Emerson Fisher DLC3020f Quick Start Guide

Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
Fisherr FIELDVUE™ DLC3020f Digital Level
July 2012
Controller for F
OUNDATION
Contents
Installation 3.....................
Mounting 10......................
Electrical Connections 14...........
Configuration 18..................
Calibration 33.....................
Nameplates and Schematics 37......
Specifications 41..................
This quick start guide applies to:
Device Type Device Revision Hardware Revision Firmware Revision DD Revision
3020 1
1.0
1.0 0x03
Note
This quick start guide provides installation and initial setup and calibration information for the DLC3020f digital level controller using AMS Suite: Intelligent Device Manager.
www.Fisher.com
DLC3020f Digital Level Controller
July 2012
nInstallation Check List
Mounting
Instrument correctly configured and mounted on the sensor. See the appropriate
j
mounting procedure or installation instructions provided with the mounting kit.
Wiring and Electrical Connections
Conduit or I.S. barrier, if necessary, properly installed. Refer to local and national
j
electrical codes.
Quick Start Guide
D103470X012
Loop wiring properly connected to the LOOP + and - terminals in the terminal box.
j
Connect loop wiring as described on page 14.
2
Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
July 2012
Installation
Do not install, operate, or maintain a DLC3020f digital level controller without being fully trained and qualified in field instrument and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it
is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. If you have any questions regarding these instructions contact your Emerson Process
Management sales office before proceeding.
Refer to figure 1 for the installation flow chart.
Figure 1. Installation Flowchart
Install Heat
Insulator
Yes
START
Factory mounted
on 249 sensor
No
High
temperature
application?
No
Mount DLC3020f
to Sensor
Make Electrical
Connections
Power Device
Yes
Proceed to
Set Up and Calibration
Configuration: On the Bench or in the Field
Configure the digital level controller before or after installation in the field.
It may be useful to configure the instrument on the bench before installation to ensure proper operation, and to familiarize yourself with its functionality.
3
DLC3020f Digital Level Controller
July 2012
Quick Start Guide
D103470X012
Protecting the Coupling and Flexures
CAUTION
Damage to flexures and other parts can cause measurement errors. Observe the following steps before moving the sensor and controller.
Lever Lock
The lever lock is built in to the coupling access door. When the door is open, it positions the lever in the neutral travel position for coupling. In some cases, this function is used to protect the lever assembly from violent motion during shipment.
A DLC3020f digital level controller will have one of the following mechanical configurations when received:
1. A fully assembled and coupled caged‐displacer system shipped with the displacer or driver rod blocked within the operating range by mechanical means. In this case, the access handle (figure 2) will be in the unlocked position. Remove the displacer blocking hardware before calibration (see the appropriate sensor instruction manual). The coupling should be intact.
Figure 2. Sensor Connection Compartment (Adapter Ring Removed for Clarity)
MOUNTING STUDS
ACCESS HOLE
SHAFT CLAMP
1
SET SCREW
PRESS HERE TO
MOVE ACCESS HANDLE
NOTE: 1 SET SCREW IS USED TO LOCK THE LEVER IN PLACE FOR OPERATION
SLIDE ACCESS HANDLE TOWARD FRONT OF UNIT TO EXPOSE ACCESS HOLE
CAUTION
When shipping an instrument mounted on a sensor, if the lever assembly is coupled to the linkage, and the linkage is constrained by the displacer blocks, use of the lever lock may result in damage to bellows joints or flexure.
4
Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
July 2012
2. If the displacer cannot be blocked because of cage configuration or other concerns, the transmitter is uncoupled from the torque tube by loosening the coupling nut, and the access handle will be in the locked position. Before placing such a configuration into service, couple the instrument to the sensor as follows:
a. Slide the access handle to the open position to lock the lever assembly in place and expose the access hole. Press
on the back of the handle as shown in figure 2 then slide the handle toward the front of the unit. Be sure the locking handle drops into the detent.
b. If in process, ensure that the level or interface is in the lowest position on the displacer.
c. If on the bench, ensure that the displacer is dry and the displacer rod lever arm is not hitting a travel stop.
d. Insert a 10 mm deep well socket through the access hole and onto the torque tube shaft clamp nut. Tighten the
clamp nut to a maximum torque of 2.1 NSm (18 lbfSin).
e. Slide the access handle to the closed position. for operation or calibration. (Press on the back of the handle as
shown in figure 2 then slide the handle toward the rear of the unit.) Be sure the locking handle drops into the detent.
