Ariston E-COMBI 24, E-COMBI 30, E-COMBI 38 Installation and Servicing Manual

Gas red condensing wall hung combination boilers
G.C.N : 47-116 - 62 (24 kW) G.C.N : 47-116 - 63 (30 kW) G.C.N : 47-116 - 64 (38 kW)
E-COMBI 24
E-COMBI 30
E-COMBI 38
Country of destination GB, IE
overview
INDEX
Overview
General Information ........................................................... 3
Advice for the Installer ....................................................... 4
CE Labelling ........................................................................... 4
Data Plate Symbols ............................................................. 4
Safety Regulations ..............................................................5
Product description
Control Panel.........................................................................6
Overall View ........................................................................... 7
Overall Dimension .............................................................. 8
Minimum Clearances .........................................................8
Technical Information ........................................................ 9
Installation
Reference Standards ........................................................10
Condensate Discharge ....................................................13
Installing the Boiler ........................................................... 14
Gas Connection ..................................................................15
Water Connection .............................................................15
Instructions for Opening the Casing and Performing
an Internal Inspection ...................................................... 15
Connecting the Flue .........................................................17
Fitting the Coaxial Flue (Ø 60/100 Horizontal) ........18
Fitting the 5” Flue (Ø 80/125 Horizontal / Vertical) 19
Fitting the Coaxial Flue (Ø 60/100 Vertical) .............. 20
Fitting the Twin Pipe (Ø 80/80) .....................................21
Electrical Connections .....................................................25
Peripheral Unit Connection ...........................................25
Room Thermostat Connection .....................................26
Outdoor Sensor Connection .........................................26
Electrical Diagram .............................................................27
Commissioning
Initial Preparation .............................................................. 28
Electricity Supply ...............................................................28
Filling the Heating System .............................................28
Filling of the DHW System ..............................................28
Gas Supply ...........................................................................28
Water Treatment ................................................................28
First Igniton Operation .................................................... 29
Ignition procedure ............................................................ 30
Test Function and Combustion Analysis ...................32
Boiler Protection Devices
Boiler Protection Devices ...............................................33
Anti-Frost Device ...............................................................33
Table summarising error codes ....................................33
Maintenance
General Comments ...........................................................34
General Access ...................................................................36
Electrical Unit ......................................................................37
Hydraulic Unit ..................................................................... 39
Burner Unit ..........................................................................47
Fan Unit .................................................................................50
Gas Valve ...............................................................................51
Annual Maintenance ........................................................ 52
Benchmark Commissioning Checklist .......................53
Benchmark Service Interval Record ............................54
Spare Parts Short List .......................................................55
overview
These instructions are suitable for E-COMBI boilers : Do not forget the Log Book! MTS supports Benchmark, the heating industry code to ensure the correct installation, commissioning and servicing of domestic central heating systems.
To The Householder Make sure you have a completed Log Book for your boiler. This provides a record of the commissioning of your boiler. It contains important information about your particular installation that may be required by service engineers. The Log Book will also provide contact details for the installer should you need guidance in the use of this appliance or if there are any problems. As with your car, your boiler will work more reliably and eciently if regularly serviced. We recommend an annual service check. The service history of the appliance will be recorded on the Log Book. In the unlikely event of any problems with your boiler or system you should rst contact your installer. If your installer cannot resolve the problem he should telephone our national service helpline. A charge may be made if MTS Service is called out to resolve a non-product related fault. Your statutory rights are not aected.
To The Installer
As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the Householder. Please ensure that your customer is aware of the importance of keeping the Log Book safe as a record of the installation and the appliance service history.
Please ensure that your customer is aware of the correct operation of the system, boiler and controls.
MTS recommend the use of protective clothing, when installing and working on the appliance i.e. gloves.
CUSTOMER CARE
MTS, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing high quality products and a high quality after sales service. Advice on installation or servicing can also be obtained by contacting the MTS Technical and Customer Service Departments at High Wycombe. TECHNICAL DEPARTMENT CUSTOMER SERVICE DEPARTMENT Tel: 0870 241 8180 Tel: 0870 600 9888 Fax: 01494 459775 Fax: 01494 459775
GUARANTEE
The manufacturer’s guarantee is for 2 years from the date of purchase. The guarantee is invalidated if the appliance is not installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an ecient after sales service, please return the guarantee registration card enclosed with the boiler without delay.
CAUTION
In the United Kingdom, installation, start-up, adjustments and maintenance, must be performed by a competent person only, in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided.
In the Republic of Ireland, the installation and initial start up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Buidling Regulations, reference should also be made to the current ETCI rules for electrical installation.
All CORGI registered installers carry a CORGI ID card, and have a registration number. Both should be recorded in your boiler Log Book. You can check your installer is CORGI registered by calling CORGI direct on:- (01256) 372300.
Improper installation may cause damage or injury to individuals, animals and personal property for which the manufacturer will not be held liable. To ensure ecient and safe operation it is recommended that the boiler is serviced annually by a competent person.
If it is known that a fault exists on the appliance, it must not be used until the fault has been corrected by a competent person.
This instruction booklet is especially designed for appliances installed in the UK and the Republic of Ireland
overview
Advice for the installer
The installation and rst ignition of the boiler must be performed by qualied personnel in compliance with current national regulations regarding installation, and in conformity with any requirements established by local authorities and public health organisations. After the boiler has been installed, the installer must ensure that the end user receives the declaration of conformity and the operating manual, and should provide all necessary information as to how the boiler and the safety devices should be handled.
This appliance is designed to produce hot water for domestic use. It should be connected to a heating system and a distribution network for domestic hot water, both of which must be compatible with its performance and power levels. The use of the appliance for purposes other than those specied is strictly forbidden. The manufacturer cannot be held responsible for any damage caused by improper, incorrect and unreasonable use of the appliance or by the failure to comply with the instructions given in this manual. Installation, maintenance and all other interventions must be carried out in full conformity with the governing legal regulations and the instructions provided by the manufacturer. Incorrect installation can harm persons, animals and possessions; the manufacturing company shall not be held responsible for any damage caused as a result. The boiler is delivered in a carton. Once you have removed all the packaging, make sure the appliance is intact and that no parts are missing. If this is not the case, please contact your supplier. Keep all packaging material (clips, plastic bags, polystyrene foam, etc.) out of reach of children as it may present a potential hazard. In the event of a fault and/or malfunction, turn the appliance o, turn o the gas cock and do not attempt to repair it yourself. Contact a qualied professional instead. Before any maintenance or repair work is performed on the boiler, make sure you have disconnected it from the electricity supply by switching the external bipolar switch to the “OFF” position and removing the fuse. All repairs, which should only be performed using original spare parts, should be carried out by a qualied professional. Failure to comply with the above instructions could compromise the safety of the appliance and invalidate all liability on the part of the manufacturer. In the event of any maintenance or other structural work in the immediate vicinity of the ducts or ue gas exhaust devices and their accessories, switch the appliance o by switching the external bipolar switch to the “OFF” position and shutting o the gas control valve. When the work has been completed, ask a qualied technician to check the eciency of the ducting and the devices.
Turn the boiler o and turn the external switch “OFF” to clean the exterior parts of the appliance. Clean using a cloth dampened with soapy water. Do not use aggressive detergents, insecticides or toxic products. If the appliance is used in full compliance with current legislation, it will operate in a safe, environmentally-friendly and cost-ecient manner. If using kits or optional extras, make sure they are authentic.
CE labelling
The CE mark guarantees that the appliance conforms to the following directives:
-
90/396/CEE
relating to gas appliances
-
2004/108/CEE
relating to electromagnetic compatibility
-
92/42/CEE
relating to energy eciency
-
2006/95/CEE
relating to electrical safety
Symbols used on the data plate
Gas
MAX
MIN
Gas
mbar
mbar
1
2
5
4
3
6
7
19
8
9
10
11
12
14 15
16
17
18
13
20 21 22
Légende :
1.
Brand
2. Manufacturer
3. Boiler model - Serial number
4. Commercial reference
5. certication number
6. Destination country - gas category
7. Gas setting
8. Installation
type
9. Electrical data
10. Maximum domestic hot water pressure
11. Maximum heating pressure
12. Boiler type
13. NOx class / Eciency
14. Input rating nominal heating
15. Power ouput
heating
16. DHW specic ow rate
17. Boiler output eciency
18. Input rating nominal DHW
19. Gases which may be used
20. Température ambiante de fonctionnement
21. Max. central heating temperature
22. Max. Domestic Hot Water temperature
overview
Safety regulations
Key to symbols:
Failure to comply with this warning implies the risk of personal injury, in some circumstances even fatal Failure to comply with this warning implies the risk of damage, in some circumstances even serious, to property, plants or animals.
Install the appliance on a solid wall which is not subject to vibration.
Noisiness during operation.
When drilling holes in the wall for installation purposes, take care not to damage any electrical wiring or existing piping.
Electrocution caused by contact with live wires. Explosions, res or intoxication caused by gas leaking from damaged piping. Damage to existing installations. Flooding caused by water leaking from damaged piping.
Perform all electrical connections using wires which have a suitable section.
Fire caused by overheating due to electrical current passing through undersized cables.
Protect all connection pipes and wires in order to prevent them from being damaged.
Electrocution caused by contact with live wires. Explosions, res or intoxication caused by gas leaking from damaged piping. Flooding caused by water leaking from damaged piping.
Make sure the installation site and any systems to which the appliance must be connected comply with the applicable norms in force.
Electrocution caused by contact with live wires which have been installed incorrectly. Damage to the appliance caused by improper operating conditions.
Use suitable manual tools and equipment (make sure in particular that the tool is not worn out and that its handle is xed properly); use them correctly and make sure they do not fall from a height. Replace them once you have nished using them.
Personal injury from the falling splinters or fragments, inhalation of dust, shocks, cuts, pricks and abrasions. Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Use electrical equipment suitable for its intended use (in particular, make sure that the power supply cable and plug are intact and that the parts featuring rotary or reciprocating motions are fastened correctly); use this equipment correctly; do not obstruct passageways with the power supply cable, make sure no equipment could fall from a height. Disconnect it and replace it safely after use.
