Fire Alarm Systems | FLM-325-NA4 Supervised Output Modules
FLM-325-NA4 Supervised Output Modules
www.boschsecurity.com
The modules provide a supervised polarity reversal output used for audible and visual signaling devices or to trigger a remote NAC power expander. They require a 24 VDC auxiliary input voltage that can be provided by the FPA 1000 Analog Addressable Fire Panels or other UL listed power supplies.
The modules provide a Class B Circuit rated for 2 A at 24 VDC. They fit into a standard 4 inch square or double gang electrical back box.
Functions
Evacuation Tones
The following programmable patterns are selectable:
•Steady
•Pulsing
•Temporal 3
Flexibility
The operating parameters for the modules are saved at the integrated EEPROM and maintained by the module so that during emergency situations no communication with the fire panel is needed which provides flexibility and quick response to emergency conditions. The fire panel only broadcasts system conditions on the Signaling Line Circuit (SLC) and each module processes them according to its configuration.
uContacts are rated 2 A at 24 VDC
uFlexible application and quick response to emergency conditions
uCan be alarmed or reset by zone or by individual address
uModule address programming with the D5070 Analog Device Programmer
uBi colored LED provides module status
Status display
A bi colored LED flashes every time the module is polled and can be switched on steady when the module goes into active condition.
Short Circuit Isolation
Built in short circuit isolating (SCI) circuitry that, in the event of a short circuit on the SLC line, will prevent entire loop failure and send a short circuit condition report to the FACP, and, upon removal of the short circuit condition, automatically restore the entire loop to normal operation.
Certifications and approvals
Region |
Certification |
|
|
|
|
USA |
UL |
UOXX: Control Unit Accessories, System |
|
|
(ANSI/UL 864) |
|
CSFM |
see our website |
|
|
|
Installation/configuration notes
Compatibility Information
The following products are compatible with the modules:
2 | FLM-325-NA4 Supervised Output Modules
Category |
Product ID |
Product Description |
Fire Panels |
FPA 1000 |
Analog Addressable Fire Panels |
Programmer |
D5070 |
Analog Device Programmer |
Parts included
Quant. Component
1FLM 325 NA4 Family Supervised Output Module
1Wall plate
1Literature pack
Technical specifications
Electrical
Voltage
Input: |
|
25.3 VDC to 39 VDC |
|
|
|
Auxiliary Input: |
24 VDC |
|
|
|
|
Current Consumption |
|
|
|
|
|
• |
FLM 325 NA4: |
Typical: 0.22 mA |
|
|
Maximum: 6 mA |
|
|
|
• |
FLM 325 NAI4 |
Typical: 0.42 mA |
|
: |
Maximum: 6 mA |
|
|
|
• |
Maximum |
2 A at 24 VDC, power limited |
|
Output: |
|
|
|
|
SCI |
|
|
|
|
|
• |
Fault Detection |
12 V typical |
|
Threshold: |
|
|
|
|
• |
Isolation |
10 mA typical |
|
Current: |
|
|
|
|
Environmental |
|
|
|
|
|
Operating |
+32°F to +120°F (0°C to +49°C) |
|
Temperature: |
|
|
|
|
|
Relative Humidity: |
Up to 90 %, non condensing |
|
|
|
|
Mechanical |
|
|
|
|
|
Dimensions |
4.7 in. x 4.2 in. x 1.4 in. (11.9 cm x 10.7 cm |
|
(H x W x D): |
x 3.6 cm) |
|
|
|
|
Bicolored LED: |
Red and green |
|
|
|
|
Ordering information
FLM-325-NA4 Supervised Output Module (Class A and B)
Can be wired for Class A or Class B circuits; compatible with 254 addresses
FLM-325-NAI4 Supervised Output Module (Class A and B, with isolator)
Built-in short circuit isolator circuitry; can be wired for Class A or Class B circuits; compatible with 254 addresses
Order number FLM-325-NAI4
Accessories
D5070 Analog Device Programmer
Used to program address settings on
EEPROM programmable analog devices
Order number D5070
Order number FLM-325-NA4