IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORTCIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH
ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND
INFORMATION.
This kit includes the following parts
Tab le 1
Kit
Suction gas
name
BHFQ23P907
(2)
BHFQ23P1357
joint
ID Ø31.8
ID Ø28.6
ID Ø25.4
ID Ø28.6
ID Ø25.4
ID Ø22.2
ID Ø19.1
1x1x1x1x1x1x1x1x1x2x1x
ID Ø38.1
ID Ø31.8
ID Ø25.4
ID Ø28.6
ID Ø31.8
1x1x1x2x1x1x2x2x
ID Ø31.8
ID Ø28.6
HP/LP gas
joint
(1)
(2)
ID Ø22.2
ID Ø25.4
ID Ø28.6
ID Ø25.4
ID Ø28.6
ID Ø25.4
ID Ø22.2
ID Ø19.1
ID Ø31.8
ID Ø28.6
ID Ø25.4
ID Ø28.6
ID Ø25.4
ID Ø22.2
ID Ø19.1
ID Ø22.2
ID Ø25.4
ID Ø28.6
Liquid
(1)
(2)
joint
Outdoor unit multi connection piping kit
Shape
Equalizer
ID Ø22.2
ID Ø19.1
ID Ø15.9
ID Ø15.9
ID Ø12.7
ID Ø9.5
joint
—
Suction gas reducerHP/LP gas reducer
(1)
ID Ø19.1
ID Ø22.2
ID Ø25.4
ID Ø28.6
OD Ø25.4
(1)
ID Ø22.2
ID Ø19.1
ID Ø15.9
ID Ø15.9
ID Ø19.1
ID Ø19.1
ID Ø22.2
ID Ø25.4
ID Ø28.6
OD Ø25.4
(4)
ID Ø19.1
ID Ø15.9
ID Ø41.3
OD Ø38.1
(5)
(2)
(2)
ID Ø19.1
ID Ø22.2
ID Ø25.4
ID Ø28.6
OD Ø25.4
ID Ø28.6
ID Ø31.8
OD Ø31.8
ID Ø34.9
OD Ø31.8
(3)
(3)
ID Ø34.9
OD Ø31.8
ID Ø19.1
ID Ø22.2
ID Ø25.4
ID Ø28.6
OD Ø25.4
(1)
(1)
(3)
ID Ø25.4
OD Ø25.4
ID Ø25.4
OD Ø25.4
ID Ø22
ID Ø26
ID Ø28
OD Ø26
Installation manual
Liquid
reducer
(2)
(2)
ID Ø19.1
ID Ø22.2
OD Ø25.4
ID Ø19.1
ID Ø22.2
OD Ø25.4
(1)
(1)
ID Ø9.5
ID Ø12.7
OD Ø15.9
ID Ø9.5
ID Ø12.7
OD Ø15.9
Insulation
(a)
Gas
Liquid
ID Ø25.4
ID Ø28.6
ID Ø25.4
ID Ø22.2
ID Ø19.1
ID Ø25.4
ID Ø28.6
ID Ø25.4
ID Ø22.2
ID Ø19.1
1x1x1x1x1x3x1x2x4x2x
(a) For both suction gas pipes and HP/LP gas pipes
NOTE
Do not throw away any of the accessories until installation is completed.
Be sure to read this manual before installation and follow the instructions carefully when performing installation.
For installation of the outdoor units, refer to the installation manual of the outdoor unit.
The installation of refrigerant pipes between outdoor and indoor units needs to be arranged by refnet joints and refnet
headers, and is to be purchased separately.
For combination of outdoor units follow Engineering Data.
Field supply parts
Tab le 2
Quantity
Parts
Insulation for pipes
Connection pipes
Installation manual
1 set
1
ID Ø15.9
ID Ø12.7
ID Ø9.5
Selection procedure907 1357
See "Pipe size selection and
cutting position of the joint" on
page 3 and on page 10.
