Endress+Hauser E 100 Specifications

Page 1
TI01351D/06/EN/01.17 71377313
Products Solutions Services
Technical Information
Proline Promass E 100
Coriolis flowmeter
The flowmeter with minimum total cost of ownership and an ultra-compact transmitter
Application
• Measuring principle operates independently of physical fluid properties such as viscosity or density
• Accurate measurement of liquids and gases for a wide range of standard applications
Device properties
• Medium temperature up to +150 °C (+302 °F)
• Process pressure: up to 100 bar (1 450 psi)
• Robust, ultra-compact transmitter housing
• Highest degree of protection: IP69
• Local display available
Your benefits
• Cost-effective – multi-purpose device; an alternative to conventional volumetric flowmeters
• Fewer process measuring points – multivariable measurement (flow, density, temperature)
• Spacesaving installation – no in/outlet run needs
• Spacesaving transmitter – full functionality on smallest footprint
• Timesaving local operation without additional software and hardware – integrated web server
• Integrated verification – Heartbeat Technology
Page 2

Table of contents

Proline Promass E 100
About this document ........................ 4
Symbols used ................................ 4
Function and system design ................... 5
Measuring principle ............................ 5
Measuring system ............................. 5
Equipment architecture ......................... 7
Safety ..................................... 7
Input ..................................... 8
Measured variable ............................. 8
Measuring range .............................. 8
Operable flow range ........................... 9
Output ................................... 9
Output signal ................................ 9
Signal on alarm .............................. 10
Ex connection data ........................... 12
Low flow cut off ............................. 13
Protocol-specific data .......................... 13
Power supply ............................. 23
Terminal assignment .......................... 23
Pin assignment, device plug ...................... 30
Supply voltage .............................. 32
Power consumption ........................... 33
Current consumption .......................... 33
Power supply failure .......................... 33
Electrical connection .......................... 34
Potential equalization ......................... 39
Terminals ................................. 39
Cable entries ............................... 39
Cable specification ............................ 39
Performance characteristics .................. 41
reference operating conditions .................... 41
Maximum measured error ....................... 41
Repeatability ............................... 43
Response time .............................. 43
Influence of ambient temperature ................. 43
Influence of medium temperature .................. 43
Influence of medium pressure .................... 44
Design fundamentals .......................... 44
Shock resistance ............................. 48
Impact resistance ............................ 48
Interior cleaning ............................. 49
Electromagnetic compatibility (EMC) ............... 49
Process .................................. 49
Medium temperature range ...................... 49
Density ................................... 49
Pressure-temperature curves ..................... 50
Secondary containment ........................ 53
Rupture disk ................................ 53
Flow limit ................................. 53
Pressure loss ............................... 53
System pressure ............................. 53
Thermal insulation ........................... 54
Heating ................................... 54
Vibrations ................................. 54
Mechanical construction .................... 55
Dimensions in SI units ......................... 55
Dimensions in US units ......................... 68
Weight ................................... 76
Materials .................................. 76
Process connections ........................... 78
Surface roughness ........................... 78
Operability ............................... 78
Operating concept ............................ 78
Local display ................................ 79
Remote operation ............................ 79
Service interface ............................. 81
Certificates and approvals ................... 83
CE mark ................................... 83
C-Tick symbol ............................... 83
Ex approval ................................ 84
Sanitary compatibility ......................... 84
HART certification ............................ 84
Certification PROFIBUS ......................... 84
Certification PROFINET ........................ 85
EtherNet/IP certification ........................ 85
Modbus RS485 certification ..................... 85
Pressure Equipment Directive .................... 85
Other standards and guidelines ................... 85
Installation ............................... 45
Mounting location ............................ 45
Orientation ................................ 46
Inlet and outlet runs .......................... 47
Special mounting instructions .................... 47
Mounting Safety Barrier Promass 100 ............... 48
Environment .............................. 48
Ambient temperature range ..................... 48
Storage temperature .......................... 48
Climate class ............................... 48
Degree of protection .......................... 48
Vibration resistance ........................... 48
Ordering information ....................... 86
Application packages ....................... 86
Heartbeat Technology ......................... 86
Concentration ............................... 87
Accessories ............................... 87
Device-specific accessories ...................... 87
Communication-specific accessories ................ 87
Service-specific accessories ...................... 88
System components ........................... 88
2 Endress+Hauser
Page 3
Proline Promass E 100
Supplementary documentation ............... 89
Standard documentation ........................ 89
Supplementary device-dependent documentation ....... 89
Registered trademarks ...................... 90
Endress+Hauser 3
Page 4

About this document

A
1.
-
.

Symbols used Electrical symbols

Symbol Meaning
Proline Promass E 100
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Symbols for certain types of information
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
Symbols in graphics
Symbol Meaning
1, 2, 3, ... Item numbers
, 2., 3., … Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
Hazardous area
Safe area (non-hazardous area)
Flow direction
4 Endress+Hauser
Page 5
Proline Promass E 100
21 3

Function and system design

Measuring principle

The measuring principle is based on the controlled generation of Coriolis forces. These forces are always present in a system when both translational and rotational movements are superimposed.
Fc = 2 · ∆m (ν · ω)
Fc = Coriolis force
∆m = moving mass
ω = rotational velocity
ν = radial velocity in rotating or oscillating system
The amplitude of the Coriolis force depends on the moving mass ∆m, its velocity ν in the system and thus on the mass flow. Instead of a constant rotational velocity ω, the sensor uses oscillation.
In the sensor, two parallel measuring tubes containing flowing fluid oscillate in antiphase, acting like a tuning fork. The Coriolis forces produced at the measuring tubes cause a phase shift in the tube oscillations (see illustration):
• At zero flow (when the fluid is at a standstill) the two tubes oscillate in phase (1).
• Mass flow causes deceleration of the oscillation at the inlet of the tubes (2) and acceleration at the outlet (3).

Measuring system

A0028850
The phase difference (A-B) increases with increasing mass flow. Electrodynamic sensors register the tube oscillations at the inlet and outlet. System balance is ensured by the antiphase oscillation of the two measuring tubes. The measuring principle operates independently of temperature, pressure, viscosity, conductivity and flow profile.
Density measurement
The measuring tube is continuously excited at its resonance frequency. A change in the mass and thus the density of the oscillating system (comprising measuring tube and fluid) results in a corresponding, automatic adjustment in the oscillation frequency. Resonance frequency is thus a function of medium density. The microprocessor utilizes this relationship to obtain a density signal.
Volume measurement
Together with the measured mass flow, this is used to calculate the volume flow.
Temperature measurement
The temperature of the measuring tube is determined in order to calculate the compensation factor due to temperature effects. This signal corresponds to the process temperature and is also available as an output signal.
The device consists of a transmitter and a sensor. If a device with Modbus RS485 intrinsically safe is ordered, the Safety Barrier Promass 100 is part of the scope of supply and must be implemented to operate the device.
The device is available as a compact version: The transmitter and sensor form a mechanical unit.
Endress+Hauser 5
Page 6
Transmitter
Promass 100 Device versions and materials:
• Compact, aluminum, coated: Aluminum, AlSi10Mg, coated
• Compact, hygienic, stainless: Hygienic version, stainless steel 1.4301 (304)
• Ultra-compact, hygienic, stainless:
A0016693
A0016694
A0016695
Hygienic version, stainless steel 1.4301 (304)
Configuration:
• Via operating tools (e.g. FieldCare, DeviceCare)
• Additionally for device version with local display: Via Web browser (e.g. Microsoft Internet Explorer)
• Also for device version with 4-20 mA HART, pulse/frequency/switch output: Via Web browser (e.g. Microsoft Internet Explorer)
• Also for device version with EtherNet/IP output: – Via Web browser (e.g. Microsoft Internet Explorer) – Via Add-on Profile Level 3 for automation system from Rockwell
Automation
– Via Electronic Data Sheet (EDS)
• Also for device version with PROFINET output: – Via Web browser (e.g. Microsoft Internet Explorer) – Via device master file (GSD)
Proline Promass E 100
Sensor
Promass E • For standard applications where stable and reliable measurements are
required
• Simultaneous measurement of flow, volume flow, density and temperature (multivariable)
• Immune to process influences
• Nominal diameter range: DN 8 to 80 (³⁄₈ to 3")
• Materials:
A0030940
– Sensor: stainless steel, 1.4301 (304) – Measuring tubes: stainless steel, 1.4539 (904L) – Process connections: stainless steel, 1.4404 (316/316L)
Safety Barrier Promass 100
• Dual-channel safety barrier for installation in non-hazardous locations or zone 2/div. 2: – Channel 1: DC 24 V power supply – Channel 2: Modbus RS485
• In addition to current, voltage and power limitation, it offers galvanic isolation of circuits for explosion protection.
• Easy top-hat rail mounting (DIN 35 mm) for installation in control
A0016763
cabinets
6 Endress+Hauser
Page 7
Proline Promass E 100
2 3
7
8
6
9
10
11
4
1
5

Equipment architecture

A0016779
 1 Possibilities for integrating measuring devices into a system
1 Control system (e.g. PLC) 2 EtherNet/IP 3 PROFIBUS DP 4 PROFINET 5 Modbus RS485 6 4-20 mA HART, pulse/frequency/switch output 7 Safety Barrier Promass 100 8 Modbus RS485 intrinsically safe 9 Non-hazardous area 10 Non-hazardous area and Zone 2/Div. 2 11 Hazardous area and Zone 1/Div. 1

Safety IT security

We only provide a warranty if the device is installed and used as described in the Operating Instructions. The device is equipped with security mechanisms to protect it against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide additional protection for the device and device data transfer must be implemented by the operators themselves.
Endress+Hauser 7
Page 8

Input

Measured variable Direct measured variables

• Mass flow
• Density
• Temperature
Calculated measured variables
• Volume flow
• Corrected volume flow
• Reference density

Measuring range Measuring ranges for liquids

Proline Promass E 100
DN Measuring range full scale values 
[mm] [in] [kg/h] [lb/min]
8 ³⁄₈ 0 to 2 000 0 to 73.50
15 ½ 0 to 6 500 0 to 238.9
25 1 0 to 18 000 0 to 661.5
40 0 to 45 000 0 to 1 654
50 2 0 to 70 000 0 to 2 573
80 3 0 to 180 000 0 to 6 615
min(F)
to 
max(F)
Measuring ranges for gases
The full scale values depend on the density of the gas and can be calculated with the formula below: 
= 
max(G)
max(G)
max(F)
< 
max(G)
ρ
G
x Constant dependent on nominal diameter
max(F)
max(F)
· ρG : x
Maximum full scale value for gas [kg/h]
Maximum full scale value for liquid [kg/h]
can never be greater than 
max(G)
Gas density in [kg/m³] at operating conditions
max(F)
DN x
[mm] [in] [kg/m3]
8 ³⁄₈ 85
15 ½ 110
25 1 125
40 125
50 2 125
80 3 155
To calculate the measuring range, use the Applicator sizing tool →  88
Calculation example for gas
• Sensor: Promass E, DN 50
• Gas: Air with a density of 60.3 kg/m³ (at 20 °C and 50 bar)
• Measuring range (liquid): 70 000 kg/h
• x = 125 kg/m³ (for Promass E, DN 50)
8 Endress+Hauser
Page 9
Proline Promass E 100
Maximum possible full scale value: 
max(G)
= 
· ρG : x = 70 000 kg/h · 60.3 kg/m³ : 125 kg/m³ = 33 800 kg/h
max(F)
Recommended measuring range
"Flow limit" section →  53

Operable flow range

Over 1000 : 1.
Flow rates above the preset full scale value do not override the electronics unit, with the result that the totalizer values are registered correctly.

Output

Output signal HART current output

Current output 4-20 mA HART (active)
Maximum output values • DC 24 V (no flow)
Load 0 to 700 Ω
Resolution 0.38 µA
Damping Adjustable: 0.07 to 999 s
Assignable measured variables
• 22.5 mA
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
The range of options increases if the measuring device has one or more
application packages.
Pulse/frequency/switch output
Function Can be set to pulse, frequency or switch output
Version Passive, open collector
Maximum input values • DC 30 V
• 25 mA
Voltage drop For 25 mA: ≤ DC 2 V
Pulse output
Pulse width Adjustable: 0.05 to 2 000 ms
Maximum pulse rate 10 000 Impulse/s
Pulse value Adjustable
Assignable measured variables
Frequency output
Output frequency Adjustable: 0 to 10 000 Hz
Damping Adjustable: 0 to 999 s
Pulse/pause ratio 1:1
• Mass flow
• Volume flow
• Corrected volume flow
Endress+Hauser 9
Page 10
Proline Promass E 100
Assignable measured variables
Switch output
Switching behavior Binary, conductive or non-conductive
Switching delay Adjustable: 0 to 100 s
Number of switching cycles
Assignable functions • Off
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
The range of options increases if the measuring device has one or more
application packages.
Unlimited
• On
• Diagnostic behavior
• Limit value – Mass flow – Volume flow – Corrected volume flow – Density – Reference density – Temperature – Totalizer 1-3
• Flow direction monitoring
• Status – Partially filled pipe detection – Low flow cut off
The range of options increases if the measuring device has one or more
application packages.