Personal injury caused by falling splinters or fragments, inhalation of dust, knocks, cuts, puncture wounds, abrasions, noise and vibration. Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Make sure any portable ladders are positioned securely, that they are suitably strong and that the steps are intact and not slippery and do not wobble when someone climbs them. Ensure someone provides supervision at all times.
Personal injury caused by falling from a height or cuts (stepladders shutting accidentally).
Make sure any rolling ladders are positioned securely, that they are suitably strong, that the steps are intact and not slippery and that the
ladders are tted with handrails on either side of the ladder and parapets on the landing.
Personal injury caused by falling from a height.
During all work carried out at a certain height (generally with a dierence in height of more than two metres), make sure that parapets are used to surround the work area or that individual harnesses are used to prevent falls. The space where any accidental fall may occur should be free from dangerous obstacles, and any impact upon falling should be cushioned by semi-rigid or deformable surfaces.
Personal injury caused by falling from a height.
Make sure the workplace has suitable hygiene and sanitary conditions in terms of lighting, ventilation and solidity of the structures.
Personal injury caused by knocks, stumbling etc.
Protect the appliance and all areas in the vicinity of the work place using suitable material.
Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Handle the appliance with suitable protection and with care.
Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.
During all work procedures, wear individual protective clothing and equipment.
Personal injury caused by electrocution, falling splinters or fragments, inhalation of dust, shocks, cuts, puncture wounds, abrasions, noise and vibration.
Place all debris and equipment in such a way as to make movement easy and safe, avoiding the formation of any piles which could yield or collapse.
Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.
All operations inside the appliance must be performed with the necessary caution in order to avoid abrupt contact with sharp parts.
Personal injury caused by cuts, puncture wounds and abrasions.
Reset all the safety and control functions aected by any work performed on the appliance and make sure they operate correctly before restarting the appliance.
Explosions, res or intoxication caused by gas leaks or an incorrect ue gas exhaust. Damage or shutdown of the appliance caused by out-of-control operation.
Before handling, empty all components that may contain hot water, carrying out any bleeding if necessary.
Personal injury caused by burns.
Descale the components, in accordance with the instructions provided on the safety data sheet of the product used, airing the room, wearing protective clothing, avoid mixing dierent products, and protect the appliance and surrounding objects.
Personal injury caused by acidic substances coming into contact with skin or eyes; inhaling or swallowing harmful chemical agents. Damage to the appliance or surrounding objects due to corrosion caused by acidic substances.
If you detect a smell of burning or smoke, keep clear of the appliance, disconnect it from the electricity supply, open all windows and contact the technician.
Personal injury caused by burns, smoke inhalation, intoxication.
product description
90°40°
50°
60° 70°
80°
on/o
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
9
6
12
I
1
2
3
4
5
8
9
10
6
7
Control panel
Legend :
1. Green indicator CH temperarure and errors indicator
2. ON/OFF button
3. Green indicator ON/OFF
4.
Pressure gauge
5. Winter / Summer switch - Heating temperature regulation knob
6. Domestic Hot Water adjustment knob
7. Time clock
8. Green indicator : ame ON Red indicator : locking light
9. Yellow
indicator : fumes exhaust malfunction
10. R
ESET button
product description
1. ue connector
2.
air pressure switch
3. burner
4.
detection Electrode
6.
C.H. Return temperature probe
7.
C.H. Flow temperature probe
8.
gas valve
9.
secondary heat exchanger
11. siphon
12. C.H. pressure relief valve
13. electrical box
15.
C.H. circuit lter
16.
D.H.W. Flow switch
17.
circulation Pump with air release valve
18.
diverter valve
19.
switch On-O
20. silencer
21.
modulating Fan
22.
ignition electrodes
23. ignitor
24. thermal fuse
25.
combustion Analysis Test Point
Overall view
1
2
3
4
6
7
8
9
11
12
13
25
24
23
22
21
20
18
19
17
15
16
product description
28
770
200
150
120 120
200
180
65 6567 67
25770
Overall Dimensions
24/30/38
A. Central Heating Flow B. Domestic Hot Water Outlet C. Gas Inlet D. Domestic Cold Water Inlet E. Central Heating Return
450
003
003
50 50
Minimum clearances
In order to allow easy access to the boiler for maintenance operations, The boiler must be installed in accordance with the clearances stated below.
product description
Technical Data
GENERAL
NOTE
Model E-COMBI
243038
CE Certication (pin)
0085BR0347
Boiler type
B23-C13-C33-C43-C53-C83
POWER SPECIFICATIONS
Max/min nominal caloric ow rate (Pci) Qn
KW
22,0/5,5
28,0/6,5
31,0/7,5
Max/min nominal caloric ow rate (Pcs) Qn
KW
24,4/6,1
31,1/7,2
34,4/8,3
Domestic hot water max/min nominal caloric ow rate (Pci) Qn
KW
25,0/5,5
30,0/6,5
38,0/7,5
Domestic hot water max/min nominal caloric ow rate (Pcs) Qn
KW
27,8/6,1
33,3/7,2
42,2/8,3
Max/min power output (80°C-60°C) Pn
KW
21,6/5,2
27,4/6,2
30,3/7,3
Max/min power output (50°C-30°C) Pn
KW
23,5/5,8
29,5/6,9
33,1/8,0
Domestic hot water max/min power output Pn
KW
25,0/5,0
30,0/6,0
38,9/7,1
Combustion eciency (of ue gas)
%
97,9
97,9
98,0
Nominal caloric ow rate eciency (60/80°C) Hi/Hs
%
98,0/88,2
98,0/88,2
97,6/87,9
Nominal caloric ow rate eciency (30/50°C) (condensation) Hi/Hs
%
107,0/96,4
105,3/94,8
106,9/96,3
Eciency at 30% at 30°C (condensation) Hi/Hs
%
108,0/97,3
110,3/99,3
107,2/96,5
Eciency at 30% at 47°C Hi/Hs
%
101,0/90,9
98,2/88,4
103,1/92,8
Minimum caloric ow rate eciency (60/80°C) Hi/Hs
%
95,0/85,5
95,6/86,1
96,8/87,2
Eciency rating (dir. 92/42/EEC)
stars
****
****
****
Sedbuk class
class
A / 90,3
A / 90,1
A / 90,1
Loss when stopped (∆T = 50°C)
%
0,2
0,1
0,1
Loss of burner gas when operating
%
2,1
2,1
2,0
EMISSIONS
Available air pressure
Pa
137
141
132
NoX class
class555Flue gas temperature (G20) (80°C-60°C)
°C636363CO2 content (G20) (80°C-60°C)
%
9,0
9,0
9,6
CO content (0%O2) (80°C-60°C)
ppm
< 100
< 100
< 125
O2 content (G20) (80°C-60°C)
%
4,5
4,5
3,5
Maximum ue gas ow (G20) (80°C-60°C)
Kg/h
41,2
49,4
59,2
Excess air (80°C-60°C)
%2727
20
HEATING CIRCUIT
Expansion chamber ination pressure
bar11
1
Maximum heating pressure
bar33
3
Expansion chamber capacity
L
6,5
6,5
6,5
Maximum water capacity with in the appliance (75°C-35°C)
L
100/300
100/300
100/300
Min/max heating temperature (high temperature range)
°C
35/82
35/82
35/82
Min/max heating temperature (low temperature range)
°C
20/45
20/45
20/45
DOMESTIC HOT WATER
CIRCUIT
Domestic hot water max/min temperature
°C
36/60
36/60
36/60
Specic ow rate of domestic hot water (∆T=30°C)
l/mn
12,0
15,0
18,2
Quantity of hot water ∆T=25°C
l/mn
14,4
18,0
21,8
Quantity of hot water ∆T=35°C
l/mn
10,3
12,9
15,6
Hot water comfort rating (EN13203)
stars
***
***
***
Hot water minimum ow rate
l/mn
< 2
< 2
< 2
Domestic hot water max/min pressure
bar
7/0,3
7/0,3
7/0,3
ELECTRICAL
Power supply frequency/voltage
V/Hz
230/50
230/50
230/50
Total electrical power absorbed
W
114
115
150
Minimum ambient temperature for use
°C+5+5
+5
Protection level for the electrical appliance
PI
X5D
X5D
X5D
Weightkg323535,5
10
installation
Reference Standards
In the United Kingdom, the installation and initial start-up of the boiler must be by a CORGI registered installer in accordance with the installation standards currently in eect, as well as with any and all local health and safety standards i.e. CORGI.
In the Republic of Ireland the installation and initial start-up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations” and the current Building Regulations, reference should also be made to the current ETCI rules for electrical installation.
The installation of this appliance must be in accordance with the relevant requirements of the Local Building Regulations, the current I.E.E. Wiring Regulations, the by-laws of the local authority, in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No. 635, “Electricity at Work Regulations 1989” and in the Republic of Ireland with the current edition of I.S. 813 and the Local Building Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are non-hazardous and no special precautions are required when servicing.
Codes of Practive
Installation should also comply with the following British Standards Code of Practice:
BS 7593:1992 Treatment of water in domestic
hot water central heating systems
BS 5546:1990 Installation of hot water supplies
for domestic purposes BS 5440-1:2000 Flues BS 5440-2:2000 Air supply BS 5449:1990 Forced cicrulation hot water
systems BS 6798:2000 Installation of gas red hot
water boilers of rated input not
exceeding 70kW BS 6891:1989 Installation of low pressure gas
pipes up to 28mm BS 7671:2001 IEE Wiring Regulations BS 4814:1990 Specication for expansion
vessels BS 5482:1994 Installation of L.P.G.
and in the Republic of Ireland in accordancce with the following codes of practice:
I.S. 813 Domestic Gas Installations
Avoid installing the boiler where the air inlet can be polluted by checmical products such as chlorine (swimming pool area), or ammonia (hair dresser), or alkalin products (launderette).
Flue
Detailed information on ue assembly can be found in the “Connecting the Flue” section. The boiler must be installed so that the ue terminal is exposed to the free passage of external air at all times and must not be installed in a place likely to cause nuisance. It must not be allowed to discharge into another room or space such as an outhouse or closed lean-to.
