This instruction manual provides information about the operation and installation of the BE1-79M Multiple
Shot Reclosing Relay. To accomplish this, the following information is provided:
General Information and Specifications
Controls and Indicators
Functional Description
Installation
Testing
Maintenance
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the BE1-79M is hard-wired to earth ground with no smaller than
12 AWG copper wire attached to the ground terminal on the rear of the unit
case. When the BE1-79M is configured in a system with other devices, it is
recommended to use a separate lead to the ground bus from each unit.
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use,
subject to return on request, and with the mutual understanding that it will not
be used in any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
For terms of service relating to this product and software, see the Commercial Terms of Products and Services document available at www.basler.com/terms
.
Basler Electric
12570 State Route 143
Highland IL 62249-1074 USA
www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-79M Introduction 9170100990 Rev N
REVISION HISTORY
The following information provides a historical summary of the changes made to this instruction manual
(9170100990) of the BE1-79M.
Manual
Revision and Date
N, 04/12
M, 01/11
L, 06/09
K, 11/06
J, 06/98
I, 01/97
H
Change
Improved accuracy of Pilot timings.
Improved Figures 3-6 and 4-11.
Removed reference to test set from Figure 5-1.
Standardized case and cover drawings in Section 4.
Updated Note 2 for Style Chart in Section 1.
Updated Figure 2-1 to match latest board layout.
Updated Storage statement in Section 6.
Removed In-House Repair from Section 6.
Removed BE1-79M Test Set from Section 6.
Updated power supply options descriptions in Style Chart.
Added manual part number and revision letter to page footers.
Added Notes 1 and 4 to style chart in Section 1.
Deleted reference to Service Manuals.
Replaced Power Supply paragraph on page 3-6 starting with “Basler
Electric enhanced the power supply…”
Deleted Figure 3-4 and added Table 3-3.
Corrected the Figure numbering following Figure 3-4.
Changed the burden data for new power supply in Table 1-2.
Separated Section 4 into two sections. Now Section 5 is TESTS and
ADJUSTMENTS.
Revised all numbers referring to figures, tables, and sections involved
in this change.
Added new dimension figures to include all options available (S1
Double-Ended and both mounting positions).
Added case ground to Figure 4-9.
Changed the format of the manual.
Corrected Figure 1-1 by adding 7, 8 to note #2.
Changed Specifications to reflect the updates in the Outputs, RFI,
and Surge Withstand Capability.
Clarified first paragraph on page 3-3.
Changed “INST” to “2
Added disconnects to 20 and 11 in Figure 4-3.
Revised Section 5, paragraph 1 to include both Service Manual
numbers.
Corrected an error on page 5-2.
Changed Introduction to include Service Manual, Publication
9170100623.
Added new Figures 4-3 and 4-9.
ND
TIME DELAY” in Figure 3-7.
9170100990 Rev N BE1-79M Introduction iii
Manual
Revision and Date
G
F
E
D
C
B
A
—, 01/86
Change
Changed Style Number Identification Chart first character from A to B
in response to ECA 12237.
Changed operational Test Procedure, Section 4 to improve
procedures and correct typographical error.
Added old Style Number Identification Chart to Section 7.
Manual revised to support the following relay changes:
o Six additional control output options.
o Two additional reclose time delay options.
o Y-type power supply option.
o Reset timer 1-100 second time delay option.
o Four additional special contact assignments options.
o A four function field selectable logic switch.
o Moved sensing input power module from outside the case to
inside the case.
Added Section 7, Difference Data, to support BE1-79M Relay revision
D and previous.
Operational test procedure revised.
Pages 5-5 and 5-6 added.
Section 6 added.
Temperature ....................................................................................................................................... 1-4
Figures
Figure 1-1. Style Number Identification Chart ........................................................................................... 1-3
Tables
Table 1-1. Burden (Nominal) Per Non-isolated Sensing Contact .............................................................. 1-6
Table 1-2. Power Supplies ........................................................................................................................ 1-6
9170100990 Rev N BE1-79M General Information i
ii BE1-79M General Information 9170100990 Rev N
SECTION 1 • GENERAL INFORMATION
Purpose
The BE1-79M Multiple Shot Reclosing Relay automatically recloses circuit breakers, which have been
tripped by protective relays or other devices in power transmission and distribution systems.
•Over 90% of faults occurring on overhead lines may be cleared by momentarily de-energizing the
line. Once the circuit breaker has been opened to de-energize the line, the BE1-79M provides a
reliable automatic reclosure. The advantages are:
•Improved Service Continuity - returns the line to service quickly, preserving line integrity and
minimizing outage effects on critical loads.
• System Stability - prevents disjointing of the system grid.
• Higher Line Loading - decreases likelihood of loss of line.
