ATEN PE9222, PE9216, PE7216, PE7214, PE9330 User Manual

...
0 (0)

eco PDU PE Series

PE7214 / PE7216 / PE7324 / PE7328 / PE8121kJ / PE8216 / PE8316G / PE8324 / PE8324A / PE8324JA / PE9216 / PE9222 / PE9324 / PE9330

Power Distribution Unit

User Manual

www.aten.com

eco PDU PE Series User Manual

FCC, CE Information

FEDERAL COMMUNICATIONS COMMISSION INTERFERENCE STATEMENT: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.

CE Warning: This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

NOTE: The KJ and J model series do not meet or qualify for FCC or CE certification, as they are produced for countries outside the FCC’s jurisdiction.

RoHS

This product is RoHS compliant.

SJ/T 11364-2006

The following contains information that relates to China.

ii

eco PDU PE Series User Manual

User Information

Online Registration

Be sure to register your product at our online support center:

International http://eservice.aten.com

Telephone Support

For telephone support, call this number:

International

886-2-8692-6959

China

86-10-5255-0110

 

 

Japan

81-3-5615-5811

 

 

Korea

82-2-467-6789

 

 

North America

1-888-999-ATEN ext 4988

 

 

United Kingdom

44-8-4481-58923

 

 

User Notice

All information, documentation, and specifications contained in this manual are subject to change without prior notification by the manufacturer. The manufacturer makes no representations or warranties, either expressed or implied, with respect to the contents hereof and specifically disclaims any warranties as to merchantability or fitness for any particular purpose. Any of the manufacturer's software described in this manual is sold or licensed as is. Should the programs prove defective following their purchase, the buyer (and not the manufacturer, its distributor, or its dealer), assumes the entire cost of all necessary servicing, repair and any incidental or consequential damages resulting from any defect in the software.

The manufacturer of this system is not responsible for any radio and/or TV interference caused by unauthorized modifications to this device. It is the responsibility of the user to correct such interference.

The manufacturer is not responsible for any damage incurred in the operation of this system if the correct operational voltage setting was not selected prior to operation. PLEASE VERIFY THAT THE VOLTAGE SETTING IS CORRECT BEFORE USE.

PE Device Safety Notice

Set the maximum permissible breaker protection in the building circuitry to the current rating specified on the rating plate. Observe all national regulations and safety codes as well as deviations for breakers.

Only connect the PE Device to a grounded power outlet or a grounded system!

Make sure that the total current input of the connected systems does not exceed the current rating specified on the rating plate of the PE Device.

There is a risk of explosion if the battery is replaced with an incorrect type. Dispose of used batteries according to the relevant instructions.

iii

eco PDU PE Series User Manual

Package Contents

The eco PDU PE Series package consists of:

1 PE7214, PE7216, PE7324, PE7328, PE8121kJ, PE8216, PE8316G, PE8324, PE8324A, PE8324JA, PE9216, PE9222, PE9324, or PE9330 Power Distribution Unit

1 Power Cord (14-port, 16-port, 21-port, and 22-port models only; excluding PE8316G)

1 Mounting Kit

1 CD-ROM

1 User Instructions*

Check to make sure that all of the components are present and in good order. If anything is missing, or was damaged in shipping, contact your dealer.

Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the eco PDU installation.

*Features may have been added to the eco PDU since this manual was published. Please visit our website to download the most up-to-date version.

Copyright © 2013 ATEN® International Co., Ltd.

Manual Date: 2013-12-23

NRGence and the NRGence logo are registered trademarks of ATEN International Co., Ltd. All rights reserved. All other brand names and trademarks are the registered property of their respective owners.

iv

eco PDU PE Series User Manual

Contents

FCC Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii SJ/T 11364-2006. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii Online Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii Telephone Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii User Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii PE Device Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix

Chapter 1.

