Installation Guide
AME 13
AME 13 + AME 13 + AME 13 + AME 13 + AME 13 +
VM 2 (DN 15-25) VB 2 (DN 15, 20) VRBZ (DN 20-40) VZ (DN 15, 20) AVQM (DN 15, 20)
VS 2 (DN 20, 25) VZL (DN 15, 20)
ENGLISH
DANSK
DEUTSCH
FRANÇAIS
ESPAÑOL
NEDERLANDS
SUOMI
POLSKI
РУССКИЙ
中文
AME 13 www.danfoss.com Page 4
AME 13
AME 13
AME 13 www.danfoss.fr Page 7
AME 13
AME 13 www.danfoss.nl Page 9
AME 13 www.danfoss. Sivu 10
AME 13 www.danfoss.pl Strona 11
AME 13 www.danfoss.ru Страница 12
AME 13
www.danfoss.dk
www.danfoss.de
www.danfoss.es
www.danfoss.com.cn
Side 5
Seite 6
Page 8
第14页
Danfoss Heating EI.96.J2.8C DH-SMT/SI
1
Installation Guide AME 13
➊
❷
❸
❹ ❺
2
DH-SMT/SI EI.96.J2.8C Danfoss Heating
Installation Guide AME 13
❻
❽
❼
❾
❿
Danfoss Heating EI.96.J2.8C DH-SMT/SI
33
Installation Guide AME 13
LANGUAGEENGLISH
Safety Note
To avoid injury and damage to persons
and devices, it is absolutely necessary
these instructions are carefully read
and observed prior to assembly and
commissioning.
Necessary assembly, start-up, and
maintenance work must be performed
only by qualied, trained and authorised
personnel.
Prior to assembly and maintenance work
on the controller, the system must be:
- depressurised
- cooled down
- emptied and
- cleaned
Please comply with the instructions of the
system manufacturer or system operator.
Do not remove the cover before the
power supply is fully switched o.
Disposal instruction
This product should be
dismantled and its
components sorted, if
possible, in various groups
before recycling or disposal.
Always follow the local disposal
regulations.
Mounting ➊
Fix the AME 13 on the valve ❷.
Wiring ❸
Do not touch anything on the PCB!
Switch o the power line before wiring
the actuator! Lethal voltage!
Wire the actuator according to the wiring
diagram.
Output signal
Output signal from the terminal X can be
used for indication of the current position.
Range depends on the DIP switch settings.
Supply voltage
Supply voltage (24 V~ -15 to +10%, 50 Hz)
must be connected to the terminals SN
and SP.
DIP switch settings
ALL switches are on OFF position!
All combinations of DIP switches are
allowed. All functions that are selected are
added consecutively. There is only one logic
override of functionalities i.e. the switch No.6
Proportional /3 point, which sets actuator to
ignore control signal and works as a “simple”
3-point actuator.
SW1: U/I ❹
voltage control signal (0-10 V).
SW2: 2-10 V/0-10 V ❺
2-10 V.
SW3: Direct/Inverse ❻
DIRECT
SW4: ---/Sequential ❼
Two actuators can be set to work parallel
with one control signal. If the SEQUENTIAL
is set than an actuator responds to split
control signal (see 0(2)-5(6) V/5(6)-10 V).
This combination works in combination with
switch No.5: 0(2)-5(6) V/5(6)-10 V.
U I
2 V_---V 0 V_- --V
Direct Inv erse
--- Se quential
0(2) V_5(6) V 5(6) V_10 V
Proport ional 3 point/ RL
Reset Res et
Factory settings:
NOTE:
Factory setting is:
Factory setting is:
Factory setting is:
NOTE:
SW6: Proportional/3 point ❾
Actuator can operate as “simple” 3-point
actuator, if the 3-point function is selected.
Power supply should be connected on
SN and SP ports. On port 1 or 3 24 VAC
signal is connected for rising or lowering
of actuator. Return signal X indicates the
correct position.
NOTE:
if 3 point function is selected actuator does
not respond to any control signal on port Y.
It only rises and lowers spindle if power is
supplied on port 1 or 3.
SW7: Not in use
SW8: Not in use
SW9: Reset ❿
After the actuator has been connected
to power supply, the actuator will start
the self-adjustment procedure. The
indicator LED ashes until self adjustment
is nished. The duration depends on the
spindle travel and will normally last a few
minutes. The stroke length of the valve is
stored in the memory after self adjustment
has been completed. To restart self
adjustment, change the position of RESET
switch (switch No.9). If the supply voltage
is switched o or falls below 80 % in more
than 0.1 s, the current valve position will be
stored in the memory and all data remain
saved in the memory also after a power
supply cut-out.
Function test
The indicator light shows whether the
positioner is in operation or not. Moreover,
the indicator shows the control status and
faults.
Constant light
- normal operation
No light
- no operation or no power supply
Intermittent light (1 Hz)
- self adjusting-mode
Intermittent light (3 Hz):
- power supply too low
- insucient valve stroke (<20 s)
- end-position cannot be reached.
Control signal
Control signal from the controller must be
connected to terminals Y (input signal) and
SN (common) on the AME printed board.
