American Power Conversion AP9221EXPX166, AP9221X166 User Manual

MasterSwitch™VM
Power Distribution Unit
AP9221X166
AP9221EXPX166
Installation and
®
Thank You!
Thank you for selecting the (vertical-mount) power distribution unit ( designed for many years of reliable, maintenance-free service. performance electrical power conversion and control products. We hope that you will find this product a valuable, convenient addition to your system.
Please read this manual! It provides important safety, installation, and operating instructions that will help you get the most from your MasterSwitch
APC
is dedicated to the development of high-
Additional Documentation
This Installation and Quick Start Manual and the online User Guide are available on the supplied
site: http://www.apcc.com/ additional information about the following topics related to MasterSwitch
• detailed product description
• current sensing capabilities
• management interfaces
• user accounts
• customizing setup
• outlet control actions
•security
• obtaining customer service
• product information ( policy, specifications)
VM
:
APC
MasterSwitch
VM
unit.
. The online User Guide contains
LEDs
, warranty, life-support
VM
PDU
). It has been
CD
or on our Web
Contents
PreliminaryInformation .....................1
Features of MasterSwitch VM 1
Inventory 2
Please recycle 2
InstallingMasterSwitchVM ..................3
Mounting in a NetShelter enclosure 3
Mounting the controller 5
Hardwiring procedure 7
ConnectingMasterSwitchVM.................8
Caution 8
Setting up a single unit 8
Setting up multiple units 9
QuickConfiguration ......................10
Required configuration 10
Configuring TCP/IP settings 10
Accessing MasterSwitch VM 14
i

Preliminary Information

Features of MasterSwitch
VM
American Power Conversions MasterSwitch
VM
is a vertically-mounted, stand-alone, network-manageable power distribution unit (
PDU
) designed to accommodate a total of 16
outlets: eight individually-managed outlets and eight always-
SNMP
VM
VM
through
interfaces.
include:
on outlets. You can control MasterSwitch available Web, Control Console, or Additional features of MasterSwitch
Independent control of each outlet for:Power On DelayPower Off DelayReboot Duration
Three levels of user access accounts:AdministratorDevice Manager
16
– Outlet User (
independent accounts)
An audible overload alarm to measure current for:overloaduser-set overloaduser-set low load
MD5
Basic and
A sleek, vertical design that occupies no
authentication password security.
U
-space in a rack environment. Includes rack-mount brackets for mounting in an
EIA310-D)19
(
APC
NetShelter®or other standard
-inch rack.
Synchronized switching across units to permit control of redundant-feed devices.
The capability of being daisy-chained in a series of up to four units, thereby providing outlet management control
32
for up to
outlets (with an additional32always-on
outlets).
A versatile design that allows units to be easily hard­wired.
VM
Event Logging of the MasterSwitch
unitslast300
events.
Auto-configuration feature, allowing customized
ASCII
configuration of all units from one
text file.
Continued on next page
1
Preliminary Information
continued

Inventory

MasterSwitch
VM(AP9221X166
items:
Item Part Number Quantity
MasterSwitch
MasterSwitchVMController with a pre-installed Web/
SNMP
Communication cable
Configuration cable
CD-ROM
documentation and the Management Card Wizard
Brackets for the unit with 14 flat-head screws
Brackets for the controller with 4 flat-head screws
Installation and Quick Start Manual
Warranty registration card
VM
unit
SmartSlot Card
containing product
) comes with the following
AP9221EXPX166
AP9221NX166
607-0035A
940-0024
991-1055C
870-8215
870-8213 and 870­8183
990-6020A
N/A
1
1
1
1
1
3
2
1
1

Please recycle

2
The shipping materials for MasterSwitch
VM
are recyclable. Please save them for later reuse or dispose of them appropriately.
Installing MasterSwitch
VM