Introduction

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Comparison Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Remote Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 eco Sensors Energy Management Software* . . . . . . . . . . . . . . . . . . . . 7 Proactive Overload Protection (POP) . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Environment Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Door Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Cable Holders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 PE7214B / PE7214G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 PE7216 / PE8216 / PE9216 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 PE8316G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 PE8121kJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 PE9222B / PE9222G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 PE7324 / PE8324 / PE9324 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 PE8324A / PE8324JA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 PE7328 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 PE9330 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Port and LED Panel (All models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Chapter 2.

Hardware Setup

Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

v

eco PDU PE Series User Manual

PDU Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Installation Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Securing the Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Securing the Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Chapter 3.

Basic Operation and First Time Setup

Operation Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 eco Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 First Time Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Changing the Administrator Login . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Moving On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Chapter 4.

Logging In

Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 The eco PDU Main Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Page Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Chapter 5.

Energy

Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Chapter 6.

User Management

Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Administrator Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Chapter 7.

Log

Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

The System Log Event List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Chapter 8.

Setup

Device Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Device Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

vi

eco PDU PE Series User Manual

Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Login Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Working Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Account Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Login String / IP Filter / Mac Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

Authentication & Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Private Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Chapter 9.

PDU

PDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Firmware File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Restore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Appendix

Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 The eco PDU’s Main Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Securing the Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Resetting the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Recovery Procedure:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 IP Address Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 PE7214B / PE7214G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 PE7216B / PE8216B / PE9216B . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 PE7216G / PE8216G / PE9216G . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 PE8316G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 PE8121kJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 PE9222B / PE9222G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 PE7324B/J / PE8324B/J / PE9324B/J . . . . . . . . . . . . . . . . . . . . . . . . 91 PE8324A / PE8324JA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 PE7324G / PE8324G / PE9324G . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 PE7328B/J / PE7328G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 PE9330B/J / PE9330G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Administrator Login Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

vii

eco PDU PE Series User Manual

Conventions

This manual uses the following conventions:

Monospaced

Indicates text that you should key in.

[ ]

Indicates keys you should press. For example, [Enter] means

 

to press the Enter key. If keys need to be chorded, they

 

appear together in the same bracket with a plus sign

 

between them: [Ctrl+Alt].

1.Numbered lists represent procedures with sequential steps.

Bullet lists provide information, but do not involve sequential steps.

Indicates selecting the option (on a menu or dialog box, for example), that comes next. For example, Start Run means to open the Start menu, and then select Run.

Indicates critical information.

viii

eco PDU PE Series User Manual

Product Information

For information about all NRGence products and how they can help you save money in the data center, visit NRGence on the Web or contact an ATEN Authorized Reseller. Visit ATEN on the Web for a list of locations and telephone numbers

International – http://www.aten.com

North America – http://www.aten-usa.com

ix

Chapter 1

Introduction

Overview

As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7214 / PE7216 / PE7324 / PE7328 / PE8121kJ / PE8216 / PE8316G / PE8324 / PE8324A / PE8324JA / PE9216 / PE9222 / PE9324 / PE9330 eco PDUs are intelligent PDUs that contain 14, 16, 21, 22, 24, 28, or 30 AC outlets and are available in various IEC socket configurations. Models in the advanced PE9 range feature a dedicated 8/14-outlet bank for critical load devices, and both the PE8 and PE9 ranges feature NRGence’s proactive overload protection, which automatically powers off the last outlet that caused the current overload.

NRGence eco PDUs provide secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center's health environment via sensors*. The basic characteristics of each model are shown in the table on page 3.

NRGence eco PDUs offer remote power control combined with real-time power measurement – allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device, bank, or outlet level, depending on the model, from practically any location via a TCP/IP connection*.

The power status of each outlet can be set individually, allowing users to switch each device On/Off. The eco PDU also offers comprehensive power analysis reports which can separate departments and locations, providing precise measurements of current, voltage, power and watt-hour in a real-time display.

Installation and operation is fast and easy: plugging cables into their appropriate ports and user-friendly browser-based configuration and management is all that is entailed. Since the eco PDU firmware is upgradeable over the Net, you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available.