Condensing boilers have a tendency to form a plume of water vapour from the ue terminal due to the low temperature of the ue gasses. The terminal should therefore be located with due regard for the damage or discolouration that may occur to building within the vicinity and consideration must also be given to adjacent boundaries, openable windows should also be taken into consideration when siting the ue.
11
installation
NOTE: THE FLUE MUST NOT BE INSTALLED IN A PLACE LIKELY TO
CAUSE A NUISANCE AND POSITIONED TO ENSURE THAT PRODUCTS OF COMBUSTION DO NOT DISCHARGE ACROSS A BOUNDARY
It may be necessary to protect the terminal with a guard, if this is the case it will be necessary to purchase a stainless steel terminal guard. Reference should be made to the Building Regulations for guidance.
Ventilation
The room in which the boiler is installed does not require specic ventilation. If the boiler is installed in a cupboard or compartment ventillation is not required for cooling purposes.
Gas Supply
The gas installation and tightness testing must be in accordance with the requirements of BS6891. Ensure that the pipe size is adequate for demand including other gas appliances on the same supply.
Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and must be in accordance with current I.E.E. regulations. It must also be possible to be able to completely isolate the appliance electrically. Connection should be via a 3 amp douple pole
fused isolating switch with contact separation of at least 3mm on both poles. Alternatively, a fused 3 Amp, 3 pin plug and unswitched socket may be used, provided it is not used in a room containing a bath or shower, it. It shoild only supply the appliance.
Water Supply
The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 6 bar. All ttings and pipework for the appliance should be of the same standard. If there is a possibility of the incoming mains pressure exceeding 6 bar, particularly at night, then a suitable pressure limiting valve must be tted. The boiler is designed to provide hot water on demand to multiple outlets within the property. If there is a requirement for greater demands, for example if the boiler has several bathrooms and cloakrooms, a vented or unvented hot water storage system may be used.
Showers
Any shower valves used with the appliance should be of a thermostatic or pressure balanced type. Refer to the shower manufacturer for performance guidance and suitability.
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 2500 mm
- I From a terminal facing a terminal 2500 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical ue terminal
The minimum acceptable clearances are shown below:
12
installation
Flushing and Water Treatment
The boiler is equipped with a stainless steel heat exchanger.
The detailed recommendations for water treatment are given in BS 7593:1992 (Treatment of water in domestic hot water central heating systems); the following notes are givent for general guidance;
If the boiler is installed on an existing system, any unsuitable additives must be removed.
Under no circumstances should the boiler be red before the system has been thoroughly ushed; the ushing procedure must be in line with BS 7593:1992.
We highly recommend the use of a ushing detergent appropriate for the metals used in the circuit. These include cleansers produced by Fernox BetzDearbon, whose function is to disolve any foreign matter that may be in the system;
In hard water areas or where large quantities of water are in the system the treatment of water to prevent premature scaling of the main exchanger is necessary.
The formation of scale strongly compromises
the eciency of the thermic exchanger because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this situation it is necessary to treat the water with an appropriate corrosion inhibitor.
Any treatment of water by additives in the system for frost protection or for corrosion inhibition has to be absolutely suitable for all metals used in the circuit.
The use of a corrosion inhibitor in the sysem such as Fernox MB-1, BetzDearborn Sentinel X100 or Fernox System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and system;
If anti-freeze substances are to be used in the system, check carefully that they are compatible with the metals used in the circuit.
MTS suggests the use of suitable anti-freeze products such as Fernox ALPHI 11, which will prevent rust and incrustation taking place. Preiodically check the pH balance of the water/anti­freeze mixture of the boiler circuit and replace it when the amount measured is out of the range stipulated by the manufacturer (7 < pH < 8). DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
In under-oor systems, the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosion of the systems metal parts (metal piping, boiler etc), through the formation of oxides and bacterial agents.
To prevent this problem it is necessary to use pipes with an “oxygen proof barrier”, in accordance with standards DIN 4726/4729. If pipes of this kind are
not used, keep the system separate by installing heat exchangers of those with a specic system water treatment.
IMPORTANT Failire to carry out the water treatment procedure will invalidate the appliance guarantee.
System Controls
The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls. The addition of such external controls can be benecial to the ecient operation of the system. The boiler connections for external contols are 12V DC and so only controls of 12V DC that have voltage free contacts should be used. (page 26). MTS supply a range of wired and wireless system controls. Contact your supplier for more details.
Location
The boiler can be installed on any suitable internal wall (suitable sound proong may be required when installing onto a stud partition wall). Provision must be made to allow for the correct routing of the ue and siting of the terminal to allow the safe and ecient removal of the ue products. A compartment or cupbaord may be used provided that it has been built or modied for this purpose. It is not necessary to provide permanent ventillation for cooling purposes. Detailed recommendations are given in BS 5440 Part 2. If it is proposed that it is to be installed in a timber framed building then reference should be made to British Gas Document DM2, IGE/UP/7 or advice sought from CORGI.
Where a room sealed appliance is installed in a room containing a bath or shower, the appliance and any electrical switch or appliance control, utilising mains electricity should be situated specically in accordance with current IEE Wiring Regulations.
For unusual locations, special procedures may be necessary. BS 6798:2000 gives detailed guidance on this aspect.
13
installation
Condensate Discharge
The condensate discharge hose from the boiler must have a continuous fall of 2.5o and must be inserted by at least 50mm into a suitable acid resistant pipe - e.g. plastic waste or overow pipe. The condensate discharge pipe must have a minimum diameter of 22mm, must have a continuous fall and preferably be installed and terminated to prevent freezing. The discharge pipe must be terminated in a suitable position:
i) Connecting into an internal soil stack (at least 450mm above the invert of the stack). A trap giving a water seal of at least 75mm must be incorporated into the pipe run, there also must be an air beak upstream of the trap. ii) Connecting into the waste system of the building such as a washing maching or sink trap. The connection must be upstream of the washing machine/sink. If the connection is down stream of if the waste trap then an additional trap giving a minimum water seal of 75mm and an air break must be incorporated in the pipe run, as above. iii) Terminating into a gully, below the grid level but above the water level iv) Into a soakaway
Note: If any condensate pipework is to be installed externally then it should be kept to a minimum and be insulated with a waterproof insulation and have a continuous fall. The total length of external pipe used should not exceed 3 metres.
Some examples of the type of condensate terminations can be found below.
1. Internal termination of codensate drainage pipe to internal stack.
2. External terminaton of condensate drainage pipe via internal discharge branch (e.g. sink waste) and condensate siphon.
3. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste
- proprietary tting).
4. External termination of condensate drainage pipe via condensate siphon
14
installation
Installing the Boiler
Please check that you are familiar with the installation requirement before commencing work (pages 7 - 13).
The installation accessories described in the following list are included in the boiler packaging:
- Hanging bracket
- A paper template (showing the dimensions of the boiler with 5 mm side clearances)
- Connection valves (Compression)
- Screws and washers
- Filling loop
- Installation, Servicing and Operating Instructions
- Flue gasket
Method of positioning the boiler on the wall
The paper template can be used to ensure the correct positioning of kitchen cabinets etc.
The paper template has to be xed to the wall and used to locate the position of the hanging bracket and the centre for the ue hole. Drill and plug the wall and secure the hanging bracket using the screws provided. Remove the boiler from it’s packaging and remove the front casing panel. Place the boiler on the hanging bracket.
N
OTE: THE APPLIANCE MUST NOT BE FITTED ON A COMBUSTIBLE
WALL SURFACE.
Connecting the Boiler to the System
- Remove the boiler casing as described on page 15
- Remove the caps and connect the valves to the
boiler using the washers provided;
- 4 x bre washers for the CH ow and return, cold
water inlet and hot water outlet connections;
Safety Valve Discharge and Condense Outlet
The pressure relief valve tube is made of copper. It should terminate below the boiler safely outside the premises. Care should be taken that it does not terminate over an entrance or window or where a discharge of heated water could endanger occupants or passers by.
Fill the central heating and DHW system and bleed air from the system as described in the Commissioning instructions (page 26).
The system should be carefully checked for leaks, as frequent relling could cause premature system corrosion or unnecessary scaling of the heat exchanger. The pipe from the trap should be connected to a drain as described in the relevant regulations.
Pay special attention not to bend the condensate silicone drain pipe is such a way as to interrupt the ow. Please only use drain pipe material compatible with condensate products (refer to BS 6798:2000).
The condensate ow can reach 2 litres/hour because of the acidity of the condensate products (Ph close to 2), take care before operation.
See page 13 for condensate discharge possibiities.
Note: Connections viewed from behind boiler
A
A
- remove the 2 screws A from
the transport bar
- dispose of the transport bar and reassemble the xing screws.
15
installation
Gas connection
Make sure, using the labels on the packaging and the data plate on the appliance itself, that the boiler is in the correct country and that the gas category for which the boiler was designed corresponds to one of the categories available in the country where it will be used. The gas supply piping must be created and measured out in compliance with specic legal requirements and in accordance with the maximum power of the boiler; you should also make sure that the shut­o valve is the right size and that it is connected correctly. Check that the supplied gas corresponds to the type of gas for which the boiler was designed (see the data plate located on the appliance itself). It is also important to check that the pressure of the gas (methane or LPG) you will be using to feed the boiler is suitable, because if it is insucient the
power may be reduced, causing inconvenience for the user.
Water connection
The illustration shows the connections for the water and gas attachments of the boiler. See valves conguration on page 14. Check that the maximum water mains pressure does not exceed 6 bar; if it does, a pressure reducing valve must be installed. For the measuring of the pipes and of the heating bodies in the heating system, the residual head value should be calculated as a function of the requested ow rate, in accordance with the values shown in the circulation pump graph.
Instructions for opening the casing and performing an internal inspection
Before performing any work on the boiler, rst disconnect it from the electrical power supply using the external bipolar switch removing the fuse and shutting o the gas valve.
To access the inside of the boiler, the following is
necessary:
1.
Remove the casing by unhooking it from the control panel (a)
2. Loosen the two screws on the front casing (b), pull it forwards and unhook it from the upper pins (c)
3. Lower the control panel (d)
4. Unhook the two clips on the combustion chamber panel and lift o (e).
A
B
C
D
E
I
H
F
A. Central heating Flow B. Domestic Hot Water Outlet C. Gas Inlet D.
Domestic Cold Water Inlet E. Central Heating Return F. Safety Valve Discharge H. Drain Valve I. Drain condensate
(b)
(d)
(a)
(e)
(c)
16
installation
To calculate the size of the heating installation, refer to the "Available pressure" graph below.