Signal on alarm

PROFIBUS DP
Signal encoding NRZ code
Data transfer 9.6 kBaud…12 MBaud
Modbus RS485
Physical interface In accordance with EIA/TIA-485-A standard
Terminating resistor • For device version used in non-hazardous areas or Zone 2/Div. 2: integrated
and can be activated via DIP switches on the transmitter electronics module
• For device version used in intrinsically safe areas: integrated and can be activated via DIP switches on the Safety Barrier Promass 100
EtherNet/IP
Standards In accordance with IEEE 802.3
PROFINET
Standards In accordance with IEEE 802.3
Depending on the interface, failure information is displayed as follows:
10 Endress+Hauser
Page 11
Proline Promass E 100
Current output 4 to 20 mA
4 to 20 mA
Failure mode Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
• Actual value
• No pulses
Frequency output
Failure mode Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 12 500 Hz
Switch output
Failure mode Choose from:
• Current status
• Open
• Closed
PROFIBUS DP
Status and alarm messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Modbus RS485
Failure mode Choose from:
• NaN value instead of current value
• Last valid value
EtherNet/IP
Device diagnostics Device condition can be read out in Input Assembly
PROFINET
Device diagnostics According to "Application Layer protocol for decentralized periphery", Version 2.3
Endress+Hauser 11
Page 12
Local display
Plain text display With information on cause and remedial measures
Backlight Red backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication: – HART protocol – PROFIBUS DP – Modbus RS485 – EtherNet/IP – PROFINET
• Via service interface CDI-RJ45 service interface
Plain text display With information on cause and remedial measures
Proline Promass E 100

Ex connection data

Additional information on remote operation →  79
Web server
Plain text display With information on cause and remedial measures
Light emitting diodes (LED)
Status information Status indicated by various light emitting diodes
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
• PROFINET network available
• PROFINET connection established
• PROFINET blinking feature
These values only apply for the following device version: Order code for "Output", option M "Modbus RS485", for use in intrinsically safe areas
Safety Barrier Promass 100
Safety-related values
Terminal numbers
Supply voltage Signal transmission
2 (L-) 1 (L+) 26 (A) 27 (B)
U
nom
U
= AC 260 V
max
= DC 24 V
U
nom
U
= AC 260 V
max
= DC 5 V
12 Endress+Hauser
Page 13
Proline Promass E 100
Intrinsically safe values
Terminal numbers
Supply voltage Signal transmission
20 (L-) 10 (L+) 62 (A) 72 (B)
Uo = 16.24 V
Io = 623 mA
1)
With IIC
For an overview and for information on the interdependencies between the gas group - sensor - nominal
diameter, see the "Safety Instructions" (XA) document for the measuring device
1) The gas group depends on the sensor and nominal diameter ff.
: Lo = 92.8 µH, Co = 0.433 μF, Lo/Ro = 14.6 μH/Ω
With IIB: Lo= 372 µH, Co = 2.57 μF, Lo/Ro = 58.3 μH/Ω
Po = 2.45 W
Transmitter
Intrinsically safe values
• Option BM: ATEX II2G + IECEx Z1 Ex ia, II2D Ex tb
• Option BO: ATEX II1/2G + IECEx Z0/Z1 Ex ia, II2D
• Option BQ: ATEX II1/2G + IECEx Z0/Z1 Ex ia
• Option BU: ATEX II2G + IECEx Z1 Ex ia
• Option C2: CSA C/US IS Cl. I, II, III Div. 1
• Option 85: ATEX II2G + IECEx Z1 Ex ia + CSA C/US IS Cl. I, II, III Div. 1

Low flow cut off

Protocol-specific data HART

The switch points for low flow cut off are user-selectable.
Manufacturer ID 0x11
Device type ID 0x4A
HART protocol revision 7
Device description files (DTM, DD)
HART load Min. 250 Ω
Order code for
"Approval"
For an overview and for information on the interdependencies between the gas group - sensor - nominal diameter, see the "Safety Instructions" (XA) document for the measuring device
Information and files under:
www.endress.com
Supply voltage Signal transmission
20 (L-) 10 (L+) 62 (A) 72 (B)
Terminal numbers
Ui = 16.24 V
Ii = 623 mA Pi = 2.45 W
Li = 0 µH Ci = 6 nF
Endress+Hauser 13
Page 14
Dynamic variables Read out the dynamic variables: HART command 3
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic variable)
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
The range of options increases if the measuring device has one or more
application packages.
Heartbeat Technology application package
Additional measured variables are available with the Heartbeat Technology application package: Oscillation amplitude 0
Device variables Read out the device variables: HART command 9
The device variables are permanently assigned.
A maximum of 8 device variables can be transmitted:
• 0 = mass flow
• 1 = volume flow
• 2 = corrected volume flow
• 3 = density
• 4 = reference density
• 5 = temperature
• 6 = totalizer 1
• 7 = totalizer 2
• 8 = totalizer 3
• 13 = target mass flow
• 14 = carrier mass flow
• 15 = concentration
Proline Promass E 100
PROFIBUS DP
Manufacturer ID 0x11
Ident number 0x1561
Profile version 3.02
Device description files (GSD, DTM, DD)
Information and files under:
www.endress.com On the product page for the device: Documents/Software → Device drivers
www.profibus.org
14 Endress+Hauser
Page 15
Proline Promass E 100
Output values
(from measuring device to automation system)
Input values
(from automation system to measuring device)
Supported functions • Identification & Maintenance
Configuration of the device address
Analog input 1 to 8
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
• Density
• Reference density
• Concentration
• Temperature
• Carrier pipe temperature
• Electronic temperature
• Oscillation frequency
• Oscillation amplitude
• Frequency fluctuation
• Oscillation damping
• Tube damping fluctuation
• Signal asymmetry
• Exciter current
Digital input 1 to 2
• Partially filled pipe detection
• Low flow cut off
Totalizer 1 to 3
• Mass flow
• Volume flow
• Corrected volume flow
Analog output 1 to 3 (fixed assignment)
• Pressure
• Temperature
• Reference density
Digital output 1 to 3 (fixed assignment)
• Digital output 1: switch positive zero return on/off
• Digital output 2: perform zero point adjustment
• Digital output 3: switch switch output on/off
Totalizer 1 to 3
• Totalize
• Reset and hold
• Preset and hold
• Stop
• Operating mode configuration: – Net flow total – Forward flow total – Reverse flow total
Simplest device identification on the part of the control system and nameplate
• PROFIBUS upload/download Reading and writing parameters is up to ten times faster with PROFIBUS upload/download
• Condensed status Simplest and self-explanatory diagnostic information by categorizing diagnostic messages that occur
• DIP switches on the I/O electronics module
• Via operating tools (e.g. FieldCare)
Modbus RS485
Protocol Modbus Applications Protocol Specification V1.1
Device type Slave
Slave address range 1 to 247
Broadcast address range 0
Endress+Hauser 15
Page 16
Proline Promass E 100
Function codes • 03: Read holding register
• 04: Read input register
• 06: Write single registers
• 08: Diagnostics
• 16: Write multiple registers
• 23: Read/write multiple registers
Broadcast messages Supported by the following function codes:
• 06: Write single registers
• 16: Write multiple registers
• 23: Read/write multiple registers
Supported baud rate • 1 200 BAUD
• 2 400 BAUD
• 4 800 BAUD
• 9 600 BAUD
• 19 200 BAUD
• 38 400 BAUD
• 57 600 BAUD
• 115 200 BAUD
Data transfer mode • ASCII
• RTU
Data access Each device parameter can be accessed via Modbus RS485.
For Modbus register information, see "Description of device parameters"
documentation
EtherNet/IP
Protocol • The CIP Networks Library Volume 1: Common Industrial Protocol
• The CIP Networks Library Volume 2: EtherNet/IP Adaptation of CIP
Communication type • 10Base-T
• 100Base-TX
Device profile Generic device (product type: 0x2B)
Manufacturer ID 0x49E
Device type ID 0x104A
Baud rates Automatic ¹⁰⁄₁₀₀ Mbit with half-duplex and full-duplex detection
Polarity Auto-polarity for automatic correction of crossed TxD and RxD pairs
Supported CIP connections Max. 3 connections
Explicit connections Max. 6 connections
I/O connections Max. 6 connections (scanner)
Configuration options for measuring device
Configuration of the EtherNet interface
Configuration of the device address
Device Level Ring (DLR) No
• DIP switches on the electronics module for IP addressing
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• Electronic Data Sheet (EDS) integrated in the measuring device
• Speed: 10 MBit, 100 MBit, auto (factory setting)
• Duplex: half-duplex, full-duplex, auto (factory setting)
• DIP switches on the electronics module for IP addressing (last octet)
• DHCP
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• EtherNet/IP tools, e.g. RSLinx (Rockwell Automation)
16 Endress+Hauser
Page 17
Proline Promass E 100
Fix Input
RPI 5 ms to 10 s (factory setting: 20 ms)
Exclusive Owner Multicast Instance Size [byte]
Instance configuration: 0x68 398
O → T configuration: 0x66 64
T → O configuration: 0x64 44
Exclusive Owner Multicast Instance Size [byte]
Instance configuration: 0x69 -
O → T configuration: 0x66 64
T → O configuration: 0x64 44
Input only Multicast Instance Size [byte]
Instance configuration: 0x68 398
O → T configuration: 0xC7 -
T → O configuration: 0x64 44
Input only Multicast Instance Size [byte]
Instance configuration: 0x69 -
O → T configuration: 0xC7 -
T → O configuration: 0x64 44
Input Assembly • Current device diagnostics
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
Configurable Input
RPI 5 ms to 10 s (factory setting: 20 ms)
Exclusive Owner Multicast Instance Size [byte]
Instance configuration: 0x68 398
O → T configuration: 0x66 64
T → O configuration: 0x65 88
Exclusive Owner Multicast Instance Size [byte]
Instance configuration: 0x69 -
O → T configuration: 0x66 64
T → O configuration: 0x65 88
Input only Multicast Instance Size [byte]
Instance configuration: 0x68 398
O → T configuration: 0xC7 -
T → O configuration: 0x65 88
Input only Multicast Instance Size [byte]
Instance configuration: 0x69 -
O → T configuration: 0xC7 -
T → O configuration: 0x65 88
Endress+Hauser 17
Page 18
Proline Promass E 100
Configurable Input Assembly • Current device diagnostics
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
The range of options increases if the measuring device has one or
more application packages.
Fix Output
Output Assembly • Activation of reset totalizers 1-3
• Activation of pressure compensation
• Activation of reference density compensation
• Activation of temperature compensation
• Reset totalizers 1-3
• External pressure value
• Pressure unit
• External reference density
• Reference density unit
• External temperature
• Temperature unit
Configuration
Configuration Assembly Only the most common configurations are listed below.
• Software write protection
• Mass flow unit
• Mass unit
• Volume flow unit
• Volume unit
• Corrected volume flow unit
• Corrected volume unit
• Density unit
• Reference density unit
• Temperature unit
• Pressure unit
• Length
• Totalizer 1-3: – Assignment – Unit – Operating mode – Failsafe mode
• Alarm delay
PROFINET
Protocol "Application layer protocol for decentral device periphery and distributed
automation", version 2.3
Conformity class B
Communication type 100 MBit/s
Device profile Application interface identifier 0xF600
Generic device
Manufacturer ID 0x11
Device type ID 0x844A
Device description files (GSD, DTM)
Baud rates Automatic 100 Mbit/s with full-duplex detection
Information and files under:
www.endress.com On the product page for the device: Documents/Software → Device drivers
www.profibus.org
18 Endress+Hauser
Page 19
Proline Promass E 100
Cycle times From 8 ms
Polarity Auto-polarity for automatic correction of crossed TxD and RxD pairs
Supported connections • 1 x AR (Application Relation)
• 1 x Input CR (Communication Relation)
• 1 x Output CR (Communication Relation)
• 1 x Alarm CR (Communication Relation)
Configuration options for measuring device
Configuration of the device name
Output values
(from measuring device to automation system)
• DIP switches on the electronics module, for device name assignment (last part)
• Manufacturer-specific software (FieldCare, DeviceCare)
• Web browser
• Device master file (GSD), can be read out via the integrated Web server of the measuring device
• DIP switches on the electronics module, for device name assignment (last part)
• DCP protocol
Analog Input module (slot 1 to 14)
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
• Density
• Reference density
• Concentration
• Temperature
• Carrier pipe temperature
• Electronic temperature
• Oscillation frequency
• Oscillation amplitude
• Frequency fluctuation
• Oscillation damping
• Tube damping fluctuation
• Signal asymmetry
• Exciter current
Discrete Input module (slot 1 to 14)
• Empty pipe detection
• Low flow cut off
Diagnostics Input module (slot 1 to 14)
• Last diagnostics
• Current diagnosis
Totalizer 1 to 3 (slot 15 to 17)
• Mass flow
• Volume flow
• Corrected volume flow
Heartbeat Verification module (fixed assignment)
Verification status (slot 23)
The range of options increases if the measuring device has one or more
application packages.
Endress+Hauser 19
Page 20
Proline Promass E 100
Input values
(from automation system to measuring device)
Supported functions • Identification & Maintenance
Analog Output module (fixed assignment)
• External pressure (slot 18)
• External temperature (slot 19)
• External reference density (slot 20)
Discrete Output module (fixed assignment)
• Activate/deactivate positive zero return (slot 21)
• Perform zero point adjustment (slot 22)
Totalizer 1 to 3 (slot 15 to 17)
• Totalize
• Reset and hold
• Preset and hold
• Stop
• Operating mode configuration: – Net flow total – Forward flow total – Reverse flow total
Heartbeat Verification module (fixed assignment)
Start verification (slot 23)
The range of options increases if the measuring device has one or more
application packages.
Simple device identification via: – Control system – Nameplate
• Measured value status The process variables are communicated with a measured value status
• Blinking feature via the local display for simple device identification and assignment
Administration of software options
Input/output value Process variable Category Slot
Output value Mass flow Process variable 1 to 14
Volume flow
Corrected volume flow
Density
Reference density
Temperature
Electronic temperature
Oscillation frequency
Frequency fluctuation
Oscillation damping
Oscillation frequency
Signal asymmetry
Exciter current
Empty pipe detection
Low flow cut off
Current device diagnostics
Previous device diagnostics
Output value Target mass flow Concentration
Carrier mass flow
Concentration
Output value Oscillation damping 1 Heartbeat
1)
2)
1 to 14
1 to 14
20 Endress+Hauser
Page 21
Proline Promass E 100
Input/output value Process variable Category Slot
Oscillation frequency 1
Oscillation amplitude 0
Oscillation amplitude 1
Frequency fluctuation 1
Tube damping fluctuation 1
Exciter current 1
Input value External density Process monitoring 18
External temperature 19
External reference density 20
Flow override 21
Zero point adjustment 22
Status verification Heartbeat Verification 23
1) Only available with the "Concentration" application package.
2) Only available with the "Heartbeat" application package.
Endress+Hauser 21
Page 22
Startup configuration
Proline Promass E 100
Startup configuration (NSU)
If startup configuration is enabled, the configuration of the most important device parameters is taken from the automation system and used.
The following configuration is taken from the automation system:
• Management – Software revision – Write protection
• System units – Mass flow – Mass – Volume flow – Volume – Corrected volume flow – Corrected volume – Density – Reference density – Temperature – Pressure
• Concentration application package – Coefficients A0 to A4 – Coefficients B1 to B3
• Sensor adjustment
• Process parameter – Damping (flow, density, temperature) – Flow override
• Low flow cut off – Assign process variable – Switch-on/switch-off point – Pressure shock suppression
• Empty pipe detection – Assign process variable – Limit values – Response time – Max. damping
• Corrected volume flow calculation – External reference density – Fixed reference density – Reference temperature – Linear expansion coefficient – Square expansion coefficient
• Measuring mode – Medium – Gas type – Reference sound velocity – Temperature coefficient sound velocity
• External compensation – Pressure compensation – Pressure value – External pressure
• Diagnostic settings
• Diagnostic behavior for diverse diagnostic information
22 Endress+Hauser
Page 23
Proline Promass E 100
A
B
C
2
2.1 2.2
3
3.1 3.2
1
1.1 1.2 1.3
4
4.2
4.1

