Installation Manual
The ARD-AYK12 is a RFID proximity card reader to be installed
for use with access control systems.
This installation manual contains the following information:
-Mounting Instructions
-Wiring Instructions
-Operation Instructions
-Technical Specifications
MOUNTING INSTRUCTIONS
1 = To remove the top cover you need to unscrew the top
cover screw located on the bottom of the reader.
2 = Remove the top cover to reveal the screw holes for
mounting.
Mount the reader with the appropriate screws (not supplied) as
indicated on the template.
To mount the reader, perform the following:
1.Determine an appropriate mounting position for the
reader.
2.Peel off the back of the self-stick mounting label template
included with the unit and place at the desired mounting
position. If you do not have the self-stick mounting
Bosch Sicherheitssyteme GmbH | V 1.2 | 2009.09
6en | Installation ManualARD-AYK12
template label, refer to the Mounting Diagrams in this
manual for the dimensions.
3.Using the template as a guide, drill the holes (hole size is
indicated on mounting template) for mounting the reader
to the surface.
4.Drill a
7/16" (10 mm) hole for the cable. If mounting on
metal, place a grommet or electrical tape around the edge
of the hole.
5.Route the interface cable from the reader to the controller.
A linear type power supply is recommended
NOTICE!
Card readers are to be used with a listed access control unit
whose power supply is UL Listed Class 2 or equivalent.
WIRING INSTRUCTIONS
The ARD-AYK12 is supplied with an 18 inch (45 cm) pigtail,
having a 6-conductor cable.
To connect the reader to the controller, perform the following
steps:
1.Prepare the reader cable by cutting the cable jacket back
1/4 inches (3,4 cm) and strip the wires 1/2 inch (1,3 cm).
1
2.Prepare the controller cable by cutting the cable jacket
back 1
1/4 inches (3,4 cm) and strip the wires 1/2 inch
(1,3 cm).
3.Splice the reader pigtail wires to the corresponding
controller wires and cover each connection with insulating
tape.
4.If the tamper output is being utilized, connect the purple
wire to the correct input on the controller.
5.Trim and cover all conductors that are not used.
The table below shows how you should wire the reader to the
controller.
ColorWiegand Output
RedDC + Input
BlackGround
WhiteData 1
GreenData 0
| V 1.2 | 2009.09Bosch Sicherheitssyteme GmbH
ARD-AYK12Installation Manual | en7
ColorWiegand Output
BrownLED Control
PurpleTamper
Cable Notes:
1.The individual wires coming out of the reader are color
coded according to the recommended Wiegand standard.
2.When using a separate power supply for the reader, this
supply and the controller's power supply must have a
common ground.
3.The cable shield wire on the reader should be attached to
an earth ground (best) or signal ground connection at the
panel or power supply end of the cable. This configuration
is best for shielding the reader cable from external
interference.
OPERATION INSTRUCTIONS
The reader should be tested after wiring it to a power supply
and the controller.
Do this by performing the following steps:
1.Power up the reader. The LED and beeper will activate
three times. This indicates that the reader is working
properly.
2.Present the appropriate type of proximity card to the
reader. The LED will momentarily flash green and a short
beep will be emitted. This indicates that the card was read
properly by the Proximity Card Reader.
3.After the card data is processed by the controller, the
controller can then turn the LED green. Refer to the
controller description of the LED operation if the reader
LED is controlled by the controller.
Bosch Sicherheitssyteme GmbH | V 1.2 | 2009.09
8en | Installation ManualARD-AYK12
TECHNICAL SPECIFICATIONS
Electrical Characteristics
Power Supply TypeLinear type recommended
Operating Voltage Range 5 - 16 VDC
Maximum Input CurrentStandby: 35 mA
Read: 50 mA
Tamper OutputOpen collector, active low, max
sink current 16 mA
Max Cable Distance to
500 ft. (150 meters)
Controller
Output modulation26-bit Wiegand
Card read distance*3.15 inch (8 cm)
RF ModulationASK
Regulatory ApprovalsUSA: UL 294 & FCC Part 15B
Europe: CE Listed
Environmental Characteristics
Operating Temp. Range-25°F to 145°F (-31°C to 63°C )
Operating Humidity0 to 95% (non condensing)
Dimensions
Height x Widht X Depth3.15 x 1.57 x 0.50 inch
(79.91 x 39.91 x 12.8 mm)
* Measured using Bosch Proximity Card (P/N ACD-ATR11ISO) or
equivalent. Range also depends on electrical environment and/
or proximity to metal.