NRGence eco PDU supports any 3rd party V3 SNMP Manager Software and NRGence eco Sensors (eco PDU Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive

1

Chapter 1. Introduction

and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.

With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible.

Note: 1. Sensors are optional accessories. A sensor-enabled installation is required to generate a more complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. See Optional Accessories, page 9, for further information.

2.eco PDUs are primarily designed for access via Intranet; extra network security protection is suggested for Internet access usage.

3.Not all models support all features. See Comparison Chart, page 3, and Specifications, page 83, for full details.

2

eco PDU PE Series User Manual

Comparison Chart

Model

Inlet / Cord

 

Outlets

Metering

Outlet

 

Level

Switching

 

 

 

 

 

 

 

 

 

 

PE7214B

NEMA 6-20P

14

12 x IEC320 C13 +

PDU /

No

 

(208V)

 

2 x IEC320 C19

1 x Bank /

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

PE7214G

IEC 60320 C20

14

12 x IEC320 C13 +

PDU /

No

 

 

 

2 x IEC320 C19

1 x Bank /

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

PE7216B

NEMA 6-20P

16

14 x IEC 320 C13 +

PDU /

No

 

 

 

2 x IEC 320 C19

1 x Bank /

 

PE8216B

 

 

Yes 16/16

 

 

 

 

Outlet

 

PE9216B

 

 

 

 

Yes 8/16

 

 

 

 

 

 

PE7216G

IEC 60320 C20

 

 

 

No

 

 

 

 

 

 

PE8216G

 

 

 

 

Yes 16/16

 

 

 

 

 

 

PE9216G

 

 

 

 

Yes 8/16

 

 

 

 

 

 

PE8316G

IEC 60309 32A

16

10 x IEC 320 C19 +

PDU /

Yes 16/16

 

 

 

6 x IEC 320 C13

2 x Bank /

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

PE8121kJ

NEMA L6-15P

21

21 x IEC 320 C13 with

PDU / 1 x

Yes 21/21

 

 

 

lock

Bank /

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

PE9222B

NEMA 6-20P

22

19 x IEC320 C13 +

PDU / 1 x

Yes 8/22

 

(208V)

 

3 x IEC320 C19

Bank /

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

PE9222G

IEC 60320 C20

22

19 x IEC320 C13 +

PDU / 1 x

Yes 8/22

 

 

 

3 x IEC320 C19

Bank /

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

PE8324A

NEMA L5-30P

24

24 x NEMA 5-15R

PDU / 2 x

Yes 24/24

 

(UL)

 

 

Bank /

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

PE8324JA

NEMA L5-30P

24

24 x NEMA 5-15R

PDU / 2 x

Yes 24/24

 

(PSE)

 

 

Bank /

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

PE7324B / J

NEMA L6-30P

24

21 x IEC 320 C13 +

PDU /

No

 

 

 

3 x IEC 320 C19

2 x Bank /

 

PE8324B / J

 

 

Yes 24/24

 

 

 

 

Outlet

 

PE9324B / J

 

 

 

 

Yes 16/24

 

 

 

 

 

 

PE7324G

IEC 60309 32A

 

 

 

No

 

 

 

 

 

 

PE8324G

 

 

 

 

Yes 24/24

 

 

 

 

 

 

PE9324G

 

 

 

 

Yes 16/24

 

 

 

 

 

 

3

Chapter 1. Introduction

 

 

 

 

 

 

 

 

 

 

 

 

Model

Inlet / Cord

 

Outlets

Metering

Outlet

 

Level

Switching

 

 

 

 

 

 

 

 

 

 

PE7328B / J

NEMA L6-30P

28

24 x IEC 60320 C13 +

PDU / 2 x

No

 

 

 

4 x IEC 60320 C19

Bank /

 

PE7328G

IEC 60309 32A

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

PE9330B / J

NEMA L6-30P

30

26 x IEC 60320 C13 +

PDU / 2 x

Yes 16/30

 

 

 

4 x IEC 60320 C19

Bank /

 

PE9330G

IEC 60309 32A

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

Note: For the complete specifications of individual models, including bank- by-bank outlet details, please reference Specifications, page 83.