5
DLC3020f Digital Level Controller
July 2012
Quick Start Guide
D103470X012
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installation in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, and area re‐classification.
Note
This information supplements the nameplate markings affixed to the product.
Always refer to the nameplate itself to identify the appropriate certification. Contact your Emerson Process Management sales
office for approval/certification information not listed here.
CSA
Intrinsically Safe, Explosion‐proof, Division 2, Dust Ignition‐proof
No special conditions for safe use.
Refer to table 1 for approval information, figure 21 for the CSA schematic, and figure 23 for a typical CSA/FM nameplate.
Table 1. Hazardous Area Classifications—CSA (Canada)
Certification Body Certification Obtained Entity Rating Temperature Code Enclosure Rating
Fieldbus
CSA
Intrinsically Safe Class I, II, III Division 1 Groups A,B,C, D,E,F,G T4 per drawing GE37118
Explosion‐proof Class I Division 1 Groups B,C,D T6
Class I Division 2 Groups A,B,C,D T6 Dust Ignition‐proof
Class II Division 1,2 Groups E,F,G T6
Class III
RTD Terminals
Voc = 6.6 VDC Isc = 29.5 mA Po = 49 mW Ca
22 μF
40 mH
La
RTD Terminals
Voc = 6.6 VDC Isc = 29.5 mA Po = 49 mW Ca
22 μF
40 mH
La
Main Circuit Terminals
Vmax
24 VDC
Imax
380 mA
Pi
1.4 W
Ci = 5 nF Li = 0 mH
FISCO
Main Circuit Terminals
Vmax
17.5 VDC
Imax
380 mA
Pi
5.32 W
Ci = 5 nF Li = 0 mH
- - -
T4(Tamb 80_C) Type 4X
T6(Tamb 80_C) Type 4X
T6(Tamb 80_C) Type 4X
6
Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
July 2012
FM
Intrinsically Safe, Explosion‐proof, Non-Incendive, Dust Ignition‐proof
No special conditions for safe use.
Refer to table 2 for approval information, figure 24 for the FM schematic, and figure 23 for a typical CSA/FM nameplate.
Table 2. Hazardous Area Classifications—FM (United States)
Certification Body Certification Obtained Entity Rating Temperature Code Enclosure Rating
Fieldbus
FM
Intrinsically Safe Class I, II, III Division 1 Groups A,B,C, D,E,F,G T4 per drawing GE37117
Explosion‐proof Class I Division 1 Groups A,B,C,D T5
Non‐Incendive Class I,II,III Division 2 Groups A,B,C,D, E,F,G T4
Dust Ignition‐proof Class II Division 1 Groups E,F,G T5
RTD Terminals
Voc = 6.6 VDC Isc = 29.5 mA Po = 49 mW Ca
22 μF
40 mH
La
RTD Terminals
Voc = 6.6 VDC Isc = 29.5 mA Po = 49 mW Ca
22 μF
40 mH
La
Main Circuit Terminals
Vmax
24 VDC
Imax
380 mA
Pi ≤ 1.4 W Ci = 5 nF Li = 0 mH
FISCO
Main Circuit Terminals
Vmax
17.5 VDC
Imax
380 mA
Pi
5.32 W
Ci = 5 nF Li = 0 mH
− − −
T4(Tamb ≤ 80_C) NEMA 4X, IP66
T5(Tamb 80_C) NEMA 4X, IP66
T4(Tamb 80_C) NEMA 4X, IP66
T5(Tamb 80_C) NEMA 4X, IP66
7
DLC3020f Digital Level Controller
July 2012
Quick Start Guide
D103470X012
ATEX
Special Conditions for Safe Use
Intrinsically Safe & Dust
This apparatus can only be connected to an intrinsically safe certified equipment and this combination must be compatible regarding the intrinsic safety rules (see electrical parameters in table 3).
Flameproof & Dust, Type n & Dust
No special conditions for safe use.