4
DH-SMT/SI EI.96.J2.8C Danfoss Heating
SW5: 0(2)-5(6) V/5(6)-10 V ❽
NOTE:
This function is available if switch No.4: ---/
Sequential is set.
Installation Guide AME 13
DANSK
Sikkerhedsbestemmelser
For at undgå personskader og
erstatningsskader på produkter, er det
absolut nødvendig at gennemlæse
følgende instruktion.
Montering, opstart og vedligeholdelse må
kun foretages af kvaliceret og autoriseret
personale.
Forud for monterings- og
vedligeholdelsesarbejde på
regulatorenskal systemet være:
- trykløst
- nedkølet
- tømt
- rengjort
Leverandørens retningslinier skal følges.
Fjern ikke dækslet, før strømforsyningen
erhelt koblet fra.
Bortskaelsesinstruktion
Dette produkt skal, om muligt,
adskilles og sorteres i dets
forskellige materialegrupper,
før det genbruges eller
bortskaes.
Følg altid de lokale regulativer for
bortskaelse.
Montering ❶
Fastgør AME 13 på ventilen ❷.
Elektrisk tilslutning ❸
Forsyningsspænding
Forsyningsspændingen (24 V~ -15/+10%,
50 Hz) skal tilsluttes klemme SN og SP.
Indstilling af DIP kontakter
Alle kontakter er I OFF position!
Alle kombinationer af kontaktindstillinger
er tilladelige. Alle funktionsvalg er
tilføjet en efter en. Der er kun en logisk
overskridelse af funktionaliteten: Kontakt
Nr. 6 Proportional/3-punkt styring, som
sætter aktuatoren i stand til at ignorere
reguleringssignalet og arbejde som en
”simpel” 3- punkt motor
U/I ❹
Spændingssignal (0 - 10 V).
2 V-10/0V-10 V ❺
2-10 V.
Direkte/Indirekte ❻
DIREKTE
---/Sekvens ❼
To aktuatorer kan arbejde parallelt med et
reguleringssignal.
I SEKVENS indstilling reagerer aktuatoren
på delt styresignal (se 0(2)-5(6) V/5(6)-10 V).
U I
2 V_---V 0 V_- --V
Direkte I ndirekte
--- Sek vens
0(2) V_5(6) V 5(6) V_10 V
Proport ional 3-punk t/RL
Reset Res et
Fabriksindstilling:
Bemærk:
Fabriksindstilling
Fabriksindstilling:
Fabriksindstilling:
3 tilsluttes 24 VAC signal til åbne- lukke
funktion af aktuatoren. Udgangssignal X
indikerer korrekt position.
Bemærk:
Hvis 3-punkt funktionen er valgt, reagerer
aktuatoren ikke på signaler på klemme Y.
Motorspindelen bevæger sig kun opad eller
nedad ved signaler på klemme 1 eller 3.
Reset ❿
Efter tilslutning af forsyningsspænding,
vil aktuatoren starte en selvjusterings
procedure. LED indikatoren blinker indtil
selvjusteringen er færdig. Varigheden
afhænger af spindelvandringen og tager
normalt nogle få minutter. Ventilens
spindelvandring lagres i hukommelsen
efter selvjusteringen er færdig. For at
starte selvjustering, skiftes positionen
af RESET kontakten (kontakt Nr. 9). Hvis
forsyningsspændingen svigter eller
falder til under 80 % i mere end 0,1
sekund, vil den aktuelle ventilposition
lagres i hukommelsen og alle data bliver
bevaret i hukommelsen, også efter at
forsyningsspændingen afbrydes.
Funktions test
Lysdioden indikerer, om aktuatoren er
i drift, ligesom den viser driftsstatus og
eventuelle fejl.
• Konstant lys
- normal drift
• Intet lys
- ikke i drift, ingen strømforsyning
• Interval blink (1 Hz)
- selvjusteringsmodul
• Interval blink (3 Hz)
- strømforsyning for lav
- ventil slaglængde utilstrækkelig
- endestilling kan ikke nås
Rør ikke ved PCB!
Sluk for strømmen inden elektrisk
tilslutning af motoren! Kan være livsfarlig!
Tilslut motoren iht. ledningsdiagrammet.
Bemærk:
Denne kombination arbejder sammen med
kontakt Nr. 5: 0(2)-5(6) V/5(6)-10 V
0(2)-5(6) V/5(6)-10 V ❽
Styresignal
Styresignalet fra regulatoren skal tilsluttes
terminal Y (indgangssignal) og SN (fælles)
på AME´s klemrække.
Udgangssignal
Udgangssignal fra terminal X kan anvendes
til indikering af aktuel position.
Området afhænger af DIP kontakternes
indstilling.
Danfoss Heating EI.96.J2.8C DH-SMT/SI
Bemærk:
Denne funktion er tilgængelig hvis kontakt
Nr. 4:---/Sekvens er indstillet.
Proportional/3-punkt ❾
Aktuatoren arbejder som en “simpel”
3-punkt aktuator, hvis 3-punkt funktionen
er valgt. Forsyningsspænding tilsluttes
klemmerne SN og SP. På klemmerne 1 og
55