To avoid injury of persons and damages
to the device, it is absolutely necessary
to read and observe these instructions
carefully.
Necessary assembly, start-up, and
maintenance work must be performed by
qualified and authorized personnel only.
Prior to assembly and depressurizing the
system.
Please comply with the instructions of the
system manufacturer or system operator.
Mounting
Fix the AME 10 on the valve.
Wiring
Control signal
Control signal from the controller must be
connected to terminals Y (input signal) and
SN (common) on the AME printed board.
Output signal
Output signal from the terminal X can be
used for indication of the current position.
Range depends on the DIP switch settings.
Supply voltage
Supply voltage
(24 V~ -15 to +10%, 50 Hz) must be
connected to the terminals SN and SP.
1
2
DIP switch settings
Factory settings:
ALL switches are on OFF position!
Note:
All combinations of DIP switches are
allowed. All functions that are selected are
added consecutively. There is only one logic
override of functionalities i.e. the switch No.6
Proportional / 3 point, which sets actuator to
ignore control signal and works as a “simple”
3-point actuator.
SW1:
4
U/I
Actuator can responde to a voltage or
current control signal. With switch No.1: U/I
actuator can be set either to operate with
a voltage control signal (actuator responds
to signal between 0 … 10 V), or current
control signal (actuator responds to signal
between 0 … 20 mA).
Factory setting:
voltage control signal (0 … 10 V).
3
SW2:
2V … 10 / 0V … 10
Actuator can be set to response on a
control signal from 2 V, or 0 V. If the
actuator is set to current signal than it
responds to control signal from 4 mA or
0 mA.
Factory setting is:
2 … 10V.
SW3:
Direct/Inverse
Actuator can be set for spindle to travel
downwards on rising control signal
(DIRECT), OR for spindle to travel upwards
on rising control signal (INVERSE).
Factory setting is:
DIRECT
SW4:
---/Sequential
Two actuators can be set to work parallel
with one control signal. If the SEQUENTIAL
is set than an actuator responds to split
control signal (see 0(2) V … 5(6 V) /
6(6) V … 10 V).
Note:
This combination works in combination with
switch No.5: 0(2) V … 5(6 V) / 6(6) V … 10 V
SW5:
0(2) V … 5(6 V)/6(6) V … 10 V 8
Note:
This function is available if switch No.4:
--- / Sequential is set.
Actuator can be set to match the range of the
control signal:
2 … 6 V (switch No.2: 2 V … 10)
0 … 5 V (switch No.2: 0 V … 10)
4 … 12 mA (switch No.2: 2 V … 10)
0 … 10 mA (switch No.2: 0 … 10)
OR
6 … 10 V (switch No.2: 2 V … 10)
5 … 10 V (switch No.2: 0 V … 10)
12 … 20 mA (switch No.2: 2 V … 10)
10 … 20 mA (switch No.2: 0 … 10)
SW6:
Proportional/3 point 9
Actuator can operate as “simple” 3-point
actuator, if the 3-point function is selected.
Power supply should be connected on
SN and SP ports. On port 1 or 3 24 VAC
signal is connected for rising or lowering
of actuator. Return signal X indicates the
correct position.
Note:
If 3 point function is selected actuator does
not respond to any control signal on port Y.
It only rises and lowers spindle if power is
supplied on port 1 or 3.
5
6
7
SW7:
LOG/LIN - Not in use
SW8:
100% kvs/Reduced kvs - Not in use
SW9:
10
Reset
After the actuator has been connected to
power supply, the actuator will start the
self-adjustment procedure. The indicator
LED flashes until self adjustment is finished.
The duration depends on the spindle travel
and will normally last a few minutes. The
stroke length of the valve is stored in the
memory after self adjustment has been
completed. To restart self adjustment,
change the position of RESET switch
(switch No.9). If the supply voltage is
switched off or falls below 80% in more
than 0.1 s, the current valve position will be
stored in the memory and all data remain
saved in the memory also after a power
supply cut-out.
