Basler Electric BE3-27 User Manual

www.basler.com
+1 618.654.2341 (USA)
info@basler.com
INTRODUCTION
SPECIFICATIONS
Inputs
All units are self-powered. Nominal Voltage: 120 Vac, 240 Vac, 380 Vac,
480 Vac
Overload Withstand: 1.25 times nominal continuously.
2 times nominal for 3 s. Frequency: 50, 60, or 400 Hz Burden: <2.5 VA per phase on single units.
<3 VA per phase on combined units.
Setpoint
Undervoltage Range: Adjustable 75 to 100% (±3%) of
nominal Overvoltage Range: Adjustable 100 to 125% (±3%) of
nominal Repeatability: Better than 0.5% of full span Reset: Adjustable 1 to 15% Operating Time: 200 ms typical
Outputs
Relay Type: D.P.D.T. AC Rating: 250 V, 5 A, non-resistive,
1200 VA DC Rating: 125 V, 1 A, resistive, 120 W Mechanical Life: 5 million operations
Temperature
Operating Temperature: 0°C (32°F) to 60°C (140°F) Functional Temperature: –25°C (–13°F) to 70°C (158°F) Storage Temperature: –40°C (–40°F) to 70°C (158°F) Temperature Coefficient: 0.03% per °C (300 ppm/°C)
Humidity
Relative Humidity: 95% non-condensing
Physical
Mounting: DIN rail 1.38” by 0.29” (35 mm by 7.5
mm) Case: Complies with IEC 529, DIN 40050,
BS 5490 Case Material: Complies with UL 94VO
Weight
Single Function: 0.88 lb (0.4 kg) Multiple Function: 1.32 lb (0.6 kg)
Size
Single Function: 2.17” wide (55 mm) Multiple Function: 3.93” wide (100 mm)
Model
BE3-27, BE3-59, and BE3-27/59
AGENCY
cULus listed to UL 508 and CSA C22.2 No. 14 CE compliant GOST-R certified per the relevant standards of Gosstandart of
Russia
OPERATION
BE3-27 and BE3-59 ac voltage relays have two external, user­adjustable controls marked SET and RESET. The BE3-27/59 has four controls: UNDER SET, OVER SET, UNDER RESET, and OVER RESET. The SET control adjusts the relay trip point. An overvoltage trip causes the relay output to energize when the voltage rises above the SET threshold. The overvoltage SET level is adjustable from 100 to 125% (±3%) of nominal input (V undervoltage trip causes the relay output to de-energize when the voltage decreases below the SET threshold. The undervoltage SET level is adjustable from 75 to 100% (±3%) of nominal input. The RESET control adjusts the difference between the nominal input voltage and the reset voltage. An undervoltage reset occurs when the voltage increases above the RESET setting. The undervoltage RESET setting is set as the percentage below V will reset. An overvoltage reset occurs when the voltage decreases below the RESET setting. The overvoltage RESET setting is set as the percentage above V undervoltage and overvoltage RESET setting range is 1 to 15%.
Setting Example: a BE3-59 relay with a nominal input rating of 240 Vac has the following settings:
SET - 120% RESET - 10% A trip occurs when the sensing voltage rises above 288 Vac, line-to-
line. Reset occurs when the voltage decreases below 264 Vac (10% of nominal below the setpoint).
where the relay will reset. The
nom
when the relay
nom
nom
). An
INSTALLATION
BE3 ac voltage relays are designed for mounting on standard DIN rails that comply to DIN-EN 50022. Mounting involves hooking the top edge of the cutout on the base of the case over one edge of the DIN rail. The opposite side of the cutout containing the release clip is then pushed over the opposite side of the DIN rail. To remove or reposition the relay, lever the release clip and move the relay as required. BE3 relays should be installed in a dry, vibration-free location where the ambient temperature does not exceed the operating temperature range. Connections to the relay should be made using wire that meets applicable codes and is properly sized for the application. Figure 1 shows the terminal connections for the BE3-27, BE3-59, and BE3-27/59 relays.
CALIBRATION
The calibration marks on the faceplate have a maximum error of 10% and are provided only as guides. Proper calibration requires using an accurate voltmeter in parallel with the input signal. Use the following procedure to calibrate your relay.
Overvoltage
Adjust the SET and RESET controls fully clockwise (CW). Apply the desired trip voltage to the relay. Slowly adjust the SET control counterclockwise (CCW) until the
relay trips. Reduce the applied voltage to the desired reset level. Slowly adjust the RESET control CCW until the relay resets.
Publication
9319200990
Revision
E
Instructions
Date
04/14
Copyright
2014
Undervoltage
BE3-27, BE3-
59, BE3-27/59
N
1) Single Phase
3) Three Phase Three Wire
4) Three Phase Four Wire
Sensing Input
Type
MODEL NO.
P0
061-
74
A) 120 Vac B) 240 Vac C) 380
Vac D) 480 Vac S) Special voltage
Nominal Input Type
1 2
1) 50/60 Hz
2) 400 Hz
Frequency
N) Not required
External Power
1) Energize to trip (59)
2) De-energize to trip (27)
3) Energize to trip over, de­energize to trip under (27/59)
Output Type
1
2
For other voltage applications, contact Basler Electric. Voltages are line-to-line.
Adjust the SET control fully CCW and the RESET control fully CW. Decrease the applied sensing voltage from the nominal value until
the desired tripping voltage is reached. Slowly adjust the SET control CW until the relay trips. Increase the applied voltage to the desired reset level. Slowly adjust the RESET control CCW until the relay resets.
FIGURES
MAINTENANCE
BE3 relays are solid-state devices that require no maintenance. In the event that your relay requires repair, contact Basler Electric, Highland, IL, USA for return authorization.
ORDERING INFORMATION
Figure 2 shows the BE3 style number identification chart.
9319200990
Publication
Figure 1. BE3-27, BE3-59, BE3-27/59 AC Voltage Connections
Figure 2. BE3-27, BE3-59, BE3-27/59 Style Number Identification Chart
Revision
E
Instructions
Date
04/14
Page
2 of 2