Druck 1195 Quick Start Guide

Page 1
00825-0100-4686, Rev FA
Rosemount™ 1195 Integral Orifice
Assembly
Quick Start Guide
September 2017
Page 2
Quick Start Guide
NOTICE
This document provides basic installation guidelines for the Rosemount1195 Integral Orifice Assembly. For comprehensive instructions for detailed configuration, diagnostics, maintenance, service, installation, or troubleshooting refer to the Rosemount 1195 Reference Ma nual electronically on EmersonProcess.com /Rosemount
If the Rosemount 1195 Integral Orifice was ordered assembled to a Rosemount Pressure Transmitter, refer to the following Quick Start Guides for information on configuration and hazardous locations cer tifications:
Rosemount 3051S Quick Start Guide
Rosemount 3051SMV Quick Start Guide
Rosemount 3051 Quick Start Guide
Process leaks may cause harm or result in death
To avoid process leaks, only use gaskets designed to seal with the corresponding flange and O-rings to seal process connections.
.
. The manual and this guide are also available
Contents
Rosemount 1195 Integral Orifice Assembly
View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Location and orientation . . . . . . . . . . . . . page 3
Primary element orientation . . . . . . . . . . page 6
2
Primary element installation . . . . . . . . . . page 8
Preparing for operation . . . . . . . . . . . . . .page 10
Product certifications . . . . . . . . . . . . . . .page 14
Page 3
September 2017
A
B
C
D
E
F
G
Quick Start Guide

1.0 Rosemount 1195 Integral Orifice Assembly View

Figure 1. Enhanced Support Body
A. Manifold B. Gaskets C. Studs D. Nuts
E. Transmitter F. Rosemount 1195 enhanced support body G. Enhanced support orifice plate
(1)

2.0 Location and orientation

Install the Rosemount 1195 Integral Orifice in the correct location within the piping branch to prevent inaccurate measurement caused by flow disturbances.
2.1 Straight pipe length
Use the upstream (U) and downstream (D) lengths provided below in conjunction with figures below to determine the appropriate upstream (U) and downstream (D) pipe lengths. For example, for a 1-in. line size with a beta ratio (β) of 0.4 using installation of Figure 3, the straight length of upstream piping required is 25 1 = 25-in., and downstream 10 1 = 10-in.
Note
The Rosemount 1195 Integral Orifice comes with the associated pipe lengths (18D upstream and 8D downstream) when ordered with process pipe-end connections.
1. Transmitter and housing are shown for clarity purposes - only supplied if ordered.
3
Page 4
Quick Start Guide
U D
U
D
U D
Straight run requirements
(1)
Figure 2. Reducer
U D
(2 d to d over a length of 1.5 d to 3 d)
Figure 3. Single 90° Bend Flow from One Branch
Figure 4. Two or More 90° Bends in Same Planes
Figure 5. Two or More 90° Bends in Different Planes
Figure 6. Expander
U D
(0.5 d to d over a length of d to 2 d)
1. For dimensions, see Tab le 1 on p age 5.
4
Page 5
September 2017
U D
Quick Start Guide
Figure 7. Ball/Gate Valve Fully Open
Table 1. Straight Run Requirements (in Pipe Diameters)
Figure 3
(1)
β
upstream
(U)
0.20 20 24 25 30 22 22 10
0.40 20 25 27 31 22 22 10
0.50 20 25 28 33 23 23 10
0.60 20 27 31 37 25 25 10
0.70 23 32 35 42 28 28 10
0.75 25 35 38 45 30 30 10
1. Interpolation of intermediate β values can be used.
All straight lengths are expressed as multiples of the pipe inside diameter (d) and shall be measured f rom the upstream face of orifice
2.
plate.
Figure 4
upstream
(U)
Figure 5
upstream
(U)
Figure 6
upstream
(U)
Figure 7
upstream
(U)
Figure 8
upstream
(U)
Figures 3–8
On downstream
(D)
(2)
5
Page 6
Quick Start Guide
D
FLOW
A
C
B
A
C
B
FLOW
F
E
D