Quantity
Parts
Suction gas pipes 1x1x
Joint
(angle
HP/LP gas pipes2x2x
of 90°)
Equalizer pipes4x5x
Selection procedure907 1357
The joint size must be the same as
the gas pipe size of the outermost
outdoor unit. Refer to “Pipe size
selection and cutting position of the
joint” on page 3 and page 10.
The quantity and selection procedure for use of joints
with an angle of 90° only apply to front connection
installations.
For lower front connection and bottom connection
installations, the quantity and selection procedure are
different. Please refer to the dedicated instructions.
Joints for pipes with the same diameter are only
needed for bottom connection installations. See
dedicated instructions for quantities and specifications.
ESTRICTIONS
R
MULTI
CONNECTION
Install the joints horizontally, so that the caution label (1)
attached to the joint comes to the top.
Do not tilt the joint more than ±15° (see view A).
ON
INSTALLING
PIPING
view
±15
0°
A
1
KIT
THE
When installing the multi outdoor system, connect the
units as shown in the figure below.
If installed in a different order, the outdoor unit multi
connection piping kit may not fit properly and some
additional field supplied pipe size reducers may be
required.
Outdoor unit multi
connection piping kit type:
Unit capacity:
To indoor unit
Outdoor unit multi connection piping kit (first branch)
Outdoor unit multi connection piping kit (second branch)
If the total capacity of the connected indoor units
exceeds the total capacity of the outdoor units,
cooling and heating performance may be reduced
when running the indoor units. Refer to the capacity
table in the Engineering Data Book for more details.
Use piping with temper grade in function of the pipe
diameter as listed in the table below.
The pipe thickness of the refrigerant piping must
comply with relevant local and national regulations.
The minimum pipe thickness for R410A piping must
be in accordance with the table below (for design
pressure of 4.0 MPa (40 bar)).
BHFQ23P907 BHFQ23P1357
A≥BA≥B≥C
AB
1 2
AB
1 2
3
C
Do not install the joint vertically (see view B).
view
B
1
Make sure that the total length of the piping connected to the
joint is absolute straight for more than 500 mm. Only if a straight
field piping of more than 120 mm is connected, more than
500 mm of straight section can be ensured.
>120 m
m
>500 m
m
Improper installation may lead to malfunction of the outdoor unit.
BHFQ23P907+1357
Outdoor unit multi connection piping kit
4PW38477-1
Installation manual
2
OR
F
Pipe size selection and cutting position of the joint
Select the correct pipe size according the tables below and cut the
joints and reducers on the correct cutting point with a pipe cutter.
BHFQ23P907
Refer to the installation manual of the outdoor unit for
selection and restrictions for the piping between outdoor
branches. Not observing restrictions on the interconnecting
piping may result in malfunctioning of the unit.
N
I
1. E
■
CASE
XTERIOR
■
■
OF
■
FRONT
PIPING
1
4
2
5
3
A
1
2
3
4
5
AABB
1 234
Tab le 4
Select the pipe size in function of the total capacity of the
outdoor unit.
(a) OD x minimum wall thickness (temper grade type)
When upsizing the main pipe, use gas reducer (3).
When using pipes of Ø19.1 or larger, make sure to use pipes
with 1/2H temper grade with a wall thickness of 1.0 mm. In case
there is no alternative and you use the O temper grade for pipes
with Ø19.1, a minimal wall thickness of 1.2 mm or more is
required and connections need to be brazed.
Upsizing main pipe
For units with total capacity of 24~32 Hp, the suction gas reducer (3)
has to be used. Connect the reducer to the suction gas joint as
shown in the figure below.
(a) OD x minimum wall thickness (temper grade type)
Cut the pipe with a pipe cutter.
Suction gasHP/LP gasLiquid
Suction gasHP/LP gasLiquid
Suction gasHP/LP gasLiquid
1Main pipe, see table 4 on page 3
2Joint (refer to "Restrictions on
installing the multi connection
piping kit" on page 2)
3Pipe between joint and the outdoor
unit A, see table 5 on page 3
4Pipe between joint and the outdoor
unit B, see table 6 on page 3
(a)
Pipe size
(a)
Pipe size
(a)
Pipe size
1
2
3
4
5
2. D
198
NOTE
BB
BB
Liquid joint
To indoor unit
Suction gas joint
IMENSIONS
To p viewFront view
detail
181
148
152
300 mm (standard)
Liquid pipe
Suction gas pipe
HP/LP gas pipe
Equalizer pipe
Bottom frame
In case dimension A exceeds 300 mm, extend the field
supplied interconnection piping between the joint and
the outdoor unit.