Mounting in a NetShelter enclosure

MasterSwitch VM comes with rack-mount brackets for mounting in an
EIA310-D)19
(
1. Align the brackets (provided) with the holes on the rear of the unit.
2. Attach the brackets to the rear of the unit, as shown, using 4 flat-head screws (provided) for each bracket.
3. Choose a suitable location for the unit. The figure on page 4 shows the unit mounted in four different locations in the enclosure.
Note: To avoid interfering with shelves or equipment, install
the unit so that it hangs on the outside edge of the vertical rail. The figure on page 4 and the suggestions below illustrate how to orient the brackets with the vertical mounting rail.
APC
NetShelter enclosure or other standard
-inch rack. To mount in an enclosure:
To install the unit in the rear of the enclosure: Adjust the back rail so that the rear door will close. Some equipment that you have installed may also make it necessary for you to adjust the front rail as well.
To install the unit on a side of the enclosure: Move the horizontal cross members to the highest and lowest positions on the vertical mounting rails.
To install the unit into an expansion enclosure:Move the baying brackets from the highest and lowest positions on the rail (if they have not been moved since shipping) and then move the horizontal cross members to the highest and lowest positions on the vertical rails.
Continued on next page
3
Installing MasterSwitch VM
Mounting in a NetShelter enclosure, continued
continued
4. Insert a caged nut above and below a notched hole on a vertical mounting rail at the highest point in your chosen location.
5. Align the mounting holes of the top bracket on the unit with the caged nuts you installed in Step 4.
Continued on next page
4
Installing MasterSwitch VM
continued
Mounting in a NetShelter enclosure, continued

Mounting the controller

6. Insert two mounting screws (provided with the enclosure) and secure the top bracket to the enclosure.
7. Insert two caged nuts above and below a notched hole on the vertical mounting rail where the middle and bottom brackets align with the rail.
8. Insert two mounting screws (provided with the enclosure) where the middle and bottom brackets align with the rail, and secure the brackets to the enclosure.
To complete installation of MasterSwitchVM, install the MasterSwitch enclosure. To mount the controller in an enclosure:
1. Remove the rubber feet from the bottom of the controller.
2. Attach the brackets (APC part numbers 870-8213 and 870-8183) to the controller using four flat-head screws (provided).
VM
Controller on a flat surface or in an
Continued on next page
5
Installing MasterSwitch VM
continued
Mounting the controller, continued
3. Insert caged nuts on the vertical mounting rails at your chosen location.
4. Align the controllers brackets with the caged nuts that youinsertedinStep3.
5. Insert mounting screws (provided with enclosure) and tighten.
Continued on next page
6
Installing MasterSwitch VM
continued

Hardwiring procedure

1. Make sure that the unit is powered off.
2. Unplug any attached equipment to prevent damage if a mistake is made during wiring.
3. Remove the inspection cover on the power inlet end of the unit by removing the top two screws and sliding the inspection cover off of the unit.
4. Loosen the two screws and remove the nuts that are used to attach the power cord's wires to the termination block.
5. Remove the power inlet end cap by removing the remaining two bottom screws and lifting the end cap off of the unit.
6. Locate the provided hardwiring end cap (
870-8209
7. Attach a 3/4" conduit termination to the hardwiring end cap.
8. Attach the hardwiring end cap assembly to the end of the unit, using the screws removed in Step 5.
9. Attach wires to the terminal block as shown in the figure below. Attaching the wires is easier to do if you back the terminal block screws out several turns.
).
Note: The wires should be attached as shownfrom
the bottom to the top: green, white, black.
APC
part number
10. Replace the inspection cover with the screws that were removedinStep3.
11. Power the unit on, observing the MasterSwitch LED on the opposite end. If the unit is connected properly, the LED will illuminate.
12. Power the unit off and reattach your equipment to the MasterSwitch
VM
outlets.
VM
status
7
Connecting MasterSwitch
VM