Application
Four major factors should be considered when establishing a reclosing philosophy.
• Desired number of reclosure attempts.
• Time delay between breaker opening and reclosure.
• Supervisory control.
• System coordination.
The first major factor is the desired number of reclosure attempts. Where most faults are attributable to
heavy tree exposure, as in distribution networks, multiple reclosure attempts are common. This is
possible because of low voltage levels and is desirable considering customer inconvenience during
outages. The BE1-79M is programmable for up to four reclosure attempts per sequence. This allows
tailoring of the reclosing sequence to the specific needs of the circuit.
The second major factor is the time delay between breaker opening and reclosure. On subtransmission
and distribution networks, it is necessary to ensure that motors are no longer running and that local
generation is off-line prior to attempting reclosure. At the same time, a rapid reclosure minimizes damage,
ionization, and system shock in transmission networks. After the first reclosure attempt, additional
attempts are generally delayed to allow for de-ionization of the interrupter. The BE1-79M incorporates one
instantaneous reclosing attempt with bypass capability, and up to three individually adjustable, timedelayed, reclosing attempts.
A third major factor to be considered in reclosing is supervisory control. Supervisory control allows the
operator to maintain control of the system at all times. The BE1-79M has inputs available to bypass the
instantaneous reclose attempt and to drive the relay to LOCKOUT inhibiting relay operation at any time.
In addition, a separate input is available which may be used to initiate a pilot reclosing sequence.
The fourth major factor is system coordination. The BE1-79M has outputs available which may be used to
block or enable instantaneous tripping of the circuit breaker and block a transformer's automatic load tap
changer operation during a reclosing sequence.
9170100990 Rev N BE1-79M General Information 1-1
Model and Style Number
The electrical characteristics and operational features included in a specific relay are defined by a
combination of letters and numbers, which constitutes the device's style number. The style number
together with the model number describe the features and options in a particular device and appear on
the front panel, drawout cradle and inside the case assembly. The model number BE1-79M designates
the relay as a Basler Electric, Class 100, Multiple Shot Reclosing Relay. The BE1-79M style chart is
shown in Figure 1-1.
Style Number Example
The following style number identification chart illustrates the features and options for BE1-79M relays. For
example, if the style number were BE1-79M B6A A6J C0L0F, the device would have the following
features:
BE1-79M Model Number
B Multiple shot
6 Lockout and reset with reclose fail and maximum cycle
A Instantaneous trip enable
A6 Reclose time delay adjustable from 0.1 to 99.9 seconds
J Operating power derived from 125 Vdc or 120 Vac source
C Reset time delay adjustable from 10 to 1000 seconds
0 Standard contact assignment
L Non-isolated contact sensing
0 No option 3 available
F Semi-flush mounting
Style Number Change
Effective November 18, 1991 (serial number 2812 and subsequent), the BE1-79M Multiple Shot
Reclosing Relay, style number identification for multiple shot is changed from A to B. This style number
change was made to differentiate relays with sensing input power module on the outside of the case
(style number A) and relays with the sensing input power module inside the case (style number B).
Section 7 of this manual provides difference data for style number A relays.
Compatibility
Relays with style number B are backwards compatible. That is, they may be used in place of relays with
style number A. The only exception is for a relay with a type Z power supply (250 Vdc/230 Vac) and
isolated sensing. For details, see section 7 of this manual.
Relays with style number A are NOT forward compatible. They may NOT be used in place of relays with
style number B.
1-2 BE1-79M General Information 9170100990 Rev N
Figure 1-1. Style Number Identification Chart
9170100990 Rev N BE1-79M General Information 1-3
Specifications
isolated sensing,
Accurate within 1% of
increments or
Accurate within 1% of setting or 0.5 seconds,
The BE1-79M Relay is available with the following features and capabilities.
Contact Sensing
Reclose Initiate
Breaker (52b)
Pilot Initiate
Instantaneous Reclose
Bypass
Drive to Lockout
Power Supply
Outputs
Timing
The contact sensing circuits require user-supplied contacts with a
minimum rating of 0.025 A at 250 Vdc. Sensing current is supplied by
the relay in styles with isolated sensing. Styles with non-isolated
sensing require an applied sensing voltage equal to the relay dc power
supply input rating. Burden per contact for nondependent on power supply type, is listed in Table 1-1.
Refer to Table 1-2.
Output contacts are rated as follows:
Resistive
120 Vac Make, break, and carry 7 Aac continuously.
250 Vdc Make and carry 30 Adc for 0.2 seconds, carry 7 Adc
continuously, break 0.3 Adc.