Graph representing the available circulation pump pressure T20oC
Before the rst time the equipment is used, the trap must be lled with water. To do this, add approximately 1/4 litre of water via the ue outlet before tting the ue system, or unscrew the cap on the trap positioned under­neath the boiler, ll it with water and ret it
Warning! insucient water in the trap can temporarily cause the ue gas to be expelled into the surrounding ambient air
Underoor heating
For appliances with underoor heating, t a safety thermostat onto the underoor heating outlet. For the electrical connection of the thermostat see the section on “Electrical connections - page 26”.
If the outlet temperature is too high, the boiler will stop both domestic hot water and the heating pro-
duction and the error code 116 “oor thermostat
contact open” will appear on the display. The boiler will restart when the thermostat is closed during automatic resetting.
If the thermostat cannot be installed, the underoor heating equipment must be protected by a thermos­tatic valve, or by a by-pass to prevent the oor from reaching too high a temperature.
Water circuit diagram
A
B
C
D
E
I
G
H
F
1
4
3
11
8
10
12
14
15
16
17
18
19
20
21
22
7
6
5
A B C D E
1. Manual air vent
3.
Burner
4.
Detection electrode
5.
C.H. ow temperature probe
6.
C.H. return temperature probe
7.
Secondary heat exchanger
8. C.H. pressure relief valve
10. By-pass
11.
Drain valve
12. Condensate trap
14.
C.H. circuit lter
15.
D.H.W. Flow switch
16.
diverter valve
17.
water pressure sensor
18.
circulation Pump
19. expansion vessel
20.
modulating Fan
21.
ignition electrodes
22. thermal fuse
0
50
100
150
200
250
300
350
400
450
500
0 100 200 300 400 500 600 700 800 900 1000 1100 1200
mbar
l/h
24 kW
30-35 kW
30-38 kW
17
installation
Connecting the Flue
Flue System The provision for satisfactory ue termi­nation must be made as described in BS 5440-1. The appliance must be installed so that the ue terminal is exposed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times. The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity, it must also be located in a place not likely to cause nuisance. In cold or humid weather water vapour may condense on leaving the ue terminal. The eect of such “steaming” must be consi­dered. If the terminal is less than 2 metres above a balcony, above ground or above a at roof to which people have access, then a suitable stain­less steel terminal guard must be tted.
The minimum acceptable spacing from the ter­minal to obstructions and ventilation openings are specied in Fig. 1.
Fig. 1
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 2500 mm
- I From a terminal facing a terminal 2500 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical ue terminal
118 mm
See table
118 mm
4
See table on page 23
180
Fig. 2
18
installation
Warning
The exhaust gas ducts must not be in contact with or close to inammable material and must not pass throu­gh building structures or walls made of inammable material. When replacing an old appliance, the ue system must be changed.
Important
Ensure that the ue is not blocked. Ensure that the ue is supported and assembled in accordance with these instructions.
150 mm
118
* pente 5 mm par mètre
150 mm
* pente
Installation without extension
Installation with extension
slope 5 mm per metre
Level
Level
slope
Fig. 3
Fitting the Coaxial Flue (Ø 60 / 100 Horizontal)
Contents: 1x Silicone O-Ring (60mm) 1x Elbow (90°) 2x Wall Seals (Internal & External) 1x Flue Pipe including Terminal (1 metre - 60/100) 2x Flue Clamps 4x Screws 2x Seals
Once the boiler has been positioned on the wall, t the rubber ue seal into the internal ue turret (see diagram opposite),
insert the elbow into the socket and rotate to the required position. note: It is possible to rotate the elbow 360° on its vertical axis.
Using the ue clamp, seals and screws supplied (Fig
4) secure the elbow to the boiler.
The 1 metre horizontal ue kit (3318073) supplied is suitable for an exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face of the ue elbow (X - Fig 2), this gure must now be subtracted from 753mm, you now have the total amount to be cut from the plain end of the ue.
Draw a circle around the outer ue and cut the ue to the required length taking care not to cut the inner ue, next cut the inner ue ensuring that the length between the inner and outer ue is maintai­ned. (Fig 4).
e.g. X = 555mm 753-555 = 198mm (Length to be cut from the plain end of the ue).
Once cut to the required length, ensure that the ue is free from burrs and reassemble the ue. If tting the ue from inside of the building attach the grey outer wall seal to the ue terminal and push the ue through the hole, once the wall seal has passed through the hole, pull the ue back until the seal is ush with the wall. Alternatively, the ue can be installed from outside of the building, the grey outer seal being tted last.
Should the ue require extending, the ue connec­tions are push t, however, one ue bracket should be used to secure each metre of ue.
Note: See table for maximum and minimum ue runs.
19
installation
Clamp
Seal
Screws
Once the boiler has been positioned on the wall, it is ne­cessary to insert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical ue runs into the boiler ue soc­ket (not supplied with ue kit - Part No 3318095).
Push the adaptor onto the boilers ue connection, grease the seals then add extensions or elbows as re­quired, secure the adaptor, using the clamp and screws provided.
To t extensions or elbows it is rst necessary to en­sure that the lip seal is tted correctly into the inner ue, once veried, it is simply necessary to push them together, no clamps are necessary to secure the ue components.
Before proceeding to t the ue, ensure that the ma­ximum ue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, the maximum ue length is 10 me­tres, for each additional 90° elbow 1 metre must be su­btracted from the total ue length, and for each 45° 0.5 metres must be subtracted from the total ue length (the height of the vertical adaptor and a 45° bend can be seen in Fig.6 and a 90° bend in Fig. 7).
Note: DO NOT cut the vertical ue kit.
180 mm
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fitting the 5” Flue (Ø 80 / 125 Horizontal/vertical)
20
installation
Fitting the Coaxial Flue (Ø 60 / 100 Vertical)
Note: See table for maximum and minimum ue runs.
Contents: 1x Silicone O-Ring (60mm) 1x Conical Adaptor (60/100mm) 1x Vertical Flue Kit (80/125mm) 3x Screws
The vertical ue kit is supplied with a specially de­signed weather proof terminal tted, it can be used either with a at roof or a pitched roof.
The Vertical ue kits useable lengths with the pitched roof ashings are indicated in Fig. 7.
Before proceeding to t the ue, ensure that the maximum ue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, the maximum ue length is see table, for each additional 90° elbow 1 metre must be subtracted from the total ue length, and for each 45° 0.5 metres must be subtracted from the total ue length (the height of the vertical adaptor and a 45° bend can be seen in Fig. 8).
Mark the position of the ue hole in the ceiling and/or roof (see Fig. 7 for distance from wall to the centre of the ue).
Cut a 130mm diameter hole through the ceiling and/or roof and t the ashing plate to the roof.
DO NOT cut the vertical ue kit.
To connect the vertical ue kit directly to the boiler, place the vertical starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust manifold and secure with the clamp, t the vertical adaptor onto the vertical starter kit (note: there is no need to use a clamp to secure this as it is a push t connection), the vertical ue kit must then be inserted through the roof ashing, this will ensure that the correct clearance above the roof is provided as the terminal is a xed height.
Should extensions be required, they are availa­ble in 1 metre (Part No. 3318077), 500mm (Part No. 3318078) and 160mm lengths, they must be connected directly to the vertical starter kit before connecting the adaptor to allow the vertical ue kit to be tted. In the event that extension pieces need to be shortened, they must only be cut at the male end and it must be ensured that the inner and outer ue remain ush.
When utilising the vertical ue system, action must be taken to ensure that the ue is supported adequately to prevent the weight being transferred to the appliance ue connection by using 1 ue bracket per extension.
When the ue passes through a ceiling or wooden oor, there must be an air gap of 25mm between any part of the ue system and any combustible material. The use of a ceiling plate will facilitate this. Also when the ue passes from one room to another a re stop must be tted to prevent the passage of smoke or re, irrespective of the structural material through which the ue passes.
180 mm
Fig. 7
Fig. 8
21
installation
Fitting the Twin Pipe (Ø80 / 80)
Note: See table for maximum and minimum ue runs.
Where it is not possible to terminate the ue within the distance permitted for coaxial ues, the twin ue pipe can be used by tting a special adaptor to the ue connector and using the aperture for the air intake located on top of the combustion chamber.
Always ensure that the ue is adequately supported, using one ue bracket per extension and avoiding low points. (MTS supply suitable clamps as Part No.
705778). To utilise the air intake it is necessary to:
1) Take the air intake cover o the top of the ap­pliance
2) Assemble the ange on the header supplied with the boiler
3) Insert the header on the tube or the elbow up until the lower stop (you do not have to use the washer).
4) Insert the elbow/header in the boiler air intake hole and fasten it with screws.
The twin ue pipes can be tted with or without ad­ditional elbows and need no clamps, simply ensure that the red o-ring is inserted in the female end of the ue pipe and push the extension piece fully into the previous section of ue pipe or elbow, check that the o-ring is not dislodged when assembling the ue (greasing the seal will aid assembly).
Twin pipe can also be converted back to Coaxial ue to enable vertical termination with a coaxial kit by using the pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089). When running the twin ue pipe vertically.
It is not possible to terminate concentrically hori­zontally. Termination is only possible with separate air and exhaust terminals. When siting the twin ue pipe, the air intake and exhaust terminals must terminate on the same wall, the centres of the terminals must be a minimum of 280 mm apart and the air intake must not be sited above the exhaust terminal (refer to Fig. 10). The air intake pipe can be run horizontally, however, the terminal and the nal 1 metre of ue must be installed either horizontally or with a slight fall away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be constructed of insulated pipe to prevent condense forming on the outside of the tube.
The maximum permissible ue length for twin ue is dependent on the type of run used (see table on page 23).
For further information relating to ue runs not illustrated, please contact the Technical Department on 0870 241 8180.
22
installation
For coaxial systems, the maximum development value, mentioned in the table below also takes into account an elbow. For twin ue systems the maximum development value, mentioned in the table includes the exhaust gas/air intake terminal.