4

eco PDU PE Series User Manual

Features

Power Distribution

Space saving 0U rack mount design with rear mounting

Various IEC outlet models

2 digit 7-segment front panel LED shows PDU/Phase / Bank / Outlet ID

3 digit 7-segment front panel LED shows Current / Voltage / Power Dissipation, IP address, and readings from up to 4 environment sensors

Safe shutdown support

Separate power for the unit's own power and its power outlets – the user interface is still accessible even when an overload condition trips the devices' circuit breaker

Dedicated 8/14-outlet bank for critical load devices (PE9 models only: PE9216/PE9324 8 outlets; PE9222/PE9330 14 outlets) – always powered on

Proactive overload protection (POP) (PE8 / PE9 models only) – automatically powers off the last outlet that caused the current overload (see Proactive Overload Protection (POP), page 7)

Remote Access

Remote power control via TCP/IP and a built in 10/100 Ethernet port

Network Protocols: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP, NTP, DNS, auto sense, Ping

Remote users can monitor outlet status via web pages on their browsers

eco PDU Power Management software – eco Sensors

Supports SNMP Manager V3

Operation

Local and Remote power outlet control (On, Off, Power Cycle) by individual outlets (PE8 / PE9 models)

Supports multiple power control methods – Wake on LAN, System after AC Back, Kill the Power

Power-on sequencing – set the power on sequence and delay time for each outlet to allow equipment to be powered on in the correct order

Easy setup and operation via a browser-based user interface

Multibrowser support (IE, Mozilla, Firefox, Chrome, Safari, Opera)

5

Chapter 1. Introduction

RTC support to keep the timer running during times of no power

Up to 8 user accounts and 1 administrator account

Management

Power metering and monitoring at the PDU / Bank / Outlet level

LED indicators for current, voltage, power dissipation at the PDU / Bank / Outlet levels

Real-time aggregate current, voltage, and power and power dissipation displayed in a browser-based UI for monitoring at the PDU, bank and outlet level (14-port, 16-port*, 21-port, and 22-port models offer 1 bank metering; 24-port, 28-port, 30-port, and PE8316G models offer 2 bank metering)

Alert notification for selected events (On, Off, Recycle, Failure, exceeding threshold settings, etc.), via blinking LEDs (locally), SMTP, SNMP trap notification

Supports Management Information Base (MIB) files for SNMP

Environment monitoring – supports external temperature / humidity / differential pressure sensors for rack environment monitoring

Door Sensor support – allows the monitoring of rackmount enclosure door access to notify users when a door has been opened.

Current and voltage threshold setting

Naming support for outlets

User outlet access assignment on an outlet-by-outlet basis

Event logging and syslog support

Upgradeable firmware

Multilanguage support – English, Traditional Chinese, Simplified Chinese, Japanese, German, Italian, Spanish, French, Russian, Korean, Portuguese

*PE8316G has 2 bank metering

Security

Two-level password security

Strong security features include strong password protection and advanced encryption technologies – 128 bit SSL

Remote authentication support: RADIUS

6

eco PDU PE Series User Manual

eco Sensors Energy Management Software*

Automatic discovery of all PE devices within the same intranet

Remote real-time power measurement and monitoring

Real-time environment sensor monitoring

Plotting/monitoring of all PE devices

Exceed threshold alert through SMTP and System log

Power Analysis report

Note: eco Sensors is designed to work with NRGence PDUs, and is bundled with all PE series packages.

Proactive Overload Protection (POP)

The PE8121kJ, PE8216, PE8316G, PE8324, PE8324A, PE8324JA, PE9216, PE9222, PE9324, and PE9330 models feature NRGence’s exclusive Proactive Overload Protection (POP) technology. Effective on all non-critical outlets, this added safety feature automatically powers off the last outlet that caused the current overload.

