This instruction manual pr o v ides infor mation about the operation an d ins ta lla tio n o f the BE1-59NC Neutral
Overvoltage relay. To accomplish this, the following information is provided:
• General Information and Specifications
• Controls and Indicators
• Functional Description
• Installation
• Testing
WARNING!
To avoid personal inj ury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the re lay is ha r d-wir ed t o e ar th ground with no sma ller tha n 1 2 AWG
copper wire attached t o the ground terminal o n the rear of the unit case . When
the relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each unit.
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject
to return on request, and with the mutual understanding that it will not be used in
any manner detrimental to the interest of Basler Electric.
It is not the intent ion of th is manual to cover a ll detai ls and variat ions in eq uipment, n or does this manu al
provide data for ever y poss ibl e cont ing enc y regar di ng i nstal lat ion or operation. The avai lab il ity and des i gn
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
BASLER ELECTRIC
12570 STATE ROUTE 143
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-59NC Introduction 9279400990 Rev D
REVISION HISTORY
Revision and Date
Change
The following information provides a historical summary of the changes made to the BE1-59NC
instruction manual (9279400990). Revisions are listed in reverse chronological order.
Manual
D, 03/14
C, 01/13
B, 09/07
A, 09/94
—, 04/94
• Corrected inverse and definite timing accuracies in Section 1.
• Updated case and cover drawings in Section 4.
• Updated Output Contacts ratings in Section 1.
• Moved content of Section 6, Maintenance to Section 4.
• Updated front panel illustrations to show laser graphics.
• Moved content of Section 7, Manual Change Information to manual
introduction.
• Added manual part number and revision to all footers.
• Updated cover drawings.
• Updated power supply burden data in Secti on 1.
• Updated Target Indicator description in Section 3.
• Corrected voltage sensing input range in Specifications and
throughout the manual.
•Changed Figure 1-3, Overvoltage Inverse Time Curves to divide the
curves for low ranges (sensing input ranges 1, 3, 5, and 7) and high
ranges (sensing input ranges 2, 4, 6, and 8).
• Corrected typographical error in Figure 4-9.
• Changed Testing Procedures, D1 and D2 Timing Options TIME DIAL
settings.
• Added Section 7.
• Initial release
9279400990 Rev D BE1-59NC Introduction iii
This page intentionally left blank .
iv BE1-59NC Introduction 9279400990 Rev D
CONTENTS
SECTION 1 • GENERAL INFORMATION ................................................................................................ 1-1
BE1-59NC Neutral Ov ervoltage Relays provide s ensitive protection for capaci tor banks. There are three
common types of capacitor bank failures that BE1-59NC Neutral Overvoltage Relays recognize. They are:
• Unit dielectric failure
• Capacitor bank insulator failure
• Blown fuses
BE1-59NC Neutral Ov erv ol tage r e lays prot ect for ov er v oltag e due t o in ter na l volt a ge s hifts th at oc c ur as a
result of these types of failures.
APPLICATION
Capacitor banks are wi dely used by utilities to mai ntain specified system vo ltage. Addition of capacitive
loads at appropriate points on the system compens ate for heavy inductiv e loading that norma lly tends to
reduce voltage. This addin g of leading megavars to compensate f or the lagging megavar component o f
electric loads is frequ ently referred to as power factor correction. Capacitor banks must be switched in
response to actual load conditions in order to obtain maximum power factor c or rec tion ben efits.
Capacitor Bank Switching
One of the common metho ds of maximizing capacitor bank benefits is by evaluating the b us voltage. A
bandwidth surroundi ng the desir ed bus vo ltage lev el is est ablished. When the bus volta ge falls below the
bandwidth level, the capacitor bank is switched into the circuit. When the bus voltage rises above the
bandwidth level, the capacitor bank is switched out.
Protection
Protection of capacitor banks has always been diff icult. It is es pecially d ifficult to s ense failures i nside the
capacitor banks because of the configuration. Experience indicates that most capacitor bank faults
involve one or more insulat or failur es with arc ing ac ross groups and/or phase-to-phase inside the ba nk . In
most cases, these types of faults are n ot seen by the bus differ entia l or other prot ection unless the ar cing
spills over to the area between the fuses and the circuit switcher. A fault across an insulator usually
means that one or more groups of parallel units are shorted. This will cause a neutral shift and
unbalanced phase currents. Unbalanced phase current magnitudes are determined by the number of
series connected groups . For full phase-to-neutral flashover, the maximum phase c urrent is three times
normal capacitor bank load in the faulted phase.
One main protection conc ern is overvoltage cascading. A capac itor bank is unique in that cascading of
units may take place aft er a pr edet er mined number of unit fuses have operated. Normally af t er a fus e h as
blown in any other ty pe of equipment, the faulted apparatus is disconnected and us ually does not affect
any remaining equipment that is in service. That is not so w ith a capacitor bank. Each fuse tha t blows to
isolate the faulted unit s ets up an incr ease d voltag e str ess on the rem ainin g units (Figure 1-1). Somet ime
later, the next weakest unit in that group fails. As each successive fuse blows, the voltage increases
another step and rapidly causes the next unit to fail. Cascading takes place and results in serious damage
to the capacitor bank and p ossible hazards to pers onn el. Wh ile the ca pacit or ban k is failing, th e stat ion in
minimally affected. The v oltage is nearly normal, t he current flow is al most unaffected, and statio n relay
protection is not taking any action until the failure has developed into a phase-to-phase or phase-toground fault.