FOR
INSTALLATION
BB
B
12 3 4
HP/LP gas joint
Equalizer pipe
5
58
152
211
283
105
181
63
123
Installation manual
3
≥15
1Joint or reducer
2Cut in order to have a
fitting depth of ≥15 mm
3Field pipe
Outdoor unit multi connection piping kit
BHFQ23P907+1357
4PW38477-1
3. I
NSTALLATIONOFSUCTIONGASAND
HP/LP
GASPIPES
Cutting the field supplied gas pipes
Use the following tables in case dimension A is 300 mm (refer to
"Dimensions for installation" on page 3.
If dimension A exceeds 300 mm, extend the L dimension of the
suction gas pipes 1 and 2 and HP/LP gas pipes accordingly.
■For suction gas pipes only
For L dimension of suction gas pipes 1 and 2, dimension B of
the field supplied angled joint as in table 8 on page 4 has been
taken into account. If dimension B of the angled joint you use is
different from that dimension B, adjust the L dimension of
suction gas pipes 1 and 2 accordingly.
For L dimension of HP/LP gas pipes 1, 2 and 3, dimension B of
the field supplied angled joint as in table 10 on page 4 has been
taken into account. If dimension B of the angled joint you use is
different from that dimension B, adjust the L dimension of HP/LP
gas pipes 1, 2 and 3 accordingly.
Tab le 9
Pipe 1
Outdoor unit
18~24 Hp5024559
26+28 Hp8024559
30+32 Hp8023947
L (mm)
Pipe 2
L (mm)
Tab le 10
Joint (angle of 90°) (field supply)
Outdoor unit
18~28 Hp17
B (mm)
Pipe 2
L (mm)
B
B
B
Pipe 3
L (mm)
L
L
Connection piping
■Connect the suction gas and HP/LP gas pipes as shown in the
figure below.
Before connecting the pipes, first connect the suction gas joint
and the suction gas reducer (1), the HP/LP gas joint and the
HP/LP gas reducers (1) and (2).
■See "Dimensions for installation" on page 3 for the location
(height) of the joint.
■Refer to the installation manual delivered with the outdoor unit for
cautions on brazing pipes.
■Keep the joint in a horizontal position, see view A in the figure
below.
■Connect the HP/LP gas reducer (1) by tilting it ±50° and connect
the HP/LP gas reducer (2), see view A in the figure below.
■Refer to "Pipe size selection and cutting position of the joint" on
page 3 for the cutting requirements.
4
±15
view
50°
0°
5
A
±15
0°
A
1
2
9
7 854
6
1Suction gas accessory pipe (1) supplied with the outdoor unit
2Suction gas pipe (1) (field supply) refer to table 7 on page 4
3HP/LP gas accessory pipe (1) supplied with the outdoor unit
4Suction gas joint
5HP/LP gas joint
6Suction gas reducer (1)
7HP/LP gas reducer (1)
8HP/LP gas reducer (2)
9HP/LP gas pipe (1) (field supply) refer to table 9 on page 4
10HP/LP gas pipe (field supply) (select the pipe length on site)
11Suction gas pipe (field supply) (select the pipe length on site)
12Joint (1) (angle of 90°) (field supply) refer to table 8 on page 4
13HP/LP gas pipe (3) (field supply) refer to table 9 on page 4
14Joint (2) (angle of 90°) (field supply) refer to table 10 on page 4
15Suction gas pipe (2) (field supply) refer to table 7 on page 4
16HP/LP gas pipe (2) (field supply) refer to table 9 on page 4
17Suction gas accessory pipe (2) supplied with the outdoor unit
18HP/LP gas accessory pipe (2) supplied with the outdoor unit
3
15
14 161117 18131210
30+32 Hp23
B
Cutting suction gas reducer (1) and HP/LP gas
reducer (2)
Suction gas
reducer (1)
14
18 Hp
20~32 Hp
2
BHFQ23P907+1357
Outdoor unit multi connection piping kit
4PW38477-1
HP/LP gas
reducer (2)
6
33
26~32 Hp
5
1Connection to suction gas
2Connection to suction gas joint
3Cutting position
4Connection to HP/LP gas pipe 1
5Connection to HP/LP gas
6No cutting for 18~24 Hp
pipe 1 (field supply)
(field supply)
reducer (1)
Installation manual
4
4. INSTALLATIONOFLIQUIDPIPESAND
836117
40°
104
9
8
10
546 7
2
1
3
0°
±15
A
A
view
3
EQUALIZERPIPES
Cutting the field supplied equalizer pipes
Use the following tables in case dimension A is 300 mm (refer to
"Dimensions for installation" on page 3.
