This instruction manual provides information about the operation and installation of the BE1-50/51B-244
Overcurrent Relay. To accomplish this, the following information is provided:
General Information and Specifications
Controls and Indicators
Functional Description
Installation and Maintenance
Testing
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear of the unit case.
When the relay is configured in a system with other devices, it is
recommended to use a separate lead to the ground bus from each unit..
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use,
subject to return on request, and with the mutual understanding that it will not
be used in any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
BASLER ELECTRIC
12570 STATE ROUTE 143
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-50/51B-244 Introduction 9252000793 Rev C
REVISION HISTORY
The following information provides a historical summary of the changes made to this instruction manual
(9252000793). Revisions are listed in reverse chronological order.
Manual
Revision and Date
C, 12/11
B, 05/11
A, 04/11
—, 03/11
Clarified target operate current specs in Sections 1 and 2.
Replaced Figure 4-3, Outline Dimensions, FT21 case.
Replaced Figures 4-2, 4-3, and 4-6. Removed terminal 7 and the
Replaced Figures 4-2, 4-3, and 4-6. Added terminal 7 and a
Initial release
Change
connection between terminal 7 and ground.
connection between terminal 7 and ground.
9252000793 Rev C BE1-50/51B-244 Introduction iii
iv BE1-50/51B-244 Introduction 9252000793 Rev C
CONTENTS
SECTION 1 • GENERAL INFORMATION ................................................................................................ 1-1
SECTION 2 • CONTROLS AND INDICATORS ........................................................................................ 2-1
Features ................................................................................................................................................. 1-1
Type Tests .......................................................................................................................................... 1-5
Table 1-1. Westinghouse Relays Suitable for Direct Replacement .......................................................... 1-1
9252000793 Rev C BE1-50/51B-244 General Information i
ii BE1-50/51B-244 General Information 9252000793 Rev C
SECTION 1 • GENERAL INFORMATION
Introduction
BE1-50/51B-244 protective relays are direct replacements for Westinghouse type CO relays. The BE150/51B-244 has a 5-ampere current sensing input. The BE1-50/51B-244 is provided with a case that fits
into an FT-11 cutout or an FT-21 cutout with an adapter plate (Basler P/N 9252017005). A cover is also
provided. Compatible Westinghouse model numbers are listed in Table 1-1.
Table 1-1. Westinghouse Relays Suitable for Direct Replacement
ABB Catalog Number Curve Type
CO-2∗11∗1N
CO-5∗11∗1N
CO-6∗11∗1N
CO-7∗11∗1N
CO-8∗11∗1N
CO-9∗11∗1N
CO-11∗11∗1N
∗ Any digit covering all pickup ranges except 50 Hz models.
To replace an existing Westinghouse type CO relay, perform the following steps:
1. Select the desired relay settings on your new BE1-50/51B-244 relay.
2. Remove the existing relay and case.
3. Insert the new relay and case.
4. Install the connection plug.
5. Install the cover and secure with the captive thumbnut.
BE1-50/51B-244 relays are self-powered, compatible with 50 or 60 Hz power systems, and have three
protection elements: one time overcurrent (51) element and two instantaneous overcurrent (50) elements.
The 51 element offers timing characteristic curves similar to those used by GE IAC relays.
Short Time
Long Time
Definite
Moderately Inverse
Inverse
Very Inverse
Extremely Inverse
Features
A wide range of pickup settings and front panel selectable time characteristics permit applications
involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.
In addition, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-244 overcurrent relays have the following standard features:
• Independent time and instantaneous elements
• A secure method to manually trip the breaker at the relay front panel
• Direct reading front panel controls
• Minimum pickup setting for safety during installation
• Time characteristics extend to a pickup multiple of 40
• Rugged draw-out construction with steel case
• Gravity latching targets retain indication without power
• Field-selectable characteristic curve selection similar to GE IAC or Westinghouse CO type curves
• Field selectable instantaneous or integrating reset
• Field selectable 50 or 60 Hz operation
• Field selectable 0.0 or 0.1 second, fixed, instantaneous delay
Internal switches provide for selecting system-operating frequencies of 50 or 60 Hz, instantaneous
element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or
9252000793 Rev C BE1-50/51B-244 General Information 1-1
Westinghouse CO type curves, and instantaneous or integrating reset characteristics. Switch location and
description is provided in Section 2.
Advantages
BE1-50/51B-244 overcurrent relays have many advantages over other overcurrent relays. The primary
advantages are:
• Time characteristics are defined by equations and graphs
• Field selectable time characteristics
• Very low burden extends the linear range of the CTs
• Self powered from the sensed current
• Continuous automatic calibration
BE1-50/51B-244 overcurrent relays may be tested without removing the relay from the case. Shorting
contacts are provided for all current inputs when the connection plug is removed from the relay case.
Specifications
BE1-50/51B-244 electrical and physical specifications are listed in the following paragraphs.
Time Overcurrent (51) Element
BE1-50/51B-244 Pickup
Setting Range: 0.5 to 15.9 Aac
Setting Increment: 0.1 Aac
Accuracy: Sum of ±2% and ±25 mAac
Dropout
Dropout occurs at 95% of pickup value.