Suitable for Outdoor Use
| V 1.2 | 2009.09Bosch Sicherheitssyteme GmbH
ARD-AYK12Installation Manual | en9
MOUNTING DIAGRAM
Bosch Sicherheitssyteme GmbH | V 1.2 | 2009.09
10 en | Installation ManualARD-AYK12
| V 1.2 | 2009.09Bosch Sicherheitssyteme GmbH
ARD-AYK12Installationshandbuch | de 11
Installationshandbuch
Der ARD-AYK12 ist ein RFID-Leser für berührungslose Ausweise
und kann in Zutrittskontrollsysteme installiert werden.
Dieses Installationshandbuch enthält folgende Informationen:
-Montageanleitung
-Verkabelungsanleitung
-Bedienungsanleitung
-Technische Daten
MONTAGEANLEITUNG
1 = Um die obere Abdeckung zu entfernen, muss die an der
Unterseite des Lesers befindliche Schraube der oberen
Abdeckung abgeschraubt werden.
2 = Entfernen Sie die obere Abdeckung, um die
Schraubenöffnungen für die Montage freizulegen.
Montieren Sie den Leser wie auf der Schablone angegeben mit
den entsprechenden Schrauben (nicht im Lieferumfang
enthalten).
Gehen Sie zur Montage des Lesers wie folgt vor:
1.Legen Sie eine geeignete Montageposition für den Leser
fest.
2.Ziehen Sie die Rückseite der mit dem Gerät mitgelieferten
selbstklebenden Montagemarkierungsschablone ab, und
Bosch Sicherheitssyteme GmbH | V 1.2 | 2009.09
12 de | InstallationshandbuchARD-AYK12
bringen Sie die Schablone an der gewünschten
Montageposition an. Wenn Sie über keine selbstklebende
Montagemarkierungsschablone verfügen, können Sie die
Abmessungen aus den Montagedarstellungen in diesem
Handbuch entnehmen.
3.Bohren Sie die Löcher (der Bohrungsdurchmesser ist auf
der Montageschablone angegeben) für die Montage des
Lesers auf der entsprechenden Oberfläche.
4.Bohren Sie ein Loch mit
10 mm Durchmesser für das Kabel.
Bei der Montage auf Metall ist die Bohrungskante mit einer
Schutzmanschette oder mit Isolierband zu versehen .
5.Führen Sie das Schnittstellenkabel vom Leser zum
Kontroller. Es wird empfohlen, ein Netzteil mit linearer
Spannungsregelung zu verwenden.
HINWEIS!
Kartenleser müssen zusammen mit einem zugelassenen
Zutrittskontrollgerät verwendet werden, dessen Netzteil CEzugelassen ist bzw. das mit einem gleichwertigen Netzteil
ausgestattet ist.
VERKABELUNGSANLEITUNG
Der ARD-AYK12 wird mit einem 45 cm langen 6-adrigen
Anschlusskabel geliefert.
Gehen Sie zum Anschließen des Lesers an den Kontroller wie
folgt vor:
1.Bereiten Sie das Leser-Kabel vor, indem Sie den
Kabelmantel auf einer Länge von
Drähte auf einer Länge von
3,4 cm entfernen und die
1,3 cm abisolieren.
2.Bereiten Sie das Kontroller-Kabel vor, indem Sie den
Kabelmantel auf einer Länge von 3,4 cm entfernen und die
Drähte auf einer Länge von
1,3 cm abisolieren.
3.Verbinden Sie die Drähte der Anschlussleitung des Lesers
mit den entsprechenden Drähten des Controller-Kabels,
und isolieren Sie alle Verbindungsstellen mit Isolierband.
4.Wenn der Sabotageausgang verwendet wird, schließen Sie
den violetten Draht an den entsprechenden Eingang am
Controller an.
5.Schneiden Sie alle nicht verwendeten Leiter zurück, und
isolieren Sie sie entsprechend.
| V 1.2 | 2009.09Bosch Sicherheitssyteme GmbH