3.0 Primary element orientation

Figure 8. Rosemount 1195 Flowmeter Orientation with Traditional Style
Manifold
Gas (horizontal) Gas (vertical)
A
B
C
Liquid (horizontal) Liquid (vertical)
D
FLOW
Steam (horizontal) Steam (vertical)
A. 90° recommended zone B. Vertical plane C. Horizontal plane
6
D. 360° recommended zone E. Block valves F. V ent valve s
Page 7
September 2017
A
B
C
D
A
B
C
D
FLOW
F
E
D
Figure 9. Rosemount 1195 Flowmeter Orientation with Flange by Flange
Quick Start Guide
Manifold
Gas (horizontal) Gas (vertical)
Liquid (horizontal) Liquid (vertical)
Steam (horizontal) Steam (vertical)
B
A. 120° recommended zone B. Horizontal plane C. Vertical plane
C
A
D. 360° recommended zone E. Block valves F. Ve nt valves
Note
For saturated steam that is not high quality, it is recommended to mount in a vertical line to avoid damming effect of the liquid.
7
Page 8
Quick Start Guide
A
B
D
14
23

4.0 Primary element installation

1. Ensure the side of the orifice plate marked “inlet” is facing upstream. This stamping is found on the part of the orifice plate that extends beyond the orifice bodies. Before pressurizing line, insure torque values shown below are met. See Ta bl e 2 and Figure 10 for torque requirements of manifold studs and orifice body studs. See the appropriate transmitter manual for torque requirements of transmitter bolts.
Table 2. Stud and Nut Torque Specifications
Manifold studs Tor qu e
All Line sizes and gasket types 32 lb-ft.(44 N-m)
Orifice body studs Tor qu e
All line sizes and gasket types 60 lb-ft. (82 N-m)
1. Studs and nuts should be tightened to specification in two to three steps following a cross pattern.
2. Never reuse gaskets. Always replace gaskets after disassembly to ensure proper seal.
Figure 10. Rosemount 1195 Assembly Fastener Naming Convention
Traditional body Enhanced support body
A
(1)(2)
A. Transmitter bolts - 4 B. Manifold studs - 4
8
B
C
Torque cross pattern
C. Orifice body studs - 2 D. Orifice body studs - 4
Page 9
September 2017
2. Units with flanged process connections: a. Install the flanges in the process pipe. The distance between flanges
b. Install the unit between the flanges, using studs, nuts, and gaskets
3. Units with threaded process connections: a. Install the unit using the appropriate threaded connection hardware.
4. Units with Socketweld Bodies: a. To ensure perpendicularity of the pipe to the orifice fitting, the socket
b. To prevent damage, remove the transmitter prior to welding.
Figure 11. Recommended Support Locations for Installation
Quick Start Guide
should be equal to the overall length of the flowmeter, plus clearance for gaskets.
appropriate for the flange size/rating and process conditions. Proper support is needed at the flange connections as shown below. See Figure 11.
diameter is smaller than the standard pipe OD. The pipe OD must be machined-to-fit prior to welding.
B
AA
A. Support B. No step
5. Once the Rosemount 1195 is installed ensure that it is supported properly and take precautions to ensure that it is not used as a step. Refer to Figure 11 for support locations.
9
Page 10
Quick Start Guide