Characteristic Curves
Available curve types follow IEEE Standard C37.112 (1996) and emulate standard GE IAC,
Westinghouse CO, and BS142 curves. Appendix A, Characteristic Curves illustrates the available curves
and lists the applicable constants.
Curve Types: Short Inverse, Long Inverse, Definite Time, Moderately Inverse, Inverse,
Very Inverse, Extremely Inverse, BS142 Very Inverse, BS142 Extremely
Inverse, Fixed Time
Time Multiplier: 11 curves for each characteristic
Timing Accuracy: ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap
and is for a given measured multiple of tap.
Fixed Timing
Setting Range: 0.1 to 9.9 s
Setting Increment: 0.1 s
Timing Accuracy: ±1 cycle, ±2% of the time to trip for time dial settings ≥ 0.1.
Reset
Integrating: Simulates the disk reset of electromechanical relays and begins when
the current decreases below 95% of pickup. Appendix A, Characteristic
Curves illustrates the integrating reset characteristic curve and equation.
Instantaneous: Reset occurs within 16 ms of when the current decreases below 95% of
the pickup level.
Instantaneous Overcurrent A (50-A) Element
BE1-50/51B-244 Pickup
Setting Range: 2 to 99 Aac
Setting increment: 1 Aac
Accuracy: Sum of ±2% and ±25 mAac
Dropout
Dropout occurs at 95% of pickup value.
1-2 BE1-50/51B-244 General Information 9252000793 Rev C
Time Delay
Continuous Current
Current Sensing Input
0
2
4
6
8
10
12
14
16
-40-200204060
Ambient Temperature (C)
Current (Aac)
Switch selectable—no intentional delay (SW3-2 OFF) or a fixed delay of 100 ms (SW3-2 ON). Appendix
A, Characteristic Curves illustrates the characteristic curve for the 50-A and 50-B elements.
Instantaneous Overcurrent B (50-B) Element
BE1-50/51B-244 Pickup
Setting Range: 1 to 15.9 Aac
Setting increment: 0.1 Aac
Accuracy: Sum of ±2% and ±25 mAac
Dropout
Dropout occurs at 95% of pickup value.
Time Delay
Fixed at no intentional delay. Appendix A, Characteristic Curves illustrates the characteristic curve for the
50-A and 50-B elements.
Reset Characteristic
Resets within 16 ms of when sensed current decreases below the pickup level.
Current Sensing Input
BE1-50/51B-244
Continuous Rating: 14 Aac ∗
1 Second Rating: 400 Aac
∗ Continuous rating is 14 Aac for temperatures up to 45°C. See Figure 1-1 for derating curve.
BE1-50/51B-244 Burden
Figure 1-2
At 0.5 Aac: 2.8 Ω
At 5.0 Aac: 0.3 Ω
illustrates the current sensing input burden characteristic.
Figure 1-1. Current Sensing Input Derating Curve (BE1-50/51B-244)
9252000793 Rev C BE1-50/51B-244 General Information 1-3
BE1-50/51B-230 CT Burden
0
20
40
60
80
100
120
140
160
01020304050
Input Current (Amps)
Burden in VA (rms)
BE1-50/51B-244 CT Burden
Figure 1-2. Current Sensing Input Burden (BE1-50/51B-244)
Frequency Response
A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for
pickup.
Transient Response
<10% overreach with system time constants up to 40 ms.
Harmonic Rejection
Rejection of odd and even harmonics is illustrated in Figure 1-3.
1-4 BE1-50/51B-244 General Information 9252000793 Rev C
Figure 1-3. Harmonic Rejection
Target Indicators
A gravity-latched, manually-reset, current-operated target indicator is provided for the time-overcurrent
(51) trip output and the instantaneous overcurrent A (50-A) trip output. A target indicator is not provided
for the 50-B trip output. The level of trip circuit current required to operate each target is individually
controlled by a circuit board jumper. See Section 2, Controls and Indicators for jumper locations and
function assignments.
Target Operate Current
not
Jumper Position—Pins 1 and 2: must operate ≥ 2.25 A; must
Jumper Position—Pins 2 and 3: must operate ≥ 200 mA; must
* See Output Contacts for the maximum acceptable levels of trip circuit currents.
operate < 900 mA ∗
operate < 80 mA ∗
not
Output Contacts
Output contacts are surge protected and rated as follows.
Resistive Ratings
120/240 Vac: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive Ratings
120/240 Vac, 125/250 Vdc: Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
9252000793 Rev C BE1-50/51B-244 Controls and Indicators i
ii BE1-50/51B-244 Controls and Indicators 9252000793 Rev C
SECTION 2 • CONTROLS AND INDICATORS
A
BC
D
EF
G
H
I
P0064-42
ACTIVE/PICKUP
PICKUP
(0.5 MIN. SET)
TIME DIAL
TENTHSUNITS
++
TENTHSUNITSCURVE
+
UNITSTENS
INSTTIME
PICKUP
INSTTIME
BE1-50/51B-244
OVERCURRENT
RELAY
Introduction
BE1-50/51B-244 relay controls and indicators are located on the front panel and circuit board.
