Eaton Electrical MN05001002E User Manual

Intelligent Technologies
QCPort System Install Manual
November 2005 Supercedes November 2004
MN05001002E (C) For more information visit
www.eatonelectrical.com
November 2005
Important Notice – Please Read
The product discussed in this literature is subject to terms and conditions outlined in appropriate Cutler-Hammer selling policies. The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Cutler-Hammer selling policy.
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESC RIPTIONS CONTAINED HEREIN. In no event will Cutler-Hammer be responsible to the
purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein.
Intelligent Technologies QCPort System Install Manual
Important User Information
Due to the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes, and standards.
Only qualified persons, as defined in the National Electric Code, who are familiar with the installation, maintenance, and operation of these products and the equipment onto which they are to be installed, as well as applicable local, state, and national regulations and industry standards and accepted practices regarding safety of personnel and the equipment safety, should be permitted to install, maintain, or operate this system. These instructions are provided only as a general guide to such qualified persons and are not all-inclusive. They do not cover every application or circumstance that may arise in the installation, maintenance, or operation of this equipment. Users are advised to comply with all local, state, and national regulations and industry standards and accepted practices regarding safety of personnel and equipment safety.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for example. Since there are many variables and requirements associated with any particular installation, Cutler-Hammer does not assume responsibility or liability (including intellectual property liability) for actual use based upon the examples shown in this publication.
Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Cutler-Hammer is prohibited.
MN05001002E For more information visit
www.eatonelectrical.com
Page
2
November 2005
Throughout this manual, various types of notices are provided to alert you to possible injury to people or damage to equipment under specific circumstances. These will help you:
These
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss.
Identifies information that is especially important for successful application and understanding of the product.
Identify a hazard
Avoid the hazard
Recognize the consequences
include
“Attention” and “Important” notices; please note the following examples.
Intelligent Technologies QCPort System Install Manual
Warning
Warning
National Electric Code
Do not install or perform maintenance on the QCPort system while the system is energized. Death or severe personal injury, as well as damage to other equipment, can result from contact with energized equipment. Verify that no voltage is present before proceeding with installation or maintenance.
Much of the information provided in this manual is representative of the capability of a QCPort system and its associated components. The National Electric Code (NEC), in the United States, and the Canadian Electric Code (CE Code), in Canada, places limitations on configurations and the maximum allowable power/current that can be provided.
The instructions and examples in this manual are based on Class 2 power suppli es.
Be sure that all national and local codes are thoroughly researched and adhered to during the planning and installation of your QCPort system.
Warning
Warning
MN05001002E For more information visit
www.eatonelectrical.com
Page
3
November 2005
Table of Contents
Intelligent Technologies QCPort System Install Manual
INTERCONNECTIVITY USING QCPORT....................................................................................... 6
I
NTRODUCING
QCP
ORT PHYSICAL CHARACTERISTICS
E
XAMPLES OF
One Device Using QCPort 7 Multiple Peripherals on One Device Using QCPort 8 Multiple Devices Being Controlled And Monitored Remotely Using QCPort 9
QCPORT OPERATING MODES...................................................................................................10
Overview 10 Understanding Master-Slave 10 Understanding Peer 10
OVERVIEW OF QCPORT INTERCONNECT SYSTEM................................................................11
D
EVICE CONNECTION IN A
QCPort Backplane 11 QCPort Interconnect Cable 12
D
AISY CHAIN
T
RUNK DROP
P
HYSICAL PLACEMENT
U
SING BIASING RESISTORS
A
PPLICATION EXAMPLE
PLANNING A QCPORT INTERCONNECT SYSTEM................................................................... 18
G
UIDELINES FOR SUPPLYING POWER
IT. Power Supplies 18 Other Power Supplies 18
P
OWER RATINGS
QCPort Interconnect Cable Rating 18
L
OCATING A POWER SUPPLY
1 Power Supply 20
G
ROUNDING THE INTERCONNECT SYSTEM
SIZING A POWER SUPPLY .........................................................................................................21
S
UPPLYING POWER
A
DJUSTING THE CONFIGURATION
S
IZING CALCULATION
U
SING THE SIZING CALCULATION
Example 1 End Connected Power Supply 23 Example 2 End Connected Power Supply 23 Example 3 Middle Connected Power Supply 24
TROUBLESHOOTING AND MAINTENANCE..............................................................................25
APPENDIX A: USING LONG RUN CABLES ............................................................................... 26
TECHNICAL SUPPORT................................................................................................................28
QCP
ORT
..................................................................................................................6
...........................................................................................6
QCP
ORT USE
................................................................................................................................14
................................................................................................................................14
..........................................................................................................................18
......................................................................................................................21
....................................................................................................................22
...........................................................................................................7
QCP
ORT SYSTEM
..................................................................................................................15
...........................................................................................................16
.................................................................................................................17
.............................................................................................18
.........................................................................................................19
...................................................................................................21
...................................................................................................23
.................................................................................11
.....................................................................................20
MN05001002E For more information visit
www.eatonelectrical.com
Page
4
Intelligent Technologies QCPort System Install Manual
November 2005
Table of Figures
Figure 1: Example of One Device Using QCPort 7 Figure 2: Example of Multiple Peripherals on One Device Using QCPort 8 Figure 3: Example of Remote Connection Using QCPort 9 Figure 4: QCPort Backplane Connector 11 Figure 5: 6 Pin QCPort Linear Connector 11 Figure 6: QCPort Interconnect Cable 12 Figure 7: QCPort Powered Interconnect Cable Wiring 12 Figure 8: Long Run Cable Connection 13 Figure 9: Daisy Chain Topology 14 Figure 10: QCPort Biasing Resistor Options 16 Figure 11: Distributed Motor Control Panel 17 Figure 12: 1 Power Supply 20 Figure 13
: Example of Long Run Cable:
One Power Supply (End-Connected) 26
MN05001002E For more information visit
www.eatonelectrical.com
Page
5
November 2005
Interconnectivity Using QCPort
Introducing QCPort
The interface demands on control devices continues to increase at a rapid pace. An intelligent control device requires connection to configuration and monitoring tools, operator interfaces, and other peripheral devices, as well as the option to connect to a variety of industrial fieldbusses. At the same time, the intelligent devices continue to shrink in size and cost, forcing distribution of the field connections that once were native on the devices.