If dimension A exceeds 300 mm, extend the L dimension of the
equalizer pipes 1 and 2 accordingly.
For L dimension of equalizer pipes 1 and 2, dimension B of the field
supplied angled joint as in table 12 on page 5 has been taken into
account. If dimension B of the angled joint you use is different from
that dimension B, adjust the L dimension of the equalizer pipes 1 and
2 accordingly.
Tab le 11 Table 12
Equalizer pipeJoint (angle of 90°)
Pipe 1 (L mm) Pipe 2 (L mm)B (mm)
956017
L
Cutting liquid reducer (1)
1Connection to liquid pipe (field supply)
1
4
2Connection to liquid joint
20~32 Hp
3Cutting position
3
2
4No cutting for 18 Hp
B
B
1Liquid accessory pipe (1) supplied with the outdoor unit
2Liquid pipe (1) (field supply) (select the pipe length on site)
3Equalizer accessory pipe (1) supplied with the outdoor unit
4Liquid joint
5Liquid reducer (1)
6Joint (angle of 90°) (field supply) refer to table 12 on page 5
7Equalizer pipe (2) (field supply) refer to table 11 on page 5
8Equalizer pipe (1) (field supply) refer to table 11 on page 5
9Liquid pipe (field supply) (select the pipe length on site)
10Equalizer pipe (field supply) (select the pipe length on site)
11Liquid accessory pipe (2) supplied with the outdoor unit
Connection piping
■Connect the liquid pipes and equalizer pipes as shown in the
figure below.
Before connecting the pipes, first connect the liquid joint and the
liquid reducer (1).
■Refer to "Dimensions for installation" on page 3.
■Keep the joint in a horizontal position as shown in view A in the
figure below
■Connect the liquid reducer (1) in an angle of 40° and bend the
field supplied liquid pipe up to the stop valve as shown in the
figure, see view A in the figure below.
■Refer to the installation manual delivered with the outdoor unit
for cautions on brazing pipes.
■Refer to "Pipe size selection and cutting position of the joint" on
page 3 for the cutting requirements.
5. AFTERCONNECTIONOFTHEPIPING
Connection piping between the outdoor and indoor unit
All piping must be executed according to instructions in the
installation manual of the outdoor unit and an air tight test must be
performed after complete installation of the piping.
Insulation of joints
12
4
3
Step 1: Fit the insulation (1) around the reducer (2) and keep it in
place with tape ( ) (3).
Step 2: Fit the insulation (4) around the joint (5) and keep it in place
with tape ( ) (6) without leaving a gap between the two insulated
parts.
Step 3: Seal the seam between the insulation and the field piping
insulation () with tape ( ) (7).
Step 4: Cover the insulated parts completely with tape ( ) without
leaving any gaps (8).
■All required tape is field supply.
■In case of indoor installation, make sure that the tape
is of the fireproof type in order to comply with local
regulations.
5
7
8
6
3214
Installation manual
5
Outdoor unit multi connection piping kit
BHFQ23P907+1357
4PW38477-1