Front Panel Controls and Indicators
Front panel controls and indicators are illustrated in Figure 2-1 and described in Table 2-1. The locators
and descriptions of Table 2-1 correspond to the locators shown in Figure 2-1.
Figure 2-1. Front Panel Controls and Indicators
9252000793 Rev C BE1-50/51B-244 Controls and Indicators 2-1
Table 2-1. Front Panel Controls and Indicators
Locator
Description
A
Instantaneous Overcurrent Manual Trip Jacks. These jacks are used to manually trip a
These jacks do not activate the 50-B trip output contacts.
B
Instantaneous Overcurrent A Pickup Selector Switches. These two rotary switches select
C
Target Indicators. Red target indicators latch when the corresponding set of trip contacts
indicators are reset by pressing the target reset button (locator I).
D
Time Overcurrent Pickup Selector Switches. These two rotary switches select the time
relay is in service may cause the relay to trip.
E
Curve Selector Switch. This ten position rotary switch selects one of nine inverse timing
details about the timing characteristics of the BE1-50/51B-244.
these switches corresponds to a time delay of 0.0 to 9.9 seconds.
G
Time Overcurrent Manual Trip Jacks. These jacks are used to manually trip a breaker
terminated with two standard 0.08 inch diameter phone-tip plugs, into the two jacks.
H
Active/Pickup Indicator. This bicolor LED indicates the level of current sensed by the relay.
I
Target Reset Button. This button is pressed to reset the two, gravity-latched target
indicators (locator C).
breaker controlled by the 50-A trip output contacts. This is achieved by plugging a jumper
wire, terminated with two standard 0.08 inch diameter phone-tip plugs, into the two jacks.
the instantaneous overcurrent A (50-A) pickup current setting in amperes (UNITS and
TENTHS). Adjusting these selector switches while the relay is in service may cause the
relay to trip.
NOTE
When testing time overcurrent functions, instantaneous pickup settings of 00
will affect the calibration of the time functions. Time pickup settings of 00 also
affect instantaneous functions.
closes and sufficient trip circuit current is detected. (The level of current that will trip each
target indicator is jumper-selectable. See Circuit Board Controls for more information.) The
Time target indicates the flow of current in the time overcurrent (51) trip circuit. The Inst
target indicates the flow of current in the instantaneous overcurrent A (50-A) trip circuit. No
target is provided for the instantaneous overcurrent B (50-B) trip circuit. Both target
overcurrent pickup current setting in amperes. Adjusting these selector switches while the
characteristics or one fixed time function. Refer to Appendix A, Characteristic Curves for
F Time Overcurrent Time Dial Selector Switches. These two rotary switches select the
desired curve of the timing characteristic selected by the Curve Selector Switch (locator E).
When a fixed time characteristic is used (Curve Selector Switch setting of F), the setting of
controlled by the 51 trip output contacts. This is achieved by plugging a jumper wire,
The LED is red when the sensed current exceeds the time overcurrent pickup setting. The
LED color changes from red to green when the sensed current decreases below 95% of the
time overcurrent pickup setting. A green LED indicates that the relay is active but not picked
up.
2-2 BE1-50/51B-244 Controls and Indicators 9252000793 Rev C
Circuit Board Controls
A
B
C
P0064-45
Circuit board controls consist of two rotary selector switches, a four-position slide switch, and two
jumpers. Circuit board controls are illustrated in Figure 2-2 and described in Table 2-2. The locators and
descriptions of Table 2-2 correspond to the locators shown in Figure 2-2.
Figure 2-2. Circuit Board Controls
9252000793 Rev C BE1-50/51B-244 Controls and Indicators 2-3
Table 2-2. Circuit Board Controls
Locator
Description
A
Target Operating Current Jumpers. Two user-adjustable jumpers control the range of trip
must notB operate < 80 mA.
Four Position Slide Switch. This switch assembly, designated SW3, has four independent
instantaneous reset characteristic.
C
Instantaneous Overcurrent B Pickup Selector Switches. These two screwdriver-adjusted,
circuit current required to operate the time overcurrent (51) and instantaneous overcurrent
A (50-A) target indicators. Jumper J1 sets the minimum current range for the 50-A target
indicator and J2 sets the minimum current range for the 51 target indicator. Two jumper
positions are possible: across pins 1 and 2 or across pins 2 and 3. When the jumper is
installed across pins 1 & 2, the targets must operate ≥ 2.25 A and must
mA. When the jumper is installed across pins 2 & 3, the targets must operate ≥ 200 mA and
slide switches designated SW3-1, SW3-2, SW3-3, and SW3-4. Each switch functions as
follows:
SW3-1 selects the nominal system frequency. The OFF position selects 60 Hz operation
and the ON position selects 50 Hz operation.
SW3-2 provides an additional time delay for the instantaneous overcurrent A (50-A)
element. The ON position provides an additional delay of 100 milliseconds.
SW3-3 selects either GE IAC or Westinghouse CO type characteristic curves. The ON
position selects the GE IAC type curves (listed in Table A-1) and the OFF position selects
the Westinghouse CO type curves (listed in Table A-2).
SW3-4 selects either an instantaneous or integrating time reset characteristic. The ON
position selects an integrating reset characteristic and the OFF position selects an
not operate < 900
rotary switches select the instantaneous overcurrent B (50-B) pickup current setting in
amperes.