POP mode is engaged when the current exceeds the set threshold maximum value, powering off the outlet. The LED display shows POP and a beeper sounds. Press any button for two seconds to clear POP mode and power the outlet back on.

7

Chapter 1. Introduction

Requirements

Browsers accessing the eco PDU unit must support SSL 128 bit encryption.

For cold booting of attached computers, the computer's BIOS must support Wake on LAN or System after AC Back.

For Safe Shutdown:

The computer must be running Windows (Windows 2000 or higher) or Linux.

The Safe Shutdown program (available by download from our website or on the software CD included), must be installed and running on the computer.

8

eco PDU PE Series User Manual

Optional Accessories

Environment Sensors

For complete energy management of an instrumented data center with the use of the eco PDU and eco Sensors software, you should install 4 sensors for each of the racks in your data center in order to generate a complete energy-efficient data chart. Higher sensor installation density is helpful to generate more accurate data. 8/16-port models have 4 sensor ports. Higher sensor installation density is helpful to generate more accurate data.

To get the most complete eco Sensors Dashboard data, the recommended 4- sensor setup is show in the table, below:

Port

Location

Part Number

Sensor

 

 

 

 

Sensor 1

Intake

EA1140 or

Temperature or

 

 

EA1240

Temperature / Humidity

Sensor 2

Intake

 

 

 

 

 

 

 

Sensor 3

Exhaust

 

 

 

 

 

 

Sensor 4

Exhaust

 

 

 

 

 

 

 

or Floor

EA1340

Differential Pressure

 

 

 

 

Door Sensor

All models in the PE7xxx/PE8xxx/PE9xxx range feature a 4-pin dry contact port for door sensors that supports the monitoring of rackmount enclosure door access to notify users when a door has been opened.

See the table below for information about the two available door sensors. Please contact your ATEN dealer for purchasing information:

Port

Part Number

Sensor

 

 

 

Door Sensor

EA1440

Photo Sensor

 

 

 

 

EA1441

Inductive Proximity Sensor

 

 

 

Sensor Management

Sensors can be managed via the eco PDU’s built-in graphical user interface (GUI) or with the NRGence eco Sensors software that can be downloaded from the ATEN website. The download link can be found on the software CD provided with the eco PDU package.

9

Chapter 1. Introduction

Cable Holders

Cable holders are optional accessories. For added safety, use ATEN Lok-U- Plug cable holders to secure the cables from your attached devices in place on the eco PDU unit. Use only the ATEN Lok-U-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous.

Part Number

Description

 

 

2X-EA07

Lok-U-Plug Cable Holder (10 pcs)

 

 

2X-EA08

Lok-U-Plug Installation Tool (4 pcs)

 

 

10

eco PDU PE Series User Manual

Components

PE7214B / PE7214G

2

5

1

3

4

11

 

 

Chapter 1. Introduction

 

 

 

 

 

 

 

 

 

No.

Item

Description

 

 

 

1

Power Outlets*

14 in total (12 x IEC320 C13 + 2 x IEC320 C19)

 

 

Bank 1-1: Outlet 1–14; 12 x C13 + 2 x C19

 

 

 

2

Port and LED Panel

The Port and LED panel contains:

 

 

Readout Section and LEDs

 

 

Environmental Sensor Ports

 

 

LAN Port

 

 

Door Sensor Port

 

 

Reset Switch

 

 

Full details of this section are provided on

 

 

page 23.

 

 

 

3

Circuit Breaker

As a safety measure, if there is an overcurrent

 

Pushbutton

situation regarding the device’s power, the circuit

 

 

breakers will trip. Press the button to recover

 

 

normal operation.

 

 

Warning: See Resetting the Circuit Breaker,

 

 

page 79 for important information about resetting a

 

 

tripped circuit breaker.

 

 

 

4

Power Inlet

The power cord that connects the unit to an AC

 

 

power source plugs into this socket.