Refer to table 3 for additional approval information and figure 26 for a typical ATEX/IECEx nameplate.
Table 3. Hazardous Area Classifications—ATEX
Certification Certification Obtained Entity Rating Temperature Code Enclosure Rating
Fieldbus
Ui 24 V Ii
380 mA
Pi
1.4 W
+ 5 nF
Ci Li
+ 0 mH
Ui 17.5 V Ii
380 mA
Pi
5.32 W
+ 5 nF
Ci Li
+ 0 mH
FISCO
- - -
T5(Tamb 80_C) T6(Tamb
73_C)
T5(Tamb 80_C) T6(Tamb
73_C)
T5(Tamb 80_C) T6(Tamb
73_C)
IP66
IP66
IP66
ATEX
II 1 G & D Intrinsically Safe Ex ia IIC T5/T6 Ga Dust Ex iaD 20 IP66 T87_C (Tamb Ex iaD 20 IP66 T80_C (Tamb
II 2 G & D Flameproof Ex d IIC T5/T6 Dust Ex tD A21 IP66 T87_C (Tamb Ex tD A21 IP66 T80_C (Tamb
II 3 G & D Type n Ex nA IIC T5/T6 Dust Ex tD A22 IP66 T87_C (Tamb Ex tD A22 IP66 T80_C (Tamb
80_C) Da 73_C) Da
80_C) 73_C)
80_C) 73_C)
8
Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
July 2012
IECEx
Conditions of Certification
Intrinsically Safe & Dust
This apparatus shall only be connected to an intrinsically safe certified equipment and this combination must be compatible regarding the intrinsic safety rules (see electrical parameters in table 4).
Flameproof & Dust, Type n & Dust
No conditions of certification.
Refer to table 4 for additional approval information, and figure 26 for a typical ATEX/IECEx nameplate.
Table 4. Hazardous Area Classifications—IECEx
Certification Certification Obtained Entity Rating Temperature Code Enclosure Rating
Fieldbus
Ui 24 V Ii
380 mA
Pi
1.4 W
+ 5 nF
Ci Li
+ 0 mH
Ui 17.5 V Ii
380 mA
Pi
5.32 W
+ 5 nF
Ci Li
+ 0 mH
FISCO
- - -
T5(Tamb 80_C) T6(Tamb
73_C)
T5(Tamb 80_C) T6(Tamb
73_C)
T5(Tamb 80_C) T6(Tamb
73_C)
IP66
IP66
IP66
IECEx
Intrinsically Safe Ex ia IIC T5/T6 Ga Dust Ex iaD 20 IP66 T87_C (Tamb Ex iaD 20 IP66 T80_C (Tamb
Flameproof Ex d IIC T5/T6 Dust Ex tD A21 IP66 T87_C (Tamb Ex tD A21 IP66 T80_C (Tamb
Type n Ex nA IIC T5/T6 Dust Ex tD A22 IP66 T87_C (Tamb Ex tD A22 IP66 T80_C (Tamb
80_C) Da 73_C) Da
80_C) 73_C)
80_C) 73_C)
9
DLC3020f Digital Level Controller
July 2012
Quick Start Guide
D103470X012
Mounting
WARNING
To avoid personal injury or property damage, always wear protective gloves, clothing, and eyewear when performing any installation operations.
Personal injury or property damage due to sudden release of pressure, contact with hazardous fluid, fire, or explosion can be caused by puncturing, heating, or repairing a displacer that is retaining process pressure or fluid. This danger may not be readily apparent when disassembling the sensor or removing the displacer. Before disassembling the sensor or removing the displacer, observe the appropriate warnings provided in the sensor instruction manual.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
Mounting the 249 Sensor
The 249 sensor is mounted using one of two methods, depending on the specific type of sensor. If the sensor has a caged displacer, it typically mounts on the side of the vessel as shown in the left image in figure 3. If the sensor has a cageless displacer, the sensor mounts on the side or top of the vessel as shown in the right image in figure 3.