5.0 Preparing for operation

Note
Serious injury can occur by opening the valves when the pipes are pressurized. Do not bleed or vent process fluid if it is toxic or harmful to health or environment.
5.1 Direct mount 450 °F (232 °C) or less
Liquid applications
1. Pressurize line.
2. Open the equalizer valve.
3. Open the high and low side valves.
4. Bleed drain/vent valves until no gas is apparent in the liquid.
5. Close the vent/drain valves.
6. Close the low side valve.
7. Check the transmitter zero according to the transmitter product manual.
8. Close the equalizer valve.
9. Open the low side valve. The system is now operational.
Gas applications
1. Pressurize line.
2. Open the equalizer valve.
3. Open the high and low side valves.
4. Open drain/vent valves to ensure no liquid is present.
5. Close the vent/drain valves.
6. Close the low side valve.
7. Check the transmitter zero according to the transmitter product manual.
8. Close the equalizer valve.
9. Open the low side valve. The system is now operational.
10
Steam applications
1. Remove pressure from line.
2. Open equalizer, high, and low side valves.
3. Fill manifold and transmitter with water via drain vents.
4. Close low side valve.
5. Pressurize line.
6. Gently tap electronics body, manifold head, and integral orifice body with a small wrench to dislodge any entrapped air.
7. Check the transmitter zero according to the transmitter product manual.
8. Close equalizer valve.
9. Open the low side valve. The system is now operational.
Page 11
September 2017
FLOW
A
B
C
D
5.2 Remote mount
Gas applications-transmitter located above Rosemount 1195 Taps
1. Pressurize line.
2. Open equalizer valve on transmitter manifold.
3. Open high and low side transmitter manifold valves.
4. Open drain/vent valves on transmitter manifold to ensure no liquids are present.
5. Close drain/vent valves.
6. Close low side transmitter manifold valve.
7. Check transmitter zero according to transmitter manual.
8. Close equalizer on transmitter manifold.
9. Open low side valve on transmitter manifold. The system is now operational.
Quick Start Guide
Figure 12. Remote Gas Service
A. Low valve B. Vent C. High valve D. Equalizer valve
(1)
1. Applicable to both body assemblies.
11
Page 12
Quick Start Guide
Liquid applications-transmitter located below Rosemount 1195 Ta ps
1. Pressurize line.
2. Open equalizer valve on transmitter manifold. Close equalizer valve at integral orifice, if one is used.
3. Open high and low side transmitter manifold valves and high and low block valves at integral orifice.
4. Bleed drain/vent valves on transmitter manifold until no air is present.
5. Close transmitter manifold drain vent valves, then bleed vent valves at the integral orifice block valves until no air is present.
6. Close vent valves at integral orifice block valves.
7. Close equalizer valve at transmitter manifold.
8. Close low and high side block valves at integral orifice.
9. Open vent valves at integral orifice block valves.
10. Check transmitter zero according to transmitter manual.
11. Close vent valves at integral orifice block valves.
12. Open high and low side block valves at integral orifice. The system is now operational.
Steam service-transmitter located below Rosemount 1195 Taps
1. Remove pressure from line or close block valves at integral orifice.
2. Open equalizer valves, high and low side valves on the transmitter manifold.
Close equalize valve at integral orifice, if one is used.
3. Open vent valves at integral orifice block valves. To vent sensing lines.
4. Fill transmitter manifold and instrument lines with water via low side vent at
integral orifice block valves.
5. Open and close vent valves at transmitter to bleed out trapped air.
6. Close the equalizer valve at transmitter manifold.
7. Complete filling the low side and high side sensing lines.
8. Gently tap electronics body, transmitter manifold, instrument lines, and
integral orifice with a small wrench to dislodge any trapped air.
9. Check transmitter zero according to transmitter manual.
10. Close vent valves at integral orifice block valves.
11. If block valves at integral orifice had been closed they should now be
opened. System is now operational for steam flow measurement.
12
Page 13
September 2017
FLOW
A
B
C
D
E
Quick Start Guide
Figure 13. Remote Steam and Liquid Service
A. Vent B. High valve C. Equalizer valve D. Vent valves E. Low valve
(1)
1. Applicable to both body assemblies.
13
Page 14
Quick Start Guide

