Desa 2 PLAQUE series, 3 PLAQUE series, 5 PLAQUE series Safety Information And Installation Manual

UNVENTED (VENT-FREE) INFRARED GAS HEATER
SAFETY INFORMATION AND INSTALLATION MANUAL
2 PLAQUE MODELS: 10550, 10551, 10552 AND 10553 3 PLAQUE MODELS: 10554, 10555, 10556 AND 10557 5 PLAQUE MODELS: 10558, 10559, 10560 AND 10561
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s in­structions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
www.desatech.com 113681-01A
2
WARNING: Improper installation, adjustment, altera­tion, service, or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Air for Combustion and
Ventilation
section on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
TABLE OF CONTENTS
Safety Information ............................................... 3
Local Codes ........................................................ 4
Product Identification .......................................... 4
Unpacking ........................................................... 4
Product Features ................................................ 4
Air For Combustion and Ventilation ..................... 5
Installation ........................................................... 7
Operating Heater .............................................. 13
Inspecting Heater .............................................. 17
Cleaning and Maintenance ............................... 18
Service Hints ..................................................... 18
Technical Service .............................................. 18
Troubleshooting ................................................. 19
Specifications .................................................... 22
Accessories ....................................................... 23
Replacement Parts ........................................... 23
Service Publications .......................................... 23
Illustrated Parts Breakdown and Parts List ....... 24
Parts Central ..................................................... 29
Warranty Information .......................... Back Cover
www.desatech.com 3113681-01A
SAFETY INFORMATION
WARNING: This product con­tains and/or generates chemicals known to the State of California to cause cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this heater. Im­proper use of this heater can cause serious injury or death from burns, fire, explosion, elec­trical shock, and carbon mon­oxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of car-
bon monoxide poisoning resemble the flu, with head­aches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alco­hol, and those at high altitudes.
Natural and Propane/LP Gas:
Natural and Propane/LP gases are odorless. An odor-making agent is added to these gases. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn­ings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not use a blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
Due to high temperatures, the appliance should be located out of traffic and away from furni­ture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Surface of heater becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will re­main hot for a time after shut­down. Allow surface to cool be­fore touching.
Carefully supervise young chil­dren when they are in the same room with heater.
Make sure grill guard is in place before running heater.
Keep the appliance area clear and free from combustible ma­terials, gasoline and other flam­mable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appli­ance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in­side any structure. Locate propane/LP supply tank(s) outdoors.
3. This heater shall not be installed in a bath­room. Three and five plaque heaters shall not be installed in a bedroom.
4. If you smell gas
• Shut off gas supply
• Do not try to light any appliance
• Do not touch any electrical switch; do not
use any phone in your building
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call
the fire department
www.desatech.com 113681-01A
4
5. Always run heater with plaque control knob at locked positions. Never set control knob between locked positions. Poor combustion and higher levels of carbon monoxide may result.
6. This heater needs fresh, outside air ventila­tion to run properly. This heater has an Oxy­gen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Com- bustion and Ventilation, page 5.
7. Keep all air openings in front and bottom of heater clear and free of debris. This will in­sure enough air for proper combustion.
8. If heater shuts off, do not relight until you pro­vide fresh, outside air. If heater keeps shut­ting off, have it serviced.
9. Do not run heater
• where flammable liquids or vapors are used
or stored
• under dusty conditions
10. Do not use heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
11. Turn off heater, unplug optional blower and let cool before servicing. Only a qualified ser­vice person should service and repair heater.
12. Operating heater above elevations of 4,500 feet could cause pilot outage.
13. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
14. Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
15.
Provide adequate clearances around air openings.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
SAFETY INFORMATION
Continued
Figure 1 - Vent-Free Gas Heater
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to heater for shipment.
3. Check heater for any shipping damage. If heater is damaged, promptly notify store where you bought heater.
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/ pilot is a required feature for vent-free room heat­ers. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system re­quires no matches, batteries, or other sources to light heater.
THERMOSTATIC HEAT CONTROL
(Thermostat Models Only)
Thermostat models have a thermostat sensing bulb and a control valve. This results in the greatest heater comfort. This can also result in lower gas bills.