Figure 3. Typical Mounting
10
A3789‐1
TYPICAL CAGED SENSOR MOUNTING
A3788‐1
TYPICAL CAGELESS SENSOR MOUNTING
Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
July 2012
The DLC3020f digital level controller is typically shipped attached to the sensor. If ordered separately, it may be convenient to mount the digital level controller to the sensor and perform the initial setup and calibration before installing the sensor on the vessel.
Note
Caged sensors have a rod and block installed on each end of the displacer to protect the displacer in shipping. Remove these parts before installing the sensor to allow the displacer to function properly.
DLC3020f Orientation
Mount the DLC3020f with the torque tube shaft clamp access hole (see figure 2) pointing downward to allow accumulated moisture drainage.
Note
If alternate drainage is provided by the user, and a small performance loss is acceptable, the instrument could be mounted in 90 degree rotational increments around the pilot shaft axis. The LCD meter may be rotated in 90 degree increments to accommodate this.
The digital level controller and torque tube arm are attached to the sensor either to the left or right of the displacer, as shown in figure 4. This can be changed in the field on the 249 sensors (refer to the appropriate sensor instruction manual). Changing the mounting also changes the effective action, because the torque tube rotation for increasing level, (looking at the protruding shaft), is clockwise when the unit is mounted to the right of the displacer and counter‐ clockwise when the unit is mounted to the left of the displacer.
All 249 caged sensors have a rotatable head. That is, the digital level controller can be positioned at any of eight alternate positions around the cage as indicated by the position numbers 1 through 8 in figure 4. To rotate the head, remove the head flange bolts and nuts and position the head as desired.
Mounting the DLC3020f on a 249 Sensor
Refer to figure 2 unless otherwise indicated.
1. If the set screw in the access handle (figure 5) is driven against the spring plate, back it out until the head is flush with the outer surface of the handle, using a 2 mm hex key. Slide the access handle to the open position to lock the lever assembly in place and to expose the access hole. Press on the back of the handle as shown in figure 2 then slide the handle toward the front of the unit. Be sure the locking handle drops into the detent.
2. Using a 10 mm deep well socket inserted through the access hole, loosen the shaft clamp (figure 2).
3. Remove the hex nuts from the mounting studs. Do not remove the adapter ring.
CAUTION
Measurement errors can occur if the torque tube assembly is bent or misaligned during installation.
11
DLC3020f Digital Level Controller
July 2012
Quick Start Guide
D103470X012
Figure 4. Typical Mounting Positions for the FIELDVUE DLC3020f Digital Level Controller on a Fisher 249 Sensor
SENSOR
1
5
CAGED
CAGELESS
249VS
1 NOT AVAILABLE FOR SIZE NPS 2 CL300 AND CL600 249C SENSOR.
LEFT‐OF‐DISPLACER
7
3
1
4
6
249W
RIGHT‐OF‐DISPLACER
3
8
1
2
7
1 5
249W
2
8
4
6
249VS
Figure 5. Close‐up of Set‐Screw
SET‐SCREW (2mm)
4. Position the digital level controller so the access hole is on the bottom of the instrument.
5. Carefully slide the mounting studs into the sensor mounting holes until the digital level controller is snug against the sensor mounting flange.
6. Reinstall the hex nuts on the mounting studs and tighten the hex nuts to 10 NSm (88.5 lbfSin).
Mounting the DLC3020f for High Temperature Applications
Refer to figure 7 for parts identification except where otherwise indicated.
The digital level controller requires an insulator assembly when temperatures exceed the limits shown in figure 6.
A torque tube shaft extension is required for a 249 sensor when using an insulator assembly.
12
Quick Start Guide
D103470X012
Figure 6. Guidelines for Use of Optional Heat Insulator Assembly
AMBIENT TEMPERATURE (_C)
-40 -30
800
-20 -10
010 20
HEAT INSULATOR
400
0
1
TOO COLD
-325
PROCESS TEMPERATURE (_F)
0 20 40 60 80 100 120 140 160
-20-40
REQUIRED
NO HEAT INSULATOR NECESSARY
HEAT INSULATOR REQUIRED
AMBIENT TEMPERATURE (_F)
30 40 50 60
TOO HOT
70
80
425 400
300
200
100
0
-100
-200
176
PROCESS TEMPERATURE (_C)
STANDARD TRANSMITTER
NOTES:
1
FOR PROCESS TEMPERATURES BELOW -29_C (-20_F) AND ABOVE 204_C (400_F) SENSOR MATERIALS MUST BE APPROPRIATE FOR THE PROCESS - SEE TABLE 9.