The 50-B pickup switches are accessed on the top side of the draw-out assembly by
removing the draw-out assembly from the case.
The left-hand switch (SW9) is a 16-position switch that sets the units portion (#.#) of the 50B pickup setting in amperes. SW9 setting positions consist of 0 through 9 which correspond
to values of 0 to 9 amperes and A through F which correspond to values of 10 to 15
amperes. The right-hand switch (SW10) is a 10-position switch that sets the tenths portion
) of the 50-B pickup setting in amperes. SW10 setting positions consist of 0 through 9
(#.#
which correspond to values of 0.0 to 0.9 amperes.
The minimum allowable 50-B pickup setting is 1.0 Aac and the maximum allowable 50-B
pickup setting is 15.9 Aac. Adjusting the 50-B pickup selector switches while the relay is in
service may cause the relay to trip.
Example: SW9 position 2 and SW10 position 5 is a setting of 2.5 Aac.
2-4 BE1-50/51B-244 Controls and Indicators 9252000793 Rev C
Figure 3-1. Function Block Diagram .......................................................................................................... 3-1
9252000793 Rev C BE1-50/51B-244 Functional Description i
ii BE1-50/51B-244 Functional Description 9252000793 Rev C
SECTION 3 • FUNCTIONAL DESCRIPTION
Introduction
This section illustrates and describes the functional capabilities of the BE1-50/51B-244 relay.
Functional Block Descriptions
The function blocks of the BE1-50/51B-244 relay are illustrated in Figure 3-1 and described in the
following paragraphs.
Figure 3-1. Function Block Diagram
Current Sensing Input
Single-phase ac current supplied by a system current transformer (CT) is applied to the BE1-50/51B-244
through terminals 8 and 9. Sensing current is applied to internal power and signal CTs.
Power CT and Power Supply
The output of the power CT is supplied to the power supply which provides rectified and filtered operating
power for all relay circuitry. A precision 5 Vdc output of the power supply serves as a reference for
automatic calibration.
Signal Conditioning
Current from the signal CT is rectified and applied to three independent sets of scaling resistors controlled
by the Time Overcurrent (51), Instantaneous Overcurrent A (50-A), and Instantaneous Overcurrent B (50B) pickup switches. The analog-to-digital converter receives the analog voltage developed across the
scaling resistors and converts it into a digital signal that is supplied to the microprocessor.
Microprocessor
The microprocessor performs program operations based on the sensed current, switch settings, and the
internal software program.
When sufficient current is sensed by the relay, the microprocessor is active and executing code, and the
Active/Pickup LED is green. When the sensed current decreases below the operating threshold,
microprocessor operation is interrupted and the Active/Pickup LED turns off. A watchdog circuit resets the
microprocessor program when code execution is interrupted.
Power-off sensing circuits measure the voltage across a capacitor at power-down and power-up. These
circuits determine how long power has been removed based on the difference voltage and the circuit’s
9252000793 Rev C BE1-50/51B-244 Functional Description 3-1
RC time constant. This provides information from the integrating reset function even when power has
been entirely removed.
The microprocessor performs the program operations based on the inputs and the internal software
program. When the sensed current exceeds the TIME PICKUP setting, the ACTIVE/PICKUP LED turns
from green to red. The 50-A/51 contact is closed in accordance with the TIME characteristic equation or if
the sensed current exceeds the INST PICKUP setting. Likewise, sensed current exceeding the
Instantaneous Overcurrent B Pickup selector switch setting causes the 50-B Trip output contacts to close.
Outputs
Each protective element (time overcurrent (51), instantaneous overcurrent A (50-A), and instantaneous
overcurrent B (50-B)) is equipped with a set of normally-open contacts rated for tripping duty. A system
circuit breaker controlled by the 51 or 50-A output contacts can be manually tripped by connecting a
jumper across the Time Overcurrent Manual Trip jacks or the Instantaneous Overcurrent Manual Trip
jacks. (Manual trip jacks are not provided for the system circuit breaker controlled by the 50-B output
contacts.) Current flow in a trip circuit is indicated by operation of the corresponding target. The targets
will not operate without adequate relay operating power.
WARNING!
Trip circuit voltage is present at the front panel trip jacks. When shorting the
trip jacks, use insulated jumpers to avoid contact with these voltages.
Target Indicators
Gravity-latched, manually-reset, current-operated target indicators are provided for the time overcurrent
(51) trip output and the instantaneous overcurrent A (50-A) trip output. A target indicator is not provided
for the 50-B trip output. The level of trip circuit current required to operate each target is individually
controlled by a circuit board jumper. The minimum operating current range can be set for 80 to 200
milliamperes or 0.9 to 2.25 amperes. See Section 2, Controls and Indicators for jumper locations and
function assignments.
3-2 BE1-50/51B-244 Functional Description 9252000793 Rev C
General .................................................................................................................................................. 4-1
When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to
prevent damage during transit. Immediately upon receipt of a relay, check the model and part number
against the requisition and packing list to see that they agree. Visually inspect the relay for damage that
may have occurred during shipment. If there is evidence of damage, immediately file a claim with the
carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric,
Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedure of Section 5.
