SUPPLEMENTARY SHEET
English language: Original Instructions
All other language: Translation of the Original Instruction
BLDC fan coil units
BLDC
BRUSHLESS MOTOR
Supplementary sheet
MOTORE BRUSHLESS
Scheda integrativa
English
Deutsch
Français
Español
Italiano
1
Speed
[Rpm]
1550
1450
1350
1250
1150
1050
950
850
1 2 3 4
100
0.5
0.25
Speed = (Vin - 0.5)* K+100
IN
[0 ÷ 10V]
2 3
Alarm types LED indications
Over temperature
Over voltage
Under voltage
Blink alarm LED 3s
ON 0,5s OFF
Over current
Over load
Safety control Temperature limiting
Stop
4
Blink alarm LED
0,5s ON 0,5s OFF
Alarm LED ON
permanently
Alarm indications
DIP4=OFF
Blink alarm output
3s ON 0,5s OFF
Blink alarm output
0,5s ON 0,5s OFF
Alarm LED ON
permanently
Actions Notes
Autoreset alarm. After about 1,5 min of
Motor OFF
persistance condition the alarm is set
permanently: LED ON, Alarm ON and system is in
STOP mode
Speed reduction
Power limiting
Motor OFF Set 0V ON input to reset the alarms