Power supply

Terminal assignment Overview: housing version and connection versions

A0016770
A Housing version: compact, aluminum coated B Housing version: compact, hygienic, stainless C Housing version: ultra-compact, hygienic, stainless 1 Connection version: 4-20 mA HART, pulse/frequency/switch output
1.1 Signal transmission: pulse/frequency/switch output
1.2 Signal transmission: 4-20 mA HART
1.3 Supply voltage 2 Connection version: Modbus RS485
2.1 Signal transmission
2.2 Supply voltage 3 Connection versions: EtherNet/IP and PROFINET
3.1 Signal transmission
3.2 Supply voltage 4 Connection version: PROFIBUS DP
4.1 Signal transmission
4.2 Supply voltage
Transmitter
Connection version 4-20 mA HART with pulse/frequency/switch output
Order code for "Output", option B
Endress+Hauser 23
Page 24
Proline Promass E 100
L
L
26
27
+
_
24
25
1
2
+
_
+
_
1
2
3
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.
Order code
Connection methods available
"Housing"
Options
Outputs
Terminals Terminals • Option A: coupling M20x1
A, B
Options A, B
Options A, B, C
Device plugs
→  31
Device plugs
→  31
Order code for "Housing":
• Option A: compact, coated aluminum
• Option B: compact, hygienic, stainless
• Option C ultra-compact, hygienic, stainless
Power
"Electrical connection"
supply
• Option B: thread M20x1
• Option C: thread G ½"
• Option D: thread NPT ½"
Terminals • Option L: plug M12x1 + thread NPT ½"
• Option N: plug M12x1 + coupling M20
• Option P: plug M12x1 + thread G ½"
• Option U: plug M12x1 + thread M20
Possible options for order code
Device plugs
Option Q: 2 x plug M12x1
→  31
 2 Terminal assignment 4-20 mA HART with pulse/frequency/switch output
1 Power supply: DC 24 V 2 Output 1: 4-20 mA HART (active) 3 Output 2: pulse/frequency/switch output (passive)
Terminal number
Order code
"Output"
Power supply Output 1 Output 2
2 (L-) 1 (L+) 27 (–) 26 (+) 25 (–) 24 (+)
Option B DC 24 V 4-20 mA HART (active) Pulse/frequency/switch
Order code for "Output": Option B: 4-20 mA HART with pulse/frequency/switch output
A0016888
output (passive)
24 Endress+Hauser
Page 25
Proline Promass E 100
L
L
26 27BA
1
2
+ _
1
2
PROFIBUS DP connection version
For use in the non-hazardous area and Zone 2/Div. 2
Order code for "Output", option L
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.
Order code
"Housing"
Options A, B
Options A, B
Options A, B, C
Order code for "Housing":
• Option A: compact, coated aluminum
• Option B: compact, hygienic, stainless
• Option C ultra-compact, hygienic, stainless
Connection methods available
Output
Terminals Terminals • Option A: coupling M20x1
Device plugs
→  31
Device plugs
→  31
Power supply
Terminals • Option L: plug M12x1 + thread NPT ½"
Device plugs
→  31
Possible options for order code
"Electrical connection"
• Option B: thread M20x1
• Option C: thread G ½"
• Option D: thread NPT ½"
• Option N: plug M12x1 + coupling M20
• Option P: plug M12x1 + thread G ½"
• Option U: plug M12x1 + thread M20
Option Q: 2 x plug M12x1
A0022716
 3 PROFIBUS DP terminal assignment
1 Power supply: DC 24 V 2 PROFIBUS DP
Terminal number
Order code
"Output"
Option L DC 24 V B A
Order code for "Output": Option L: PROFIBUS DP, for use in non-hazardous areas and Zone 2/Div. 2
Power supply Output
2 (L-) 1 (L+) 26 (RxD/TxD-P) 27 (RxD/TxD-
N)
Endress+Hauser 25
Page 26
Proline Promass E 100
L
L
26 27
A
B
1
2
+ _
1
2
Modbus RS485 connection version
For use in the non-hazardous area and Zone 2/Div. 2
Order code for "Output", option M
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.
Order code
Connection methods available
"Housing"
Options
Output
Terminals Terminals • Option A: coupling M20x1
A, B
Options A, B
Options A, B, C
Device plugs
→  31
Device plugs
→  31
Order code for "Housing":
• Option A: compact, coated aluminum
• Option B: compact, hygienic, stainless
• Option C ultra-compact, hygienic, stainless
Power
"Electrical connection"
supply
• Option B: thread M20x1
• Option C: thread G ½"
• Option D: thread NPT ½"
Terminals • Option L: plug M12x1 + thread NPT ½"
• Option N: plug M12x1 + coupling M20
• Option P: plug M12x1 + thread G ½"
• Option U: plug M12x1 + thread M20
Possible options for order code
Device plugs
Option Q: 2 x plug M12x1
→  31
A0019528
 4 Modbus RS485 terminal assignment, connection version for use in non-hazardous areas and Zone 2/Div.
2
1 Power supply: DC 24 V 2 Modbus RS485
Terminal number
Order code
"Output"
Power supply Output
1 (L+) 2 (L-) 26 (B) 27 (A)
Option M DC 24 V Modbus RS485
Order code for "Output": Option M: Modbus RS485, for use in non-hazardous areas and Zone 2/Div. 2
26 Endress+Hauser
Page 27
Proline Promass E 100
L L
62 72
A
B
10 20
+ _
1
2
Modbus RS485 connection version
For use in the intrinsically safe area. Connection via Safety Barrier Promass 100.
Order code for "Output", option M
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.
Order code
"Housing"
Options
A, B
A, B, C Device plugs
Order code for "Housing":
• Option A: compact, coated aluminum
• Option B: compact, hygienic, stainless
• Option C ultra-compact, hygienic, stainless
 5 Modbus RS485 terminal assignment, connection version for use in intrinsically safe areas (connection via
Safety Barrier Promass 100)
1 Intrinsically safe power supply 2 Modbus RS485
Connection methods available
Output
Terminals Terminals • Option A: coupling M20x1
→  31
Power supply
Possible options for order code
"Electrical connection"
• Option B: thread M20x1
• Option C: thread G ½"
• Option D: thread NPT ½"
Option I: plug M12x1
A0030219
Order code
"Output"
Option M Intrinsically safe supply voltage Modbus RS485 intrinsically safe
Order code for "Output": Option M: Modbus RS485, for use in the intrinsically safe area (connection via Safety Barrier Promass 100)
Endress+Hauser 27
10 (L+) 20 (L-) 62 (B) 72 (A)
Page 28
Proline Promass E 100
L
L
1
2
+ _
1
2
EtherNet/IP connection version
Order code for "Output", option N
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.
Order code
"Housing"
Options A, B
Options A, B, C
Order code for "Housing":
• Option A: compact, coated aluminum
• Option B: compact, hygienic, stainless
• Option C ultra-compact, hygienic, stainless
 6 EtherNet/IP terminal assignment
1 Power supply: DC 24 V 2 EtherNet/IP
Connection methods available
Output
Device plugs
→  32
Device plugs
→  32
Power supply
Terminals • Option L: plug M12x1 + thread NPT ½"
Device plugs
→  32
Possible options for order code
"Electrical connection"
• Option N: plug M12x1 + coupling M20
• Option P: plug M12x1 + thread G ½"
• Option U: plug M12x1 + thread M20
Option Q: 2 x plug M12x1
A0017054
Order code
"Output"
Option N DC 24 V EtherNet/IP
Order code for "Output": Option N: EtherNet/IP
Terminal number
Power supply Output
2 (L-) 1 (L+) Device plug M12x1
28 Endress+Hauser
Page 29
Proline Promass E 100
L
L
1
2
+ _
1
2
PROFINET connection version
Order code for "Output", option R
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.
Order code for
"Housing"
Options A, B
Options A, B, C
Order code for "Housing":
• Option A: compact, coated aluminum
• Option B: compact, hygienic, stainless
• Option C ultra-compact, hygienic, stainless
 7 PROFINET terminal assignment
1 Power supply: DC 24 V 2 PROFINET
Connection methods available
Output
Device plugs
→  30
Device plugs
→  30
Power supply
Terminals • Option L: plug M12x1 + thread NPT ½"
Device plugs
→  30
Possible options for order code
"Electrical connection"
• Option N: plug M12x1 + coupling M20
• Option P: plug M12x1 + thread G ½"
• Option U: plug M12x1 + thread M20
Option Q: 2 x plug M12x1
A0017054
Order code for "Output": Option R: PROFINET
Terminal number
Order code for
"Output"
Option R DC 24 V PROFINET
Power supply Output
2 (L-) 1 (L+) Device plug M12x1
Endress+Hauser 29
Page 30
Safety Barrier Promass 100
A
Safe area
1
L+2L
27
26
B A
Power supply 24V
DC
Modbus
RS485
10207262
L+L B A
Power supply
Modbus
RS485
Hazardous area
Safety Barrier Promass 100
Power
Communication
Lift panel for bus termination
1
2
A
1
2
4
3
5
 8 Safety Barrier Promass 100 with terminals
1 Non-hazardous area, Zone 2, Class I Division 2 2 Intrinsically safe area
Proline Promass E 100
A0030220

Pin assignment, device plug

Order codes for the M12x1 connectors, see the "Order code for electrical connection" column:
• 4-20 mA HART, pulse/frequency/switch output →  23
• PROFIBUS DP→  25
• Modbus RS485 →  26
• EtherNet/IP →  28
• PROFINET→  29
Supply voltage
For all connection versions except MODBUS RS485 intrinsically safe (device side)
Device plug MODBUS RS485 intrinsically safe with supply voltage →  31
Pin Assignment
1 L+ DC 24 V
2 Not assigned
3 Not assigned
4 L- DC 24 V
A0016809
5 Grounding/shielding
Coding Plug/socket
A Plug
The following is recommended as a socket:
• Binder, series 763, part no. 79 3440 35 05
• Alternatively: Phoenix part no. 1669767 SAC-5P-M12MS – With the order code for "Output", option B: 4-20 mA HART, pulse/frequency/switch output – With the order code for "Output", option N: EtherNet/IP
• When using the device in a hazardous location: Use a suitably certified socket.
30 Endress+Hauser
Page 31
Proline Promass E 100
3
2
4
1
5
3
2
4
1
5
1
2
4
3
5
4-20 mA HART with pulse/frequency/switch output
Device plug for signal transmission (device side)
Pin Assignment
1 + 4-20 mA HART (active)
2 - 4-20 mA HART (active)
3 + Pulse/frequency/switch output (passive)
4 - Pulse/frequency/switch output (passive)
A0016810
• Recommended plug: Binder, series 763, part no. 79 3439 12 05
• When using the device in a hazardous location, use a suitably certified plug.
5 Grounding/shielding
Coding Plug/socket
A Socket
PROFIBUS DP
For use in the non-hazardous area and Zone 2/Div. 2.
Device plug for signal transmission (device side)
Pin Assignment
1 Not assigned
2 A PROFIBUS DP
3 Not assigned
4 B PROFIBUS DP
A0016811
• Recommended plug: Binder, series 763, part no. 79 4449 20 05
• When using the device in a hazardous location, use a suitably certified plug.
5 Grounding/shielding
Coding Plug/socket
B Socket
MODBUS RS485
Device plug for signal transmission with supply voltage (device side), MODBUS RS485 (intrinsically safe)
Pin Assignment
1 L+ Supply voltage, intrinsically safe
A0016809
2 A
3 B
4 L- Supply voltage, intrinsically safe
5 Grounding/shielding
Coding Plug/socket
A Plug
Modbus RS485 intrinsically safe
• Recommended socket: Binder, series 763, part no. 79 3439 12 05
• When using the device in a hazardous location: Use a suitably certified socket.
Endress+Hauser 31
Page 32
Proline Promass E 100
3
2
4
1
5
3
2
4
1
3
2
4
1
Device plug for signal transmission (device side), MODBUS RS485 (not intrinsically safe)
For use in the non-hazardous area and Zone 2/Div. 2.
Pin Assignment
1 Not assigned
2 A Modbus RS485
3 Not assigned
4 B Modbus RS485
A0016811
• Recommended plug: Binder, series 763, part no. 79 4449 20 05
• When using the device in a hazardous location, use a suitably certified plug.
EtherNet/IP
Device plug for signal transmission (device side)
5 Grounding/shielding
Coding Plug/socket
B Socket
Pin Assignment
1 + Tx
2 + Rx
3 - Tx
4 - Rx
A0016812
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.
Coding Plug/socket
D Socket
PROFINET
Device plug for signal transmission (device side)
Pin Assignment
1 + TD +
2 + RD +
3 - TD –
4 - RD –
A0016812
Coding Plug/socket
D Socket
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.

