READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN
YOUR FILES FOR FUTURE REFERENCE.
Before operating the unit, make sure the installation has
been carried out correctly by a professional Daikin dealer.
If you feel unsure about operation, contact your Daikin
Dealer for advice and information.
NTRODUCTION
I
Thank you for purchasing this Daikin inverter chiller.
Packaged air-cooled water chillers and
packaged reversible air to water heat pumps
age
P
This manual
This manual describes how to start up and switch off the unit, set
parameters and configure the schedule timer by means of the
controller, maintain the unit and solve operational problems.
For “Checks before initial start-up” and “Initial start-up”
procedures refer to the “Installation manual” of this unit.
This unit
This unit is designed for outdoor installation and used for both
heating and cooling applications. The unit is designed to be
combined with fan coil units or air handling units for air conditioning
purposes.
This chiller range consists of 2 main versions: a heat pump (EWYQ)
version and a cooling only (EWAQ) version, available in 3 standard
sizes (5 kW, 6 kW and 7 kW).
Operation manual
O
PERATING
Operating the unit comes down to operating the digital controller.
Never let the digital controller get wet. This may cause an
electric shock or fire.
Never press the buttons of the digital controller with a hard,
pointed object. This may damage the digital controller.
Never service the digital controller yourself, ask a qualified
service person to do this.
Features and functions
The digital controller is a state of the art controller that offers full
control over your installation. It can control a cooling/heating and a
cooling only installation.
Both installations are available in multiple versions which vary in
capacity.
NOTE
Basic controller functions
The basic controller functions are:
Tu r ning the unit ON/OFF.
Operation mode change-over:
- heating (refer to "Heating operation (h)" on page 3),
- cooling (refer to "Cooling operation (c)" on page 3),
- quiet mode (refer to "Quiet mode operation (s)" on page 3).
Temperature set point adjustment (refer to "Controller
operations" on page 3).
Clock function
The clock functions are:
24 hour real time clock.
Day of the week indicator.
Schedule timer function
The schedule timer function allows the user to schedule the
operation of the installation according to a daily or a weekly program.
THE
DIGITAL
Some functions described in this manual may not be
available or should not be available. Ask your installer
or your local Daikin dealer for more information on
permission levels.
CONTROLLER
Main components
The main components of the system are:
The digital controller which allows the complete configuration
and follow-up of the system.
The manometer which indicates the pressure in the closed
water circuit.
The safety valve which prevents the pressure in the closed water
circuit from exceeding 3 bar.
Operation manual
1
EWAQ+EWYQ005~007ACV3P
Packaged air-cooled water chillers and
packaged reversible air to water heat pumps
4PW33164-1B
1
2
3
h
4
5
6
7
8
9
Name and function of buttons and icons
13
56 228
7
9
12
10
21
20
30
26
24
27
25
ON/OFF BUTTON o
The ON/OFF button starts or stops the controller.
Pressing the ON/OFF button consecutively too many times may
cause malfunction of the system (maximum 20 times per hour).
OPERATION LED 0
The operation LED is lit during cooling or heating operation. The
LED blinks if a malfunction occurs. When the LED is OFF,
cooling or heating are inactive.
OPERATION MODE ICONS hcs
These icons indicate the current operation mode(s): heating (h),
cooling (c) or quiet mode (s). Quiet mode is a feature of the
cooling or heating operation mode. When quiet mode is
activated, the quiet mode icon and the heating or cooling mode
icon will be displayed simultaneously.
In a cooling only installation, the
CENTRALIZED CONTROL e
This icon indicates that the unit is in remote off mode, cooling
mode or heating mode. This disables some functions of the
remote controller.
DAY OF THE WEEK INDICATOR 1234567
This indicator shows the current weekday.
When reading or programming the schedule timer, the indicator
shows the set day.
CLOCK DISPLAY 8
The clock display shows the current time.
When reading or programming the schedule timer, the clock
display shows the action time.
SCHEDULE TIMER ICON p
This icon indicates that the schedule timer is enabled.
ACTION ICONS q
These icons indicate the programming actions for each day of
the schedule timer.
OFF ICON x
This icon indicates that the OFF action is selected when
programming the schedule timer.
INSPECTION REQUIRED k and l
These icons indicate that inspection is required on the
installation. Consult your Daikin Dealer.
SET TEMPERATURE DISPLAY 9
The display shows the current set temperature of the
installation.
21615
icon will never be displayed.
10
11
12
13
14
15
16
17
18
19
25
26
27
28
SETTING $
Not used. For installation purposes only.
NOT AVAILABLE n
This icon is displayed whenever a function is not available in
your configuration.
n
may also appear due to the
restrictions of the user permission level set by the installer.
DEFROST MODE ICON d
This icon indicates that the defrost mode is active.
4
14
19
17
9
18
13
COMPRESSOR ICON ç
This icon indicates that the compressor in the outdoor unit of the
installation is active.
PUMP ICON é
This icon indicates that the circulation pump is active.
23
OUTDOOR TEMPERATURE DISPLAY u
When this icon is flashing, the outdoor ambient temperature is
displayed.
WEATHER DEPENDENT SET POINT ICON a
29
28
This icon indicates that the controller will adapt the temperature
set point automatically, based on the outdoor ambient
temperature.