500 Vdc Make and carry 15 Adc for 0.2 seconds, carry 7 Adc
Reclose Fail (Optional) Adjustable from 0.1 to 9.9 seconds in 0.1 second increments. Accurate
Maximum Cycle (Optional) Adjustable from 1 to 1000 seconds in 1 second increments. Accurate
Temperature
Operating
Storage
1-4 BE1-79M General Information 9170100990 Rev N
Adjustable from 00.1 to 99.9 seconds in 0.1 second increments.
Accurate within 1% of setting or 0.05 seconds, whichever is greater.
Optionally adjustable from 1 to 999 seconds in one second increments
for the second and third reclose time delays.
setting or 0.5 seconds, whichever is greater.
Optionally adjustable from 0.03 to 0.99 seconds in 0.01 increments.
Accurate to within ±0.01 seconds of setting. If reclose time delay option
A8 is not specified, pilot reclose time is ≤ 0.035 seconds.
Adjustable from 10 to 1,000 seconds in 10-second
optionally adjustable from 1 to 100 seconds in 1 second increments. A
setting of 00 indicates a 1000 second reset time or optionally a 100
second reset time.
whichever is greater.
within 1% of setting or 0.05 seconds, whichever is greater.
within 1% of setting or 0.5 seconds, whichever is greater.
–40°C (–40°F) to 70°C (158°F)
–65°C (–85°F) to 100°C (212°F)
Radio Frequency
Relay Systems to Radiated Electromagnetic Interference from
nd held
perpendicular planes without structural damage or degradation of
sweeps, 15 minutes each sweep, without structural damage or
ugh 4 and 11 through 20, the maximum voltage
applied must be no greater than 300 V because of the MOV
1989 Standard Surge Withstand
1989 Standard Surge Withstand
Interference (RFI)
Maintains proper operation when tested for interference in accordance
with IECC C37.90.2-1989, Trial-Use Standard Withstand Capability of
Transceivers, and 99-1188, field tested using a 5 watt, ha
transceiver operating at random frequencies centered around 144 MHz
and 440 MHz, with the antenna located 6 inches from the relay in both
horizontal and vertical planes.
Shock
Vibration
Isolation
Surge Withstand Capability
Oscillatory
Fast Transient
In standard tests, the relay has withstood 15g in each of three mutually
performance.
In standard tests the relay has withstood 2g in each of three mutually
perpendicular planes swept over the range of 10 to 500 Hz for six
degradation of performance.
At terminals 1 thro
suppressors employed at these locations. At the remaining terminals,
2,500 Vac at 60 Hz for one minute may be applied in accordance with
IEC 255-5 and ANSI/IEEE C37.90-1989 (Dielectric Test).
Qualified to ANSI/IEEE C37.90.1Capability (SWC) Tests for Protective Relays and Relay Systems.
Qualified to ANSI/IEEE C37.90.1Capability (SWC) Tests for Protective Relays and Relay Systems.
Impulse Test
GOST-R Certification
Weight
Case Size
Qualified to IEC 255-5.
GOST-R certified per the relevant standards of Gosstandart of Russia.
13 lbs (5.9 kg)
S1; Refer to Section 4, Installation.
9170100990 Rev N BE1-79M General Information 1-5
Table 1-1. Burden (Nominal) Per Non-Isolated Sensing Contact
Power Supply Type K J L Z
Nominal Burden Per Input 0.75 W 1.60 W 0.70W 2.20 W
NOTE: For type Y Power supply, use burden for type K or type J power supply depending on nominal
operating voltage.
Table 1-2. Power Supplies
Type
K (midrange) 48 Vdc 24 to 150 Vdc 5.4 W
J (midrange)
L (low range) 24 Vdc 12 to 32 Vdc * 5.3 W
Y (midrange)
Z (high range)
∗ Type L power supply may initially require 14 Vdc to begin operating. Once operating, the voltage may
be reduced to 12 Vdc and operation will continue.
9170100990 Rev N BE1-79M Human-Machine Interface i
ii BE1-79M Human-Machine Interface 9170100990 Rev N
SECTION 2 • HUMAN-MACHINE INTERFACE
Controls and Indicators
Figure 2-1 illustrates the location of controls and indicators on the front panel. Table 2-1 explains the callouts shown in Figure 2-1. Table 2-2 lists the functions enabled per logic switch (S23) position.
Figure 2-1. Location of Controls and Indicators
9170100990 Rev N BE1-79M Human-Machine Interface 2-1
Table 2-1. BE1-79M Controls and Indicators (Refer to Figure 2-1)
al. Thumbwheel
adjustable from 10 to 1000 seconds in 10 second
adjustable from 0.1 to 9.9 seconds in 0.1 second
Locator Control or Indicator Function
A RECLOSE TIME
Controls (1, 2, 3)
B RESET Control
C RESET Switch
D RESET LED
E PILOT or RESET INHIBIT
LED (Optional)
Establish reclose time delays for corresponding time-
adjustable from 00.1 to 99.9 seconds in 00.1 second
increments or if reclose time delay option is A7, second and
third RECLOSE TIME thumbwheels are adjustable from
001 to 999 seconds in one second increments. A setting of
000 on a RECLOSE TIME thumbwheel indicates the
reclosing attempt is not desired and sends the relay to
lockout at this point in the reclosing sequence.
