 35 V
• 50 mA
For information on the Ex connection values → 9
6Endress+Hauser
Proline Promag H 200
Voltage drop• For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current≤ 0.05 mA
Pulse output
Pulse widthAdjustable: 5 to 2000 ms
Maximum pulse rate100 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
• Volume flow
• Mass flow
• Volume flow
• Mass flow
Unlimited
• On
• Diagnostic behavior
• Limit value
– Volume flow
– Mass flow
• Flow direction monitoring
• Status
– Empty pipe detection
– Low flow cut off
Signal on alarm
FOUNDATION Fieldbus
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
PROFIBUS PA
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
Depending on the interface, failure information is displayed as follows:
Current output
HART
Device diagnosticsDevice condition can be read out via HART Command 48
Endress+Hauser7
Pulse/frequency/switch output
Pulse output
Failure modeChoose from:
• Actual value
• No pulses
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1250 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
Proline Promag H 200
FOUNDATION Fieldbus
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-912
0 mA
PROFIBUS PA
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text displayWith information on cause and remedial measures
BacklightAdditionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Operating tool
• Via digital communication:
– HART protocol
– FOUNDATION Fieldbus
– PROFIBUS PA
• Via service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 61
8Endress+Hauser
Proline Promag H 200
0
100
200
300
400
500
14
161820
2224
26283032
U [V]
s
R [ ]bW
1.11.21
3436
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage
• For US = 18 to 18.9 V: RB ≤ (US - 18 V): 0.0036 A
• For US = 18.9 to 24.5 V: RB ≤ (US - 13.5 V): 0.022 A
• For US = 24.5 to 30 V: RB ≤ 500 Ω
A0013563
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with non-Ex and Ex d
Sample calculation
Supply voltage of the power supply unit: US = 19 V
Maximum load: RB ≤ (19 V - 13.5 V): 0.022 A = 250 Ω
Ex connection dataSafety-related values
Type of protection Ex d
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
Endress+Hauser9
Proline Promag H 200
Order code for "Output"Output typeSafety-related values
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
1)Internal circuit limited by Ri = 760.5 Ω
Ex nA type of protection
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Type of protection XP
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
10Endress+Hauser
Proline Promag H 200
Order code for "Output"Output typeSafety-related values
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
P
max
nom
U
max
P
max
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Endress+Hauser11
Proline Promag H 200
Type of protection Ex ic
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Type of protection IS
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
12Endress+Hauser
Proline Promag H 200
Order code for "Output"Output typeIntrinsically safe values
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are user-selectable.
All outputs are galvanically isolated from one another.
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x48
HART protocol revision7
Device description files
(DTM, DD)
HART load• Min. 250 Ω
Dynamic variablesRead out the dynamic variables: HART command 3
Device variablesRead out the device variables: HART command 9
Information and files under:
www.endress.com
• Max. 500 Ω
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Off
• Volume flow
• Mass flow
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
The device variables are permanently assigned.
FOUNDATION Fieldbus
Manufacturer ID0x452B48
Ident number0x1048
Device revision1
Endress+Hauser13
DD revisionInformation and files under:
CFF revision
Device Tester Version (ITK
version)
ITK Test Campaign NumberIT094200
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Max. response delayMin. 5
• www.endress.com
• www.fieldbus.org
6.1.1
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
Proline Promag H 200
Transducer Blocks
BlockContentsOutput values
Setup Transducer Block
(TRDSUP)
Advanced Setup
Transducer Block
(TRDASUP)
Display Transducer
Block
(TRDDISP)
HistoROM Transducer
Block
(TRDHROM)
Diagnostic Transducer
Block
(TRDDIAG)
Expert Configuration
Transducer Block
(TRDEXP)
All parameters for standard commissioning.No output values
All parameters for more accurate measurement
configuration.
Parameters for configuring the local display.No output values
Parameters for using the HistoROM function.No output values
Parameters that require the user to have indepth knowledge of the operation of the device
in order to configure the parameters
appropriately.
No output values
• Temperature (7)
• Volume flow (9)
• Mass flow (11)
No output values
14Endress+Hauser
Proline Promag H 200
BlockContentsOutput values
Expert Information
Transducer Block
(TRDEXPIN)
Service Sensor
Transducer Block
(TRDSRVS)
Service Information
Transducer Block
(TRDSRVIF)
Total Inventory
Counter Transducer
Block
(TRDTIC)
Heartbeat Technology
Transducer Block
(TRDHBT)
Heartbeat Results 1
Transducer Block
(TRDHBTR1)
Heartbeat Results 2
Transducer Block
(TRDHBTR2)
Heartbeat Results 3
Transducer Block
(TRDHBTR3)
Heartbeat Results 4
Transducer Block
(TRDHBTR4)
Parameters that provide information about the
state of the device.