Function test
The indicator light shows whether the
positioner is in operation or not. Moreover,
the indicator shows the control status and
faults.
Constant light
- normal operation
No light
- no operation or no power supply
Intermittent light (1 Hz)
- self adjusting-mode
Intermittent light (3 Hz):
- power supply too low
- insufficient valve stroke (<20 s)
- end-position cannot be reached.
DANSK
Sikkerhedsbestemmelser
For at undgå personskader og
erstatningsskader på produkter, er det
absolut nødvendig at gennemlæse
følgende instruktion.
Montering, opstart og vedligeholdelse må
kun foretages af kvalificeret og autoriseret
personale.
Før montering eller demontering skal
anlægget gøres trykløst.
Leverandørens retningslinier skal følges.
Montering
Fastgør AME 10 på ventilen.
Elektrisk tilslutning
Styresignal
Styresignalet fra regulatoren skal tilsluttes
terminal Y (indgangssignal) og SN (fælles)
på AME´s klemrække.
Udgangssignal
Udgangssignal fra terminal X kan anvendes
til indikering af aktuel position.
Området afhænger af DIP kontakternes
indstilling.
Forsyningsspænding
Forsyningsspændingen (24 V~ -15/+10%,
50 Hz) skal tilsluttes klemme SN og SP
1
2
Indstilling af DIP kontakter
Fabriksindstilling:
Alle kontakter er I OFF position!
Bemærk:
Alle kombinationer af kontaktindstillinger
er tilladelige. Alle funktionsvalg er tilføjet en
efter en. Der er kun en logisk overskridelse af
funktionaliteten: Kontakt Nr. 6 Proportional
/ 3-punkt styring, som sætter aktuatoren i
stand til at ignorere reguleringssignalet og
arbejde som en ”simpel” 3- punkt motor
3
2V…10/ 0V…10
Aktuatoren kan indstilles til at reagere på
signaler fra 2V, eller 0V.
Er aktuatoren indstillet til strømsignal,
reagerer aktuatoren på signaler fra 4mA
eller 0mA.
Fabriksindstilling:
2 … 10V.
Direkte / Indirekte
Aktuatoren kan indstilles til nedadgående
spindel ved stigende kontrolsignal
(DIREKTE)
Eller opadgående spindel ved stigende
kontrolsignal (INDIREKTE)
Fabriksindstilling:
DIREKTE
---/ Sekvens
To aktuatorer kan arbejde parallelt med et
reguleringssignal.
I SEKVENS indstilling reagerer aktuatoren
på delt styresignal (se 0(2)V…5(6V) /
6(6)V…10V).
Bemærk:
Denne kombination arbejder sammen med
kontakt Nr. 5: 0(2)V…5(6V) / 6(6)V…10V
0(2)V…5(6V) / 6(6)V…10V8
Bemærk:
Denne funktion er tilgængelig hvis kontakt
Nr. 4:---/ Sekvens er indstillet. Aktuatoren kan
afpasses til styresignalet:
2 … 6 V (kontakt Nr.2: 2 V … 10)
0 … 5 V (kontakt Nr.2: 0 V … 10)
4 … 12 mA (kontakt Nr.2: 2 V … 10)
0 … 10 mA (kontakt Nr.2: 0 … 10)
Eller
6 … 10 V (kontakt Nr.2: 2 V … 10)
5 … 10 V (kontakt Nr.2: 0 V … 10)
12 … 20 mA (kontakt Nr.2: 2 V … 10)
10 … 20 mA (kontakt Nr.2: 0 … 10)
5
6
7
10
Reset
Efter tilslutning af forsyningsspænding,
vil aktuatoren starte en selvjusterings
procedure. LED indikatoren blinker indtil
selvjusteringen er færdig. Varigheden
afhænger af spindelvandringen og tager
normalt nogle få minutter. Ventilens
spindelvandring lagres i hukommelsen
efter selvjusteringen er færdig. For at
starte selvjustering, skiftes positionen
af RESET kontakten (kontakt Nr. 9). Hvis
forsyningsspændingen svigter eller
falder til under 80% i mere end 0,1
sekund, vil den aktuelle ventilposition
lagres i hukommelsen og alle data bliver
bevaret i hukommelsen, også efter at
forsyningsspændingen afbrydes.
