53-1001792-01
January 31, 2010
Fixed Rack Mount Kit
Installation Procedure
Supporting PowerConnect B-200E, 300, 4100, 4900, 5000, 5100, 5300,
7500 series, 7600, 7800, 8000, AP7420, Encryption Switch, and VA-40FC
53-1001792-01
*53-1001792-01*
Notes, Cautions, and Warnings
A NOTE indicates important information that helps you make better use of your computer.
See the safety and regulatory information that shipped with your system. For additional regulatory
information, see the Regulatory Compliance Homepage on www.dell.com at the following location:
www.dell.com/regulatory_compliance.
A CAUTION indicates potential damage to hardware or loss of data if instructions are not followed.
A DANGER indicates a potential for property damage, personal injury, or death.
____________________
Information in this document is subject to change without notice.
© 2009 Dell Inc. All rights reserved.
Reproduction of these materials in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell, the DELL logo, Inspiron, Dell Precision, Dimension, OptiPlex, Latitude, PowerEdge, PowerVault, PowerApp, Dell
OpenManage and the YOURS IS HERE
in the U.S. and other countries; Microsoft, Windows, Windows Server, MS-DOS and Windows Vista are either trademarks or registered trademarks
of Microsoft Corporation in the United States and/or other countries.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products.
Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
Regulatory Model Codes: Brocade DCX-4S, Brocade DCX
2 Fixed Rack Mount Kit Installation Procedure
logo are trademarks of Dell Inc.; Intel, Pentium, and Celeron are registered trademarks of Intel Corporation
53-1001792-01
In this guide
•Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
•Installation requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
•Tool requirements and parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
•Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Introduction
This document provides instructions to install a 1U, 1.5U, or 2U switch (or SAN Router) in a 19-in. (48.3 cm) EIA
cabinet using the Fixed Rack Mount Kit.
The supported switches are listed in Table 1. The switch can be installed so that the port side is either flush with the
front rails or recessed from the front rails. A recessed position allows a more gradual bend in the fiber optic cables
connected to the switch.
TABLE 1 Supported switches
Switch Height Switch Model
1U PowerConnect B-200E
PowerConnect B-300
PowerConnect B-4100
PowerConnect B-5000
PowerConnect B-5100
PowerConnect B-7500 series
PowerConnect B-7600
PowerConnect B-7800
PowerConnect B-8000
PowerConnect B-VA-40FC
2U PowerConnect B-4900
PowerConnect B-5300
PowerConnect B-AP7420
Brocade Encryption Switch
Installation requirements
Allow 15 to 30 minutes to complete this procedure. Note the following requirements to ensure correct installation
and operation:
• Provide space in a 19-in. (48.3 cm) EIA cabinet, as required for the switch type, with a minimum distance of
28.25 in. (71.76 cm) and a maximum distance of 29.88 in. (75.90 cm) between the front and back rails.
• Verify that the additional weight of the switch does not exceed the cabinet’s weight limits.
Fixed Rack Mount Kit Installation Procedure 3
53-1001792-01