Fire Alarm Systems | D7042 and D7042B Eight‑input Remote Modules
D7042 and D7042B Eight‑input Remote
Modules
www.boschsecurity.com
u Has eight Class B (Style B) initiating circuits
u Includes eight UL Listed EOL resistors
The D7042 and D7042B Addressable Multiplex
Eight‑input Remote Modules have eight input loops for
conventional contacts that can be used to monitor
four‑wire smoke detectors, waterflow contacts, and
supervisory sensors. The module must be wired Class
B to the multiplex bus of the D7024 or FPD‑7024 Fire
Alarm Control Panel (FACP).
Notice
The D7024 is not listed under UL864, 9th edition.
Notice
A D7024 or FPD‑7024 FACP and one D7039
Multiplex Expansion Module are required when
using the D7042 or D7042B.
Up to 30 D7042 or D7042B modules can be supported
per FACP (15 on bus A and 15 on bus B). The D7042
module comes with a plastic enclosure and can be
mounted inside or outside the FACP enclosure. The
D7042B module comes with its own red metal fire
enclosure for remote mounting.
u Convenient plastic case (D7042) or red metal fire
enclosure (D7042B) for remote mounting
u Easy to install
u Connects to multiplex bus
Certifications and approvals
Region Certification
USA UL UOJZ: Control Units, System (ANSI/UL
FM D7042\D7042B
CSFM see our website
FDNYCoA
864) D7042 only
#6173
Installation/configuration notes
Compatible Products
The following products are compatible with the D7042
and D7042B Eight‑input Remote Modules:
Category Product ID Product Description
Control
Panels
D7024 Addressable FACP
D7024‑EXP Addressable FACP for export
FPD‑7024 Addressable FACP
2 | D7042 and D7042B Eight‑input Remote Modules
Wiring Considerations
Use a minimum of 18 AWG (ISO 0.75 mm2) wire for the
initiating device circuit wiring connected to the D7042
or D7042B. Wire length per loop cannot exceed 250 ft
(76 m). For multiplex wiring requirements, see the
D7039 Installation Guide.
Notice
Do not use shielded or twisted-pair cable.
Parts included
D7042
Quant. Component
1 D7042 board
1 Plastic enclosure with spring tamper
8 47 kΩ EOL resistors (P/N: 28010)
1 Literature pack
D7042B
Quant. Component
1 D7042 board attached to mounting skirt
1 Metal fire enclosure
8 47 kΩ EOL resistors (P/N: 28010)
1 Literature pack
1 Hardware pack
Material
D7042: ABS plastic
D7042B: Metal
Weight (assembled)
D7042: 0.6 lb (0.27 kg)
D7042B: 2.6 lb (1.2 kg)
Power Requirements
Current
(alarm and standby):
Battery Calculation
10 mA at 12 VDC through multiplex bus; 8 mA
from option bus
18 mA
Current
(alarm and standby):
Voltage (operating): 8 VDC peak minimum bus
Ordering information
D7042 Eight‑input Remote Module
Board and plastic enclosure with spring tamper
Order number D7042
D7042B Eight‑input Remote Module with Fire Enclosure
Board on mounting plate with metal enclosure
Order number D7042B
Technical specifications
Circuit Designation
MUX Bus: Class B (Style 4) SLC
Inputs: Class B (Style B) IDC
Environmental Considerations
Environment: Indoor, dry
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Mechanical Properties
Color
D7042: White
D7042B: Red
Dimensions (HxWxD)
Board: 3.4 in. x 5.7 in. x 0.6 in.
(8.6 cm x 14.5 cm x 1.5 cm)
Enclosure (D7042): 3.7 in. x 6.0 in. x 1.4 in.
(9.4 cm x 15.2 cm x 3.6 cm)
Enclosure (D7042B): 5.25 in. x 7.75 in. x 2.5 in.
(13.3 cm x 19.7 cm x 6.4 cm)