Caution

Setting up a single unit

MasterSwitch Therefore,
VM
does not provide power protection.
APC
does not recommend plugging the unit directly
into any unprotected power source, such as a wall outlet.
1. Connect the power cord of each device you wish to connect to the outlets on the front of the unit.
2. Connect the
10
Base-Tnetwork port located on the rear panel of the controller to the network, using an appropriate cable.
3. Connect the front panel to the
RJ-11
port labeled To
RJ-11
port labeled In on the unit, using
the provided communication cable (
0035A
).
PDU
on the controller
APC
part number
607-
4. Plug the unit into a protected power source.
Continued on next page
8
Connecting MasterSwitch VM
continued

Setting up multiple units

1. Follow steps 1–3 listed Setting up a single uniton page 8 for the first unit in your configuration.
2. For each succeeding unit to be connected, refer to the figure on page 9 and follow the steps below:
a. Insert one end of a communication cable (
number the unit.
b. Insert the other end of the communication cable into the
RJ-11
607-0035A
port labeled In on the succeeding unit.
)intothe
RJ-11
port labeled Out on
APC
part
3. Plug each unit into a protected power source.
Note: You can also connect AP9222 units to
AP9221EXPX166 units in a daisy-chain configuration.
9

Quick Configuration

Required configuration

Configuring TCP/IP settings

You must configure the network settings of MasterSwitch
VM
before it can operate on a network. The required settings are:
IP
address of MasterSwitch
VM
Subnet Mask
IP
address of the default Gateway
After you have configured MasterSwitch
VM
network settings, no further configuration is required. The remaining MasterSwitch
VM
properties are pre-configured at the factory. However, these properties may not be appropriate for your application. See the chapter entitled Managing MasterSwitch
VM
in the User Guide (usrguide.pdf) for more details.
Choose the configuration method that matches your environment:
If you are using Windows Windows
NT
,see“Through the Management Card
95
,Windows98,or
Wizardon page 11.
If you are not using Windows or require direct serial configuration, see Serially through the Control Consoleon page 11.
If you are a network administrator using
BOOTP
,see
Over the Network by BOOTPon page 12.
If you are a network administrator and have access to a
computer connected to the local subnet, see Over the Network by ARPon page 13
10
Continued on next page
Quick Configuration
continued
Configuring TCP/IP settings, continued
Through the Management Card Wizard. The MasterSwitch
VM
controller contains a management card that provides the network interface. The Management Card Wizard provides a quick way to configure all management card settings, including TCP/IP settings. To access the Management Card Wizard, run the program setup.exe on the CD-ROM supplied with MasterSwitch
VM
on a Windows 95, Windows 98, or Windows NT 4.0 workstation and follow the on-screen instructions.
Serially through the Control Console. If you are not using a Windows platform or require direct serial configuration, use the Configuration port to configure MasterSwitch management card
TCP/IP
settings:
1. Connect the supplied configuration cable ( number
940-0024
) to an available serial port on your
VM
APC
part
computer and to the Configuration port on the front panel of the controller.
2. Disable PowerChute plus,
UNIX
Respond, or other service that may be using the serial port on the computer.
3. Run a terminal emulator such as, Windows HyperTerminal.
4. Configure the appropriate serial port with the following settings:
2400
bps, no parity, 8 data bits, 1 stop bit, and
no flow control.
Note: Some terminal emulators, such as
HyperTerminal, require that you disconnect and reconnect in order for the new serial settings take effect.
5. From your computer, press E
NTER
until the user name
prompt appears.
Continued on next page
11
Quick Configuration
continued
Configuring TCP/IP settings, continued
6. Enter the default user name and password: apc, both lowercase.
7. Once the Main menu appears, choose Network.
8. From the Network menu, choose TCP/IP.
9. Within the
a. Disable
TCP/IP
BOOTP
menu:
b. Accept changes.
c. Set a valid
IP
address, Subnet Mask and default Gate-
way for your network.
d. Accept changes.
SC
e. Press
E
until the Main menu appears.
f. From the Main menu, select Logout.
Note: The new settings will not take effect until you log
out.
Over the Network by
BOOTP
Use a
server to configure MasterSwitch
BOOTP.BOOTP
is enabled by default.
VM TCP/IP
settings:
1. Enter the MasterSwitch
VM MAC
address,IPaddress, Subnet Mask, default Gateway, and optional boot-up filename.
Note: The
MAC
address can be found on the Quality Assurance slip, on the bottom of the management card, and on the
TCP/IP
menu from the Control
Console.
2. The
BOOTP
MasterSwitch MasterSwitch
TFTPorFT P
a
BOOTP
server. MasterSwitch
server will provide network settings to
VM
. If a boot-up file name was specified,
VM
will attempt to transfer that file from
serveronthesamecomputerasthe
VM
will assume all settings specified in the boot-up file. Otherwise, MasterSwitch Telnet, Web, or
VM
can be configured remotely using the
SNMP
interfaces.
Note: You must use the Management Card Wizard to
create the boot-up file.
12
Continued on next page
Quick Configuration
continued
Configuring TCP/IP settings, continued
Over the Network by ARP. (Address Resolution Protocol) To configure MasterSwitch
1. Connect the unit to the network.
2. From a command prompt on a computer connected to the local subnet, type arp -s ip_addr_card mac_card. See the example below:
arp -s 159.215.240.22 00-c0-b7-78-ad-
Note: The
Assurance slip, on the Control Console, and on a sticker on the bottom of the unit.
3. Type telnet ip_addr. See the example below:
telnet 159.215.240.22
The default user name and password are both apc. Configure the correct Subnet Mask and default Gateway in the section of the Network menu.
VM TCP/IP
MAC
address can be found on the Quality
settings using
90
TCP/IP
Continued on next page
ARP
:
menu from the
TCP/IP
13
Quick Configuration
continued
Accessing MasterSwitch
VM
Additional information
You can access MasterSwitch Telnet, or
SNMP
. See the appropriate paragraph below for
VM
using a Web browser,
details.
ThroughaWebbrowser.
1. From your Web browser, enter the System
DNS
name, if configured, of the MasterSwitchVMunit.
2. LogontoMasterSwitch
VM
. The default User Name
IP
address or
andPasswordareapc (lowercase).
Through Telnet.
1. From your Telnet session, enter the System IP address of the MasterSwitch
2. LogontoMasterSwitch
VM
unit.
VM
. The default User Name
andPasswordareapc (lowercase).
Through SNMP.
You can access MasterSwitch
VM
using
SNMP
. The default read-only community name is public. The default read/write community name is private.
See the online User Guide for additional information about the following topics related to MasterSwitch
VM
:
detailed product description
current sensing capabilities
management interfaces
user accounts
customizing setup
outlet control actions
security
obtaining customer service
LEDs
product information (
, warranty, life-support
policy, specifications)
14

