Basic Rack PDU
Overview
The American Power Conversion
PDU distributes power to devices in the rack.
Outlets. The Rack PDU has twenty (20)
IEC-320- C13 outlets, and four (4) IEC-320 - C19
outlets.
Power cord. The 3-foot (0.91-meter) power cord
terminates with a IEC- 309 16 A connector.
AP7551
®
Basic Rack
Specifications for AP7551
Electrical
Input connector IEC-309 16 A plug
Output connectors (20) IEC-320-C13,
Nominal input voltage 230 VAC
Acceptable input voltage ± 10% of normal voltage
Input frequency 47– 63 Hz
Cord length 0.91 m (3 ft)
(4) IEC-320-C19 outlets
Physical
(H × W × D) 161.92× 5.56×4.39 cm
Shipping dimensions
(H × W × D)
Weight 5.56 kg (12.25 lb)
Shipping weight 6.46 kg (14.25 lb)
(63.75 × 2.19×1.73 in)
213.36× 15.24×12.7 cm
(84.00 × 6.00×5.00 in)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
15 000 ft ( 4500 m)
50 000 ft (15 000 m)
Temperature
Operating
Storage
Humidity
Operating
Storage
–5 to 45° C (23 to 115° F)
–25 to 65° C (–13 to 149° F)
5 – 95% RH non-condensing
5 – 95% RH non-condensing
Compliance
Safety verification VDE 0805, CE, EN 60950,
990-1940-001 07/2004
IEC 60950
*990-1940-001*