 

 

B models connect to a NEMA 6-20P (208V)

 

 

source

 

 

G models connect to an IEC 60320 C20 source

 

 

 

5

Output Power Indicator

This LED lights steady to indicate output power for

 

 

the related bank.

 

 

 

Note: Holes for ATEN Lok-U-Plug cable holders are located around the outlets. See Securing the Cables, page 35, for further information.

12

ATEN PE9222, PE9216, PE7216, PE7214, PE9330 User Manual

eco PDU PE Series User Manual

PE7216 / PE8216 / PE9216

PE7216

PE8216

PE9216

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

5

 

2

1

5

5

 

 

3

4

Note: The PE7216 / PE8216 / PE9216 unit components are identical except for the outlet LEDs – the PE7216 has none; the PE8216 has 16; and the PE9216 has 8, as shown by number 9 above.

13

 

 

Chapter 1. Introduction

 

 

 

 

 

 

 

 

 

No.

Item

Description

 

 

 

1

Power Outlets*

16 in total (14 x IEC 320 C13 + 2 x IEC 320 C19)

 

 

Bank 1-1: Outlet 1–8: 7 C13; 1 x C19

 

 

Bank 1-2: Outlet 9–16: 7 x C13; 1 x C19

 

 

 

2

Port and LED Panel

The Port and LED panel contains:

 

 

Readout Section and LEDs

 

 

Environmental Sensor Ports

 

 

LAN Port

 

 

Door Sensor Port

 

 

Reset Switch

 

 

Full details of this section are provided on

 

 

page 23.

 

 

 

3

Circuit Breaker

As a safety measure, if there is an overcurrent

 

Pushbutton

situation regarding the device’s power, the circuit

 

 

breakers will trip. Press the button to recover

 

 

normal operation.

 

 

Warning: See Resetting the Circuit Breaker,

 

 

page 79 for important information about resetting a

 

 

tripped circuit breaker.

 

 

 

4

Power Inlet

The power cord that connects the unit to an AC

 

 

power source plugs into this socket.

 

 

B models connect to a NEMA 6-20P source

 

 

G models connect to an IEC 60320 C20 source

 

 

 

5

Outlet Status LEDs

PE8216 (x 16) and PE9216 (x 8) only.

 

 

These LEDs indicate outlet status.

 

 

Lights ORANGE for powered on.

 

 

Off for powered off.

 

 

 

Note: Holes for ATEN Lok-U-Plug cable holders are located around the outlets. See Securing the Cables, page 35, for further information.

14

eco PDU PE Series User Manual

PE8316G

1

5

 

2

1

5

 

3

4

15

 

 

Chapter 1. Introduction

 

 

 

 

 

 

 

 

 

No.

Item

Description

 

 

 

1

Power Outlets*

Total : 6 x IEC320 C13 + 10 x IEC320 C19

 

 

Bank 1: Outlet 1–8; 3 x C13 + 5 x C19

 

 

Bank 2: Outlet 9–16; 3 x C13 + 5 x C19

 

 

 

2

Port and LED Panel

The Port and LED panel contains:

 

 

Readout Section and LEDs

 

 

Environmental Sensor Ports

 

 

LAN Port

 

 

Door Sensor Port

 

 

Reset Switch

 

 

Full details of this section are provided on

 

 

page 23.

 

 

 

3

Circuit Breakers

As a safety measure, if there is an overcurrent

 

 

situation regarding the device’s power, the circuit

 

 

breakers will trip. Press the button to recover

 

 

normal operation.

 

 

Warning: See Resetting the Circuit Breaker,

 

 

page 79 for important information about resetting a

 

 

tripped circuit breaker.

 

 

 

4

Power Cord

Plug the cord into an AC power source.

 

 

B models connect to a NEMA L6-30P source

 

 

G models connect to an IEC 60309 32A source

 

 

 

5

Outlet Status LEDs

These 16 LEDs indicate outlet status.