APC Worldwide Customer Support

Customer support for this or any other APC product is available at no charge in any of the following ways:
Visit the APC Web site to find answers to frequently asked questions (FAQs), to access documents in the APC Knowledge Base, and to submit customer support requests.
http://www.apcc.com (Corporate Headquarters)
Connect by links to APC Web pages for specific countries and regions, each of which provides customer support information.
http://www.apcc.com/support
Submit customer support requests.
Contact an APC Customer Support center by telephone or e-mail.
Regional centers:
.
APC Headquarters (U.S. and Canada)
/
(1) (800) 800-4272 (toll free)
Latin America
Europe, Middle East, Africa
Japan
Local, country-specific centers: go to
(1) (401) 789-5735 (United States) apctchla@apcc.com
(353) (91) 702020 (Ireland) apceurtech@apcc.com
(03) 5434-2021 jsupport@apcc.com
http://www.apcc.com/support/contact
for contact information.
Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.
Entire contents copyright © 2000 American Power Conversion. All rights reserved. Reproduction
in whole or in part without permission is prohibited. APC, MasterSwitch, and NetShelter are trademarks or
registered trademarks of American Power Conversion Corporation. All other trademarks,
product names, and corporate names are the property of their respective
owners and are used for informational purposes only.
990-6020A 08/2000
Loading...