Ignitor Button
Control Knob
Heater Cabinet
Front Panel
Plaque
Grill Guard
PRODUCT
IDENTIFICATION
www.desatech.com 5113681-01A
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven­tilation air. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy effi­cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol­lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 5 through 7 will help
you classify your space and provide adequate ven­tilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ven­tilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10
-11
kg per pa-sec-m2) or less with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to ar-
eas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, be­tween wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of these three crite­ria, you must provide additional fresh air. See
Ventilation Air From Outdoors
, page 7.
If your home does not meet all of the three criteria above, proceed to
Determining
Fresh-Air Flow For Heater Location
.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose vol-
ume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an un­confined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m
3
per kw) of the aggregate input rating of all appli­ances installed in that space. Rooms communicat­ing directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills be­tween them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless pas­sageways or ventilation grills between the rooms.
www.desatech.com 113681-01A
6
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft. (volume of space)
Example:
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (vol­ume of space)
If additional ventilation to adjoining room is sup­plied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example:
2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater __________ Btu/Hr Gas water heater* __________ Btu/Hr Gas furnace __________ Btu/Hr Vented gas heater __________ Btu/Hr Gas fireplace logs __________ Btu/Hr Other gas appliances* + __________ Btu/Hr Total = __________ Btu/Hr * Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater _________ Btu/Hr Vent-free heater _________ Btu/Hr Total _________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
________
Btu/Hr (maximum the space can support)
________
Btu/Hr (actual amount of Btu/Hr used)
Example:
51,200 Btu/Hr (maximum the space can support)
60,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi­mum Btu/Hr the space can support. You must pro­vide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an uncon­fined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
AIR FOR COMBUSTION
AND VENTILATION
Continued
C. Install a lower Btu/Hr heater, if lower Btu/Hr size
makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un­confined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be oper­ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section
5.3
or applicable local codes
.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un­confined space. When ventilating to an adjoining unconfined space, you must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
40,000 + 20,000 = 60,000
Figure 2 - Ventilation Air from Inside
Building
Or
Remove Door into Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
www.desatech.com 7113681-01A
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent open­ings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
Do not provide openings for inlet or outlet air into attic if attic has a thermostat-con­trolled power vent. Heated air entering the attic will activate the power vent.
AIR FOR COMBUSTION
AND VENTILATION
Continued
Figure 3 - Ventilation Air from Outdoors
Outlet Air
Ventilated Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified ser­vice person must install heater. Follow all local codes.
CHECK GAS TYPE
Use only the correct type of gas (natural or pro­pane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.
WARNING: This appliance is equipped for (natural or pro­pane/LP) gas. Field conversion is not permitted.
INSTALLATION ITEMS
Before installing heater, make sure you have the items listed below.
• for propane/LP gas, external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• for natural gas, test gauge connection*
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. The optional CSA design­certified equipment shutoff valve can be purchased from your dealer. See Accessories, page 23.
LOCATING HEATER
This heater is designed to be mounted on a wall.
WARNING: Maintain the mini­mum clearances shown in Fig­ure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.
Figure 4 - Mounting Clearances As
Viewed From Front of Heater
Minimum From Sides Of Heater
36"
2"
FLOOR
CEILING
Minimum
Minimum To Top Surface Of Carpeting, Tile Or Other Combustible Material
Left Side
Right Side
10" for 3 & 5 Plaque 8" for 2 Plaque
www.desatech.com 113681-01A
8
You can locate heater on floor, away from a wall. An optional floor mounting stand is needed. Pur­chase the floor mounting stand from your dealer. See Accessories, page 23.
WARNING: Never install the
heater
• in a bathroom
• in a bedroom (3 & 5 plaque models)
• in a recreational vehicle
• where curtains, furniture, cloth­ing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must be at least 18 inches above floor
• locate heater where moving vehicle will not hit it
CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impuri­ties (such as, but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
INSTALLATION
Continued
IMPORTANT:
Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5. If high hu­midity is experienced, a dehumidifier may be used to help lower the water vapor content in the air.
For convenience and efficiency, install heater
• where there is easy access for operation, inspec-
tion, and service
• in coldest part of room An optional fan kit is available from your dealer.
See Accessories, page 23. If planning to use fan, locate heater near an electrical outlet.
THERMOSTAT SENSING BULB
(Thermostat Models Only)
The thermostat sensing bulb has been placed be­low the heater.
1. Place clamp on thermostat sensing bulb as
shown in Figure 5. Clamp is provided in hard­ware package.
