SUPPLEMENTARY SHEET
English language: Original Instructions
All other language: Translation of the Original Instruction
BLDC fan coil units
BLDC
BRUSHLESS MOTOR
Supplementary sheet
MOTORE BRUSHLESS
Scheda integrativa
English
Deutsch
Français
Español
Italiano

1
Speed
[Rpm]
1550
1450
1350
1250
1150
1050
950
850
1 2 3 4
100
0.5
0.25
Speed = (Vin - 0.5)* K+100
IN
[0 ÷ 10V]
2 3
Alarm types LED indications
Over temperature
Over voltage
Under voltage
Blink alarm LED 3s
ON 0,5s OFF
Over current
Over load
Safety control Temperature limiting
Stop
4
Blink alarm LED
0,5s ON 0,5s OFF
Alarm LED ON
permanently
Alarm indications
DIP4=OFF
Blink alarm output
3s ON 0,5s OFF
Blink alarm output
0,5s ON 0,5s OFF
Alarm LED ON
permanently
Actions Notes
Autoreset alarm. After about 1,5 min of
Motor OFF
persistance condition the alarm is set
permanently: LED ON, Alarm ON and system is in
STOP mode
Speed reduction
Power limiting
Motor OFF Set 0V ON input to reset the alarms

Brushless
Brushless
Scheda integrativa
Schemi elettrici di collegamento FWec3
Comando a microprocessore per installazione a parete
legenda dei Simboli degli Schemi elettrici (Figura 1)
Vo Velocità Superminima
V1 Velocità Minima
V2 Velocità Media
V3 Velocità Massima
L Fase
PE Terra
N Neutro
RE Resistenza Elettrica
SW Sonda Acqua
SA Sonda Aria
SU Sonda Umidità
DI1 Ingresso digitale 1
DI2 Ingresso digitale 2
CI12 Comune ingressi digitali
A/B/GND RS 485
F Fusibile (non fornito)
IL Interruttore di linea (non fornito)
VC Valvola solenoide Raffreddamento
VH Valvola solenoide Riscaldamento
….. Collegamenti elettrici a cura dell'installatore
101 Uscita 0-10V 1
COM Comune uscite 0-10V
102 Uscita 0-10V 2
DO2 Uscita digitale 2
DO1 Uscita digitale 1
CO12 Comune uscite digitali
Per ogni ventilconvettore prevedere sulla rete di alimentazione un
interruttore (IL) con contatti di apertura con distanza di almeno 3mm
e un fusibile (F) di protezione adeguato.
Supplementary sheet
Wiring diagramS FWec3
Wall-mounted microprocessor control
Key to SymbolS uSed in Wiring diagramS (Figure 1)
Vo Extra-low speed
V1 Minimum speed
V2 Medium speed
V3 Maximum speed
L Phase
PE Ground
N Neutral
RE Heating element
SW Water sensor
SA Air sensor
SU Humidity Probe
DI1 Digital 1 input
DI2 Digital 2 input
CI12 Digital input common
A/B/GND RS 485
F Fuse (not supplied)
IL Circuit breaker (not supplied)
VC Solenoid valve - Cooling
VH Solenoid valve - Heating
….. Electrical connections to be made by installer
101 0-10V 1 Output
COM 0-10V Output Common
102 0-10V 2 Output
DO2 Digital 2 output
DO1 Digital 1 output
CO12 Digital output Common
Each fan-coil requires a switch (IL) on the feeder line with a distance
of at least 3 mm between the opening contacts, and a suitable safety
fuse (F).
Collegare al massimo 20 terminali BLDC ad un unico interruttore
differenziale.
caratteriStiche di regolazione dell'inverter (Figura 2)
Il settaggio della curva richiesta può essere effettuato in fabbrica (e
modicato in cantiere se necessario) mediante impostazione dei dip
switch.
tabella di Selezione dellle rampe di velocità (Figura 3)
N° Velocità MAX DIP 1 DIP 2 DIP 3 DIP 4
1
2
3
4
5
6
7
8
La velocità massima (1550 rpm) non viene utilizzata.
1550 rpm OFF OFF OFF -
1450 rpm ON OFF OFF -
1350 rpm OFF ON OFF -
1250 rpm ON ON OFF -
1150 rpm OFF OFF ON -
1050 rpm ON OFF ON -
950 rpm OFF ON ON -
850 rpm ON ON ON -
allarmi (Figura 4)
Connect up to 20 BLDC terminals to a single differential circuit
breaker.
inverter characteriSticS oF regulation (Figure 2)
The full speed curve setting can be factory made (modied on site if
necessary) by using the dip switches on the mail board.
Full Speed Selection table (Figure 3)
N° MAX speed DIP 1 DIP 2 DIP 3 DIP 4
1
2
3
4
5
6
7
8
Max speed (1550 rpm) is not used.
1550 rpm OFF OFF OFF -
1450 rpm ON OFF OFF -
1350 rpm OFF ON OFF -
1250 rpm ON ON OFF -
1150 rpm OFF OFF ON -
1050 rpm ON OFF ON -
950 rpm OFF ON ON -
850 rpm ON ON ON -
alarmS (Figure 4)
BLDC
Fan coil units
Supplementary sheet
UT66003633 - 00

Zandvoordestraat 300, B-8400 Oostende, Belgium