If the relay will not be installed immediately, store the relay in its original shipping carton in a moisture and
dust-free environment.
Mounting
Relay outline dimensions and panel drilling diagrams are shown in Figures 4-1 through 4-3.
Figure 4-1. Panel Drilling Diagram, FT11 Case
9252000793 Rev C BE1-50/51B-244 Installation 4-1
Figure 4-2. Outline Dimensions, FT11 Case
Figure 4-3. Outline Dimensions, FT21 Case
Factory Settings
Factory settings for the internal switches of SW3 and jumper settings are as follows:
• SW3-1 — OFF (60 hertz operation).
• SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element).
• SW3-3 — OFF (Westinghouse CO type characteristic curves).
• SW3-4 — ON (Integrating reset characteristics).
• J1 pins 2-3 — 50-A minimum target operating current of 80 to 200 mA
• J2 pins 2-3 — 51 minimum target operating current of 80 to 200 mA
4-2 BE1-50/51B-244 Installation 9252000793 Rev C
Installation
Select the desired relay settings before putting the relay into service. Changing pickup current settings
while the relay is in service may cause tripping. Perform the following procedures to install the BE150/51B-244 relay.
1. Select the desired relay settings on your new BE1-50/51B-244 relay.
2. Remove the existing relay and case.
3. Insert the new relay and case.
4. Install the connection plug.
5. Install the cover and secure with the captive thumbnut.
Connections
Typical ac and dc connections are shown in Figures 4-4 and 4-5. Figure 4-6 shows a rear view of the
relay and the connections.
Figure 4-4. Typical AC Connections
9252000793 Rev C BE1-50/51B-244 Installation 4-3
1
50-A
51
S SHORT INVERSE
LONG INVERSE
L
DEFINITE TIME
D
MODERATELY INVERSE
M
INVERSE
IC
BS142 EXTREMELY INVERSE
B
BS142 VERY INVERSE
F
FIXED TIME
E
EXTREMELY INVERSE
VERY INVERSEV
CURVE DEFINITIONS
2
4
6
37
108
9
OVERCURRENT
CT
50-B
GND
P0064-48
Figure 4-5. Typical DC Connections
Figure 4-6. Terminal Connections, Rear View
4-4 BE1-50/51B-244 Installation 9252000793 Rev C
Application Coordination
KBD
CM
AD
T
N
T
++
−
=
110
1
M
RD
T
2
R
−
=
seconds 15.5
10
27.75
2
−=
−
×
=
In a typical application coordination scheme, a BE1-50/51B-244 is used to provide primary protection for a
radial distribution feeder. An electromechanical overcurrent relay with extremely inverse timing provides
protection for the transformer and bus. To improve coordination with the electromechanical relay, the
BE1-50/51B-244 is configured with the following settings:
• Integrating reset enabled (SW3-4 ON)
• Westinghouse CO type curves selected (SW3-3 OFF)
The feeder reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a
permanent fault occurs (magnitude 10 times pickup), calculate the feeder breaker trip time for each of the
three operations. Refer to Appendix A for the characteristic curve constants and definition of the terms
used in the following time characteristic curve equations.
From the time characteristic curve equation:
27624.7
=
0938.2
From the reset characteristic curve equation:
×
−
= 0.209 seconds
+×+
028.0)202758.0(
M equals 0 if current goes to zero. A negative result indicates reset time.
Result: Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.
In Figure 4-7:
= 0.209 seconds (relay was at reset)
T
A
= value<TA because rewind has not gone to zero
T
B
= value<TA because rewind has not gone to zero
T
C
Figure 4-7. Coordination Timing Diagram
9252000793 Rev C BE1-50/51B-244 Installation 4-5
Maintenance
BE1-50/51B-244 relays require no preventative maintenance other than periodic checking of relay
connections to make sure that they are clean and tight. If the relay fails to function properly, contact the
Technical Sales Support department of Basler Electric.
Storage
This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once
per year.
Dielectric Test ........................................................................................................................................ 5-1
Test Procedures ..................................................................................................................................... 5-1
Model BE1-50/51B-244 (Five Ampere Sensing Input) ....................................................................... 5-1
Time Overcurrent (51) Pickup ........................................................................................................ 5-1
Time Dial ......................................................................................................................................... 5-2
Observe all applicable electrostatic discharge (ESD) precautions when
Introduction
Proper relay operation may be confirmed by performing the test procedures in this section.
Dielectric Test
In accordance with IEC 255-5 and IEEE C37.90-1989, one-minute dielectric (high potential) tests may be
performed as follows:
All circuits to ground: 2,828 Vdc or 2,000 Vac
Input to output circuits: 2,828 Vdc or 2,000 Vac
Output contacts are surge protected.
Test Procedures
The following test procedure verifies operation of the BE1-50/51B-244 relay. The test setups illustrated in
Figures 5-1 through 5-6 are intended primarily as an illustration of the principles involved. Other test
equipment known to be capable of testing with the stated and implied tolerances (including equipment
designed specifically for testing protective relays) may be used.