QCPort is a flexible interface port that integrates the many connectivity needs of the intelligent device into a single device port for the means of control, setup, and configuration. The integration of these capabilities provides interface options that are powerful and cost effective. In addition to the interface functionality of QCPort, care has been taken to insure that systems that connect via QCPort are simple to configure, connect, and maintain.
QCPort Physical Characteristics
In an effort to use existing proven technology, QCPort uses the RS485 physical layer. This physical layer is common to many industrial communication interfaces and has a long and proven track record within industrial applications. QCPort is a four-wire system where there is an A and B for signal and a +DC and Ground for device power. Depending on the type of device interconnect and the distance between devices, there are many choices for the type of interconnect physical media; these choices will be discussed further in the manual.
Intelligent Technologies QCPort System Install Manual
MN05001002E For more information visit
www.eatonelectrical.com
Page
6
November 2005
Examples of QCPort Use
One Device Using QCPort
In many applications, the QCPort will be used as the connection between a motor controller and the user interface/configuration keypad. The following figure contains a one-to-one solution, where the user interface is powered from the motor controller’s QCPort. A separate power supply is not required for the user interface. In this example, the user interface is connected to Channel 0 of the motor controller. Channel 0 is specifically used for connection to the user interface and operator stations.
Intelligent Technologies QCPort System Install Manual
Figure 1: Example of One Device Using QCPort
The interconnect supplied with the operator interface connects the operator interface to the motor controller. This connection provides for 24V DC and communication; the operator interface is powered from the motor controller. Configuration of the operator interface or the motor controller for this application is not required for communication to be established. The user can then use the operator interface to configure the motor controller parameters, operate the motor controller, and monitor the operation of the motor controller.
The information contained within this manual does not include instructions for setup or operation of the motor controller or operator interface. For instructions on how to apply the operator interface, refer to the manual for that device.
MN05001002E For more information visit
www.eatonelectrical.com
Page
7
Intelligent Technologies QCPort System Install Manual
November 2005
Multiple Peripherals on One Device Using QCPort
QCPort has been designed to support multiple devices connected to one motor controller, without the motor controller having prior knowledge of the connected device. Devices that can be connected to a motor controller include u ser interface products and IO products. Once again, the devices are connected to Channel 0 of the motor controller.
The figure below illustrates an application example that includes a user interface and IO modules. The input module is used to apply a hard-wired HOA while the output module is used to annunciate the motor controller status and trip conditions. The mapping of the data between the motor controller and the IO devices does not require a tool and is seamless to the user.
Figure 2: Example of Multiple Peripherals on One Device Using QCPort
When multiple devices are connected to one motor controller, the user has to be aware of the power demand of all of the peripherals. Verify the power requirement of this system by adding up the power demands of the peripherals to see if they exceed the power capacity of the motor controller. If the power capacity of the motor controller is exceeded, a power supply is required for QCPort. To help size the power supply, consult “Locating a Power Supply” later in the manual.
MN05001002E For more information visit
www.eatonelectrical.com
Page
8
Intelligent Technologies QCPort System Install Manual
November 2005
Multiple Devices Being Controlled And Monitored Remotely Using QCPort
When an industrial fieldbus adapter is used within a system, the adapter will act as a subscanner presenting the QCPort devices as IO to the industrial fieldbus. This allows the QCPort devices to be monitored, controlled, and configured from a remote location. For this type of application, a power supply will be required; it can be the same power supply that is used for the motor controllers.
DeviceNet
IT. EM Starters and D77B-QSNAPs
IT. 24V DC
Power Supply
Figure 3: Example of Remote Connection Using QCPort
Since a power supply sizing is required, refer to “Locating a Power Supply” later in this manual. Along with the power supply sizing, physical media restrictions must be followed. This includes the length of the interconnects, type of interconnects, and the power capabilities for the interconnects.
This type of application requires some configuration. The Group IDs for the QCPort devices need to be set to unique IDs, the adapter requires an address configuration, and then the mapping feature needs to be invoked to map the QCPort data to the industrial fieldbus. None of these configuration requirements require a software tool. If advanced configuration of the QCPort devices is required, then a software tool or a QCPort user interface will be required. For information on configuration of the QCPort devices, refer to the user manual for those devices.
MN05001002E For more information visit
www.eatonelectrical.com
Page
9
Loading...
+ 20 hidden pages