Data sheet Electric Actuators with Spring Function
Code No.
Style
Description
Signal
* code no. 003Z0694 adapter is required to mount to the AB-QMvalve
Type
AME 25SU
AME 25SD
Power supply
24 VAC, +10…-15%
Power consumption
14 VA
Frequency
50 Hz / 60 Hz
0…10VDC (2…10VDC) Ri=24k
0…20mA (4…20mA) Ri=500Ω
3-point Floating
Output signal, X
0…10V (2…10V)
Safety function
Normally open
Normally closed
Actuator force
101.1 lbf (450N)
Max. stroke
15mm
Speed
15 s/mm
Max. medium temperature
302°F (150°C)
Enclosure rating
NEMA 2
Weight
5.1 lb (2.3 kg)
AME 25SU/SD
For ABQM, Pressure Independent Control Valve AME25SU, AME25SD
Ordering:
Technical Data:
082H3041
082H3038
AME 25SU
AME25SD
The AME 25 series of low voltage electronic actuators are proportionally controlled and internally incorporate a safety spring function. In the event of power loss, the actuator will return to either a normally open or normally closed position depending on the style selected (spring up-SU or spring down-SD). These series of actuators are mounted to ABQM valves in sizes of 1-½” to 4” valves.
Electric actuator with safety spring open function
Electric actuator with safety spring down function
Proportional &
3-point floating
Control input, Y
1
VDHUA322Danfoss 6/2016
Data sheet Electric Actuators with Spring Function
For ABQM, Pressure Independent Control Valve AME25SU, AME25SD
Installation Orientation:
Manual Override:
Dimensions:
The actuator should be mounted with the valve stem either horizontal or pointing upwards. Use a 4 mm Allen key (not supplied) to fit the actuator to the valve body. Allow necessary clearance for maintenance purposes. During commissioning, the movement of the actuator (e.g. opens for heat) can be indicated by fitting red and blue pins (supplied) at either end of the position indication scale.
On spring versions manual override is achieved by disconnecting the power supply, removing the cover and inserting a 5 mm Allen key (not supplied) into the top of the positioning spindle and turning the key against the spring. Observe the direction of rotation symbol. To hold a manual override position, the key must be wedged.
If manual override has been used then X and Y signal are not correct until the actuator reaches its end position. Another alternative to correct this is to reset the actuator.