The minimum test equipment requirements are:
• Current source with a range of 0 to 20 Aac (sensing input current)
• AC or DC voltage source (target operation)
• Timer or counter
NOTES
To ensure proper timing during testing, remove the current from the relay for R
times D seconds. (Refer to Appendix A, Characteristic Curves for definitions of
R and D.
When testing TIME overcurrent functions, INST PICKUP settings of 00 will
affect the calibration of the TIME functions. TIME PICKUP settings of 00 also
affect INST functions.
handling the relay assembly.
Model BE1-50/51B-244 (Five Ampere Sensing Input)
Time Overcurrent (51) Pickup
1. Connect and configure the relay for 51 pickup testing:
a. Connect the test setup shown in Figure 5-1.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set the TIME DIAL to 0.0.
d. Set CURVE to S.
e. Set TIME PICKUP to 0.5.
f. Set INST PICKUP (50-A) to 90.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (15.0 Aac).
9252000793 Rev C BE1-50/51B-244 Testing 5-1
2. Apply and increase current to terminals 8 and 9 until the Active/Pickup LED turns red. The applied
current should be no greater than 0.55 Aac.
3. Decrease the applied current until the Active/Pickup LED changes from red to green and then off.
4. Set TIME PICKUP to 2.2.
5. Slowly increase current to terminals 8 and 9 until the Active/Pickup LED turns red. The applied
current should be between 2.131 and 2.269 Aac.
6. Reduce the applied current to zero.
Time Dial
1. Connect and configure the relay for time dial testing:
a. Connect the test setup shown in Figure 5-1.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set TIME DIAL to 4.5.
d. Set CURVE to S.
e. Set TIME PICKUP to 1.0.
f. Set INST PICKUP (50-A) to 90.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (15.0 Aac).
2. Prepare to apply 1.5 Aac to terminals 8 and 9 and record the elapsed time from when current is
applied until the 51 output contacts close.
3. Apply the current (step from 0 to 1.5 Aac) and record the elapsed time. The elapsed time should be
between 0.345 and 0.424 seconds. (This tolerance is greater than ±2% because it is the
accumulation of both pickup and timing tolerances.)
4. Remove the input current.
Integrating Reset
1. Connect and configure the relay for integrating reset testing.
a. Connect the test setup shown in Figure 5-1.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set TIME DIAL to 9.9
d. Set CURVE to V.
e. Set TIME PICKUP to 1.0.
f. Set INST PICKUP (50-A) to 90.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (15.0 Aac).
2. Apply 4.0 Aac to terminals 8 and 9. After the unit trips, remove the applied current for 29 ±0.25
seconds, then reapply the current (4.0 Aac). Note the elapsed time from the reapplication of current to
the second trip. The elapsed time should be 2.08 ±0.4 seconds.
5-2 BE1-50/51B-244 Testing 9252000793 Rev C
Instantaneous Overcurrent A (50-A) Pickup
1. Connect and configure the relay for 50-A pickup testing:
a. Connect the test setup shown in Figure 5-1.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set TIME DIAL to 0.0.
d. Set CURVE to S.
e. Set TIME PICKUP to 15.0.
f. Set INST PICKUP (50-A) to 02.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (15.0 Aac).
2. Apply and slowly increase current to terminals 8 and 9 until the 50-A output contacts close. The
applied current should be between 1.935 and 2.065 Aac.
3. Decrease the applied current until the 50-A output contacts open.
4. Set INST PICKUP (50-A) to 08.
5. Slowly increase the current applied to terminals 8 and 9 until the 50-A output contacts close. The
applied current should be between 7.815 and 8.185 Aac.
6. Reduce the applied current to zero.
Figure 5-1. 51 Pickup, Time Dial, Integrating Reset, and 50-A Pickup Test Setup
Instantaneous Overcurrent B (50-B) Pickup
1. Connect and configure the relay for 50-B pickup testing:
a. Connect the test setup shown in Figure 5-2.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set TIME DIAL to 0.0.
d. Set CURVE to S.
e. Set TIME PICKUP to 15.0.
9252000793 Rev C BE1-50/51B-244 Testing 5-3
f. Set INST PICKUP (50-A) to 90.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to 20 (2.0 Aac).
2. Apply and slowly increase current to terminals 8 and 9 until the 50-B output contacts close. The
applied current should be between 1.935 and 2.065 Aac.
3. Decrease the applied current until the 50-B output contacts open.
4. Set INST PICKUP (50-B) to 80 (8.0 Aac).
5. Slowly increase the current applied to terminals 8 and 9 until the 50-B output contacts close. The
applied current should be between 7.815 and 8.185 Aac.
6. Reduce the applied current to zero.
Figure 5-2. 50-B Pickup Test Setup
Target Indicators
1. Connect and configure the relay for target indicator testing:
a. Connect the test setup shown in Figure 5-3.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set TIME DIAL to 0.0.
d. Set CURVE to S.
e. Set TIME PICKUP to 1.0.
f. Set INST PICKUP (50-A) to 90.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (15.0 Aac).
2. Apply 2 Aac to terminals 8 and 9 to trip the 51 relay output.
3. Slowly increase the voltage source to provide target current and verify that the Time target operates
at the level of current determined by the Target Operating Current Jumpers.
The Target Operating Current Jumpers are located on the circuit board and identified as J1 and J2.