Type 5 outlets should respect the following instruc­tions: 1- Use the same ø 80 mm ue pipes for the air
intakes and exhaust gas ducts.
2- If you need to insert elbows in the air intake and
exhaust gas ducts, you should consider for each one the equivalent length to be included in the calculation of developed length.
3- The exhaust gas duct should jut above the roof by
at least 0.5 m.
4- The intake and exhaust gas ducts in Type C13 +
C53 must be installed on the same wall, or where the exhaust is vertical and the air intake horizon­tal, the terminals must be on the same side of the building.
EXHAUS T
AIR IN TAKE
AIR IN TAKE
AIR IN TAKE MUS T NO T BE
FITTED ABOVE THE EXHAUS T
195
105
120
180
Fig. 9
Fig. 10
23
installation
Table of ue gas exhaust duct lengths
COAXIAL SYSTEM
FLUE TYPE
MAX
LENGTH
DIAMETER of
PIPE
C13
Flue gas exhaust and air suction
duct through external wall in the
same range of pressure
24
12 m 36 m
60/100 80/125
30
10 m 30 m
60/100 80/125
38
6 m
18 m
60/100 80/125
C 33
Flue gas exhaust and air suction
duct from outside with roof
terminal in the same range of
pressure
24
12 m 42 m
60/100 80/125
30
10 m 35 m
60/100 80/125
38
8 m
21 m
60/100 80/125
C43
Individual or shared ue gas
exhaust and air suction through
ue ducting built into the building 24
12 m
0 m
60/100 80/125
30
10 m
0 m
60/100 80/125
38
8 m 0 m
60/100 80/125
24
installation
TWIN-PIPE SYSTEM
FLUE TYPE
MAX
LENGTH
DIAMETER of
PIPE
C13
Flue gas exhaust and air suction
duct through external wall in the
same range of pressure
24
36 m
(S1=S2)
80/80
30
30 m
(S1=S2)
38
18 m
(S1=S2)
C 33
Flue gas exhaust andair suction
duct from outsidewithroof
terminalin the same range of
pressure
24
60 m
(S1=S2)
80/80
30
50 m
(S1=S2)
38
21 m
(S1=S2)
C53
Flue gas exhaust leading outside
and air suction duct through
external wall not in the same range
of pressure
24
84 m
(S1+S2)
80/80
30
70 m
(S1+S2)
38
42 m
(S1+S2)
S1 = Air intake S2 = Flue gas exhaust
S1 = S2 - Air intake and ue gas exhaust equal lengths S1 + S2 - Air intake and ue gas exhaust unequal lengths
25
installation
WARNING Before performing any work on the boiler, rst disconnect it from the electrical power supply using the external bipolar switch and remove the fuse.
Electrical connections
For increased safety, ask a qualied technician to perform a thorough check of the electrical system. The manufacturer is not responsible for any damage caused by the lack of a suitable earthing system or by the malfunctioning of the electricity mains supply. Make sure that the system is able to withstand the maximum power absorbed by the boiler (this is indicated on the appliance data plate). Check that the section of the wires is suitable and is not less 0,75 mm2 The appliance must be connected to an eecient
earthing system if it is to operate correctly. The power supply cable must be connected to a 230V-50Hz network, where the L-N poles and the earth connection are all respected. Important! In the event that the power supply cable must be changed, replace it with one with the same specications.
Power supply cable
Important! The appliance is supplied with a y-lead already connected, this must be connected to a 240V supply fused at 3 Amp and must facilitate completed electrical isolation of the appliance, by use od a fused double pole isolator having a contact separation of at least 3mm in all poles or alternatively by means of a 3A fused three pin plug and unswitched shuttered socket outlet both complying with BS1363.
The use of multiplugs, extension leads or adaptors is strictly prohibited. It is strictly forbidden to use the piping from the hydraulic, heating and gas systems for the appliance earthing connection. The boiler is not protected against the eects caused by lightning. If the mains fuses need to be replaced, use 2A rapid fuses.
Peripheral unit connection
To access peripheral unit connections carry out the following steps:
- Disconnect the boiler from the power supply
- Remove the casing by unhooking it from the instrument panel
- Rotate the control panel while pulling it forwards
- Unscrew the three screws on the back cover of the instrument panel
- Unhook the right side clip and the right front clip; then lift the ap
The terminal board (see gure) may be accessed in order to connect:
Outdoor sensor Room thermostat 1
Optional P.C.B.s can also be installed for further accessories:
BUS P.C.B. Clima Manager Modulating Room Sensor Programmable Room Thermostat Outdoor Sensor
- other plugs: for managing multi-zones
multitemperatures, Solar kit, etc...
Caution! For the connection and positioning of the wires belonging to optional peripheral units, please refer to the installation manu­als of these units.
H05V2V2-F
120
140
26
installation
Room Thermostat / Remote Clock Connection
To connect a room thermostat, it is necessary to:
1. Open the control panel
2. Loosen the cable clamp using a screwdriver and insert the wires leading from the room thermostat
3. Connect the wires to the terminals as indicated in the gure below, removing the link
4. If a remote time clock is to be tted, using a volt free switching time clock connect the switching wires from the time clock following points 1 - 3 above
5. If using an external time clock and room thermostat, these must be connected in series as shown in diagram C,
6. Ensure that they are well connected and not subject to stress when the control panel is closed
NOTE: WHEN CONNECTING THE BOILER TO EXTERNAL CONTROLS,
DO NOT RUN 240V CABLES AND CABLES FOR SWITCHING CIRCUITS (WHICH ARE LOW VOLTAGE) TOGETHER, USE SEPERATE CABLES TO PREVENT INDUCED VOLTAGE ON THE LOW VOLTAGE CIRCUITS.
CARTE CHAUDIERE
ACO-GAL1
Transmetteur BUS
(Optionnel)
Emplacement
carte optionnelle
SE
TA
TP/
Connector TA on PCB (low voltage switching)
Connector TA on PCB (low voltage switching)
Connector TA on PCB (low voltage switching)
27
installation
Electrical diagram
For increased safety, ask a qualied technician to perform a thorough check of the electrical system.
The manufacturer is not responsible for any damage caused by the lack of a suitable earthing system or by the
malfunctioning of the electricity mains supply.
8
1
Connessione sonda solare
5
1
ON
Display
Display
1 8
Flussimetro
sanitario
Elettrodo
Rilevazione
Ventilatore
AccenditoreValvola gas
Valvola dev. motorizzata
L N
FAN
VALVOLA GAS
ACCENDITORE
EARTH
FLAME
FLOW
PUMP
ZONE1
FILLING
PUMP
SPEED
1
1
FUSE 2AT
1 2 3 4 1 2 3 45 6
Circolatore
6
1
1
234
Termostato Ambiente
Sonda NTC mandata risc.
CN04
CN04
CN07
CN22
CN22
Pressostato di minima
Sonda NTC ritorno risc.
Term. protezione scambiatore
P
13 12 11 10 9 8 7 6 5 4 3 2 1
12 11 10 9 8 7 6 5 4 3 2 1
11 10 9 8 7 6 5 4 3 2 1
11 10 9 8 7 6 5 4 3 2 1
2
1
8 7 6 5 4 3 2 1
Termostato sovratemperatura
ignitor
detection electrode
gas
valve
display
room
thermostat
circulation
pump
diverter valve
C.H. ow temp.
probe
thermal fuse
modulating fan
C.H. return temp.
probe
D.H.W ow
switch
Switch on/o
28
commissioning
Initial preparation
MT S (G B) L imi ted sup por t the ben chm ark initiative. On pages pages 65 and 66 of this manual the Benchmark Commissioning Checklist and Service interval Record can be found. It is important that this is completed in the presence of your customer, they are shown how to use it, and it is signed by them. Please instruct your customer that they must have this manual with them whenever they contact a service engineer or us.
Preliminary electrical system checks to ensure elec trical sa fety m ust be car ried o ut b y a competent person i.e. polarity, earth continuity, resistance to earth and short circuit.
Electricity supply
- Check that the voltage and frequency of the
electricity supply correspond to the data shown on the boiler data plate;
- Make sure that the earthing connection is
ecient.
Filling the Heating System:
Switch the electrical supply to the boiler on in order to view the system pressure on the display; Remove the front casing panel and lower the control panel as described on page 13). Open the central heating flow and return cocks supplied with the connection kit; Lift the cap on the automatic air release valve and leave open permanently; Close all air release valves on the central heating system; Gradually open the valves at the filling point (filling loop) until water is heard to flow, do not open fully; Open ea ch air rele ase tap startin g with the lowest point and close them only when clear water free of air is visible; Purge the air from the pump by unscrewing the pump plug anti-clockwise, also manually rotate the pump shaft in the direction indicated by the pump label to ensure the pump is free; Refit the pump plug; Continue filling the system until at least 1.5 bar registers on the pressure gauge; Inspect the system for water tightn ess and remedy any leaks discovered.
IMPORTANT! MANUALLY VENT THE HEAT EXCHANGER AT THE MANUAL AIR
VENT. FAILURE TO VE NT ADEQ UATELY MAY DAMAGE THE HEAT EXCHANGER (PAGE 7, LEGEND 2).
Filling of the DHW System:
Close all hot water draw off taps; Open the cold water inlet cock supplied with the
connection kit; Slowly open each draw off tap and close them only when clear water, free of bubbles, is visible.
Gas Supply:
Inspect the entire installation inc ludin g the gas meter and test for tightness. The entire installation should be in accordance with the relevant standards. In GB this is BS 6891 and in IE this is the current edition of I.S.813.
The connection on the the appliance is a 15mm nut and olive located at the rear of the gas service cock.
If the gas supply serves other appliances, ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time.
Pipe work must be of an adequate size. Pipes of less than 22mm should not be used, final connection being 15mm.
Open the gas cock (supplied with the connection kit ) to the app lia nce and che ck the gas connection on the appliance for leaks.
Water Treatment:
The boiler is equipped with a stainless steel heat exchanger. Th e d eta ile d r ecomm end ati ons fo r w ate r treatment are given in BS 7593:1992 (Treatment of water in domestic hot water central heating syste ms); the followi ng notes are gi ven fo r general guidance;
If the boiler is installed on an existing system, any unsuitable additives must be removed;
Under no circumstances should the boiler be fired before the system has been thoroughly flushed; the flushing procedure must be in line with BS7593:1992.
