Fire Alarm Systems | D9068 Fire Digital Alarm Communicator Transmitter (DACT)
D9068 Fire Digital Alarm Communicator Transmitter (DACT)
www.boschsecurity.com
u 12 VDC or 24 VDC operation
u Supports multiple reporting formats
The D9068 Fire Communicator is a complete digital alarm communicator transmitter (DACT) for use with compatible fire alarm control panels (FACPs). Use dry contacts or open collector outputs for alarms and communications with the D9068.
Functions
Five Input Points
The DACT supports five inputs that can be activated by dry contact relays or open collector outputs. Each of these inputs can be configured for one of seven types of conditions: Fire Alarm, Waterflow Alarm, Supervisory, Monitor Alarm, System Fault, AC Failure and Low Battery.
System Supervision
The DACT is supervised with a hardware watchdog circuit. Failure of the control program results in a hardware reset within two seconds. The on‑board trouble relay releases for the duration of the reset (the relay is normally held energized).
Style B)
u 100-event history buffer
u Dual phone line interface
The DACT's EEPROM memory, input points, and phone lines are automatically tested periodically. The EEPROM checksum is verified every 10 minutes. If the EEPROM checksum fails, a trouble condition is locally annunciated and a trouble report sent.
Serial Data Input Dialing
The DACT connects through the D9052 Serial Module to the D10024, D10024A, D9024, and D8024 analog FACPs, and transmits by point in all available formats.
User Interface
An FMR‑DACT‑KEYPAD LCD Keypad connects to a five­pin connector (option bus interface) and is used to program and troubleshoot the D9068. A D7033 Liquid­Crystal Display (LCD) Remote Keypad can also be used.
Reporting Formats
The DACT supports five reporting formats: Modem IIIa2, Contact ID, SIA110, SIA300, and 4/2.
2 | D9068 Fire Digital Alarm Communicator Transmitter (DACT)
Report Routing
There are six different report groups that can be routed to one of four phone settings. These report groups consist of non-supervisory alarms, supervisory alarms, alarm restorals, resets, supervisory restorals, tests and troubles, and trouble restorals.
Reset Report
A reset report is sent when the D9068 resets from any off-normal condition.
Phone Line Selection
The DACT follows a pre‑determined sequence to select between the phone lines. It also implements the new NFPA requirements for alternation of phone lines during test reporting. The DACT maintains a variable that selects either Phone Line 1 or Phone Line 2 for automatic test reports. After each successful test report, the variable switches to select the other phone line.
Communication Failed Indication
The DACT indicates a communication failure after ten attempts to communicate are completed without success. This causes the trouble output to activate and report the fault.
History Buffer
The DACT has a history buffer that retains up to 100 events. Each event is tagged with the date and time of occurrence. This buffer can be viewed when an FMR‑DACT‑KEYPAD LCD Keypad (or a D7033 LCD Remote Keypad) is connected to the D9068. When the buffer is full, old events are discarded to make room for new events.
Lightning Suppression
MOVs and spark gaps suppress lightning surges and static discharges for inputs and telephone interface.
Certifications and approvals
Category Product ID Product Description
Control Panels D7022 Conventional FACP
D8024 Analog FACP
D9024 Analog FACP
D10024 Analog FACP
D10024A Analog FACP
Keypads and Annunciators
FMR‑DACT‑KEYPAD LCD keypad
Modules D9052 Serial interface module
D7033 LCD keypad
Parts included
Quant. Component
1 D9068 board
1 Metal enclosure (red)
1 Lightpipe
1 DCT-HWD hardware kit
Technical specifications
Environmental Considerations
Environment: Indoor, dry
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Mechanical Properties
Dimensions (HxWxD): 7.75 in. x 5.1 in. x 2.5 in.
Weight: 3.1 lb (1.4 kg)
(19.7 cm x 13.1 cm x 6.4 cm)
Outputs
Trouble Relay: One Form C relay onboard
Region Certification
USA UL UOXX: Control Unit Accessories, System
FM D9068
CSFM see our website
NYC­MEA
NYC­MEA
(UL864, 9th edition)
26-02-E, Vol. II
26-02-E, Vol. III
Installation/configuration notes
Compatible Products
The following products are compatible with the D9068 Fire DACT:
Relay Rating: 1 A at 30 VDC
Power Requirements (use power-limited source)
Current (alarm): 190 mA maximum
Current (standby): 150 mA maximum
Voltage: 10.2 VDC to 28 VDC
Ordering information
D9068 Fire Digital Alarm Communicator Transmitter (DACT)
Complete digital alarm communicator transmitter (DACT) for use with compatible fire alarm control panels (FACPs)
Order number D9068