Basic Rack PDU
Overview
The American Power Conversion (APC
Rack Power Distribution Unit (PDU) distributes
power to devices in the rack.
Outlets. The Rack PDU has twenty (20)
IEC-320- C13 outlets and four (4) IEC-320 - C19
outlets.
Power cord. The 10-foot (3.05-meter) power cord
terminates with a IEC- 309 16A connector.
AP7554
®
) Basic
Specifications for AP7554
Electrical
Input connector IEC-309 16A plug
Output connectors (20) IEC-320-C13
Nominal input voltage 230 VAC
Acceptable input voltage ± 10% of nominal voltage
Input frequency 47– 63 Hz
Cord length 10ft (3.05 m)
(4) IEC-320-C19 outlets
Physical
Dimensions
(H × W × D)
Shipping dimensions
(H × W × D)
Weight 12.25 lb (5.56 kg)
Shipping weight 14.25lb (6.46 kg)
63.75× 2.19 ×1.73 in
(161.92 × 5.56 × 4.39 cm)
84.00× 6.00 ×5.00 in
(213.36× 15.24×12.70 cm)
Environmental
Maximum elevation (above
MSL)
Operating
Storage
10,000 ft (3 000m)
50,000 ft (15 000m)
Temperature
Operating
Storage
Humidity
Operating
Storage
–5 to 45° C (23 to 115°F)
–25 to 65° C (–13 to 149°F)
5 – 95% RH, non-condensing
5 – 95% RH, non-condensing
Compliance
Safety verifications VDE 0805, CE, EN 60950-1,
990-2208-001 10/2004
IEC 60950-1
*990-2208-001*