Funktions test
Lysdioden indikerer, om aktuatoren er
i drift, ligesom den viser driftsstatus og
eventuelle fejl.
Konstant lys
- normal drift
Intet lys
- ikke i drift, ingen strømforsyning
Interval blink (1Hz)
- selvjusteringsmodul
Interval blink (3 Hz)
- strømforsyning for lav
- ventil slaglængde utilstrækkelig
- endestilling kan ikke nås
4
U / I
Aktuatoren kan modtage
reguleringssignaler i spænding eller
strøm. Med kontakt Nr.1: U / I kan
aktuatoren indstilles til at arbejde med
spændings- signal (aktuatoren reagerer på
signal mellem 0…10V), eller strømsignal
(aktuatoren reagerer på signal mellem
0…20mA).
Aktuatoren arbejder som en “simpel”
3-punkt aktuator, hvis 3-punkt funktionen
er valgt. Forsyningsspænding tilsluttes
klemmerne SN og SP. På klemmerne 1 og
3 tilsluttes 24 VAC signal til åbne- lukke
funktion af aktuatoren. Udgangssignal X
indikerer korrekt position.
Bemærk:
Hvis 3-punkt funktionen er valgt, reagerer
aktuatoren ikke på signaler på klemme Y.
Motorspindelen bevæger sig kun opad eller
nedad ved signaler på klemme 1 eller 3.
Um Verletzungen an Personen und
Schäden am Gerät zu vermeiden, diese
Anleitung unbedingt beachten.
Montage, Inbetriebnahme und
Wartungsarbeiten dürfen nur von
sachkundigen und autorisierten Personen
durchgeführt werden. Anlage vor Montage,
Demontage unbedingt drucklos machen.
Die Vorgaben des Anlagenherstellers und
Anlagenbetreibers sind zu beachten.
Montage
AME 10 am Ventil ansetzen.
Elektrischer Anschluß
Steuersignal
Das Steuersignal des Reglers ist an Klemme
Y (Eingangssignal) und Klemme SN
(Sammelklemme) an der AME-Printplatte
anzuschließen.
Ausgangssignal
Das Ausgangssignal von Klemme X kann
zur Anzeige der aktuellen Position benutzt
werden. Der Bereich hängt von der Brücke
ab.
Spannungsversorgung
Die Spannungsversorgung (24 V~ -15 bis
+10%, 50 Hz) ist an Klemme SN und SP
anzuschließen.
1
2
Einstellung der DIP Brücke
WERKSEINSTELLUNG:
ALLE Schalter sind in der Position OFF!
BEMERKUNG:
alle Kombinationen von DIP Schalter
sind erlaubt. Gewählte Funktionen sind
hintereinandergelegt. Es gibt nur eine
logische Umsteuerung der Funktionen:
Brücke Nr.6 proportional / 3-Punkt. Dadurch
wird der Antrieb so umgeschaltet, dass
das Signal ignoriert wird und arbeitet als
“üblicher” 3-Punkt Anrieb.
4
U/I
Antrieb kann auf Strom- oder
Spannungsregelsignale reagieren. Mit
dem Schalter No.1: U/I kann der Antrieb
zwischen Spannungsregelsignal (Antrieb
reagiert auf Y Signal von 0 bis 10 V), oder
Stromregelsignal (Antrieb reagiert auf
Signal von 0…20 mA).
Werkseinstellung:
Spannungsregelsignal (0 … 10V).