Supply voltage

The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).
32 Endress+Hauser
Page 33
Proline Promass E 100
Transmitter
For device version with communication type:
• HART, PROFIBUS DP, EtherNet/IP: DC 20 to 30 V
• Modbus RS485, device version: – For use in the non-hazardous area and Zone 2/Div. 2: DC 20 to 30 V – For use in the intrinsically safe area: power supply via Safety Barrier Promass 100
Promass 100 safety barrier
DC 20 to 30 V
Power consumption Transmitter
Order code for "Output"
Option B: 4-20 mA HART with pulse/frequency/switch output 3.5 W
Option L: PROFIBUS DP 3.5 W
Option M Modbus RS485, for use in non-hazardous areas and Zone 2/ Div. 2
Option M: Modbus RS485, for use in intrinsically safe areas 2.45 W
Option N: EtherNet/IP 3.5 W
Option R: PROFINET 3.5 W
Promass 100 safety barrier
Order code for "Output"
Option M: Modbus RS485, for use in intrinsically safe areas 4.8 W
Current consumption Transmitter
Order code for "Output"
Option B: 4-20mA HART, pul./freq./switch output 145 mA 18 A (< 0.125 ms)
Option L: PROFIBUS DP 145 mA 18 A (< 0.125 ms)
Option M Modbus RS485, for use in non-hazardous areas and Zone 2/Div. 2
Option M: Modbus RS485, for use in intrinsically safe areas
Option N: EtherNet/IP 145 mA 18 A (< 0.125 ms)
Option R: PROFINET 145 mA 18 A (< 0.125 ms)
Maximum

Power consumption

Maximum
Power consumption
Maximum

Current consumption

90 mA 10 A (< 0.8 ms)
145 mA 16 A (< 0.4 ms)
switch-on current
3.5 W
Maximum
Promass 100 safety barrier

Power supply failure

Order code for "Output"
Option M: Modbus RS485, for use in intrinsically safe areas
• Totalizers stop at the last value measured.
Maximum
Current consumption
230 mA 10 A (< 0.8 ms)
Maximum
switch-on current
• Depending on the device version, the configuration is retained in the device memory or in the plug-in memory (HistoROM DAT).
• Configuration is retained in the plug-in memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.
Endress+Hauser 33
Page 34

Electrical connection Connecting the transmitter

1 2 1 2 3 4
A B C
4
4...20 mA
5
2
1
3
6
A Housing version: compact, aluminum coated B Housing version: compact hygienic, stainless 1 Cable entry or device plug for signal transmission 2 Cable entry or device plug for supply voltage C Housing version: ultra-compact, hygienic, stainless, M12 device plug 3 Device plug for signal transmission 4 Device plug for supply voltage
Proline Promass E 100
A0016924
• Terminal assignment→  23
• Pin assignment, device plug→  30 In the case of device versions with a connector, the transmitter housing does not need to be
opened to connect the signal cable or power supply cable.
Connection examples
Current output 4 to 20 mA HART
A0029055
 9 Connection example for 4 to 20 mA HART current output (active)
1 Automation system with current input (e.g. PLC) 2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications →  39 3 Connection for HART operating devices →  79 4 Resistor for HART communication (≥ 250 Ω): observe maximum load 5 Analog display unit: observe maximum load 6 Transmitter
34 Endress+Hauser
Page 35
Proline Promass E 100
2
3
4...20 mA
41
5
1
2
3
12345
1
2
3
A0028762
 10 Connection example for 4 to 20 mA HART current output (passive)
1 Automation system with current input (e.g. PLC) 2 Power supply 3 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications →  39 4 Analog display unit: observe maximum load 5 Transmitter
Pulse/frequency output
 11 Connection example for pulse/frequency output (passive)
1 Automation system with pulse/frequency input (e.g. PLC) 2 Power supply 3 Transmitter: Observe input values
Switch output
 12 Connection example for switch output (passive)
1 Automation system with switch input (e.g. PLC) 2 Power supply 3 Transmitter: Observe input values
A0028761
A0028760
Endress+Hauser 35
Page 36
Proline Promass E 100
2
1
A
B
3
4
4
A
B
A
B
2
1
A
B
3
4
4
A
B
A
B
PROFIBUS DP
A0028765
 13 Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1 Control system (e.g. PLC) 2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
3 Transmitter
If baud rates > 1.5 MBaud an EMC cable entry must be used and the cable shield must continue as far as the terminal wherever possible.
Modbus RS485
Modbus RS485, non-hazardous area and Zone 2/Div. 2
A0028765
 14 Connection example for Modbus RS485, non-hazardous area and Zone 2/Div. 2
1 Control system (e.g. PLC) 2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications →  39 3 Distribution box 4 Transmitter
36 Endress+Hauser
Page 37
Proline Promass E 100
21
A
B
3
A B
L+
L-
L- L+
A B
5 6 7
4
8
A B
L+ L-
1
2
4
3
5
5
Modbus RS485 intrinsically safe
A0028766
 15 Connection example for Modbus RS485 intrinsically safe
1 Control system (e.g. PLC) 2 Cable shield, observe cable specifications 3 Safety Barrier Promass 100 4 Observe cable specifications 5 Non-hazardous area 6 Non-hazardous area and Zone 2/Div. 2 7 Intrinsically safe area 8 Transmitter
EtherNet/IP
 16 Connection example for EtherNet/IP
1 Control system (e.g. PLC) 2 Ethernet switch 3 Observe cable specifications 4 Device plug 5 Transmitter
A0028767
Endress+Hauser 37
Page 38
PROFINET
1 2 4
5
5
3
2
4...20 mA
3
41
+
-
5
+
­6
 17 Connection example for PROFINET
1 Control system (e.g. PLC) 2 Ethernet switch 3 Observe cable specifications 4 Device plug 5 Transmitter
HART input
Proline Promass E 100
A0016805
 18 Connection example for HART input (burst mode) via current output (active)
1 Cable shield, observe cable specifications 2 Resistor for HART communication (≥ 250 Ω): observe maximum load 3 Connection for HART operating devices 4 Analog display unit 5 Transmitter 6 Sensor for external measured variable
A0019828
38 Endress+Hauser
Page 39
Proline Promass E 100
3
4...20 mA
4
521
+
-
6
4...20 mA
+
­7
3
4
52
+
-
-
+
A0019830
 19 Connection example for HART input (master mode) via current output (active)
1 Automation system with current input (e.g. PLC).
Prerequisite: automation system with HART version 6, HART commands 113 and 114 can be processed. 2 Cable shield, observe cable specifications 3 Resistor for HART communication (≥ 250 Ω): observe maximum load 4 Connection for HART operating devices 5 Analog display unit 6 Transmitter 7 Sensor for external measured variable

Potential equalization Requirements

No special measures for potential equalization are required.
Please consider the following to ensure correct measurement:
• Same electrical potential for the medium and sensor
• Company-internal grounding concepts
For devices intended for use in hazardous locations, please observe the guidelines in the Ex documentation (XA).

Terminals

Transmitter
Spring terminals for wire cross-sections0.5 to 2.5 mm2 (20 to 14 AWG)
Promass 100 safety barrier
Plug-in screw terminals for wire cross-sections0.5 to 2.5 mm2 (20 to 14 AWG)

Cable entries

• Cable gland: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– M20 – G ½" – NPT ½"

Cable specification Permitted temperature range

• The installation guidelines that apply in the country of installation must be observed.
• The cables must be suitable for the minimum and maximum temperatures to be expected.
Power supply cable
Standard installation cable is sufficient.
Signal cable
Current output 4 to 20 mA HART
A shielded cable is recommended. Observe grounding concept of the plant.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Endress+Hauser 39
Page 40
Proline Promass E 100
PROFIBUS DP
The IEC 61158 standard specifies two types of cable (A and B) for the bus line which can be used for every transmission rate. Cable type A is recommended.
Cable type A
Characteristic impedance 135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance < 30 pF/m
Wire cross-section
Cable type Twisted pairs
Loop resistance ≤110 Ω/km
Signal damping Max. 9 dB over the entire length of the cable cross-section
Shield Copper braided shielding or braided shielding with foil shield. When grounding
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used for every transmission rate. Cable type A is recommended.
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
Cable type A
Characteristic impedance 135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance < 30 pF/m
Wire cross-section
Cable type Twisted pairs
Loop resistance ≤110 Ω/km
Signal damping Max. 9 dB over the entire length of the cable cross-section
Shield Copper braided shielding or braided shielding with foil shield. When grounding
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a cable used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to the "Media Planning and Installation Manual. EtherNet/IP" of ODVA Organization
PROFINET
Standard IEC 61156-6 specifies CAT 5 as the minimum category for a cable used for PROFINET. CAT 5e and CAT 6 are recommended.
For more information on planning and installing PROFINET networks, see: "PROFINET Cabling and Interconnection Technology", Guideline for PROFINET
Connecting cable between Safety Barrier Promass 100 and measuring device
Cable type Shielded twisted-pair cable with 2x2 wires. When grounding the cable shield,
observe the grounding concept of the plant.
Maximum cable resistance 2.5 Ω, one side
Comply with the maximum cable resistance specifications to ensure the operational reliability of the measuring device.
40 Endress+Hauser
Page 41
Proline Promass E 100
The maximum cable length for individual wire cross-sections is specified in the table below. Observe the maximum capacitance and inductance per unit length of the cable and connection values for hazardous areas .
Wire cross-section Maximum cable length
[mm2] [AWG] [m] [ft]
0.5 20 70 230
0.75 18 100 328
1.0 17 100 328
1.5 16 200 656
2.5 14 300 984

Performance characteristics

reference operating conditions

Maximum measured error

• Error limits based on ISO 11631
• Water with +15 to +45 °C (+59 to +113 °F) at2 to 6 bar (29 to 87 psi)
• Specifications as per calibration protocol
• Accuracy based on accredited calibration rigs that are traced to ISO 17025.
To obtain measured errors, use the Applicator sizing tool →  88
o.r. = of reading; 1 g/cm³ = 1 kg/l; T = medium temperature
Base accuracy
Design fundamentals →  44
Mass flow and volume flow (liquids)
• ±0.15 % o.r.
±0.10 % o.r. (order code for "Calibration flow", option A, B, C, for mass flow)
• ±0.25 % o.r.
Mass flow (gases)
±0.35 % o.r.
Density (liquids)
Under
reference operating conditions
[g/cm³] [g/cm³]
±0.0005 ±0.02
Standard density
calibration
1)
1) Valid over the entire temperature and density range
Temperature
±0.5 °C ± 0.005 · T °C (±0.9 °F ± 0.003 · (T – 32) °F)
Endress+Hauser 41
Page 42
Proline Promass E 100
Zero point stability
DN Zero point stability
[mm] [in] [kg/h] [lb/min]
8 ³⁄₈ 0.20 0.007
15 ½ 0.65 0.024
25 1 1.80 0.066
40 4.50 0.165
50 2 7.0 0.257
80 3 18.0 0.6615
Flow values
Flow values as turndown parameter depending on nominal diameter.
SI units
DN 1:1 1:10 1:20 1:50 1:100 1:500
[mm]
8 2 000 200 100 40 20 4
15 6 500 650 325 130 65 13
25 18 000 1 800 900 360 180 36
40 45 000 4 500 2 250 900 450 90
50 70 000 7 000 3 500 1 400 700 140
80 180 000 18 000 9 000 3 600 1 800 360
[kg/h] [kg/h] [kg/h] [kg/h] [kg/h] [kg/h]
US units
DN 1:1 1:10 1:20 1:50 1:100 1:500
[inch] [lb/min] [lb/min] [lb/min] [lb/min] [lb/min] [lb/min]
³⁄₈ 73.50 7.350 3.675 1.470 0.735 0.147
½ 238.9 23.89 11.95 4.778 2.389 0.478
1 661.5 66.15 33.08 13.23 6.615 1.323
1 654 165.4 82.70 33.08 16.54 3.308
2 2 573 257.3 128.7 51.46 25.73 5.146
3 6 615 661.5 330.8 132.3 66.15 13.23
Accuracy of outputs
The output accuracy must be factored into the measured error if analog outputs are used, but can be ignored for fieldbus outputs (e.g. Modbus RS485, EtherNet/IP).
The outputs have the following base accuracy specifications.
Current output
Accuracy Max. ±5 µA
Pulse/frequency output
o.r. = of reading
42 Endress+Hauser
Page 43
Proline Promass E 100
Accuracy Max. ±50 ppm o.r. (over the entire ambient temperature range)

Repeatability

Response time

Influence of ambient temperature

o.r. = of reading; 1 g/cm3 = 1 kg/l; T = medium temperature
Base repeatability
Design fundamentals →  44
Mass flow and volume flow (liquids)
±0.075 % o.r. ±0.05 % o.r. (calibration option, for mass flow)
Mass flow (gases)
±0.35 % o.r.
Density (liquids)
±0.00025 g/cm
3
Temperature
±0.25 °C ± 0.0025 · T °C (±0.45 °F ± 0.0015 · (T–32) °F)
The response time depends on the configuration (damping).
Current output
o.r. = of reading

Influence of medium temperature

Temperature coefficient Max. ±0.005 % o.r./°C
Pulse/frequency output
Temperature coefficient No additional effect. Included in accuracy.
Mass flow and volume flow
o.f.s. = of full scale value
When there is a difference between the temperature for zero point adjustment and the process temperature, the additional measured error of the sensor is typically ±0.0002 % o.f.s./°C (±0.0001 % o. f.s./°F).
The effect is reduced if zero point adjustment is performed at process temperature.
Density
When there is a difference between the density calibration temperature and the process temperature, the typical measured error of the sensor is ±0.0001 g/cm3 /°C (±0.00005 g/cm3 /°F). Field density calibration is possible.
Endress+Hauser 43
Page 44
3
[°C]
-40
0
-80
40 80 120 160 200 240 280 320
[°F]
-40
0
50
100 150
0
2
4
6
8
10
14
12
 20 Field density calibration, for example at +20 °C (+68 °F)
ZeroPoint BaseAccu
100
³
± BaseAccu
ZeroPoint BaseAccu
100
<
ZeroPoint
MeasValue
100
±
Temperature
±0.005 · T °C (± 0.005 · (T – 32) °F)
Proline Promass E 100
A0016609

Influence of medium pressure

Design fundamentals

The table below shows the effect on accuracy of mass flow due to a difference between calibration pressure and process pressure.
o.r. = of reading
It is possible to compensate for the effect by:
• Reading in the current pressure measured value via the current input.
• Specifying a fixed value for the pressure in the device parameters. Operating Instructions .
DN [% o.r./bar] [% o.r./psi]
[mm] [in]
8 ³⁄₈ no influence
15 ½ no influence
25 1 no influence
40 no influence
50 2 –0.009 –0.0006
80 3 –0.020 –0.0014
o.r. = of reading, o.f.s. = of full scale value
BaseAccu = base accuracy in % o.r., BaseRepeat = base repeatability in % o.r.
MeasValue = measured value; ZeroPoint = zero point stability
Calculation of the maximum measured error as a function of the flow rate
Flow rate Maximum measured error in % o.r.
A0021332
A0021333
44 Endress+Hauser
A0021339
A0021334
Page 45
Proline Promass E 100
½ ZeroPoint
BaseRepeat
100
³
½ ZeroPoint
BaseRepeat
100
<
ZeroPoint
MeasValue
100
½ ±
E [%]
Q [%]
0 5 10 15 20 25 30 35 40 45 50 60 6555
0
0.5
1.0
1.5
2.0
2.5
70 75 80 85 90 95 100
Calculation of the maximum repeatability as a function of the flow rate
Flow rate Maximum repeatability in % o.r.
A0021335
A0021336
Example for maximum measured error
E Maximum measured error in % o.r. (example) Q Flow rate in % of maximum full scale value

Installation

A0021340
A0021337
A0030289

Mounting location

No special measures such as supports etc. are necessary. External forces are absorbed by the construction of the device.
A0028772
To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe:
• Highest point of a pipeline.
• Directly upstream of a free pipe outlet in a down pipe.
Installation in down pipes
However, the following installation suggestion allows for installation in an open vertical pipeline. Pipe restrictions or the use of an orifice with a smaller cross-section than the nominal diameter prevent the sensor running empty while measurement is in progress.
Endress+Hauser 45
Page 46
1
2
3
4
5
 21 Installation in a down pipe (e.g. for batching applications)
1 Supply tank 2 Sensor 3 Orifice plate, pipe restriction 4 Valve 5 Batching tank
Proline Promass E 100
A0028773

Orientation

DN Ø orifice plate, pipe restriction
[mm] [in] [mm] [in]
8 ³⁄₈ 6 0.24
15 ½ 10 0.40
25 1 14 0.55
40 22 0.87
50 2 28 1.10
80 3 50 1.97
The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction (direction of medium flow through the piping).
Orientation Recommendation
A Vertical orientation
A0015591
B Horizontal orientation, transmitter at
top
C Horizontal orientation, transmitter at
bottom
D Horizontal orientation, transmitter at
side
→  22,  47
A0015589
→  22,  47
A0015590
A0015592
1)
Exceptions:
2)
Exceptions:
1) Applications with low process temperatures may decrease the ambient temperature. To maintain the minimum ambient temperature for the transmitter, this orientation is recommended.
2) Applications with high process temperatures may increase the ambient temperature. To maintain the maximum ambient temperature for the transmitter, this orientation is recommended.
46 Endress+Hauser
Page 47
Proline Promass E 100
1 2
RUPTURE DISK
i
1
DN 8 ( ")... ( ")!⁄# 50 2 DN ( ")80 3
If a sensor is installed horizontally with a curved measuring tube, match the position of the sensor to the fluid properties.
A0028774
 22 Orientation of sensor with curved measuring tube
1 Avoid this orientation for fluids with entrained solids: Risk of solids accumulating. 2 Avoid this orientation for outgassing fluids: Risk of gas accumulating.