 

 

Lights ORANGE for powered on.

 

 

Off for powered off.

 

 

 

Note: Holes for ATEN Lok-U-Plug cable holders are located around the outlets. See Securing the Cables, page 35, for further information.

16

eco PDU PE Series User Manual

PE8121kJ

1

5

 

1

5

2

1

5

 

3

4

17

 

 

Chapter 1. Introduction

 

 

 

 

 

 

 

 

 

No.

Item

Description

 

 

 

1

Power Outlets*

21 in total (21 x IEC 320 C13)

 

 

Bank 1-1: Outlet 1–7

 

 

Bank 1-2: Outlet 8–14

 

 

Bank 1-3: Outlet 15-21

 

 

 

2

Port and LED Panel

The Port and LED panel contains:

 

 

Readout Section and LEDs

 

 

Sensor Ports

 

 

LAN Port

 

 

Door Sensor Port

 

 

Reset Switch

 

 

Full details of this section are provided on

 

 

page 23.

 

 

 

3

Circuit Breaker

As a safety measure, if there is an over current

 

Pushbutton

situation regarding the device’s power, the circuit

 

 

breakers will trip. Press the button to recover

 

 

normal operation.

 

 

Warning: See Resetting the Circuit Breaker,

 

 

page 79 for important information about resetting a

 

 

tripped circuit breaker.

 

 

 

4

Power Inlet

The power cord that connects the unit to an AC

 

 

power (NEMA L6-15P) source plugs into this

 

 

socket.

 

 

 

5

Outlet Status LEDs

These 21 LEDs indicate outlet status.

 

 

Lights ORANGE for powered on.

 

 

Off for powered off.

 

 

 

18

eco PDU PE Series User Manual

PE9222B / PE9222G

6

1

2

1

5

3

4

19

 

 

Chapter 1. Introduction

 

 

 

 

 

 

 

 

 

No.

Item

Description

 

 

 

1

Power Outlets*

22 in total (19 x IEC320 C13 + 3 x IEC320 C19)

 

 

Bank 1-1: Outlet 1–14; 12 x C13 + 2 x C19

 

 

Bank 1-2: Outlet 15–22; 7 x C13 + 1 x C19

 

 

 

2

Port and LED Panel

The Port and LED panel contains:

 

 

Readout Section and LEDs

 

 

Sensor Ports

 

 

LAN Port

 

 

Door Sensor Port

 

 

Reset Switch

 

 

Full details of this section are provided on

 

 

page 23.

 

 

 

3

Circuit Breaker

As a safety measure, if there is an over current

 

Pushbutton

situation regarding the device’s power, the circuit

 

 

breakers will trip. Press the button to recover

 

 

normal operation.

 

 

Warning: See Resetting the Circuit Breaker,

 

 

page 79 for important information about resetting a

 

 

tripped circuit breaker.

 

 

 

4

Power Inlet

The power cord that connects the unit to an AC

 

 

power source plugs into this socket.

 

 

B models connect to a NEMA 6-20P (208V)

 

 

source

 

 

G models connect to an IEC 60320 C20 source

 

 

 

5

Outlet Status LEDs

These 8 LEDs indicate outlet status.

 

 

Lights ORANGE for powered on.

 

 

Off for powered off.

 

 

 

6

Output Power Indicator

This LED lights steady to indicate output power for

 

 

the related bank.

 

 

 

Note: Holes for ATEN Lok-U-Plug cable holders are located around the outlets. See Securing the Cables, page 35, for further information.

20

eco PDU PE Series User Manual

PE7324 / PE8324 / PE9324

PE7324

PE8324

PE9324

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

5

1

5

5

2

1

5

5

3

4

Note: The PE7324 / PE8324 / PE9324 unit components are identical except for the outlet LEDs – the PE7324 has none; the PE8324 has 24; and the PE9324 has 16, as shown by number 5 above.

21

Loading...
+ 76 hidden pages