APC AP7554 User Manual

Basic Rack PDU

Overview

The American Power Conversion (APC Rack Power Distribution Unit (PDU) distributes power to devices in the rack.

Outlets. The Rack PDU has twenty (20)

Power cord. The 10-foot (3.05-meter) power cord

terminates with a IEC- 309 16A connector.

AP7554

®
) Basic

Specifications for AP7554

Electrical

Input connector IEC-309 16A plug
Output connectors (20) IEC-320-C13
Nominal input voltage 230 VAC
Acceptable input voltage ± 10% of nominal voltage
Input frequency 47– 63 Hz
Cord length 10ft (3.05 m)
(4) IEC-320-C19 outlets

Physical

Dimensions (H × W × D)
Shipping dimensions (H × W × D)
Weight 12.25 lb (5.56 kg)
Shipping weight 14.25lb (6.46 kg)
63.75× 2.19 ×1.73 in (161.92 × 5.56 × 4.39 cm)
84.00× 6.00 ×5.00 in (213.36× 15.24×12.70 cm)

Environmental

Maximum elevation (above MSL)
Operating Storage
10,000 ft (3 000m) 50,000 ft (15 000m)
Temperature
Operating Storage
Humidity
Operating Storage
–5 to 45° C (23 to 115°F) –25 to 65° C (–13 to 149°F)
5 – 95% RH, non-condensing 5 – 95% RH, non-condensing

Compliance

Safety verifications VDE 0805, CE, EN 60950-1,
990-2208-001 10/2004
IEC 60950-1
*990-2208-001*
Loading...