Inlet and outlet runs

Special mounting instructions

No special precautions need to be taken for fittings which create turbulence, such as valves, elbows or T-pieces, as long as no cavitation occurs →  53.
Rupture disk
Information that is relevant to the process: →  53.
The position of the rupture disk is indicated on a sticker applied over it. If the rupture disk is triggered, the sticker is destroyed. The disk can therefore be visually monitored.
A0029956
1 Rupture disk label
Zero point adjustment
All measuring devices are calibrated in accordance with state-of-the-art technology. Calibration takes place under reference conditions→  41. Therefore, a zero point adjustment in the field is generally not required.
Experience shows that zero point adjustment is advisable only in special cases:
• To achieve maximum measuring accuracy even with low flow rates.
• Under extreme process or operating conditions (e.g. very high process temperatures or very high­viscosity fluids).
Endress+Hauser 47
Page 48
Mounting Safety Barrier
> 22.5
(> 0.89)
> 22.5
(> 0.89)
Promass 100
Proline Promass E 100
A0016894
 23 Minimum distance between additional Safety Barrier Promass 100 or other modules.Engineering unit mm
(in)

Ambient temperature range

Storage temperature

Climate class

Degree of protection

Vibration resistance

Shock resistance

Environment

Measuring device • –40 to +60 °C (–40 to +140 °F)
• Order code for "Test, certificate", option JM: –50 to +60 °C (–58 to +140 °F)
Safety Barrier Promass 100 –40 to +60 °C (–40 to +140 °F)
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
–40 to +80 °C (–40 to +176 °F), preferably at +20 °C (+68 °F)
DIN EN 60068-2-38 (test Z/AD)
Transmitter and sensor
• As standard: IP66/67, type 4X enclosure
• With the order code for "Sensor options", option CM: IP69 can also be ordered
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
Safety Barrier Promass 100
IP20
• Vibration, sinusoidal according to IEC 60068-2-6 – 2 to 8.4 Hz, 3.5 mm peak – 8.4 to 2 000 Hz, 1 g peak
• Vibration broad-band random, according to IEC 60068-2-64 – 10 to 200 Hz, 0.003 g2/Hz – 200 to 2 000 Hz, 0.001 g2/Hz – Total: 1.54 g rms
Shock, half-sine according to IEC 60068-2-27 6 ms 30 g

Impact resistance

Rough handling shocks according to IEC 60068-2-31
48 Endress+Hauser
Page 49
Proline Promass E 100
T
a
T
m
B
A

Interior cleaning

Electromagnetic compatibility (EMC)

Medium temperature range

• Cleaning in place (CIP)
• Sterilization in place (SIP)
Options
Oil- and grease-free version for wetted parts, without declaration Order code for "Service", option HA
• Depends on the communication protocol: – HART, PROFIBUS DP, EtherNet/IP:
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
– Modbus RS485:
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
– PROFINET: as per IEC/EN 61326
• Complies with emission limits for industry as per EN 55011 (Class A)
• Device version with PROFIBUS DP: Complies with emission limits for industry as per EN 50170 Volume 2, IEC 61784
The following applies for PROFIBUS DP: If baud rates > 1.5 MBaud, an EMC cable entry must be used and the cable shield must continue as far as the terminal wherever possible.
Details are provided in the Declaration of Conformity.

Process

–40 to +150 °C (–40 to +302 °F)
Dependency of ambient temperature on medium temperature
A0031121
 24 Exemplary representation, values in the table below.
TaAmbient temperature TmMedium temperature A Maximum permitted medium temperature Tm at T
require a reduced ambient temperature T
B Maximum permitted ambient temperature Ta for the maximum specified medium temperature Tm of the
sensor
a
= 60 °C (140 °F); higher medium temperatures T
a max
m
Values for devices used in the hazardous area: Separate Ex documentation (XA) for the device .

Density

0 to 5 000 kg/m3 (0 to 312 lb/cf)
Endress+Hauser 49
Page 50
Proline Promass E 100
PN100
PN63
PN40
-80
0 80 160
240
320 400
0
10
20
30
40
50
60
70
80
90
100
0
200
400
600
800
[°C]
[°F]
[bar][psi]
20015010050
0
-50
Class 600
Class 300
Class 150
-80
0 80 160
240
320 400
0
10
20
30
40
50
60
70
80
90
100
0
200
400
600
800
[°C]
[°F]
[bar][psi]
20015010050
0
-50

Pressure-temperature curves

The following pressure/temperature diagrams apply to all pressure-bearing parts of the device and not just the process connection. The diagrams show the maximum permissible medium pressure depending on the specific medium temperature.
Flange according to EN 1092-1 (DIN 2501)
A0029832-EN
 25 With flange material 1.4404 (F316/F316L)
Flange according to ASME B16.5
50 Endress+Hauser
 26 With flange material 1.4404 (F316/F316L)
A0029833-EN
Page 51
Proline Promass E 100
300 [°F]350250200150100500-50
[°C]200150100500-50
400
0
10
20
30
40
50
70
60
[bar][psi]
200
400
600
800
0
1000
63K
10K
40K
20K
DN8…40
≥ DN 50
-80
0 80 160
240
320 400
0
10
20
30
40
0
[°C]
[°F]
[bar][psi]
20015010050
0
-50
50
DN8…40
≥ DN 50
-80
0 80 160
240
320 400
0
10
20
30
40
0
[°C]
[°F]
[bar][psi]
20015010050
0
-50
50
Flange JIS B2220
A0029834-EN
 27 With flange material 1.4404 (F316/F316L)
Flange DIN 11864-2 Form A
A0029839-EN
 28 With flange material 1.4404 (316/316L)
Thread DIN 11851
Endress+Hauser 51
 29 With connection material 1.4404 (316/316L)
DIN 11851 allows for applications up to +140 °C (+284 °F) if suitable sealing materials are used. Please take this into account when selecting seals and counterparts, as these components can limit the pressure and temperature range.
A0029848-EN
Page 52
Thread DIN 11864-1 Form A
DN8…40
≥ DN 50
-80
0 80 160
240
320 400
0
10
20
30
40
0
[°C]
[°F]
[bar][psi]
20015010050
0
-50
50
-80
0 80 160
240
320 400
0
10
20
0
[°C]
[°F]
[bar][psi]
20015010050
0
-50
-80
0 80 160
240
320 400
0
10
20
0
[°C]
[°F]
[bar][psi]
20015010050
0
-50
300 [°F]350250200150100500-50
[°C]200150100500-50
400
70
80
90
[bar][psi]
100
 30 With connection material 1.4404 (316/316L)
Thread ISO 2853
Proline Promass E 100
A0029848-EN
 31 With connection material 1.4404 (316/316L)
Thread SMS 1145
 32 With connection material 1.4404 (316/316L)
VCO
A0029853-EN
A0032218-EN
52 Endress+Hauser
 33 With connection material 1.4404 (316/316L)
A0029863-EN
Page 53
Proline Promass E 100
-80
0 80 160
240
320 400
0
10
20
0
[°C]
[°F]
[bar][psi]
20015010050
0
-50
Tri-Clamp
A0032218-EN
The clamp connections are suitable up to a maximum pressure of 16 bar (232 psi). Please observe the operating limits of the clamp and seal used as they can be over 16 bar (232 psi). The clamp and seal are not included in the scope of supply.

Secondary containment

Rupture disk

Flow limit

The sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside.
The secondary containment does not have a pressure rating classification.
Reference value for the pressure loading capacity of the sensor housing: 16 bar (232 psi)
If the device is fitted with a rupture disk (order code for "Sensor option", option CA "Rupture disk"), the rupture disk trigger pressure is decisive for the maximum nominal pressure →  53.
If a measuring tube fails (e.g. due to process characteristics like corrosive or abrasive fluids), the fluid will be contained by the secondary containment.
To increase the level of safety, a device version with a rupture disk with a trigger pressure of 10 to 15 bar (145 to 217.5 psi)can be used (order code for "Sensor option", option CA "rupture disk").
Rupture disks cannot be combined with the separately available heating jacket .
Special mounting instructions: →  47
Select the nominal diameter by optimizing between the required flow range and permissible pressure loss.
For an overview of the full scale values for the measuring range, see the "Measuring range" section →  8
• The minimum recommended full scale value is approx. 1/20 of the maximum full scale value
• In most applications, 20 to 50 % of the maximum full scale value can be considered ideal
• A low full scale value must be selected for abrasive media (such as liquids with entrained solids): flow velocity < 1 m/s (< 3 ft/s).
• For gas measurement the following rules apply: – The flow velocity in the measuring tubes should not exceed half the sound velocity (0.5 Mach). – The maximum mass flow depends on the density of the gas: formula →  8
To calculate the flow limit, use the Applicator sizing tool →  88

Pressure loss

System pressure

To calculate the pressure loss, use the Applicator sizing tool →  88
It is important that cavitation does not occur, or that gases entrained in the liquids do not outgas. This is prevented by means of a sufficiently high system pressure.
For this reason, the following mounting locations are recommended:
• At the lowest point in a vertical pipe
• Downstream from pumps (no danger of vacuum)
Endress+Hauser 53
Page 54
Proline Promass E 100
A0028777

Thermal insulation

Heating

In the case of some fluids, it is important to keep the heat radiated from the sensor to the transmitter to a low level. A wide range of materials can be used for the required insulation.
NOTICE
Electronics overheating on account of thermal insulation!
Recommended orientation: horizontal orientation, transmitter housing pointing downwards.
Do not insulate the transmitter housing .
Maximum permissible temperature at the lower end of the transmitter housing: 80 °C (176 °F)
Thermal insulation with extended neck free: the insulation is omitted around the extended neck.
We recommend that you do not insulate the extended neck in order to ensure optimum dissipation of heat.
 34 Thermal insulation with extended neck free
Some fluids require suitable measures to avoid loss of heat at the sensor.
Heating options
• Electrical heating, e.g. with electric band heaters
• Via pipes carrying hot water or steam
• Via heating jackets Heating jackets for the sensors can be ordered as accessories from Endress+Hauser .→  87
A0034391

Vibrations

NOTICE
Danger of overheating when heating
Ensure that the temperature at the lower end of the transmitter housing does not exceed
80 °C (176 °F). Ensure that convection takes place on a sufficiently large scale at the transmitter neck.
Ensure that a sufficiently large area of the housing support remains exposed. The uncovered part
serves as a radiator and protects the electronics from overheating and excessive cooling.
The high oscillation frequency of the measuring tubes ensures that the correct operation of the measuring system is not influenced by plant vibrations.
54 Endress+Hauser
Page 55
Proline Promass E 100
A
B
C
G
D
L
E
F
K
M

