Intrusion Alarm Systems | D9210C Access Control Interface Module
D9210C Access Control Interface Module
www.boschsecurity.com
u Direct interface to 26‑bit Wiegand card readers
u Onboard buzzer output
u Supervised onboard point
The D9210C Access Control Interface Module is a fully
supervised, addressable SDI bus device that allows
access control integration for Bosch G Series Control
Panels. This highly reliable module offers 14
programmable levels of access authority. Authority for
access is controlled by the level of the user, the time
of day, the state of the door and the armed state of
the area. Each of the authority restrictions can be
controlled through automatic and manual functions.
Users can be added to the system with local
programming using RPS (Remote Programming
Software), D5200, or with credentials using the Add
User function through keypads.
Functions
Reader Input
• Standard 5-wire Weigand interface.
• +5 VDC or +12 VDC supplied to power readers.
• Open collector output for reader LED.
Unsupervised Inputs
• Tamper – supports normally open devices.
• REX – supports normally open devices. Request to
Exit on short.
• RTE – supports normally open devices. Request to
Enter on short.
Supervised Input
• 1000Ω End of line resistor.
• Use for door contact.
u Request to Exit and Request to Enter inputs that
can have a shunt only option
u Four door states: Locked, Unlocked, Secured, Fire
Unlock
Door States
Four-door states are controlled through the keypad,
RPS (Remote Programming Software), scheduled
events (Skeds) and automatic programmable functions
in the D9210C parameters:
• Locked: Lock Relay de-activated thru valid credential
or RTE (Request to Exit) input.
• Unlocked: allows the door to be opened for free
access. Lock Relay is activated.
• Secured: does not allow access unless a Fire Unlock
occurs. Valid credential or RTE will not activate relay.
• Fire Unlock: allows free access no matter what the
previous door state or armed state is. This is a
programmable option that can be used to allow free
access into or out off the building upon a fire alarm.
Two automatic functions link the door state to the
arming state of the area:
• Auto Door: When the area is disarmed, the door state
is switched to “Unlocked.”
• Disarm on Open: with this function as "Yes," a user
with valid access rights will activate the strike and
disarm the system after the door is opened. With this
function as "No," the area will disarm upon the strike
activation.
Indicators
• Heartbeat LED: Blue LED blinks on and off when
system is operational. A steady On or Off LED
indicates a system error.
2 | D9210C Access Control Interface Module
• Reader LED: Rapidly blinking LED indicates the Card
data is being received. When the LED is off, no card
data is being received.
Certifications and approvals
USA UL D9210C Series: ALVY: (UL294):
Access Control System Units AMCX:
Central Station Alarm Units (UL1610),
AOTX: Local Alarm Units (UL609),
APAW: Police Station Alarm Units
(UL365), APOU: Propriety Alarm Units
(UL1076), NBSX: (UL1023):
Household Burglar Alarm System
Units, UOTU: (UL985): Control Units
and Accessories – Household System
Type, UOXX: Control Unit Accessories,
System (UL864)
Region Certification
USA CSFM 7167-1615:0243 7167 -- CONTROL
UNIT (HOUSEHOLD)
CSFM 7165-1615:0242 7165 -- FIRE ALARM
CONTROL UNIT (COMMERCIAL)
Installation/configuration notes
The D9210C Access Control Interface Module is
individually programmed through the control panel it is
connected to.
Compatibility Information
Category Commercial Code Description
Readers and ARD-AYH12 EM Prox Wall Mount
Accessories ARD-AYJ12 EM Prox Mullion
ARD-AYK12 EM Prox Mini Mullion
ARD-AYQ12 EM Prox Wall Mount Vandal
Resistant
ARD-AYCE65B EM Prox or PIN Mullion
ARD-R10 HID iClass Mini Mullion
ARD-R40 HID iClass Wall Mount
D8223 HID Prox Wall Mount
D8224 HID Prox Mullion
D8224‑SP HID Prox Switch Plate Mount
D8225 HID Prox Mini Mullion
D8229 PIN Reader
Credentials ACA-ATR13 EM Tokens
ACD-ATR11ISO EM Cards
ACD-ATR14CS EM Clamshell Cards
ACD-IC2K26-50 iClass Cards
ACT-IC2K26-10 iClass Tokens
D8236‑10 HID Prox Cards
D8236KF‑10 HID Prox Tokens
Systems D9412GV4 Control Panel
D7412GV4 Control Panel
D9412GV3 Control Panel
D7412GV3 Control Panel
D9412GV2 Control Panel
D7412GV2 Control Panel
D9412G Control Panel
D7412G Control Panel
Parts included
Quantity Component
1 D9210C
1 1 kΩ ½ watt end of line resistor
3 # 6x3/8 self-tapping sheet metal screws to secure the
module to mounting skirt or enclosure
Technical specifications
Environmental Considerations
Relative Humidity Up to 93% non-condensing
Temperature Operating 0° to +49°C (+32° to +120°F)
Electrical Requirements
Current Draw: 110 mA max (Board) +150 mA max
Voltage (operating) 8.5 – 13.8 V
(Reader)
Reader Requirements
+5.2 VDC Power out to 5.2
VDC card reader
DATA 0 Data 0 input
from card reader
DATA 1 Data 1 input
from card reader
BUZZER Buzzer common
upon strike
activation
LED LED common
upon card read
response and
strike activation
5 V +/- 0.25 V for 20 to
140 mA load
150 mA maximum
continuous
High impedance input
with 47 kΩ pull up to
+5.2 V
High impedance input
with 47 kΩ pull up to
+5.2 V
Sink up to 35 mA from
5-14 VDC source
Output impedance is
100Ω
Sink up to 35 mA from
5-14 VDC source
Output impedance is
180Ω