Establishes automatic reset interv
increments. Optionally adjustable from 1 to 100 seconds in
1 second increments. A setting of 00 indicates a reset time
of 1000 seconds or optionally, 100 seconds.
Momentary toggle switch, which extinguishes STATUS
LEDs (except LOCKOUT). Accessible by linkage, which
extends through bottom of front cover.
ON when relay is in RESET.
With PILOT option, LED is ON when pilot output relay coil
is energized. Remains ON until activation of manual
RESET lever, power loss, or when relay reaches RESET if
STATUS LED reset is optionally selected by logic switch
S23. With RESET INHIBIT option, LED is ON when reset
inhibit input is closed.
F POWER LED
G OUTPUT ENERGIZE LED
H RELAY FAIL LED
I STATUS LEDs
(INST., 1, 2, 3)
(LOCKOUT)
J INSTANTANEOUS TRIP
(Optional)
KRECLOSE FAIL LED
(Optional)
LRECLOSE FAIL Control
(Optional)
ON when the power supply is delivering a nominal ±12 Vdc
to internal circuitry.
ON when reclose output relay coil is energized.
ON when relay is not operable. Also ON during power-up
sequence.
Latched ON to indicate progression of reclosing sequence.
Extinguished by RESET lever, power loss, or when relay
reaches RESET if STATUS LED reset is optionally
selected by logic switch S23.
ON when relay is in LOCKOUT. (Non-latching.)
Five toggle switches, which enable or block instantaneous
tripping of circuit breaker. Numbers correspond to the relay
state or a specific trip depending on the type of reclosing
sequence in progress.
ON when circuit breaker 52b contact does not open within
selected time after reclose output has been energized.
Limits duration of reclose command signal. Thumbwheel
increments. For a setting of 00, the reclose command
signal is continuous until the breaker closes.
MMAX. CYCLE LED
(Optional)
2-2 BE1-79M Human-Machine Interface 9170100990 Rev N
ON when maximum cycle limit, as established by the MAX.
CYCLE control, has been exceeded.
LocatorControl or IndicatorFunction
With MAX. CYCLE, establishes maximum cycle limit
sequence until RESET or LOCKOUT). Thumbwheel
Field selectable, 16 position switch (S23) enables
NMAX. CYCLE or PILOT TIME
Control (Optional)
(maximum allowable interval from initiation of reclosing
adjustable from 1 to 1000 seconds in 1 second increments.
A setting of 000 allows a 1000-second maximum cycle.
With reclose time delay option A8 (PILOT TIME), the two
least significant digits are used for the pilot time delay for a
pilot reclose attempt. Thumbwheel adjustable from 0.03 to
0.99 seconds. A setting of .00, .01, and .02 is equivalent to
.03 setting.
O NORMAL/TEST Switch
P
Logic Switch
With Power-up to Reclose enabled, relay will close the breaker during powerup if relay was in RESET when powered down and Pilot Initiate or Reclose
Initiate is present during power-up.
Provides selection of relay operating mode.
combinations of the following functions.
• Memory save
• Power-up to reclose
• Recognition dropout
• Status LED reset
Refer to Table 2-2 for switch positions and functions
enabled. To be enabled, function changes require relay
power removal and power-up after setting switch position.
CAUTION
9170100990 Rev N BE1-79M Human-Machine Interface 2-3
Table 2-2. Logic Switch (S23) Positions and Functions Enabled
Position Functions Enabled
0∗∗
1 RD
2 SL
3 SL RD
4
5
6
7
8 MS
9 MS RD
A MS SL
B MS SL RD
C MS
D MS
E MS
PR∗
PR∗
PR∗
PR∗
PR∗
PR∗
PR∗
RD
SL
SL RD
RD
SL
F MS
NOTES:
∗∗Default position from factory
RD = Recognition Dropout
SL = Status LED Reset
PR∗= Power-up to Reclose (Refer to Caution preceding Table 2-2)
MS = Memory Save
PR∗
SL RD
2-4 BE1-79M Human-Machine Interface 9170100990 Rev N
General .................................................................................................................................................. 3-1
Data Retrieval ................................................................................................................................... 3-12
Data Retention ................................................................................................................................. 3-12
Clearing Stored Data ........................................................................................................................ 3-13