Fir stly fil l th e central heat in g system with the power off, and flush through cold, fill the central heating system again, adding a flushing detergent, run the boi ler on central heating until it reaches its operating temperature and flush the system, refill the system with a suitable corrosion inhibitor,
NOTE: FAILURE TO CARRY OUT THE FLUSHING PROCEDURE WILL
RESULT IN THE WARRANTY BECOMING VOID.
29
commissioning
FIRST IGNITION OPERATION
1. Check the electrical supply.
Complete . . . . . . . . . . . . . . . . . . .
Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installer . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Check the type of gas and change the gas if necessary.
Complete . . . . . . . . . . . . . . . . . . .
3. Check the gas tightness.
Complete . . . . . . . . . . . . . . . . . . .
4. Measure the gas inlet.
Complete . . . . . . . . . . . . . . . . . . .
5. Check the exhaust fume. See section….
Complete . . . . . . . . . . . . . . . . . . .
6. Fill the installation. See section….
Complete . . . . . . . . . . . . . . . . . . .
7. Check the hydraulic water tightness.
Complete . . . . . . . . . . . . . . . . . . .
8. Spin the pump.
Complete . . . . . . . . . . . . . . . . . . .
9. Set the heating power. See section….
Complete . . . . . . . . . . . . . . . . . . .
10. Adapt the regulation at the heating installation.
Complete . . . . . . . . . . . . . . . . . . .
11. Balance the central heating circuit.
Complete . . . . . . . . . . . . . . . . . . .
12. Check the working in DHW mode.
Complete . . . . . . . . . . . . . . . . . . .
13. Adjust DHW ow rate on the boiler (if necessary).
Complete . . . . . . . . . . . . . . . . . . .
14. Make a combustion rate with once pressing on RESET button during 5 sec.
Complete . . . . . . . . . . . . . . . . . . .
15. Check the ionisation current.
Complete . . . . . . . . . . . . . . . . . . .
6. Explain to the end user the working of the boiler.
Complete . . . . . . . . . . . . . . . . . . .
30
commissioning
Ignition procedure
Press the ON/OFF button on the control panel to switch on the boiler.
Electricity supply
- Check that the voltage and frequency of the electricity supply correspond to the data shown on the boiler data plate;
- Make sure that the earthing connection is
ecient.
First ignition
1. Make sure that:
- The gas valve is closed;
- The electrical connection has been properly carried out. Make sure that, in any case, the green/yellow earthing wire is connected to an ecient earthing system;
- Use a screwdriver to lift the cap on the automatic air relief valve;
- Switch on the boiler (by pressing the ON/OFF button), the green led 3 will illuminate indicating that the boiler is ready to operate. Turn the CH buttton 5 between min. and max position. The pump will start and the burner will atemp to light, after 7 seconds the boiler will look out because there is no gas; the red Led 8 illuminates.
- Bleed the air from the radiators;
- The exhaust duct for combustion products should be suitable and free from any obstructions;
- Any necessary ventilation inlets in the room should be open (type B installation).
2. Open the gas cock and check the connection seals, including the boiler connection joints, making sure that the meter does not detect any passage of gas. Eliminate any leaks.
3. Unlock the boiler by pushing on thr reset button. The burner light, if the rst start fail, repend the operation until the burner light.
90°40°
50°
60° 70°
80°
on/o
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
9
6
12
I
31
commissioning
SETTING
Maximum CH power and soft ignition setting
1. Push ON/OFF button for 10 secondes, the
led red 8 blinks.
2. Adjusting with the CH knob 5 the maxi
CH power between 0 and 99 % (see table)
3. Adjusting with the DHW knob 6 the soft
ignition between 0 and 99 % (see table) The percentage level is visualized by the green led 1
4. To store the new values of settings, it’s
enough tu push ON/OFF button.
TAC setting and postcirculation DHW
Tac setting
After the previus phase (10 secondes of ON/OFF button pressed), pressing RESET the second level of setting is entered, so that the green led 8 blinks indicating that we are in a new regulating stage; Now we can modify :
- turn the CH knob = TAC (0,1,2,3,4,5,6
minutes, with zero, one or more temperature leds lit - see table)
Postcirculation DHW setting
- turn the DHW knob at minimum or maximum position
minimum position postcirculation = 0 min maximum position postcirculation = 3 min
gas setting
24 kW
30 kW
38 kW
G20
G31
G20
G31
G20
G31
lower Wobbe index (15°C, 1013 mbar) (MJ/m3)
45,67
70,69
45,67
70,69
45,67
70,69
gas valve restrictor(ø)
NO
3,80NO4,50NO5,250
gas ow max/min (15°C, 1013
mbar)
(nat - m3/h) (GPL - kg/h)
max D.H.W
2,65
1,94
3,17
2,33
4,02
2,95
max C.H.
2,33
1,71
2,96
2,17
3,28
2,41
min
0,58
0,43
0,69
0,50
0,79
0,58
0 min
3 min
Green Leds
Temperature indicator
Max adjustable power
and soft ignition
= no led lit
= lit
40 50 60 70 80 90 *
0 to 39 %
40 to 49 %
50 to 59 %
60 to 69 %
70 to 79 %
80 to 89 %
90 to 99 %
* This LED is red
Green Leds
Temperature indicator
TAC
= no led lit
= lit
40 50 60 70 80 90 *
0 min
1 min
2 min
3 min
4 min
5 min
6 min
* This LED is red
32
commissioning
Test function and combustion analysis
The boiler has two pressure taps to measure the com­bustion gas temperature, the combustive air and the concentrations of O2 and CO2 on the outside of the ue gas header. to access these pressure taps, unscrew the screw which holds the blanking cover and its seal to­gether.
Checking the gas setting
To carry out analyses of combustion, the test func­tion must be activated.
Maximum gas ow combustion analysis
Activate the test function at the maximum heating power, pushing for 5 secondes the RESET until the yellow led 8 blinks (also 60°C led is lit to indicate that Chimney is at max. CH absolute) Than rotating the CH knob to the min., intermediate position and max position and max. position it’s possible to switch between min, max CH absolute and max DHW power (respectively the 40°C, 60°C and 80°C are lit to indica­te the power level. The function is automatically deactivated after 10 minutes or by pressing the RESET button. Wait for the boiler to stabilise before carrying out the combustion analyses. Check the CO2 value according to the table below. Important: do not remove silencer 20
N.B.: when the front combustion chamber panel is open, the CO2 value drops by 0.3%.
If the values taken dier from the table, adjust the gas valve following the procedure described below.
Adjust the CO2 content to
± 0.2 by turning setting
screw 50 (2.5 mm allen key)
- tighten to lower the CO2 value
- unscrew to increase the CO2 value
Set the content by turning the screw about a 1/4 of a turn then wait after each change for approximately 1 minute for the CO2 value to stabilise, then repeat.
Minimum gas ow combustion analysis
Activate the cleaning function at minimum power in either heating or domestic hot water production. Wait for the boiler to stabilise before carrying out the combustion analyses. Check the CO2 value according to the table above. Important: do not remove silencer 20
N.B.: when the combustion chamber is open, the CO2 value drops by 0.3%.
If the values taken dier from the table, adjust the gas valve following the procedure described below.
To adjust the CO2 value, remove cap
2, adjust the CO2 content to ± 0.2 by turning setting screw 51 (4 mm allen key)
- unscrew to lower the CO2 value
- tighten to increase the CO2 value Set the content by turning the screw about a 1/4 of a turn then wait after each change for approximately 1 minute for the CO2 value to stabilise, then repeat. Once the settings and analyses are complete, exit test mode, and reposition the blanking cover and its seal correctly.
CO2 massimo e
minimo
243038
CO2 (%)
G20
9,0 ± 0,2
9,0 ± 0,2
9,4 ± 0,2
G31
10,7 ± 0,2
10,0 ± 0,2
10,6 ± 0,2
8
50
2
Only a 4 mm
allen key must be
used. Do not use a
screwdriver
51
Only a 2.5 mm allen key
must be used. Do not
use a screwdriver
33
boiler protection devices
Boiler protection devices
The boiler is protected from malfunctioning by means of internal checks performed by the electronic microprocessor P.C.B., which stops the boiler from operating if necessary. In the event of the boiler being shut o in this manner, the leds code show the type of shut-o and the reason behind it. There are two types of shut-o:
Safety shut-o
This type of error is “volatile”, which means that the boil­er starts up again automatically as soon as the problem which caused the shut-o is removed; the yellow led 9 blinks and green leds 1 indicating the error code- see table. In fact, soon as the cause of the shut-o disappears, the boiler starts up again and continues to operate nor­mally. In this case or if the re-balancing request is performed on a frequent basis, switch the boiler o, turn the external electric switch to the OFF position, shut o the gas cock and contact a qualied technician to check for any leaks of water.
Nota : In the event of insuciente water pressure inside the heating circuit, the boiler will perform a safety shut­o (yellow led 9 blinks - leds 40-50 light – see table). To re-pressurise the boiler, it will be necessary to connect the silver exible hose supplied to the two isolating points underneath the boiler, once the hose is con­nected, open up both of the black quarter turn handles, once the pressure reads 1.5 bar on the pressure gauge. If the pressure drops very frequently, there may be a water leak at some point in the system. If this is the case please contact your installer and ask them to check it.
Shutdown
This type of error is “non-volatile”, which means that it is
not removed automatically. The red led 8 light and green leds 1 indicating the error code- see table. To restore normal operation press the button on the control panel.
Important If this shutdown occurs frequently, contact an authorised Technical Service Centre for assistance. For safety reasons, the boiler will permit a maximum of 5 resets in 15 minutes (5 presses of the button).
Anti-frost Device.