A solution was to develop a protective scheme for the capacitor bank with the main emphasis on
preventing overvoltage cascading. To do this, a ground fault relay or neutral shift device had to be
developed that was s ensitive eno ugh to detec t blown fuses for bot h alarming a nd tripping purposes. Th e
best place to obtain the s ensing information is between the neutral of the capacitor bank and ground.
Voltage differentia ls bet ween t he nor mal c apaci tor ba nk s tatus and th at of one b lown f use are v ery s mall.
However, BE1-59NC Neutral Overvoltage relays are sensitive enough to differentiate between these
conditions and act decisively.
9279400990 Rev D BE1-59NC General Information 1-1
Figure 1-1. Ungrounded 3-Phase, 3-Wire Sys tem
Input Sensing
BE1-59NC Neutral O vervoltage relays receive the input signal from volta ge sensing devices connecte d
between the capacitor bank neutral and ground. These voltage sensing devices can be potential
transformers or resistor potential devices. Ideally, the voltage across each leg of a capacitor bank is
balanced, and the voltage from neutral to ground is zero. If a single capacitor fails and blows the
protecting fuse, an unbalanced condition occurs that shifts the neutral and creates a small but
measurable voltage. Through the potential sensing devices, the neutral relay senses this voltage
unbalance and reacts to g ive the appropriate signal (usual ly an alarm or trip depending on the vo ltage
level).
Further loss of more c apac it ors incr eas es the neutral voltage. T he r e lay sens es th i s voltage inc re as e, an d
reacts to give the appropr iate signa l. This signal is us ually a tr ip dep ending o n the voltage levels a nd how
the protection scheme is designed.
Alarms and Outputs
Sensitive settings on the relay are used as an a larm to alert that a fuse has blown and maintenance is
required. They woul d be typically set at a leve l corresponding to the vol tage rise caused by one b lown
fuse. The second out put would have a s etting that would be set to trip the capacitor bank off t he bus or
line when the voltage exce eds 110% of the nom inal capacitor bank volt age. This setting depe nds on the
capacitor bank size and configuration.
1-2 BE1-59NC General Information 9279400990 Rev D
MODEL AND STYLE NUMBER
Electrical characteristics and operational features included in a specific relay are defined by a
combination of letters and numbers that make up the style number. Mod el number BE1-59NC designates
the relay as a Basler Electric Neutral Overvoltage Relay. The model number, together with the style
number, describes the options included in a specific device and appears on the front panel, draw-out
cradle, and inside the case assembly.
The style number identification chart for the BE1-59NC relay is illustr at ed in Figure 1-2.
Figure 1-2. Style Number Identification Chart
Style Number Example
If a BE1-59NC relay has a style number of A5E–E2J–C0S1F, the relay has the following features:
A -------- Single-phase voltage sensing
5 -------- 120 Vac, 60 Hz, nominal 1 to 20 Vac pickup
E -------- Two output relays with normally open contacts
E2 ------ Setpoint 1 Definite (0.1 to 99.9 sec.), Setpoint 2 Definite (0.1 to 99.9 sec.)
J -------- 125 Vdc or 100/120 Vac power supply
C -------- Internally opera ted tar gets
0 -------- None
S -------- Push-to-energize outputs
1 -------- Two SPDT auxiliary output relays, one for setpoint 1 and one for setpoint 2
F -------- Semi-flush mounting case
9279400990 Rev D BE1-59NC General Information 1-3
SPECIFICATIONS
Electrical and physical specifications are listed in the following paragraphs.
Voltage Sensing
Maximum continuous rat ing : 36 0 V ac for 100 /12 0 V ac i nput, 48 0 Vac
for 200/240 Vac input, with a maximum burden of 2 VA.
Sensing Input Ranges
Ranges 1 and 5: 1 to 20 Vac pickup
Ranges 2 and 6: 10 to 50 Vac pickup
Ranges 3 and 7: 2 to 40 Vac pickup
Ranges 4 and 8: 20 to 100 Vac pickup
Pickup Accuracy
Ranges 1, 3, 5, or 7: ±2.0% or 100 millivolts, whichever is greater.
Ranges 2, 4, 6, or 8: ±2.0% or 200 millivolts, whichever is greater.
Dropout
98% of pickup within 7 cycles.
Timing Characteristics
Inverse: Response time decreases as the difference between the monitored
voltage and the setpoint increases. The inverse time char acteristics
switch is adjustable from 01 to 99 in 01 increments. Each position
corresponds to a specific curve except 0 0, which is instantaneous.
Accuracy is within ±5% or 25 milliseconds, whichever is greater.
Definite: Adjustable from 00.1 to 99.9 seconds, in steps of 0.1 seconds. (A
setting of 00.0 provides instantaneous timing.) Accuracy is within
±2% or 100 milliseconds, whichever is greater.