Mechanical construction

Dimensions in SI units Compact version

Order code for "Housing", option A "Compact coated aluminum"
DN
[mm]A[mm]B[mm]C[mm]D[mm]
1)
E
[mm]
1)
F
[mm]G[mm]K[mm]L[mm]M[mm]
8 147.5 93.5 54 89.1 177.1 266.2 136 5.35
15 147.5 93.5 54 100.1 177.1 277.2 136 8.3
25 147.5 93.5 54 102.1 174.2 276.2 136 12
40 147.5 93.5 54 120.7 180.2 300.8 136 17.6
50 147.5 93.5 54 175.5 194.5 369.9 136 26
80 147.5 93.5 54 205.3 210 415.3 136 40.5
1) If using a display, order code for "Display; operation", option B: values +28 mm
2) Dependent on the respective process connection
A0033787
2)
2)
2)
2)
2)
2)
44.9
44.9
51
64.3
91.1
127
Endress+Hauser 55
Page 56
Order code for "Housing", option B "Compact hygienic, stainless"
A
B
C
G
D
L
E
F
K
M
Proline Promass E 100
A0033787
DN
[mm]A[mm]B[mm]C[mm]D[mm]
1)
E
[mm]
1)
F
[mm]G[mm]K[mm]L[mm]M[mm]
8 136.8 78 58.8 89.1 172.5 261.6 133.5 5.35
15 136.8 78 58.8 100.1 172.5 272.6 133.5 8.30
25 136.8 78 58.8 102.1 169.6 271.6 133.5 12.0
40 136.8 78 58.8 120.7 175.6 296.2 133.5 17.6
50 136.8 78 58.8 175.5 189.9 365.3 133.5 26.0
80 136.8 78 58.8 205.3 205.4 410.8 133.5 40.5
1) If using a display, order code for "Display; operation", option B: values +14 mm
2) Dependent on the respective process connection
2)
2)
2)
2)
2)
2)
44.9
44.9
51
64.3
91.1
127
56 Endress+Hauser
Page 57
Proline Promass E 100
A
B
C
G
D
L
E
F
K
M
Order code for "Housing", option C "Ultra-compact hygienic, stainless"
A0033787
DN
[mm]A[mm]B[mm]C[mm]D[mm]
1)
E
[mm]
1)
F
[mm]G[mm]K[mm]L[mm]M[mm]
8 123.6 67.7 55.9 89.1 172.3 261.4 111.4 5.35
15 123.6 67.7 55.9 100.1 172.3 272.4 111.4 8.30
25 123.6 67.7 55.9 102.1 169.4 271.4 111.4 12.0
40 123.6 67.7 55.9 120.7 175.4 296 111.4 17.6
50 123.6 67.7 55.9 175.5 189.6 365 111.4 26.0
80 123.6 67.7 55.9 205.3 205.2 410.5 111.4 40.5
1) If using a display, order code for "Display; operation", option B: values +14 mm
2) Dependent on the respective process connection
2)
2)
2)
2)
2)
2)
44.9
44.9
51
64.3
91.1
127
Endress+Hauser 57
Page 58
Flange connections
C
D
A
B
E
L
Fixed flange EN 1092-1, ASME B16.5, JIS B2220
Length tolerance for dimension L in mm: +1.5 / –2.0
Proline Promass E 100
A0015621
Flange according to EN 1092-1 (DIN 2501 / DIN 2512N), PN 40
1.4404 (F316/F316L): order code for "Process connection", option D2S
Flange with groove according to EN 1092-1 Form D (DIN 2512N), PN 40
1.4404 (F316/F316L): order code for "Process connection", option D6S
DN
[mm]
1)
8
15 95 65 4 × Ø14 16 17.3 279/510
25 115 85 4 × Ø14 18 28.5 329/600
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
[mm]
95 65 4 × Ø14 16 17.3 232/510
L
2)
2)
2)
40 150 110 4 × Ø18 18 43.1 445
50 165 125 4 × Ø18 20 54.5 556/715
80 200 160 8 × Ø18 24 82.5 611/915
2)
2)
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 3.2 to 12.5 µm
1) DN 8 with DN 15 flanges as standard
2) Installation length in accordance with NAMUR recommendation NE 132 optionally available (order code
for "Process connection", option D2N or D6N (with groove))
Flange according to EN 1092-1 (DIN 2501), PN 40 (with DN 25 flanges)
1.4404 (F316/F316L) Order code for "Process connection", option R2S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
L
[mm]
8 115 85 4 × Ø14 18 28.5 302
15 115 85 4 × Ø14 18 28.5 315
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 3.2 to 12.5 µm
58 Endress+Hauser
Page 59
Proline Promass E 100
Flange according to EN 1092-1 (DIN 2501 / DIN 2512N), PN 63
1.4404 (F316/F316L): order code for "Process connection", option D3S
Flange with groove according to EN 1092-1 Form D (DIN 2512N), PN 63
1.4404 (F316/F316L): order code for "Process connection", option D7S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
50 180 135 4 × Ø22 26 54.5 565
80 215 170 8 × Ø22 28 81.7 646
Surface roughness (flange): EN 1092-1 Form B2 (DIN 2526 Form E), Ra 0.8 to 3.2 µm
Flange according to EN 1092-1 (DIN 2501 / DIN 2512N), PN 100
1.4404 (F316/F316L) Order code for "Process connection", option D4S
Flange with groove according to EN 1092-1 Form D (DIN 2512N) available, PN 100
1.4404 (F316/F316L) Order code for "Process connection", option D8S
DN
[mm]
1)
8
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
105 75 4 × Ø14 20 17.3 261
15 105 75 4 × Ø14 20 17.3 295
25 140 100 4 × Ø18 24 28.5 360
40 170 125 4 × Ø22 26 42.5 486
50 195 145 4 × Ø26 28 53.9 581
80 230 180 8 × Ø26 32 80.9 656
Surface roughness (flange): EN 1092-1 Form B2 (DIN 2526 Form E), Ra 0.8 to 3.2 µm
L
[mm]
L
[mm]
1) DN 8 with DN 15 flanges as standard
Flange according to ASME B16.5, Class 150
1.4404 (F316/F316L) Order code for "Process connection", option AAS
DN
[mm]
1)
8
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
90 60.3 4 × Ø15.7 11.2 15.7 232
15 90 60.3 4 × Ø15.7 11.2 15.7 279
25 110 79.4 4 × Ø15.7 14.2 26.7 329
40 125 98.4 4 × Ø15.7 17.5 40.9 445
50 150 120.7 4 × Ø19.1 19.1 52.6 556
80 190 152.4 4 × Ø19.1 23.9 78.0 611
Surface roughness (flange): Ra 3.2 to 6.3 µm
1) DN 8 with DN 15 flanges as standard
Flange according to ASME B16.5, Class 300
1.4404 (F316/F316L) Order code for "Process connection", option ABS
DN
[mm]
1)
8
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
95 66.7 4 × Ø15.7 14.2 15.7 232
15 95 66.7 4 × Ø15.7 14.2 15.7 279
L
[mm]
L
[mm]
Endress+Hauser 59
Page 60
Proline Promass E 100
Flange according to ASME B16.5, Class 300
1.4404 (F316/F316L) Order code for "Process connection", option ABS
DN
[mm]
25 125 88.9 4 × Ø19.0 17.5 26.7 329
40 155 114.3 4 × Ø22.3 20.6 40.9 445
50 165 127 8 × Ø19.0 22.3 52.6 556
80 210 168.3 8 × Ø22.3 28.4 78.0 611
Surface roughness (flange): Ra 3.2 to 6.3 µm
1) DN 8 with DN 15 flanges as standard
Flange according to ASME B16.5, Class 600
1.4404 (F316/F316L) Order code for "Process connection", option ACS
DN
[mm]
1)
8
15 95 66.7 4 × Ø15.7 20.6 13.9 295
25 125 88.9 4 × Ø19.1 23.9 24.3 380
40 155 114.3 4 × Ø22.4 28.7 38.1 496
50 165 127 8 × Ø19.1 31.8 49.2 583
80 210 168.3 8 × Ø22.4 38.2 73.7 671
Surface roughness (flange): Ra 3.2 to 6.3 µm
A
[mm]
A
[mm]
B
[mm]
B
[mm]
C
[mm]
C
[mm]
D
[mm]
D
[mm]
E
[mm]
E
[mm]
95 66.7 4 × Ø15.7 20.6 13.9 261
L
[mm]
L
[mm]
1) DN 8 with DN 15 flanges as standard
Flange JIS B2220, 10K
1.4404 (F316/F316L) Order code for "Process connection", option NDS
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
50 155 120 4 × Ø19 16 50 556
80 185 150 8 × Ø19 18 80 603
Surface roughness (flange): Ra 3.2 to 6.3 µm
Flange JIS B2220, 20K
1.4404 (F316/F316L) Order code for "Process connection", option NES
DN
[mm]
1)
8
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
95 70 4 × Ø15 14 15 232
15 95 70 4 × Ø15 14 15 279
25 125 90 4 × Ø19 16 25 329
40 140 105 4 × Ø19 18 40 445
50 155 120 8 × Ø19 18 50 556
L
[mm]
L
[mm]
60 Endress+Hauser
Page 61
Proline Promass E 100
Flange JIS B2220, 20K
1.4404 (F316/F316L) Order code for "Process connection", option NES
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
80 200 160 8 × Ø23 22 80 603
Surface roughness (flange): Ra 3.2 to 6.3 µm
1) DN 8 with DN 15 flanges as standard
Flange JIS B2220, 40K
1.4404 (F316/F316L) Order code for "Process connection", option NGS
DN
[mm]
1)
8
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
115 80 4 × Ø19 20 15 261
15 115 80 4 × Ø19 20 15 300
25 130 95 4 × Ø19 22 25 375
40 160 120 4 × Ø23 24 38 496
50 165 130 8 × Ø19 26 50 601
80 210 170 8 × Ø23 32 75 661
Surface roughness (flange): Ra 3.2 to 6.3 µm
L
[mm]
L
[mm]
1) DN 8 with DN 15 flanges as standard
Flange JIS B2220, 63K
1.4404 (F316/F316L) Order code for "Process connection", option NHS
DN
[mm]
1)
8
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
120 85 4 × Ø19 23 12 282
15 120 85 4 × Ø19 23 12 315
25 140 100 4 × Ø23 27 22 383
40 175 130 4 × Ø25 32 35 515
50 185 145 4 × Ø23 34 48 616
80 230 185 4 × Ø25 40 73 686
Surface roughness (flange): Ra 3.2 to 6.3 µm
1) DN 8 with DN 15 flanges as standard
L
[mm]
Endress+Hauser 61
Page 62
Proline Promass E 100
C
D
A
B
E
X X
L
Fixed flange DIN 11864-2
 35 Detail X: Asymmetrical process connection; the part shown in blue is provided by the supplier.
Length tolerance for dimension L in mm: +1.5 / –2.0
A0015627
Flange DIN11864-2 Form A, for pipe according to DIN11866 series A, flange with notch
1.4404 (316/316L) Order code for "Process connection", option KCS
DN
[mm]
8 54 37 4 × Ø9 10 10 249
15 59 42 4 × Ø9 10 16 293
25 70 53 4 × Ø9 10 26 344
40 82 65 4 × Ø9 10 38 456
50 94 77 4 × Ø9 10 50 562
80 133 112 8 × Ø11 12 81 671
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 0.8 µm: Order code for "Measuring tube material", option SB Ra ≤ 0.4 µm: Order code for "Measuring tube material", option SC
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
L
[mm]
62 Endress+Hauser
Page 63
Proline Promass E 100
L
A
B
Clamp connections
Tri-Clamp
Length tolerance for dimension L in mm: +1.5 / –2.0
Tri-Clamp (½")
1.4404 (316/316L) Order code for "Process connection", option FDW
DN
[mm]
8 ½ 25.0 9.5 229
15 ½ 25.0 9.5 273
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 0.8 µm: Order code for "Measuring tube material", option SB Ra ≤ 0.4 µm: Order code for "Measuring tube material", option SC
Clamp
[in]
A
[mm]
B
[mm]
A0015625
L
[mm]
Tri-Clamp ( ≥ 1")
1.4404 (316/316L) Order code for "Process connection", option FTS
DN
[mm]
8 1 50.4 22.1 229
15 1 50.4 22.1 273
25 1 50.4 22.1 324
40 50.4 34.8 456
50 2 63.9 47.5 562
80 3 90.9 72.9 671
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 0.8 µm: Order code for "Measuring tube material", option SB Ra ≤ 0.4 µm: Order code for "Measuring tube material", option SC
Clamp
[in]
A
[mm]
B
[mm]
L
[mm]
Endress+Hauser 63
Page 64
Threaded couplings
L
A
B
Thread DIN 11851, DIN11864-1, SMS 1145
Length tolerance for dimension L in mm: +1.5 / –2.0
Thread DIN 11851, for pipe according to DIN11866, series A
1.4404 (316/316L) Order code for "Process connection", option FMW
DN
[mm]
8 Rd 34 × ¹⁄₈ 16 229
15 Rd 34 × ¹⁄₈ 16 273
25 Rd 52 × ¹⁄₆ 26 324
40 Rd 65 × ¹⁄₆ 38 456
50 Rd 78 × ¹⁄₆ 50 562
80 Rd 110 × ¹⁄₄ 81 671
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 0.8 µm: Order code for "Measuring tube material", option SB Ra ≤ 0.4 µm: Order code for "Measuring tube material", option SC
A
[in]
B
[mm]
Proline Promass E 100
A0015628
L
[mm]
Thread DIN11864-1 Form A, for pipe according to DIN11866, series A
1.4404 (316/316L) Order code for "Process connection", option FLW
DN
[mm]
8 Rd 28 × ¹⁄₈ 10 229
15 Rd 34 × ¹⁄₈ 16 273
25 Rd 52 × ¹⁄₆ 26 324
40 Rd 65 × ¹⁄₆ 38 456
50 Rd 78 × ¹⁄₆ 50 562
80 Rd 110 × ¹⁄₄ 81 671
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 0.8 µm: Order code for "Measuring tube material", option SB Ra ≤ 0.4 µm: Order code for "Measuring tube material", option SC
A
[in]
B
[mm]
L
[mm]
64 Endress+Hauser
Page 65
Proline Promass E 100
Thread SMS 1145
1.4404 (316/316L) Order code for "Process connection", option SCS
DN
[mm]
8 Rd 40 × ¹⁄₆ 22.5 229
15 Rd 40 × ¹⁄₆ 22.5 273
25 Rd 40 × ¹⁄₆ 22.5 324
40 Rd 60 × ¹⁄₆ 35.5 456
50 Rd 70 × ¹⁄₆ 48.5 562
80 Rd 98 × ¹⁄₆ 72.9 671
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 0.8 µm: Order code for "Measuring tube material", option SB Ra ≤ 0.4 µm: Order code for "Measuring tube material", option SC
A
[in]
B
[mm]
L
[mm]
Endress+Hauser 65
Page 66
Thread ISO 2853
L
A
B
Length tolerance for dimension L in mm: +1.5 / –2.0
Thread ISO 2853, for pipe according to ISO 2037
1.4404 (316/316L) Order code for "Process connection", option JSF
DN
[mm]
8 37.13 22.6 229
15 37.13 22.6 273
25 37.13 22.6 324
40 50.68 35.6 456
50 64.16 48.6 562
80 91.19 72.9 671
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 0.8 µm: Order code for "Measuring tube material", option SB Ra ≤ 0.4 µm: Order code for "Measuring tube material", option SC
1)
A
[mm]
B
[mm]
Proline Promass E 100
A0015623
L
[mm]
1) Max. thread diameter as per ISO 2853 annex A
66 Endress+Hauser
Page 67
Proline Promass E 100
L
A
B
B
D
A
C
VCO
Length tolerance for dimension L in mm: +1.5 / –2.0
8-VCO-4 (½")
1.4404 (316/316L) Order code for "Process connection", option CVS
DN
[mm]
8 AF 1 10.2 252
A
[in]
B
[mm]
A0015624
L
[mm]
12-VCO-4 (¾")
1.4404 (316/316L) Order code for "Process connection", option CWS
DN
[mm]
15 AF 1½ 15.7 305
A
[in]
Safety Barrier Promass 100
Top-hat rail EN 60715:
• TH 35 x 7.5
• TH 35 x 15
B
[mm]
L
[mm]
A0016777
A B C D
[mm] [mm] [mm] [mm]
108 114.5 99 22.5
Endress+Hauser 67
Page 68