The anti-frost function acts on the central heating ow temperature probe, independently from other regula­tions, when the electrical supply is turned on. If the primary circuit temperature is between 3°C and 8°C the pump will run (with the diver­ter valve switching between central heating and hot water every 1 minute) until the temperature reaches > 9°C. If the ow temperature remains between 3°C and 8°C the pump will continue to run for a maximum of 20 mi
­nutes unless a temperature above > 9°C is detected in the central heating ow, after this the the burner will re (heating position) until a temperature of > 30°C is detected. If the central heating ow temperature is < 3°C, the bur­ner will re (heating position) at minimum power until the temperature reaches > 30°C, the burner will go out. If lockout is caused by overheat the burner will not re but the pump will continue to run (heating position). The anti-frost device activates only when (with the boiler operating correctly):
- the system pressure is correct;
- the boiler is electrically powered;
- there is a supply of gas.
Table summarising error codes
Green Leds
Temperature indicator
Reset
Note
Description ❍ = flashing light
= lit
40 50 60 70 80 90 yellow red
X Overheat
● ●
X Insucient circulation
Insucient water (request lling) C.H. Flow temp. probe circuit open / short circuit C.H. Return temp. probe circuit open / short circuit External sensor circuit open / short circuit Floor Thermostat contact open
● ●
X Heating delevery probe problem
Insucient circulation EEPROM error Comunication error Too many (> 5) resets in 15 minutes
X Main P.C.B. error
Room sensor circuit open / short circuit
X No ame detected
Flame detected with gas valve closed
● ● ●
X Flame lift
1st Ignition Failed 2nd Ignition Failed Flame cut-o
● ●
X Thermofuse open
● ●
X Fan speed error
34
maintenance
Important
Maintenance is an essential part of the safe and
ecient operation of the boiler and ensures its durability. It should be performed according to the instructions given in current legislation. Perform combustion analysis regularly in order to check the operating eciency of the boiler and to make sure any polluting substances relased are within the boudaries set by current legislation. Before beginning maintenance work:
- Disconnect the appliance from the electricity supply by turning the external bipolar switch to the “OFF” position;
- Close the gas valve and the central heating and domestic hot water system valve.
After the work has been completed the initial settings will be restored.
General comments
It is recommended that the following inspections be carried out on the boiler at least once a year:
1. Check the seals in the water part and, if necessary, replace the gaskets and restore the seal to perfect working order.
2. Check the seals in the gas part and, if necessary, replace the gaskets and restore the seal to perfect working order.
3. Visually check the overall condition of the boiler.
4. Visually check the combustion and, if necessary, disassemble and clean the burner.
5. Following the inspection detailed in point “3”, disassemble and clean the combustion chamber, if necessary.
6. Following the inspection detailed in point “4”, disassemble and clean the burner and injector, if necessary.
7. Cleaning the primary heat exchanger
8. Make sure the following heating safety devices are operating correctly:
- temperature limit safety device.
9. Make sure that the following gas part safety devices are operating correctly:
- absence of gas or ame safety device (ionisation).
10. Check the eciency of the domestic hot water production process (test the ow rate and temperature).
11. Perform a general inspection of the boiler operation.
12. Remove oxide from the detection electrode using an emery cloth.
13. These checks are not exhaustive. Further mechanical, electrical and combustion maintenance checks may be required.
Operational test
After having carried out the maintenance operations,
ll the heating circuit at a pressure of approximately
1.0 bar and release the air from the system. Fill the domestic hot water system at the same time.
- Begin operating the boiler.
- If necessary, release the air from the heating system again.
- Check the settings and make sure all the command, adjustment and monitoring parts are working correctly.
- Check the ue system is sealed and operating correxctly.
35
maintenance
Draining procedures
The heating system must be drained using the
following procedure:
- Switch o the boiler, make sure the external bipolar switch is in the OFF position and shut o the gas valve;
- Loosen the automatic air relief valve;
- Open the system drain o cock and collect the escaping water in a container;
- Empty the water from the lowest points of the system (where applicable).
If the system is to be left inactive in areas where the room temperature may fall below 0°C during winter, we recommend that anti-freeze liquid is added to the water in the heating system in order to avoid the need for repeated draining; when this liquid is used make sure it is compatible with the stainless steel used for the bodywork of the boiler. We recommend the use of anti-freeze products which contain PROPYLENE GLYCOLS as these inhibit corrosion and that they are used in conjunction with the anti-scaling and anti-corrosion function, in the quantities suggested by the manufacturer, at the mimimum temperature. Regularly check the pH level of the water/anti-freeze mix in the boiler circuit and replace it when the value measured is lower than the limit prescribed by the manufacturer.
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE.
The manufacturer will not be held liable for any damage caused by the appliance or the system due to the use of inappropriate anti-freeze substances or additives.
Draining the domestic hot water system and indirect cylinder
Every time there is a danger of freezing, the domestic hot water system must be drained as follows:
- Shut o the water mains inlet valve;
- Open all the hot and cold water taps;
- Empty the water from the lowest points of the
system (where applicable).
WARNING
Before handling, empty all components which may contain hot water, performing bleeding where necessary. Descale the components in accordance with the instructions provided on the safety data leaet supplied with the product used, make sure the room is well ventilated, wear protective clothing, avoid mixing dierent products, and protect the appliance and surrounding objects. Seal all openings used to take a gas pressure reading or to make any gas adjustments.
Make sure that the nozzle is compatible with the supplied gas. If a smell of burning is detected or smoke is seen leaking from the appliance, or there is a smell of gas, disconnect it from the electricity supply, shut o the gas valve, open the windows and call for technical assistance.
Cleaning the primary exchanger
Cleaning the smoke side The inside of the primary exchanger is accessed by removing the burner. Wash with water and deter­gent using a non-metallic rie-type brush, rinse with water.
Cleaning the siphon
The siphon is accessed by emptying the condensate bowl located in the bottom section. Wash with water and detergent. Replace the condensate collection bowl in its housing. NB: in the event of prolonged use of the appliance, the siphon must be lled before being used again. A lack of water in the siphon is dangerous and may cause smoke to be released into the atmosphere.
36
MAINTENANCE GUIDE
1. GENERAL ACCESS
GENERAL ACCESS
Tools
Time
3 min
1
Unclip the cover to remove Remove the two screws Remove the front panel
2
Lower the electrical box
Remove the combustion cham­ber front panel by releasing the
clips
37
MAINTENANCE GUIDE
2. ELECTRICAL UNIT
2.1 CONTROL BOX ACCESS
CONTROL BOX ACCESS
Tools
Time
4 min
1
Remove the front panel as above
and pivot the electrical box
Remove the two screws and unlock the four clamps to gain access to the control box
2.2 FUSE
FUSE
Tools Time
5 min
1
Open the control box as above Remove the fuse
38
MAINTENANCE GUIDE
2.3 MAIN PCB
MAIN PCB
Tools
Time
7 min
1
After opening the control box,
disconnect the electrical plug
connectors
Unscrew the two screws and remove the PCB
2.4 DISPLAY PCB
DISPLAY PCB
Tools
Time
7 min
1
Unclip the cover to remove
Remove the two control knobs Unscrew the four screws and pull
the assembly towards you
2
Disconnect the electrical plug
connectors, unlock the two
clamps, and remove the PCB
39
MAINTENANCE GUIDE
3. HYDRAULIC UNIT
3.2 3 WAY VALVE
3 WAY VALVE UNIT
Tools Time
5 min
1
Unplug the diverter valve cable
Remove the clip and lift the motor from the
diverter valve body
2
Drain the boiler (see 3.3). Remove the clip and
lift the diverter valve from the assembly
When reassembling, ensure the diverter valve is
aligned correctly
3.1 RIGHT HAND HYDRAULIC BLOCK ASSEMBLY
1
2
3
5
4
6
7
8
9
11
12
13
14
10
LEGEND
1. Diverter valve motor
2. Diverter valve
3. Auto air vent
4. Primary water pressure switch
5. Pump
6. Central heating lter
7. Non return valve
8. Non return valve assembly
9. DHW ow switch assembly
10. Drain valve
11. Central heating return
12. Domestic cold water intlet
13. Domestic hot water outlet
14. Central heating ow
40
MAINTENANCE GUIDE
3.3 DRAINING
DRAINING
Tools
Time
5 min
1
Turn the drain valve anti-clockwise to open and drain the water from the boiler.