3
2 V…10 / 0 V…10
Antrieb kann auf Spannungsregelsignal
von 2 V, oder 0V reagieren. Wenn der
Antrieb auf Stromsignal eingestellt ist,
reagiert auf Regelsignal vom 4 mA oder
0 mA.
Werkseinstellung:
2 … 10 V .
Direct/Inverse
Der Antrieb kann so eingestellt werden,
dass die Motorenspindel nach unten
bewegt bei steigendem Steuersignal
(DIRECT), ODER dass die Motorenspindel
nach oben bewegt bei steigendem
Steuersignal (INVERSE).
Werkseinstellung:
DIRECT
---/Sequentiell
Zwei Antriebe können parallel mit einem
Steuersignal arbeiten. Bei der Einstellung
SEQUENTIAL Antrieb reagiert auf geteilten
Steuersignal (sehe 0(2) V … 5(6 V) /
6(6) V … 10V).
BEMERKUNG:
Diese Kombination funktioniert mit dem
Schalter No.5: 0(2) V … 5(6 V) / 6(6) V … 10 V
0(2) V … 5(6 V)/6(6) V … 10 V
BEMERKUNG:
diese Funktion ist wirksam, wenn der Schalter
No.4: --- / Sequentiell eingestellt ist. Antrieb
kann auf den Steuersignalbereich angepasst
werden:
2 … 6 V (Schalter No.2: 2 V … 10)
0 … 5 V (Schalter No.2: 0 V … 10)
4 … 12 mA (Schalter No.2: 2 V … 10)
0 … 10 mA (Schalter No.2: 0 … 10)
ODER
6 … 10 V (Schalter No.2: 2 V … 10)
5 … 10 V (Schalter No.2: 0 V …1 0)
12 … 20 mA (Schalter No.2: 2 V … 10)
10 … 20 mA (Schalter No.2: 0 … 10)
Proportionäl/3-Punkt
Bei der gewählten 3-Punkt Funktion kann
der Antrieb als “einfacher” 3-Punkt Antrieb
arbeiten. Die Spannungsversorgung ist an
Klemme SN und SP anzuschließen. Auf der
Klemme 1 oder 3 = 24 VAC Steuersignal
sorgt für stetigen oder absenken der
Antriebs. Das Ausgangssignal von Klemme
X kann zur Anzeige der aktuellen Position
benutzt werden.
BEMERKUNG:
wenn die 3-Punkt Funktion gewählt wird,
reagiert der Antrieb nicht auf irgendwelche
der Steuersignale Y Klemme. Der Antrieb
bewegt die Motorenspindel nach oben oder
nach unten bei dem Steuersignal auf Klemme
1 oder 3.
5
6
7
8
9
10
Reset
Nach Einschalten der Stromversorgung
startet der Regelantrieb den
Selbstanpassungsvorgang. Die
Leuchtdiode blinkt, bis die Anpassung
abgeschlossen ist. Dies dauert
normalerweise einige Minuten,
abhängig von der Distanz der
Spindelbewegung. Die Hublänge des
Ventils wird nach abgeschlossener
Selbstanpassung im Speicher registriert.
Der Selbstanpassungsvorgang kann durch
Drücken der RESET-Taste wiederholt
werden (Schalter No. 9). Bei Ausfall der
Versorgungsspannung - oder beim
Absinken auf einen Wert kleiner 80%
- länger als 0,1 s, wird die aktuelle
Ventilposition im Speicher gespeichert.
Alle Daten sind also auch im Falle einer
Stromunterbrechung gesichert.
Funktionstest
Die Leuchtdiode zeigt den Motorbetrieb,
den Betriebszustand und eventuelle Fehler
an.
Dauerlicht
- normaler Betrieb
Kein Licht
- nicht in Betrieb oder keine
Stromversorgung
Blinklicht (1 Hz)
- Selbstanpassungsmodus
Blinklicht (3 Hz)
- Versorgungsspannung zu niedrig
- Ventilhublänge ungenügend (<20 s)
- Endposition nicht erreichbar.