Dimensions in US units Compact version

A
B
C
G
D
L
E
F
K
M
Order code for "Housing", option A "Compact coated aluminum"
Proline Promass E 100
A0033787
DN
[in]A[in]
B
[in]
C
[in]
D
[in]
E
[in]
1)
F
[in]
1)
G
[in]
³⁄₈ 5.81 3.68 2.13 3.66 7.05 10.71 5.35 0.21
½ 5.81 3.68 2.13 4.13 7.13 11.26 5.35 0.33
1 5.81 3.68 2.13 4.17 7.32 11.5 5.35 0.47
5.81 3.68 2.13 4.76 7.56 12.32 5.35 0.69
2 5.81 3.68 2.13 6.67 8.19 14.86 5.35 1.02
3 5.81 3.68 2.13 8.07 8.41 16.48 5.35 1.59
1) If using a display, order code for "Display; operation", option B: values +1.1 in
2) Dependent on the respective process connection
K
[in]
L
[in]
2)
2)
2)
2)
2)
2)
M
[in]
68 Endress+Hauser
Page 69
Proline Promass E 100
A
B
C
G
D
L
E
F
K
M
Order code for "Housing", option B "Compact hygienic, stainless"
A0033787
DN
[in]
A
[in]
B
[in]
C
[in]
D
[in]
1)
E
[in]
F
[in]
1)
G
[in]
³⁄₈ 5.39 3.07 2.31 3.66 6.85 10.51 5.26 0.21
½ 5.39 3.07 2.31 4.13 6.93 11.06 5.26 0.33
1 5.39 3.07 2.31 4.17 7.13 11.3 5.26 0.47
5.39 3.07 2.31 4.76 7.36 12.13 5.26 0.69
2 5.39 3.07 2.31 6.67 7.99 14.67 5.26 1.02
3 5.39 3.07 2.31 8.07 8.21 16.28 5.26 1.59
1) If using a display, order code for "Display; operation", option B: values +0.55 in
2) Dependent on the respective process connection
K
[in]
L
[in]
2)
2)
2)
2)
2)
2)
M
[in]
Endress+Hauser 69
Page 70
Order code for "Housing", option C "Ultra-compact hygienic, stainless"
A
B
C
G
D
L
E
F
K
M
Proline Promass E 100
A0033787
DN
[in]A[in]
B
[in]
C
[in]
D
[in]
E
[in]
1)
F
[in]
1)
G
[in]
³⁄₈ 4.87 2.67 2.2 3.66 6.85 10.51 4.39 0.21
½ 4.87 2.67 2.2 4.13 6.93 11.06 4.39 0.33
1 4.87 2.67 2.2 4.17 7.13 11.3 4.39 0.47
4.87 2.67 2.2 4.76 7.36 12.13 4.39 0.69
2 4.87 2.67 2.2 6.67 7.99 14.67 4.39 1.02
3 4.87 2.67 2.2 8.07 8.21 16.28 4.39 1.59
1) If using a display, order code for "Display; operation", option B: values +0.55 in
2) Dependent on the respective process connection
K
[in]
L
[in]
2)
2)
2)
2)
2)
2)
M
[in]
70 Endress+Hauser
Page 71
Proline Promass E 100
C
D
A
B
E
L
Flange connections
Fixed flange ASME B16.5
A0015621
Length tolerance for dimension L in inch: +0.06 / –0.08
Flange according to ASME B16.5, Cl 150
1.4404 (F316/F316L) Order code for "Process connection", option AAS
DN
[in]
1)
³⁄₈
½ 3.54 2.37 4 × Ø0.62 0.44 0.62 10.98
1 4.33 3.13 4 × Ø0.62 0.56 1.05 12.95
4.92 3.87 4 × Ø0.62 0.69 1.61 17.52
2 5.91 4.75 4 × Ø0.75 0.75 2.07 21.89
3 7.48 6.00 4 × Ø0.75 0.94 3.07 24.06
Surface roughness (flange): Ra 32 to 248 µin
1) DN ³⁄₈" with DN ½" flanges as standard
Flange according to ASME B16.5, Class 300
1.4404 (F316/F316L) Order code for "Process connection", option ABS
DN
[in]
1)
³⁄₈
½ 3.74 2.63 4 × Ø0.62 0.56 0.62 10.98
1 4.92 3.50 4 × Ø0.75 0.69 1.05 12.95
6.10 4.50 4 × Ø0.88 0.81 1.61 17.52
2 6.50 5.00 8 × Ø0.75 0.88 2.07 21.89
3 8.27 6.63 8 × Ø0.88 1.12 3.07 24.06
Surface roughness (flange): Ra 32 to 248 µin
A
[in]
3.54 2.37 4 × Ø0.62 0.44 0.62 9.13
A
[in]
3.74 2.63 4 × Ø0.62 0.56 0.62 9.13
B
[in]
B
[in]
C
[in]
C
[in]
D
[in]
D
[in]
E
[in]
E
[in]
L
[in]
L
[in]
Endress+Hauser 71
1) DN ³⁄₈" with DN ½" flanges as standard
Page 72
Proline Promass E 100
Flange according to ASME B16.5, Class 600
1.4404 (F316/F316L) Order code for "Process connection", option ACS
DN
[in]
1)
³⁄₈
½ 3.74 2.63 4 × Ø0.62 0.81 0.55 11.61
1 4.92 3.50 4 × Ø0.75 0.94 0.96 14.96
6.10 4.50 4 × Ø0.88 1.13 1.50 19.53
2 6.50 5.00 8 × Ø0.75 1.25 1.94 22.95
3 8.27 6.63 8 × Ø0.88 1.50 2.9 26.42
Surface roughness (flange): Ra 32 to 248 µin
1) DN ³⁄₈" with DN ½" flanges as standard
A
[in]
3.74 2.63 4 × Ø0.62 0.81 0.55 10.28
B
[in]
C
[in]
D
[in]
E
[in]
L
[in]
72 Endress+Hauser
Page 73
Proline Promass E 100
L
A
B
Clamp connections
Tri-Clamp
Length tolerance for dimension L in inch: +0.06 / –0.08
Tri-Clamp (½")
1.4404 (316/316L) Order code for "Process connection", option FDW
DN
[in]
³⁄₈ ½ 0.98 0.37 9.02
½ ½ 0.98 0.37 10.75
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 32 µin: Order code for "Measuring tube material", option SB Ra ≤ 16 µin: Order code for "Measuring tube material", option SC
Clamp
[in]
A
[in]
B
[in]
A0015625
L
[in]
Tri-Clamp ( ≥ 1")
1.4404 (316/316L) Order code for "Process connection", option FTS
DN
[in]
³⁄₈ 1 1.98 0.87 9.02
½ 1 1.98 0.87 10.75
1 1 1.98 0.87 12.76
1.98 1.37 17.95
2 2 2.52 1.87 22.13
3 3 3.58 2.87 26.42
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 32 µin: Order code for "Measuring tube material", option SB Ra ≤ 16 µin: Order code for "Measuring tube material", option SC
Clamp
[in]
A
[in]
B
[in]
L
[in]
Endress+Hauser 73
Page 74
Threaded couplings
L
A
B
Thread SMS 1145
Length tolerance for dimension L in inch: +0.06 / –0.08
Thread SMS 1145
1.4404 (316/316L) Order code for "Process connection", option SCS
DN
[in]
³⁄₈ Rd 40 × ¹⁄₆ 0.89 9.02
¹⁄₂ Rd 40 × ¹⁄₆ 0.89 10.75
1 Rd 40 × ¹⁄₆ 0.89 12.76
Rd 60 × ¹⁄₆ 1.40 17.95
2 Rd 70 × ¹⁄₆ 1.91 22.13
3 Rd 98 × ¹⁄₆ 2.87 26.42
3-A version available: order code for "Additional approval", option LP in conjunction with Ra ≤ 32 µin: Order code for "Measuring tube material", option SB Ra ≤ 16 µin: Order code for "Measuring tube material", option SC
A
[in]
B
[in]
Proline Promass E 100
A0015628
L
[in]
74 Endress+Hauser
Page 75
Proline Promass E 100
L
A
B
B
D
A
C
VCO
Length tolerance for dimension L in inch: +0.06 / –0.08
8-VCO-4 (½")
1.4404 (316/316L) Order code for "Process connection", option CVS
DN
[in]
³⁄₈ AF 1 0.40 9.92
A
[in]
B
[in]
A0015624
L
[in]
12-VCO-4 (¾")
1.4404 (316/316L) Order code for "Process connection", option CWS
DN
[in]
¹⁄₂ AF 1½ 0.62 12.01
A
[in]
Safety Barrier Promass 100
Top-hat rail EN 60715:
• TH 35 x 7.5
• TH 35 x 15
B
[in]
L
[in]
A0016777
A B C D
[in] [in] [in] [in]
4.25 4.51 3.9 0.89
Endress+Hauser 75
Page 76
Proline Promass E 100

Weight

All values (weight exclusive of packaging material) refer to devices with EN/DIN PN 40 flanges. Weight specifications including transmitter: order code for "Housing", option A "Compact, aluminum coated".
Different values due to different transmitter versions:
Weight in SI units
DN
[mm]
8 4.5
15 4.8
25 6.4
40 10.4
50 15.5
80 29
Weight [kg]
Weight in US units
DN
[in]
3/8 10
½ 11
1 14
1 ½ 23
2 34
3 64
Weight [lbs]
Safety Barrier Promass 100
49 g (1.73 ounce)

Materials Transmitter housing

• Order code for "Housing", option A "Compact, aluminum coated":
Aluminum, AlSi10Mg, coated
• Order code for "Housing", option B "Compact, hygienic, stainless":
Hygienic version, stainless steel 1.4301 (304)
• Order code for "Housing", option C "Ultra-compact, hygienic, stainless":
Hygienic version, stainless steel 1.4301 (304)
• Window material for optional local display (→  79):
– For order code for "Housing", option A: glass – For order code for "Housing", option B and C: plastic
76 Endress+Hauser
Page 77
Proline Promass E 100
1
2
3
Cable entries/cable glands
A0020640
 36 Possible cable entries/cable glands
1 Female thread M20 × 1.5 2 Cable gland M20 × 1.5 3 Adapter for cable entry with internal thread G ½" or NPT ½"
Order code for "Housing", option A "Compact, coated aluminum"
The various cable entries are suitable for hazardous and non-hazardous areas.
Cable entry/cable gland Material
Cable gland M20 × 1.5 Nickel-plated brass
Adapter for cable entry with internal thread G ½"
Adapter for cable entry with internal thread NPT ½"
Order code for "Housing", option B "Compact, hygienic, stainless"
The various cable entries are suitable for hazardous and non-hazardous areas.
Cable entry/cable gland Material
Cable gland M20 × 1.5 Stainless steel, 1.4404 (316L)
Adapter for cable entry with internal thread G ½"
Adapter for cable entry with internal thread NPT ½"
Device plug
Electrical connection Material
Plug M12x1 • Socket: Stainless steel, 1.4404 (316L)
• Contact housing: Polyamide
• Contacts: Gold-plated brass
Sensor housing
• Acid and alkali-resistant outer surface
• Stainless steel 1.4301 (304)
Measuring tubes
Stainless steel, 1.4539 (904L); manifold: stainless steel, 1.4404 (316L)
Endress+Hauser 77
Page 78
Proline Promass E 100

Process connections

• Flanges according to EN 1092-1 (DIN2501) / according to ASME B 16.5 / as per JIS B2220:
Stainless steel, 1.4404 (F316/F316L)
• All other process connections:
Stainless steel, 1.4404 (316/316L)
List of all available process connections →  78
Seals
Welded process connections without internal seals
Accessories
Protective cover
Stainless steel, 1.4404 (316L)
Safety Barrier Promass 100
Housing: Polyamide
Process connections

Surface roughness

• Fixed flange connections:
– EN 1092-1 (DIN 2501) flange – EN 1092-1 (DIN 2512N) flange – Namur lengths in accordance with NE 132 – ASME B16.5 flange – JIS B2220 flange – DIN 11864-2 Form A flange, DIN 11866 series A, flange with notch
• Clamp connections
Tri-Clamp (OD tubes), DIN 11866 series C
• Thread:
– DIN 11851 thread, DIN 11866 series A – SMS 1145 thread – ISO 2853 thread, ISO 2037 – DIN 11864-1 Form A thread, DIN 11866 series A
• VCO connections
– 8-VCO-4 – 12-VCO-4
For information on the different materials used in the process connections →  76
All data relate to parts in contact with fluid. The following surface roughness quality can be ordered.
• Not polished
• Ra
= 0.8 µm (32 µin)
max
• Ra
= 0.4 µm (16 µin)
max

Operability

Operating concept

78 Endress+Hauser
Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Quick and safe commissioning
• Individual menus for applications
• Menu guidance with brief explanations of the individual parameter functions
Page 79
Proline Promass E 100
1 2 3 5
7
4 6
Reliable operation
• Operation in the following languages: – Via "FieldCare", "DeviceCare" operating tool:
English, German, French, Spanish, Italian, Chinese, Japanese
– Via integrated Web browser(only available for device versions with HART, PROFIBUS DP,
PROFINET and EtherNet/IP): English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese, Bahasa (Indonesian), Vietnamese, Czech, Swedish, Korean
• Uniform operating philosophy applied to operating tools and Web browser
• If replacing the electronic module, transfer the device configuration via the plug-in memory (HistoROM DAT) which contains the process and measuring device data and the event logbook. No need to reconfigure. For devices with Modbus RS485, the data recovery function is implemented without the plug-in memory (HistoROM DAT).
Efficient diagnostics increase measurement availability
• Troubleshooting measures can be called up via the operating tools and web browser
• Diverse simulation options
• Status indicated by several light emitting diodes (LEDs) on the electronic module in the housing compartment

Local display

A local display is only available for device versions with the following communication protocols: HART, PROFIBUS-DP, PROFINET, EtherNet/IP
The local display is only available with the following device order code: Order code for "Display; operation", option B: 4-line; illuminated, via communication
Display element
• 4-line liquid crystal display with 16 characters per line.
• White background lighting; switches to red in event of device errors.
• Format for displaying measured variables and status variables can be individually configured.
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F). The readability of the display may be impaired at temperatures outside the temperature range.