2. Snap clamp into upper mounting hole as shown
in Figure 5. Mounting hole is located on lower left edge on back of heater. Make sure the ther­mostat sensing bulb is pointing up.
INSTALLING HEATER TO WALL
Mounting Bracket
Locate mounting bracket in heater carton. Remove mounting bracket from heater carton.
Figure 5 - Attaching Thermostat Sensing
Bulb
Clamp
Thermostat Sensing Bulb
Figure 6 - Mounting Bracket
www.desatech.com 9113681-01A
18 3/4"
Min.
16
1
/2"
Min.
13"
18 3/4"
Min.
13"
Min.
Adjoining Wall
13"
Adjoining Wall
Only Insert Mounting
Screws Through Last
Hole On Each End
Only Insert Mounting
Screws Through Last
Hole On Each End
Floor
Floor
9"
20 1/2"
Min.
9
1
/2"
Min.
Adjoining Wall
Only Insert Mounting
Screws Through Last
Hole On Each End
Floor
Removing Front Panel Assembly Of Heater
1. Remove the two screws, one on each side of front panel assembly.
2. Pull bottom of front panel up and forward, then out.
3. Remove any remaining packaging materials.
Figure 7 - Removing Front Panel
AssemblyOf Heater
Screw
Front Panel Assembly
INSTALLATION
Continued
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall. On the bracket for the 3 and 5 plaque heaters, these two holes are 13 inches apart at centers. On the bracket for the 2 plaque heater, these two holes are 9 inches apart at centers. Attach mounting bracket to wall in one of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Stud: This method provides the
strongest hold. Insert mounting screws through mounting bracket and into wall studs.
Attaching to Wall Anchor: This method allows you
to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Ei­ther method will provide a secure hold for the mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.
5 Plaque Heaters
2 Plaque Heaters
Figure 8 - Mounting Bracket Clearances
WARNING: Maintain mini­mum clearances shown in Fig­ure 8. If you can, provide greater clearances from floor and join­ing wall.
2. Mark screw locations on wall (see Figure 8).
Note:
Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only.
3. Remove tape and mounting bracket from wall.
3 Plaque Heaters
www.desatech.com 113681-01A
10
Placing Heater On Mounting Bracket
1. Locate two horizontal slots on back panel of heater.
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mount­ing bracket.
Figure 11 - Mounting Heater Onto
Mounting Bracket
Mounting Bracket (attached to wall)
Horizontal Slots
Stand-Out Tab
Installing Bottom Mounting Screws
1. Locate two bottom mounting holes. These holes are near bottom on back panel of heater (see Figure 12).
2. Mark screw locations on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screws into hol­low or solid wall, install wall anchors. Fol­low steps 1 through 4 under Attaching To Wall Anchor Method.
If installing bottom mounting screw into wall stud, drill holes at marked locations using 9/64" drill bit.
5. Replace heater onto mounting bracket.
6. Place spacers between bottom mounting holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.
Figure 12 - Installing Bottom Mounting
Screws
Side View
Front View
Wall
Spacer
Heater
INSTALLATION
Continued
Figure 9 - Folding
Anchor
Figure 10 - Popping
Open Anchor Wings
For Thin Walls
Attaching Mounting Bracket To Wall
Note:
Wall anchors, mounting screws, and spac­ers are in hardware package. The hardware pack­age is provided with heater.
Attaching To Wall Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64"
drill bit.
2. Place mounting bracket onto wall. Line up last
hole on each end of bracket with holes drilled in wall.
3. Insert mounting screws through bracket and
into wall studs.
4. Tighten screws until mounting bracket is
firmly fastened to wall studs.
Attaching To Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or masonry)
1. Drill holes at marked locations using 5/16"
drill bit. For solid walls (concrete or masonry), drill at least 1" deep.
2. Fold wall anchor as shown in Figure 9.
3. Insert wall anchor (wings first) into hole. Tap
anchor flush to wall.
4. For thin walls (1/2" or less), insert red key
into wall anchor. Push red key to “pop” open anchor wings.
IMPORTANT:
Do not hammer key!
For thick walls (over 1/2" thick) or solid walls, do not pop open wings.
5. Place mounting bracket onto wall. Line up last
hole on each end of bracket with wall anchors.
6. Insert mounting screws through bracket and
into wall anchors.
7. Tighten screws until mounting bracket is
firmly fastened to wall.
Loading...
+ 22 hidden pages