J1 sets the minimum current range for the 50-A target and J2 sets the minimum current range for the
51 target. A jumper installed across pins 1 and 2 gives a minimum operating current of 0.9 to 2.25 A.
A jumper installed across pins 2 and 3 gives a minimum operating current of 80 to 200 mA.
4. Remove the target and sensing current and reset the target.
5. Set TIME PICKUP to 9.0.
6. Set INST PICKUP (50-A) to 01.
7. Apply 2 Aac to terminals 8 and 9 to trip the 50-A relay output.
5-4 BE1-50/51B-244 Testing 9252000793 Rev C
8. Slowly increase the voltage source to provide target current and verify that the Instantaneous target
operates at the level of current determined by the Target Operating Current Jumpers.
9. Remove the target and sensing current and reset the target.
Figure 5-3. Target Indicator Test Setup
Manual Trip
1. Configure the relay for manual trip testing:
a. Connect the test setup as shown in Figure 5-1.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (Westinghouse CO type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set TIME DIAL to 0.0
d. Set CURVE to S.
e. Set TIME PICKUP to 1.0.
f. Set INST PICKUP (50-A) to 90.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to 20 (2.0 Aac).
2. Apply 0.9 Aac to terminals 8 and 9 (0.9 Aac provides relay operating power but is below the pickup
threshold.)
WARNING!
Trip circuit voltage is present at the front panel test points. When shorting the
test points, use insulated jumpers to avoid contact with these voltages.
3. Connect a jumper to the Time Overcurrent Manual Trip jacks. Verify that the stop input of the test set
timer recognizes a 51 contact closure.
4. Remove the jumper and the current applied at relay terminals 8 and 9.
5. Apply 0.9 Aac to terminals 8 and 9.
6. Connect a jumper to the Instantaneous Overcurrent Manual Trip jacks. Verify that the stop input of
the test set timer recognizes a 50-A contact closure
7. Remove the jumper and the current applied to relay terminals 8 and 9.
8. Reset targets.
9252000793 Rev C BE1-50/51B-244 Testing 5-5
5-6 BE1-50/51B-244 Testing 9252000793 Rev C
APPENDIX A • CHARACTERISTIC CURVES
TABLE OF CONTENTS
APPENDIX A • CHARACTERISTIC CURVES .......................................................................................... A-1
Table A-1. Time Characteristic Curve Constants with Switch SW3-3 Open (Off) ..................................... A-2
Table A-2. Time Characteristic Curve Constants with Switch SW3-3 Closed (On)
9252000793 Rev C BE1-50/51B-244 Characteristic Curves i
.................................. A-2
ii BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
APPENDIX A • CHARACTERISTIC CURVES
Introduction
This appendix describes and defines the instantaneous overcurrent, time overcurrent, and integrating
time reset characteristics of the BE1-50/51B-244 relay.
Instantaneous Overcurrent Characteristics
Timing
The instantaneous characteristic curves of the BE1-50/51B-244 relay are similar to standard
electromechanical instantaneous units. However, the time to trip for applications where the initial sensing
current is less than 400 mA may be slightly longer. This may occur on a very lightly loaded circuit or when
the relay is providing ground protection and is connected to measure neutral current. Figure A-1 shows
the instantaneous characteristic curves for the maximum time to trip.
Figure A-1. Instantaneous Characteristic Curves
The delay of the Instantaneous A (50-A) element can be set for no intentional delay (switch SW3-2 open)
or a fixed delay of 100 ms (SW3-2 closed). Figure 2-2 illustrates the location of SW3. The time delay of
the 50-B element is not switch-selectable and is fixed at no intentional delay.
Pickup
The instantaneous elements of the BE1-50/51B-244 relay may be set lower than the instantaneous
element in IAC relays and still have the same reach. This is because the BE1-50/51B-244 instantaneous
elements effectively eliminate the fault current transient overreach components. When setting the BE150/51B-244 instantaneous elements, calculate the symmetrical value without any adder for transient
overreach.
Time Overcurrent Characteristics
Nine inverse time functions and one fixed (definite) time function can be selected at the front panel. Curve
types are identified by a letter designator. Available curve types are short inverse (S), long inverse (L),
definite time (D), moderately inverse (M), inverse (I), very inverse (V), extremely inverse (E), BS142
inverse, (B), and BS142 extremely inverse (C).