Remote operation Via HART protocol

This communication interface is available in device versions with a HART output.
 37 Options for remote operation via HART protocol
1 Control system (e.g. PLC) 2 Field Communicator 475 3 Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM) 4 Commubox FXA195 (USB) 5 Field Xpert SFX350 or SFX370 6 VIATOR Bluetooth modem with connecting cable 7 Transmitter
Via PROFIBUS DP network
This communication interface is available in device versions with PROFIBUS DP.
Endress+Hauser 79
A0016948
Page 80
1 2
3
444
 38 Options for remote operation via PROFIBUS DP network
4
21 3
5 5 5
1 Automation system 2 Computer with PROFIBUS network card 3 PROFIBUS DP network 4 Measuring device
Proline Promass E 100
A0020903
Via EtherNet/IP network
This communication interface is available in device versions with EtherNet/IP.
Star topology
 39 Options for remote operation via EtherNet/IP network: star topology
1 Automation system, e.g. "RSLogix" (Rockwell Automation) 2 Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
3 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP" 4 Ethernet switch 5 Measuring device
A0032078
Via PROFINET network
This communication interface is available in device versions with PROFINET.
80 Endress+Hauser
Page 81
Proline Promass E 100
31 2
4 4 4
1
2
3
Star topology
A0026545
 40 Options for remote operation via PROFINET network: star topology
1 Automation system, e.g. Simatic S7 (Siemens) 2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, SIMATIC PDM) with COM DTM "CDI Communication
TCP/IP" 3 Switch, e.g. Scalance X204 (Siemens) 4 Measuring device

Service interface Via service interface (CDI-RJ45)

This communication interface is present in the following device version:
• Order code for "Output", option B: 4-20 mA HART, pulse/frequency/switch output
• Order code for "Output", option L: PROFIBUS DP
• Order code for "Output", option N: EtherNet/IP
• Order code for "Output", option R: PROFINET
HART
 41 Connection for the order code for "Output", option B: 4-20 mA HART, pulse/frequency/switch output
1 Service interface (CDI -RJ45) of the measuring device with access to the integrated Web server 2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP" 3 Standard Ethernet connecting cable with RJ45 plug
A0016926
Endress+Hauser 81
Page 82
Proline Promass E 100
1
2
3
1
2
3
PROFIBUS DP
A0021270
 42 Connection for order code for "Output", option L: PROFIBUS DP
1 Service interface (CDI -RJ45) of the measuring device with access to the integrated Web server 2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"
3 Standard Ethernet connecting cable with RJ45 plug
EtherNet/IP
A0016940
 43 Connection for order code for "Output", option N: EtherNet/IP
1 Service interface (CDI -RJ45) and EtherNet/IP interface of the measuring device with access to the integrated
Web server
2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"
3 Standard Ethernet connecting cable with RJ45 plug
82 Endress+Hauser
Page 83
Proline Promass E 100
1
2
3
1
2
PROFINET
A0016940
 44 Connection for order code for "Output", option R: PROFINET
1 Service interface (CDI -RJ45) and PROFINET interface of the measuring device with access to the integrated
Web server 2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP" 3 Standard Ethernet connecting cable with RJ45 plug
Via service interface (CDI)
This communication interface is present in the following device version: Order code for "Output", option M: Modbus RS485
Modbus RS485
1 Service interface (CDI) of measuring device 2 Commubox FXA291 3 Computer with "FieldCare" operating tool with COM DTM "CDI Communication FXA291"
A0030216

Certificates and approvals

CE mark

C-Tick symbol

Endress+Hauser 83
The measuring system is in conformity with the statutory requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the "Australian Communications and Media Authority (ACMA)".
Page 84
Proline Promass E 100

Ex approval

The measuring device is certified for use in hazardous areas and the relevant safety instructions are provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on the nameplate.
The separate Ex documentation (XA) containing all the relevant explosion protection data is available from your Endress+Hauser sales center.
ATEX/IECEx
Currently, the following versions for use in hazardous areas are available:
Ex ia
Category (ATEX) Type of protection
II2G Ex ia IIC T6…T1 Gb or Ex ia IIB T6…T1 Gb
II1/2G, II2D Ex ia IIC T6…T1 Ga/Gb or Ex ia IIB T6…T1 Ga/Gb
Ex tb IIIC Txx °C Db
II2G, II2D Ex ia IIC T6…T1 Gb or Ex ia IIB T6…T1 Gb
Ex tb IIIC Txx °C Db
Ex nA
Category (ATEX) Type of protection
II3G Ex nA IIC T6…T1 Gc or Ex nA IIC T5-T1 Gc
CSA
C
US
Currently, the following versions for use in hazardous areas are available:
IS (Ex i)
• Class I Division 1 Groups ABCD
• Class II Division 1 Groups EFG and Class III
NI (Ex nA)
Class I Division 2 Groups ABCD

Sanitary compatibility

• 3-A approval Only devices with the order code for "Additional approval", option LP "3A" have 3-A approval.
• EHEDG-tested Only devices with the order code for "Additional approval", option LT "EHEDG" have been tested and meet the requirements of the EHEDG. To meet the requirements for EHEDG certification, the device must be used with process connections in accordance with the EHEDG position paper entitled "Easy Cleanable Pipe Couplings and Process Connections" (www.ehedg.org).

HART certification HART interface

The measuring device is certified and registered by the FieldComm Group. The measuring system meets all the requirements of the following specifications:
• Certified according to HART 7
• The device can also be operated with certified devices of other manufacturers (interoperability)

Certification PROFIBUS PROFIBUS interface

The measuring device is certified and registered by the PNO (PROFIBUS User Organization Organization). The measuring system meets all the requirements of the following specifications:
• Certified in accordance with PROFIBUS PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)
84 Endress+Hauser
Page 85
Proline Promass E 100

Certification PROFINET PROFINET interface

The measuring device is certified and registered by the PNO (PROFIBUS User Organization Organization). The measuring system meets all the requirements of the following specifications:
• Certified according to: – Test specification for PROFINET devices – PROFINET Security Level 1 – Netload Class
• The device can also be operated with certified devices of other manufacturers (interoperability)

EtherNet/IP certification

Modbus RS485 certification

Pressure Equipment Directive

The measuring device is certified and registered by the ODVA (Open Device Vendor Association). The measuring system meets all the requirements of the following specifications:
• Certified in accordance with the ODVA Conformance Test
• EtherNet/IP Performance Test
• EtherNet/IP PlugFest compliance
• The device can also be operated with certified devices of other manufacturers (interoperability)
The measuring device meets all the requirements of the MODBUS/TCP conformity test and has the "MODBUS/TCP Conformance Test Policy, Version 2.0". The measuring device has successfully passed all the test procedures carried out.
The devices can be ordered with or without a PED approval. If a device with a PED approval is required, this must be explicitly stated in the order. For devices with nominal diameters less than or equal to DN 25 (1"), this is neither possible nor necessary.
• With the identification PED/G1/x (x = category) on the sensor nameplate, Endress+Hauser confirms conformity with the "Essential Safety Requirements" specified in Appendix I of the Pressure Equipment Directive 2014/68/EC.
• Devices bearing this marking (PED) are suitable for the following types of medium: – Media in Group 1 and 2 with a vapor pressure greater than, or smaller and equal
to0.5 bar (7.3 psi)
– Unstable gases
• Devices not bearing this marking (PED) are designed and manufactured according to good engineering practice. They meet the requirements of Art. 4, Par. 3 of the Pressure Equipment Directive 2014/68/EU. The range of application is indicated in tables 6 to 9 in Annex II of the Pressure Equipment Directive 2014/68/EC.

Other standards and guidelines

• EN 60529 Degrees of protection provided by enclosures (IP code)
• IEC/EN 60068-2-6 Environmental influences: Test procedure - Test Fc: vibrate (sinusoidal).
• IEC/EN 60068-2-31 Environmental influences: Test procedure - Test Ec: shocks due to rough handling, primarily for devices.
• EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use ­general requirements
• IEC/EN 61326 Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC requirements).
• NAMUR NE 21 Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
• NAMUR NE 32 Data retention in the event of a power failure in field and control instruments with microprocessors
• NAMUR NE 43 Standardization of the signal level for the breakdown information of digital transmitters with analog output signal.
• NAMUR NE 53 Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 80 The application of the pressure equipment directive to process control devices
• NAMUR NE 105 Specifications for integrating fieldbus devices in engineering tools for field devices
Endress+Hauser 85
Page 86
Proline Promass E 100
• NAMUR NE 107 Self-monitoring and diagnosis of field devices
• NAMUR NE 131 Requirements for field devices for standard applications
• NAMUR NE 132 Coriolis mass meter

Ordering information

Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field -> Open product page -> The "Configure" button to the right of the product image opens the Product Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop

Heartbeat Technology

Application packages

Many different application packages are available to enhance the functionality of the device. Such packages might be needed to address safety aspects or specific application requirements.
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Detailed information on the application packages: Special Documentation for the device →  89
Package Description
Heartbeat Verification +Monitoring
Heartbeat Verification
Meets the requirement for traceable verification to DIN ISO 9001:2008 Chapter
7.6 a) "Control of monitoring and measuring equipment".
• Functional testing in the installed state without interrupting the process.
• Traceable verification results on request, including a report.
• Simple testing process via local operation or other operating interfaces.
• Clear measuring point assessment (pass/fail) with high test coverage within the framework of manufacturer specifications.
• Extension of calibration intervals according to operator's risk assessment.
Heartbeat Monitoring
Continuously supplies data, which are characteristic of the measuring principle, to an external condition monitoring system for the purpose of preventive maintenance or process analysis. These data enable the operator to:
• Draw conclusions - using these data and other information - about the impact process influences (such as corrosion, abrasion, buildup etc.) have on the measuring performance over time.
• Schedule servicing in time.
• Monitor the process or product quality, e.g. gas pockets.
86 Endress+Hauser
Page 87
Proline Promass E 100

Concentration

Package Description
Concentration measurement

Accessories

Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.

Device-specific accessories For the sensor

Calculation and outputting of fluid concentrations
Many applications use density as a key measured value for monitoring quality or controlling processes. The device measures the density of the fluid as standard and makes this value available to the control system.
The observed density is converted to the concentration of a substance of a binary mixture using the "Concentration Measurement" application package:
• Choice of predefined fluids (e.g. various sugar solutions, acids, alkalis, salts, ethanol etc.)
• Common or user-defined units (°Brix, °Plato, % mass, % volume, mol/l etc.) for standard applications.
• Concentration calculation from user-defined tables.
The measured values are output via the digital and analog outputs of the device.

Communication-specific accessories

Accessories Description
Heating jacket Is used to stabilize the temperature of the fluids in the sensor.
Water, water vapor and other non-corrosive liquids are permitted for use as fluids. If using oil as a heating medium, please consult with Endress+Hauser. Heating jackets cannot be used with sensors fitted with a rupture disk.
Accessories Description
Commubox FXA195 HART
Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
HART Loop Converter HMX50
Wireless HART adapter SWA70
For intrinsically safe HART communication with FieldCare via the USB interface.
For details, see "Technical Information" TI00404F
Common Data Interface) and the USB port of a computer or laptop.
For details, see the "Technical Information" document TI405C/07
Is used to evaluate and convert dynamic HART process variables to analog current signals or limit values.
For details, see "Technical Information" TI00429F and Operating Instructions
BA00371F
Is used for the wireless connection of field devices. The WirelessHART adapter can be easily integrated into field devices and existing infrastructures, offers data protection and transmission safety and can be operated in parallel with other wireless networks with minimum cabling complexity.
For details, see Operating Instructions BA00061S
Fieldgate FXA320 Gateway for the remote monitoring of connected 4 to 20 mA measuring devices via
a Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00053S
Fieldgate FXA520 Gateway for the remote diagnostics and remote configuration of connected HART
measuring devices via a Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00051S
Endress+Hauser 87
Page 88
Proline Promass E 100
Field Xpert SFX350 Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION Fieldbus devices and can be used in non-hazardous areas.
For details, see Operating Instructions BA01202S
Field Xpert SFX370 Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION Fieldbus devices and can be used in the non-hazardous area and in the hazardous area.
For details, see Operating Instructions BA01202S

Service-specific accessories

Accessories Description
Applicator Software for selecting and sizing Endress+Hauser measuring devices:
• Choice of measuring devices for industrial requirements
• Calculation of all the necessary data for identifying the optimum flowmeter: e.g. nominal diameter, pressure loss, flow velocity and accuracy.
• Graphic illustration of the calculation results
• Determination of the partial order code, administration, documentation and access to all project-related data and parameters over the entire life cycle of a project.
Applicator is available:
• Via the Internet: https://wapps.endress.com/applicator
• As a downloadable DVD for local PC installation.
W@M W@M Life Cycle Management
Improved productivity with information at your fingertips. Data relevant to a plant and its components is generated from the first stages of planning and during the asset’s complete life cycle. W@M Life Cycle Management is an open and flexible information platform with online and on-site tools. Instant access for your staff to current, in-depth data shortens your plant’s engineering time, speeds up procurement processes and increases plant uptime. Combined with the right services, W@M Life Cycle Management boosts productivity in every phase. For more information, visit
www.endress.com/lifecyclemanagement
FieldCare FDT-based plant asset management tool from Endress+Hauser.
It can configure all smart field units in your system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
For details, see Operating Instructions BA00027S and BA00059S
DeviceCare Tool for connecting and configuring Endress+Hauser field devices.
For details, see Innovation brochure IN01047S
Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
Common Data Interface) and the USB port of a computer or laptop.
For details, see "Technical Information" TI00405C

System components

Accessories Description
Memograph M graphic data manager
iTEMP The temperature transmitters can be used in all applications and are suitable for
The Memograph M graphic data manager provides information on all the relevant measured variables. Measured values are recorded correctly, limit values are monitored and measuring points analyzed. The data are stored in the 256 MB internal memory and also on a SD card or USB stick.
For details, see "Technical Information" TI00133R and Operating Instructions
BA00247R
the measurement of gases, steam and liquids. They can be used to read in the medium temperature.
For details, see "Fields of Activity", FA00006T
88 Endress+Hauser
Page 89
Proline Promass E 100

Supplementary documentation

For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate.

Standard documentation Brief Operating Instructions

Brief Operating Instructions for the sensor
Measuring device Documentation code
Proline Promass E KA01260D
Transmitter Brief Operating Instructions
Measuring device Documentation code
Proline Promass 100 KA01334D
KA01333D KA01335D KA01332D KA01336D
Supplementary device­dependent documentation
Technical Information
Measuring device Documentation code
Proline Promass E 100 TI01351D
Description of Device Parameters
Measuring device Documentation code
Proline Promass 100 GP01033D
Proline Promass 100 GP01034D
Proline Promass 100 GP01035D
Proline Promass 100 GP01036D
Proline Promass 100 GP01037D
Safety Instructions
Content Documentation code
ATEX/IECEx Ex i XA00159D
ATEX/IECEx Ex nA XA01029D
cCSAus IS XA00160D
INMETRO Ex i XA01219D
INMETRO Ex nA XA01220D
Special Documentation
Content Documentation code
Information on the Pressure Equipment Directive SD00142D
Modbus RS485 Register Information SD00154D
Endress+Hauser 89
Page 90
Proline Promass E 100
Content Documentation code
Concentration measurement SD01152D
Concentration measurement SD01503D
Heartbeat Technology SD01153D
Heartbeat Technology SD01493D
Web server SD01820D
Web server SD01821D
Web server SD01822D
Web server SD01823D
Installation Instructions
Contents Comment
Installation instructions for spare part sets and accessories Documentation code: specified for each individual accessory .

Registered trademarks

HART®
Registered trademark of the FieldComm Group, Austin, Texas, USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
Modbus®
Registered trademark of SCHNEIDER AUTOMATION, INC.
EtherNet/IP™
Trademark of ODVA, Inc.
PROFINET®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
Microsoft®
Registered trademark of the Microsoft Corporation, Redmond, Washington, USA
TRI-CLAMP®
Registered trademark of Ladish & Co., Inc., Kenosha, USA
90 Endress+Hauser
Page 91
Page 92
www.addresses.endress.com
Loading...