TEMPERATURE ICON b
This icon is displayed together with the temperature set point,
the water outlet temperature or the outdoor ambient
temperature.
The icon is also displayed when the temperature set point is set
in schedule timer programming mode.
20TEST OPERATION ICON t
This icon indicates that the unit runs in test mode. Refer to the
installation manual.
21FIELD SET CODE ;
This code represents the code from the field set list. Refer to the
installation manual.
22ERROR CODE :
This code refers to the error code list and is for service purposes
only. Refer to the service manual.
23HEATING/COOLING BUTTON =
This button allows manual switching between cooling or heating
mode (provided the unit is not a “cooling only” unit).
24WEATHER DEPENDENT SET POINT BUTTON ba
This button enables or disables the weather dependent set point
function which is available in space heating operation only.
INSPECTION/TEST OPERATION BUTTON z
This button is used for installation purposes only. Refer to the
installation manual.
PROGRAMMING BUTTON <
This multi-purpose button is used to program the controller. The
function of the button depends on the actual status of the
controller or on previous actions carried out by the operator.
SCHEDULE TIMER BUTTON pr
The main function of this multi-purpose button is to enable/
disable the schedule timer.
The button is also used to program the controller. The function of
the button depends on the actual status of the controller or on
previous actions carried out by the operator.
If the controller is set in permission level 2 (refer to the
installation manual), the schedule timer button will not be
operational.
TIME ADJUST BUTTON pi and pj
These multi-purpose buttons are used to adjust the clock, to
toggle between temperatures (water outlet temperature and
outdoor ambient temperature) and in schedule timer
programming mode.
EWAQ+EWYQ005~007ACV3P
Packaged air-cooled water chillers and
packaged reversible air to water heat pumps
4PW33164-1B
Operation manual
2
TEMPERATURE ADJUST BUTTONS bi and bj
These multi-purpose buttons are used to adjust the current set
point in normal operation mode or in schedule timer
programming mode. In weather dependent set point mode the
buttons are used to adjust the shift value. Finally, the buttons are
also used to select the weekday while setting the clock.
QUIET MODE BUTTON s
This button enables or disables quiet mode.
NOTE
Buttons that are not described above are not used in
this configuration. Pressing these buttons (w,
wbj and wbi) has no influence on the
operation. When these buttons are pressed,
n will be displayed.
Setting up the controller
After initial installation, the user can set the clock and day of the
week.
The controller is equipped with a schedule timer that enables the
user to schedule operations. Setting the clock and day of the week is
required to be able to use the schedule timer.
Setting the clock
Hold down the pr button for 5 seconds.
The clock read-out and the day of week indicator start flashing.
Use the pi and pj buttons to adjust the clock.
Each time the pi or pj button is pressed, the time will
increase/decrease by 1 minute. Keeping the pi or pj
button pressed will increase/decrease the time by 10 minutes.
Use the bi or bj button to adjust the day of the week.
Each time the bi or bj button is pressed the next or
previous day is displayed.
Press the < button once to confirm the current set time and day
of the week.
If no button is pressed for 5 minutes, while the clock and day of
the week read-out are still flashing, the clock and day of the
week will return to their previous setting and the clock setting
function will no longer be active.
NOTE
Setting the schedule timer
To set the schedule timer, refer to chapter "Programming and
consulting the schedule timer" on page 5.
The clock needs to be set manually. Adjust the setting
when switching from summertime to wintertime and
vice versa.
29
30
1
2
3
4
)
Description of the operation modes
cc
hh
)
)
ss
)
Heating operation (hh
In this mode, heating will be activated as required by the temperature
set point. The set point can be set manually (refer to "Manual
operation" on page 3), weather dependent (refer to "Weather
dependent operation (heat pump models only)" on page 4) or
according to the defrost demand from the outdoor unit.
NOTE
NOTE
dd
Defrosting stops:
when switching between cooling and heating,
at a low outdoor temperature and a low
temperature of the incoming water,
when the desired defrost temperature is reached,
i.e. defrost stop temperature (contact your local
Daikin dealer).
Heating operation restarts automatically when the
water temperature is above the defrost stop
temperature.
Heating operation is not possible if the installation is a
"cooling only" installation.
Defrost (dd
In heating operation, freezing of the outdoor heat exchanger may
occur due to low outdoor temperature. If this risk occurs, the system
goes into defrost operation. It reverses the cycle and takes heat from
the indoor system to prevent freezing of the outdoor system. After a
maximum of 10 minutes of defrost operation, the system returns to
heating operation.
Cooling operation (cc
In this mode, cooling will be activated as required by the temperature
set point.
NOTE
The cooling temperature set point can only be set
manually (refer to "Manual operation" on page 3).
Switching between heating and cooling operation
can only be done by pressing the = button
(provided the unit is not a "cooling only" unit).
Quiet mode operation (ss
Quiet mode operation means that the outdoor unit works at reduced
capacity so that the noise produced by the outdoor unit drops. This
implies that the indoor heating and cooling capacity will also drop.
Beware of this when a certain level of heating is required indoors.
Controller operations
■
■
■
■
■
Operation manual
3
Manual operation
In manual operation, the user manually controls the temperature
settings of the installation. The last setting remains active until the
user changes it or until the schedule timer does.
As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message n will appear.
EWAQ+EWYQ005~007ACV3P