Parameters that can only be accessed by Endress
+Hauser Service.
Parameters that provide Endress+Hauser Service
with information about the state of the device.
Parameters for configuring all the totalizers and
the inventory counter.
Parameters for the configuration and
comprehensive information about the results of
the verification.
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
No output values
No output values
No output values
Process variables (AI Channel)
• Totalizer 1 (16)
• Totalizer 2 (17)
• Totalizer 3 (18)
No output values
Function blocks
BlockNumber
of
blocks
Resource Block
(RB)
Analog Input
Block
(AI)
Discrete Input
Block
(DI)
PID Block
(PID)
1This Block (extended functionality) contains
4This Block (extended functionality) receives
2This Block (standard functionality) receives a
1This Block (standard functionality) acts as a
ContentsProcess variables (Channel)
–
all the data that uniquely identify the device; it
is the equivalent of an electronic nameplate
for the device.
Process variables (AI Channel)
the measurement data provided by the Sensor
Block (can be selected via a channel number)
and makes the data available for other blocks
at the output.
Execution time: 25 ms
discrete value (e.g. indicator that measuring
range has been exceeded) and makes the
value available for other blocks at the output.
Execution time: 19 ms
proportional-integral-differential controller
and can be used universally for control in the
field. It enables cascading and feedforward
control.
Execution time: 25 ms
• Temperature (7)
• Volume flow (9)
• Mass flow (11)
• Switch output state (101)
• Empty pipe detection (102)
• Low flow cut off (103)
• Status verification (105)
–
Endress+Hauser15
Proline Promag H 200
BlockNumber
of
blocks
Multiple Digital
Output Block
(MDO)
Integrator Block
(IT)
1This Block (standard functionality) receives
1This Block (standard functionality) integrates
PROFIBUS PA
ContentsProcess variables (Channel)
Channel_DO (122)
several discrete values and makes them
available for other blocks at the output.
Execution time: 19 ms
a measured variable over time or totalizes the
pulses from a Pulse Input Block. The Block can
be used as a totalizer that totalizes until a
reset, or as a batch totalizer whereby the
integrated value is compared against a target
value generated before or during the control
routine and generates a binary signal when
the target value is reached.
Execution time: 21 ms
• Value 1: Reset totalizer 1
• Value 2: Reset totalizer 2
• Value 3: Reset totalizer 3
• Value 4: Flow override
• Value 5: Start heartbeat
verification
• Value 6: Status switch output
• Value 7: Not assigned
• Value 8: Not assigned
–
Manufacturer ID0x11
Ident number0x1563
Profile version3.02
Device description files (GSD,
DTM, DD)
Output values
(from measuring device to
automation system)
Input values
(from automation system to
measuring device)
Information and files under:
• www.endress.com
• www.profibus.org
Analog input 1 to 2
• Mass flow
• Volume flow
Digital input 1 to 2
• Empty pipe detection
• Low flow cut off
• Status switch output
• Status verification
Totalizer 1 to 3
• Mass flow
• Volume flow
• Corrected volume flow
Digital output 1 to 3 (fixed assignment)
• Digital output 1: switch positive zero return on/off
• Digital output 2: switch switch output on/off
• Digital output 3: start verification
Totalizer 1 to 3
• Totalize
• Reset and hold
• Preset and hold
• Operating mode configuration:
– Net flow total
– Forward flow total
– Reverse flow total
16Endress+Hauser
Proline Promag H 200
–
4
+
1
–
2
+
3
1
2
3
+
1
–
2
–
4
+
3
1
2
3
Supported functions• Identification & Maintenance
Configuration of the device
address
Power supply
Terminal assignmentTransmitter
Connection versions
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Local display
• via operating tools (e.g. FieldCare)
A0013570
Maximum number of terminals, without integrated
overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Ground terminal for cable shield
Order code for "Output"Terminal numbers
Output 1Output 2
1 (+)2 (-)3 (+)4 (-)
Option A4-20 mA HART (passive)-
Option B
Option E
Option G
1)Output 1 must always be used; output 2 is optional.
2)FOUNDATION Fieldbus with integrated reverse polarity protection.
3)PROFIBUS PA with integrated reverse polarity protection.
1)
1) 2)
1) 3)
4-20 mA HART (passive)Pulse/frequency/switch output
FOUNDATION Fieldbus
PROFIBUS PA
Maximum number of terminals, with integrated
overvoltage protection
A0018161
(passive)
Pulse/frequency/switch output
(passive)
Pulse/frequency/switch output
(passive)
Endress+Hauser17
Pin assignment, device plugPROFIBUS PA
1
2
4
3
1
2
4
3
Device plug for signal transmission (device side)
FOUNDATION Fieldbus
Device plug for signal transmission (device side)
Proline Promag H 200
PinAssignmentCodingPlug/socket
1+PROFIBUS PA +APlug
2Grounding
A0019021
A0019021
3-PROFIBUS PA –
4Not assigned
PinAssignmentCodingPlug/socket
1+Signal +APlug
2-Signal –
3Not assigned
4Grounding
Supply voltageTransmitter
An external power supply is required for each output.