6.0 Product certifications

6.1 Approved Manufacturing Locations
Emerson — Shakopee, Minnesota USA
Rosemount DP Flow Design and Operations — Boulder, Colorado USA
Emerson GmbH & Co. OHG — Wessling, Germany
Emerson Asia Pacific Private Limited — Singapore
Emerson Beijing Instrument Co., Ltd — Beijing, China
6.2 European Directive Information
The EU declaration of conformity for all applicable European directives for this product can be found on the at Emerson.com/Rosemount obtained by contacting our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Refer to EU declaration of conformity for conformity assessment.
Pressure Transmitter — See appropriate Pressure Transmitter QSG.
6.3 Hazardous Locations Certifications
For information regarding the transmitter product certification, see the appropriate transmitter QSG:
Rosemount 3051S with HART Protocol Quick Start Guide Rosemount 3051SMV Flowmeter Quick Start GuideRosemount 3051 Quick Start Guide
. A hard copy may be
14
Page 15
September 2017
Figure 14. Rosemount 1195 Declaration of Conformity
Quick Start Guide
15
Page 16
Quick Start Guide
16
Page 17
September 2017
Quick Start Guide
17
Page 18
Quick Start Guide
1B: 含有China RoHS
管控物彯㚨⣏㳻⹎旸ῤ的部件型号列表
Rosemount 1195
Table 1B: List of Rosemount 1195 Parts with China RoHS Concentration above MCVs
部件名称
Part Name
有害物峐ġİġHazardous Substances
Lead (Pb)
Mercury
(Hg)
Cadmium
(Cd)
六价
Hexavalent
Chromium
(Cr +6)
多ⓤ俼劗
Polybrominated
biphenyls
(PBB)
多ⓤ俼劗慂
Polybrominated diphenyl ethers
多ⓤ俼劗慂
(PBDE)
䬍ࡦ⑙ᓖՐ ᝏಘཆ༣㓴
Ԧ
Aluminum
RTD
Housing
Assembly
O O O X O O
本表格系依据
SJ/T11364
奬⭂侴⇞ἄįġ
This table is proposed in accordance with the provision of SJ/T11364 O:
󰶃宍悐ẞ䘬㇨㚱⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷⛯ỶḶ
GB/T 26572
奬⭂䘬旸慷天㯪įġ
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572. X:
󰶃⛐宍悐ẞ㇨ἧ䓐䘬㇨㚱⛯峐㛸㕁慴炻军⮹㚱ᶨ䰣⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷檀Ḷ
GB/T 26572
奬⭂䘬旸慷天㯪įġ
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
к䘠⭣᰾ӵ䘲⭘Ҿ䘹ᤙ䬍ࡦཆ༣㓴ԦⲴӗ૱DŽަԆᡰᴹᐞ঻⍱䟿а⅑ݳԦⲴ㓴ԦᡰᴹⲴ China RoHS ㇑᧗⢙䍘⎃ ᓖ൷վҾ GB/T 26572 ᡰ㿴ᇊⲴ䲀䟿㾱≲DŽޣҾᐞ঻⍱䟿䇑䘱ಘ㓴ԦⲴ㇑᧗⢙䍘⎃ᓖⲴ⭣᰾ˈ䈧৲ⴻ䘱ಘⲴᘛ 䙏ᆹ㻵ᤷইDŽ
The disclosure above applies to units supplied with aluminum connection heads. No other components supplied with DP Flow primary elements contain any restricted substances. Please consult the transmitter Quick Start Guide (QIG) for disclosure information on transmitter components.
18
Page 19
September 2017
Quick Start Guide
19
Page 20
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Europe Regional Office
Emerson Automation Solutions
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emi rates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
*00825-0100-4686*
Quick Start Guide
00825-0100-4686, Rev FA
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/us er/RosemountMeasur ement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found on the Term s
and Conditions of Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. All other marks are the property of their respective owners. © 2017 Emerson. All rights reserved.
September 2017
Loading...