3.4 AUTOMATIC AIR VENT
AUTOMATIC AIR VENT
Tools Time
5 min
1
Drain boiler (see 3.3). Remove the clip and lift the AAV from the
assembly
3.5 PRIMARY WATER PRESSURE SENSOR
PRIMARY WATER PRESSURE SENSOR
Tools Time
5 min
1
Drain boiler (see 3.3). Remove the fixing clip, unplug the
electrical connector and lift the sensor from the assembly
41
MAINTENANCE GUIDE
3.6 PUMP
PUMP
Tools
Time
10 min
1
Drain boiler (see 3.3). Remove
the clip and the two screws
Disconnect the pipe and then
move the pump to the right
disengage
Remove the pump
2
Remove the sensor (see 3.5) Remove the AAV (see 3.4)
3.7 CH FILTER
CH FILTER
Tools
Time
5 min
1
Drain boiler (see 3.3)
Remove the clip
Remove the filter
42
MAINTENANCE GUIDE
3.8 DHW FLOW SWITCH ASSEMBLY
DHW FLOW SWITCH ASSEMBLY
Tools Time
5 min
1
Drain boiler (see 3.3). Remove the clip and pull the
flow switch assembly towards you
Twist the flow switch assembly to disengage
3.9 LEFT HAND HYDRAULIC BLOCK ASSEMBLY
1
2
3
4
5
1. Left hand hydraulic block 4. Central heating ow
2. By-pass assembly 5. Domestic hot water outlet
3. Safety valve
43
MAINTENANCE GUIDE
SECONDARY HEAT EXCHANGER
Tools
Time
10 min
1
Drain primary and domestic hot water circuits. Remove the two
screws and remove the heat exchanger
3.12 CONDENSE TRAP
CONDENSE TRAP
Tools Time
5 min
1
Unscrew the condense trap from the condense
body
3.10 SECONDARY HEAT EXCHANGER
3.11 CONDENSATE TRAP
44
MAINTENANCE GUIDE
3.13 SAFETY VALVE
SAFETY VALVE
Tools
Time
3.14 BY-PASS ASSEMBLY
5 min
1
Drain boiler (see 3.3). Disconnect the
discharge pipe
Remove the first clip on the left and
pull the safety valve towards you
BY-PASS ASSEMBLY
Tools
Time
5 min
1
Drain boiler (see 3.3). Remove the
second clip and pull the assembly
toward you
Push on the by-pass to disengage it
3.12 SAFETY VALVE
3.13 BY-PASS ASSEMBLY
45
MAINTENANCE GUIDE
3.16 MANUAL AIR VENT
MANUAL AIR VENT
Tools
5 min
Time
1
Drain boiler (see 3.3)
Remove the clip and lift the manual air vent from the exchanger
3.15 MANUAL AIR VENT
3.14 TEMPERATURE SENSOR
Tools
Time
5 min
1
NTC1
NTC2
NTC1 : Black wires
NTC2 : Grey wires
Unplug the electrical connectors Remove the clip and the tempe-
rature sensor
TEMPERATURE (°C) RESISTANCE (kOmh)
0 27 10 17 20 12 25
10 30 8 40 5 50 4 60 3 70 2 80 1,5
46
MAINTENANCE GUIDE
3.17 MAIN HEAT EXCHANGER
MAIN HEAT EXCHANGER
Tools
Time
20 min
1
Drain boiler (see 3.3). Remove the four clips and disconnect the two pipes between the exchanger and pump and between the exchanger and left hand hydraulic block
Isolate the gas supply. Remove the four screws and disconnect the gas pipe from the gas valve
Remove the four screws to free
the heat exchanger
2
Pull the heat exchanger towards
you
Remove the clip and lift the
manual air vent
Twist the thermal fuse to
remove
3.16 MAIN HEAT EXCHANGEUR
47
MAINTENANCE GUIDE
4 BURNER UNIT
LEGEND
1. Burner 6. Gas valve
2. Fan 7. Mixing tube
3. Silencer 8. Detection electrode
4. Gas inlet 9. Ignition electrode
5. Air inlet 10. Spark generator
48
MAINTENANCE GUIDE
4.1 SPARK GENERATOR
4.2 ELECTRODES
SPARK GENERATOR
Tools
5 min
Time
1
Unplug the ignition electrode from
the spark generator
Remove the screw and the
spark generator
ELECTRODES
Tools
5 min
Time
1
Unplug the electrodes
Remove the screws and pull the
electrodes towards you.
49
MAINTENANCE GUIDE
4.3 BURNER
BURNER
Tools
15 min
Time
1
Remove the silencer
Isolate the gas supply. Remove the
four screws and disconnect the
gas pipe from the gas valve
Pull the assembly towards
you
2
Pull the burner toward you
Remove the three screws to free
the burner door
Replace any gaskets that are damaged or showing signs of
deterioration
1. Stainless Steel Burner
1
3
2
2. Ignition electrode
Power Length Venturi
24 KW 104.6 mm Ø 42 mm 30 KW 135.8 mm / 38 KW 167 mm
3. Detection electrode /
50
MAINTENANCE GUIDE
4.4 FAN
FAN
Tools
Time
15 min
1
Remove the three screws to free the
fan.
Remove the combustion
assembly (see 4.3)
Twist the gas valve anti-clockwise to
disengage it from the fan
1. Venturi
2. Gasket
3. Fan
Fan & mixer venturi according to the model
Power Fan Venturi diameter
24 KW
EBM RG 128 45 W Ø 17 mm
EBM RG 128 45 W Ø 21 mm
30 KW
EBM RG 128 45 W Ø 25 mm
38 KW
51
MAINTENANCE GUIDE
4.5 GAS VALVE
GAS VALVE
Tools
Time
15 min
1
Replacement Gas Valves are
not factory set and will need to
be set up (see page 34)
Remove the combustion
assembly (see 4.3)
Twist the gas valve anti-clockwise to
disconnect it from the fan
Bayonet
connection
1. Venturi 4. Inlet test nipple
2. Gas valve 5. Offset adjustment
3. Solenoids 6. Throttle adjustment
52
MAINTENANCE GUIDE
Condensate trap
Maintenance Interval: Annually or after cleaning primary heat exchanger
How : Visual inspection / Clean as necessary / Add water before replacing
Pump
Maintenance Interval: At the first ignition and annually
How: Check that the AAV is open / Visual inspection / Clean as necessary
Plate heat exchanger
Maintenance Interval: As necessary How: To measure specification of DHW performance.
By-pass & Safety valve
Maintenance Interval: Annually How: Visual inspection / Clean as necessary
Central heating filter
Maintenance Interval: Annually How: Visual inspection / Clean as necessary
Flow switch operation
Maintenance Interval: Annually
How: Visual inspection / Clean as necessary / Check flow rate
Expansion vessel
Maintenance Interval: Annually How: Check air pressure is at 1 bar (System drained)
Ignition & detection electrodes
Maintenance Interval: Annually How: Visual inspection / Clean as necessary / Distance from the burner / Ionisation current more than 1 µA
Burner
Maintenance Interval: Annually How: Visual inspection / Clean as necessary
Fan
Maintenance Interval: Annually How : Visual inspection / Clean as necessary
Primary Heat exchanger
Maintenance Interval: Annually How : Visual inspection / Clean as necessary
5 ANNUAL MAINTENANCE
GAS BOILER SYSTEM COMMISSIONING CHECKLIST
CONTROLS
Tick the appropriate boxes
Time and Temperature Control to Heating Room Thermostat and Programmable
Load/Weather Optimum Start
Programmer/Timer
Room Thermostat Compensation Control
Time and Temperature Control to Hot Water Cylinder Thermostat and Programmer/Timer
Combination Boiler
Heating Zone Valves Fitted Not Required
Hot Water Zone Valves Fitted Not Required
Thermostatic Radiator Valves Fitted Not Required
Automatic Bypass to System Fitted Not Required
Boiler Interlock Provided
ALL SYSTEMS
The system has been fl ushed and cleaned in accordance with BS7593 and boiler manufacturer’s instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity
litres
CENTRAL HEATING MODE
Measure and Record:
Gas Rate
m
3
/hr OR
ft
3
/hr
Burner Operating Pressure (if applicable)
mbar OR Gas Inlet Pressure mbar
Central Heating Flow Temperature
°C
Central Heating Return Temperature
°C
COMBINATION BOILERS ONLY
Is the installation in a hard water area (above 200ppm)? Yes No
If yes, has a water scale reducer been fi tted? Yes No
What type of scale reducer has been fi tted?
DOMESTIC HOT WATER MODE Measure and Record:
Gas Rate
m
3
/hr OR
ft
3
/hr
Burner Operating Pressure (at maximum rate) mbar OR Gas Inlet Pressure (at maximum rate) mbar
Cold Water Inlet Temperature
°C
Hot water has been checked at all outlets Yes
Temperature
°C
Water Flow Rate
l/min
CONDENSING BOILERS ONLY
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798 Yes
ALL INSTALLATIONS
If required by the manufacturer, record the following CO
2
% OR CO ppm OR CO/CO
2
Ratio
The heating and hot water system complies with the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
*
All installations in England and Wales must be notifi ed to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certifi cate will then be issued to the customer.
©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
Commissioning Engineer’s Signature
Customer’s Signature
(To confi rm satisfactory demonstration and receipt of manufacturer’s literature)
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
Customer Name Telephone Number
Address
Boiler Make and Model
Boiler Serial Number
Commissioned by (print name) CORGI ID Number
Company Name Telephone Number
Company Address
Commissioning Date
To be completed by the customer on receipt of a Building Regulations Compliance Certifi cate
*
:
Building Regulations Notifi cation Number (if applicable)
!
SERVICE RECORD
It is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Always use the manufacturer’s specifi ed spare part when replacing controls.
SERVICE 1 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 3 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 5 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 7 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 9 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 2 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 4 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 6 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 8 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 10 Date
Energy Effi ciency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
!
55
SHORT LIST
Ind 01 - 07/03/2008
Key N
Description
Manf. Pt.N
Type
Manf. date
from to
E-COMBI
24 30 38
0100 BURNER ASSEMBLY
0110 IGNITION ELECTRODE 61317432
...
0111 IONIZATION ELECTRODE 61317433
...
0112 GASKET D:85-66.5-2.5 61314753
...
0134 ELECTRODE GASKET 60000286
...
0135 COMBUSTION CHAMBER LINING KIT 60000297
...
0136 DOOR GASKET 60000623
...
0400 GAS SECTION
0401 GAS VALVE 60000537
...
0407 FAN ASSY 60000622
...
0500 HYDRAULIC BLOCK
0502 MOTOR - THREE-WAY VALVE 61302483
...
0506 3-WAY SPRING KIT (D.H.W.) 65104314
...
0517 LOW PRESSURE SWITCH 65105090
...
0530 AUTO AIR VENT WITH O-RING 65104703
...
0537 PRESSURE RELIEF VALVE 61312668
...
0538 PUMP 5M 2V 65104319
...
0543 SENSOR (REED) 65104323
...
0589 SECONDARY EXCHANGER 65104333
...
0590 LIP SEAL 61002249
...
0600 ELECTRICAL BOX
0607 IGNITER 61002105-20
...
0615 PRINTED CIRCUIT BOARD 60001129
...
0616 PRINTED CIRCUIT BOARD (DISPLAY) 60001130
...
0625 PRESSURE GAUGE 65104234
...
136
135
112
134
111
110
537
407
401
517
538
530
589
590
502
506
615
607
625
616
SHORT LIST
543
E-COMBI
420010127600 - 02/2008
Commercial subsidiaries: MTS (GB) Limited Professional Team Limited MTS Building Suites 9 & 10, Plaza 256 Hughenden Avenue Blanchardstown Corporate Park 2 High Wycombe Ballycoolin Bucks HP13 5FT Dublin 15 Telephone: (01494) 755600 Telephone: (01) 810 3723 Fax: (01494) 459775 Fax: (01) 810 3727 Internet: www.mtsgroup.com/uk Internet: www.mtsgroup.com/ie E-mail: info@uk.mtsgroup.com E-mail: info@ie.mtsgroup.com Technical Advice: 0870 241 8180 Technical Advice: (01) 437 0121 Customer Service: 0870 600 9888 Customer Service: (01) 437 0121
Loading...