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-1
Inverse Time Functions
KBD
CM
AD
T
N
T
++
−
=
Curve
Type
Similar To
Number
BE A B C N K R
S
ABB CO-2
A-2
0.2663
0.03393
1.000
1.2969
0.028
0.500
L
ABB CO-5
A-3
5.6143
2.18592
1.000
1.0000
0.028
15.750
D
ABB CO-6
A-4
0.4794
0.21359
1.000
1.5625
0.028
0.875
M
ABB CO-7
A-5
0.3022
0.12840
1.000
0.5000
0.028
1.750
I
ABB CO-8
A-6
8.9341
0.17966
1.000
2.0938
0.028
9.000
V
ABB CO-9
A-7
5.4678
0.10814
1.000
2.0469
0.028
5.500
E
ABB CO-11
A-8
7.7624
0.02758
1.000
2.0938
0.028
7.750
C
BS142-C∗
A-10
8.2506
0.00000
1.000
2.0469
0.028
8.000
F
None†
None
0.0000
1.00000
0.000
0.0000
0.000
1.000
Curve
Type
Similar To
Number
BE A B C N K R
S
GE IAC 55
A-11
0.0286
0.0208
1.000
0.9844
0.028
0.0940
L
GE IAC 66
A-12
2.3955
0.00002
1.000
0.3125
0.028
7.8001
D
ABB CO-6
A-4
0.4797
0.21359
1.000
1.5625
0.028
0.8750
M
ABB CO-7
A-5
0.3022
0.12840
1.000
0.5000
0.028
1.7500
I
GE IAC 51
A-13
0.2747
0.1042
1.000
0.4375
0.028
0.8868
V
GE IAC 53
A-14
4.4309
0.0991
1.000
1.9531
0.028
5.8231
E
GE IAC 77
A-15
4.9883
0.0129
1.000
2.0469
0.028
4.7742
B
BS142-B∗
A-9
1.4636
0.00000
1.000
1.0469
0.028
3.2500
C
BS142-C∗
A-10
8.2506
0.00000
1.000
2.0469
0.028
8.0000
F
None†
None
0.0000
1.00000
0.000
0.0000
0.000
1.0000
Characteristic curves for the inverse and definite time functions are defined by the following equation:
Where: T
= time to trip in seconds
T
D = time dial setting
M = multiple of pickup setting
A, B, C, N, K = constants for the particular curve
Characteristic Curve Groups
Either GE IAC or ABB characteristic curve groups are selected through switch SW3-3. (Refer to
Figure 2-2 for the location of SW3.)
Characteristic Curve Constants
Tables A-1 and A-2 list the time characteristic curve constants used by the relay. Constants have been
selected to conform to the characteristics of electromechanical relays over a range of pickup multiples
from 1.3 to 40. Values of the constants are provided for use in PC relay setting applications. Timing
accuracy is ±1 cycle ±2% of time to trip.
Table A-1. Time Characteristic Curve Constants with Switch SW3-3 Open (Off)
Figure
Constants
B
BS142-B∗
A-9 1.4636 0.00000 1.000 1.0469 0.028 3.250
∗ Curves B and C are defined in British Standard BS142 and IEC 255-4 (International
Electrotechnical Commission).
† Fixed time from 0.1 to 9.9 seconds.
Table A-2. Time Characteristic Curve Constants with Switch SW3-3 Closed (On)
Figure
Constants
∗ Curves B and C are defined in British Standard BS142 and IEC 255-4 (International
Electrotechnical Commission).
† Fixed time from 0.1 to 9.9 seconds.
A-2 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Characteristic Curves
Figures A-2 through A-15 illustrate the BE1-50/51B-244 time overcurrent characteristic curves.
Figure A-2. Short Inverse (S) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-2)
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-3
Figure A-3. Long Inverse (L) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-5)
A-4 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Figure A-4. Definite Time (D) Time Characteristic Curve (Similar to ABB CO-6)
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-5
Figure A-5. Moderately Inverse (M) Time Characteristic Curve (Similar to ABB CO-7)
A-6 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Figure A-6. Inverse (I) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-8)
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-7
Figure A-7. Very Inverse (V) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-9)
A-8 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Figure A-8. Extremely Inverse (E) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-11)
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-9
Figure A-9. BS142 Very Inverse (BS142-B) Time Characteristic Curve
A-10 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Figure A-10. BS142 Extremely Inverse (BS142-C) Time Characteristic Curve
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-11
Figure A-11. Short Inverse (S2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 55)
A-12 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Figure A-12. Long Inverse (L2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 66)
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-13
Figure A-13. Inverse (I2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 51)
A-14 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Figure A-14. Very Inverse (V2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 53)
9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-15
Figure A-15. Extremely Inverse (E2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 77)
A-16 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C
Timing Accuracy
1
2
−
=
M
RD
T
R
Trip to TimeKBD
CM
AD
T
N
T
=++
−
=
Reset to Time
M
RD
T
R
=
−=1
2
Timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap
and is for a given measured multiple of tap. Measurement accuracy of the multiple of tap is the sum of
±2%, ±25 mA for the BE1-50/51B-244.
Fixed Time Characteristic
The fixed time characteristic corresponds to the time dial setting and provides delays of 0.0 to 9.9
seconds. The time setting is constant over a range of pickup multiples from 1.0 to 40. Accuracy is ±1
cycle, ±2% of the time to trip for time dial settings of 0.1 and greater.
Integrating Time Reset Characteristic
The relay can be user-configured for integrating or instantaneous type reset.
Integrating reset simulates the disk reset of electromechanical relays and begins when the current
decreases below 95% of pickup. BE1-50/51B-244 relays provide the integrating reset function even when
input current decreases to zero.
Integrating reset characteristics are defined by the following equation and are illustrated in Figure A-16.
See Table A-1 and A-2 for the equation constants.
Where: T
R = constant for the particular curve
D = time dial setting
M = current in multiples of pickup setting during reset
Time characteristic curve equation:
Where: D = time dial setting
M = multiple of pickup setting