2. IF AMBIENT DEW POINT IS ABOVE PROCESS TEMPERATURE, ICE FORMATION MIGHT CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.
39A4070‐B A5494‐1
CAUTION
DLC3020f Digital Level Controller
July 2012
Measurement errors can occur if the torque tube assembly is bent or misaligned during installation.
1. When mounting a DLC3020f on a 249 sensor, secure the shaft extension to the sensor torque tube shaft via the shaft coupling and set screws, with the coupling centered as shown in figure 7.
2. Slide the access handle to the locked position to expose the access hole. Press on the back of the handle as shown in figure 2 then slide the handle toward the front of the unit. Be sure the locking handle drops into the detent.
Figure 7. Digital Level Controller Mounting on Sensor in High Temperature Applications
INSULATOR (KEY 57)
SHAFT EXTENSION (KEY 58)
DIGITAL LEVEL CONTROLLER
MN28800 20A7423‐C B2707
CAP SCREWS (KEY 63)
SENSOR
SET SCREWS (KEY 60)
SHAFT COUPLING (KEY 59)
WASHER
(KEY 78)
HEX NUTS
(KEY 34)
MOUNTING STUDS
(KEY 33)
3. Remove the hex nuts from the mounting studs.
4. Position the insulator on the digital level controller, sliding the insulator straight over the mounting studs.
5. Install 4 washers (key 78) over the studs. Install the four hex nuts and tighten.
13
DLC3020f Digital Level Controller
July 2012
Quick Start Guide
D103470X012
6. Carefully slide the digital level controller with the attached insulator over the shaft coupling so that the access hole is on the bottom of the digital level controller.
7. Secure the digital level controller and insulator to the torque tube arm with four cap screws.
8. Tighten the cap screws to 10 NSm (88.5 lbfSin).
Electrical Connections
The following describes how to make fieldbus connections to the digital level controller.
WARNING
To avoid personal injury resulting from electrical shock, do not exceed the maximum input voltage specified in table 8 or on the product nameplate. If the input voltage specified differs, do not exceed the lowest specified maximum input voltage.
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval. Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or explosion.
Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially explosive atmosphere or in an area that has been classified as hazardous. Confirm that area classification and atmosphere conditions permit the safe removal of the terminal box cover before proceeding
Fieldbus Connections
The digital level controller is normally powered over the bus from a fieldbus 9 to 32 volt power supply and can be connected to the segment using field wiring. Refer to the site preparation guide for proper wire types, termination, length, etc. for a fieldbus segment.
Note
As shipped from the factory, the DLC3020f will have the transducer block mode set Out of Service. See the Configuration section for information on setup and calibration and placing the instrument in service. The initial value for all blocks are shown in the parameter list for each block in the Blocks section.
14
Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
July 2012
1. Remove the terminal box cover (key 6) from the terminal box (key 5).
2. Bring the field wiring into the terminal box. When applicable, install conduit using local and national electrical codes which apply to the application.
3. Connect one wire from the control system output card to the LOOP + terminal in the terminal box as shown in figure 8. Connect the other wire from the control system output card to the LOOP - terminal. The instrument is not polarity sensitive.
WARNING
Personal injury or property damage, caused by fire or explosion, can result from the discharge of static electricity. Connect a 14 AWG (2.08 mm gases are present. Refer to national and local codes and standards for grounding requirements.
2
) ground strap between the digital level controller and earth ground when flammable or hazardous
4. As shown in figure 8, ground terminals are available for connecting a safety ground, earth ground, or drain wire. The safety ground terminal is electrically identical to the earth ground. Make connections to these terminals following national and local codes and plant standards.
5. Replace and tighten the terminal box cover, ensuring that it is weather‐tight; engage the optional set screw lock if required.
Figure 8. Terminal Box Assembly
CLIP‐ON +
CLIP‐ON -
RTD
SIMULATE ENABLE
LOOP+
LOOP-
SAFETY GROUND
15
Loading...
+ 33 hidden pages