Order code for "Output"
Option A
Option B
switch output
Option E
frequency/switch output
Option G
output
1)External supply voltage of the power supply unit with load.
2)For device versions with SD03 local display: The terminal voltage must be increased by DC 2 V if
3)For device version with SD03 local display: The terminal voltage must be increased by DC 0.5 V if
1) 2)
1) 2)
3)
: FOUNDATION Fieldbus, pulse/
3)
: PROFIBUS PA, pulse/frequency/switch
backlighting is used.
backlighting is used.
For information about the load see → 9
Various power supply units can be ordered from Endress+Hauser: see "Accessories" section
→ 69
For information on the Ex connection values → 9
Minimum
terminal voltage
: 4-20 mA HART• For 4 mA: ≥ DC 18 V
• For 20 mA: ≥ DC 14 V
: 4-20 mA HART, pulse/frequency/
• For 4 mA: ≥ DC 18 V
• For 20 mA: ≥ DC 14 V
≥ DC 9 V
≥ DC 9 V
Maximum
terminal voltage
DC 35 V
DC 35 V
DC 32 V
DC 32 V
Power consumptionTransmitter
Order code for "Output"Maximum power consumption
Option A: 4-20 mA HART770 mW
Option B: 4-20 mA HART, pulse/
frequency/switch output
18Endress+Hauser
• Operation with output 1: 770 mW
• Operation with output 1 and 2: 2770 mW
Proline Promag H 200
1
2
Order code for "Output"Maximum power consumption
Option E: FOUNDATION Fieldbus, pulse/
frequency/switch output
For every 4-20 mA or 4-20 mA HART current output: 3.6 to 22.5 mA
If the option Defined value is selected in the Failure mode parameter : 3.59 to 22.5 mA
PROFIBUS PA
16 mA
FOUNDATION Fieldbus
16 mA
• Operation with output 1: 576 mW
• Operation with output 1 and 2: 2576 mW
• Operation with output 1: 512 mW
• Operation with output 1 and 2: 2512 mW
Power supply failure
• Totalizers stop at the last value measured.
• Configuration is retained in the device memory (HistoROM).
• Error messages (incl. total operated hours) are stored.
Electrical connectionConnecting the transmitter
1Cable entry for output 1
2Cable entry for output 2
A0015510
Endress+Hauser19
Proline Promag H 200
2
3
4...20 mA
41
+
-
5
+
-
1
+
_
12345
2
+
–
+
–
3
1
+
_
+
_
2
+
_
3
Connection examples
Current output 4-20 mA HART
A0015511
1Connection example for 4-20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply with integrated resistor for HART communication (≥ 250 Ω)(e.g. RN221N)
Connection for HART operating devices → 61
Observe the maximum load → 9
3Cable shield, observe cable specifications
4Analog display unit: observe maximum load → 9
5Transmitter
Pulse/frequency output
2Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: observe input values → 6
Switch output
A0016801
3Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
20Endress+Hauser
2Power supply
3Transmitter: observe input values
A0016802
Proline Promag H 200
213
+
-
+
-
+
-
4
5
5
78
6
6
6
6
6
6
.
-
PROFIBUS-PA
4Connection example for PROFIBUS-PA
1Control system (e.g. PLC)
2Segment coupler PROFIBUS DP/PA
3Cable shield
4T-box
5Measuring device
6Local grounding
7Bus terminator
8Potential matching line
A0019004
Endress+Hauser21
FOUNDATION Fieldbus
213
+
-
+
-
+
-
4
5
5
78
6
6
6
6
6
6
.
-
3
4...20 mA
5
1
+
-
3
6
+
–
+
+
–
+
–
+
–
+
–
–
2
4
4
7
+
-
Proline Promag H 200
5Connection example for FOUNDATION Fieldbus
1Control system (e.g. PLC)
2Power Conditioner (FOUNDATION Fieldbus)
3Cable shield
4T-box
5Measuring device
6Local grounding
7Bus terminator
8Potential matching line
HART input
A0019004
6Connection example for HART input with a common negative
1Automation system with HART output (e.g. PLC)
2Resistor for HART communication (≥ 250 Ω): observe maximum load → 9
3Active barrier for power supply (e.g. RN221N)
4Cable shield, observe cable specifications
5Analog display unit: observe maximum load → 9
6Pressure transmitter (e.g. Cerabar M, Cerabar S): see requirements
7Transmitter
22Endress+Hauser
A0016029
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.