Agilent Technologies 4UHV User Manual

Agilent 4UHV Ion Pump Controller User Manual
A
gilent 4UHV Ion Pump
Controller
Models 929-9010, 929-9011, 929-9020, 929-9021, 929-9022, 929-9101, 929-9200, 929-9201, 929-9210, 929-9211, 929-9212, 929-9213, 929-9400, 929-9401, 929-9402
Manuale di Istruzioni Bedienungshandbuch Notice de Mode D’Emploi User Manual
87-900-137-01 (A)
03/2011
Notices
© Agilent Technologies, Inc. 2011
No part of this manual may be reproduced in any form or by any means (including electronic storage and retrieval or translation into a foreign language) without prior agreement and written consent from Agilent Technologies, Inc. as governed by United States and international copyright laws.
Manual Part Number
Publication Number: 87-900-137-01 (A)
Edition
Edition 03/2011
Printed in ITALY
Agilent Technologies Italia S.p.A.
Vacuum Products Division
Via F.lli Varian, 54
10040 Leinì (TO)
ITALY
Warranty
The material contained in this document is provided “as is,” and is subject to being changed, without notice, in future editions. Further, to the maximum extent permitted by applicable law, Agilent disclaims all warranties, either express or implied, with regard to this manual and any information contained herein, including but not limited to the implied warranties of merchantability and fitness for a particular purpose. Agilent shall not be liable for errors or for incidental or consequential damages in connection with the furnishing, use, or performance of this document or of any information contained herein. Should Agilent and the user have a separate written agreement with warranty terms covering the material in this document that conflict with these terms, the warranty terms in the separate agreement shall control.
Technology Licenses
The hardware and/or software described in this document are furnished under a license and may be used or copied only in accordance with the terms of such license.
Restricted Rights Legend
If software is for use in the performance of a U.S. Government prime contract or subcontract, Software is delivered and licensed as “Commercial computer software” as defined in DFAR 252.227-7014 (June
1995), or as a “commercial item” as defined in FAR 2.101(a) or as “Restricted computer software” as defined in FAR 52.227-19 (June 1987) or any equivalent agency regulation or
contract clause. Use, duplication or disclosure of Software is subject to Agilent Technologies’ standard commercial license terms, and non­DOD Departments and Agencies of the U.S. Government will receive no greater than Restricted Rights as defined in FAR 52.227-19(c)(1-2) (June
1987). U.S. Government users will receive no greater than Limited Rights as defined in FAR 52.227-14 (June
1987) or DFAR 252.227-7015 (b)(2) (November 1995), as applicable in any technical data.
Trademarks
Windows and MS Windows are U.S. registered trademarks of Microsoft Corporation.
Safety Notices
CAUTION
A CAUTION notice denotes a hazard. It calls attention to an operating procedure, practice, or the like that, if not correctly performed or adhered to, could result in damage to the product or loss of important data. Do not proceed beyond a CAUTION notice until the indicated conditions are fully understood and met.
WARNING
A WARNING notice denotes a hazard. It calls attention to an operating procedure, practice, or the like that, if not correctly performed or adhered to, could result in personal injury or death. Do not proceed beyond a WARNING notice
indicated conditions are
until the fully understood and met.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
4UHV Ion Pump Controller
4UHV Ion Pump Controller
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 3/104
4UHV Ion Pump Controller
4/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Contents
Contents
1 Istruzioni per l’uso 7
Informazioni Generali 8
Immagazzinamento 9
Preparazione per l’installazione 10
Installazione 11
Uso 13
Manutenzione 18
2 Gebrauchsanleitung 19
Allgemeines 20
Lagerung 21
Vor der Installation 22
Installation 23
Gebrauch 25
Wartung 30
3 Mode d’emploi 31
Indications Generales 32
Emmagasinage 33
Preparation pour l’Installation 34
Installation 35
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 5/104
Contents
Utilisation 37
Entretien 42
4 Instructions for Use 43
General Information 44
Storage 45
Prior to Installation 46
Installation 47
Usage 49
Maintenance 54
5 Technical Information 55
4UHV Controller Description 57
Specifications 59
Operating Mode 65
Start-Up 67
Serial 73
Display and Menus 91
Orderable Parts 98
6/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Agilent 4UHV Ion Pump Controller User Manual

1 Istruzioni per l’uso

Informazioni Generali 8 Immagazzinamento 9 Preparazione per l’installazione 10 Installazione 11 Uso 13 Accensione del controller dal
pannello frontale (modalità LOCAL) 15 Manutenzione 18 Smaltimento 18
Traduzio
ne delle istruzioni originali
7/104
Istruzioni per l’uso
A
1

Informazioni Generali

Informazioni Generali
Questa apparecchiatura è destinata ad uso professionale. L’utente deve leggere attentamente il presente Manuale di istruzioni ed ogni altra informazione addizionale fornita dalla Agilent prima dell’utilizzo dell’apparecchiatura. La Agilent declina ogni responsabilità dovuta alla mancata osservanza totale o anche parziale delle istruzioni fornite in questo documento, all’uso improprio dell’apparecchiatura da parte di personale non addestrato, all’esecuzione di interventi non autorizzati o alla mancata osservanza delle specifiche normative nazionali.
Nei paragrafi seguenti sono riportate tutte le informazioni necessarie a garantire la sicurezza dell’operatore durante l’utilizzo dell’apparecchiatura. Nel appendice “Technical Information” vengono fornite delle informazioni dettagliate.
Questo manuale utilizza le seguenti convenzioni:
ATTENZIONE!
VVERTENZA!
NOTA
8/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
I messaggi di attenzione sono visualizzati prima di procedure che, se non osservate, potrebbero causare danni all’apparecchiatura.
I messaggi di avvertenza attirano l’attenzione dell’operatore su una procedura o una pratica specifica che, se non eseguita in modo corretto, potrebbe provocare gravi lesioni personali.
Le note contengono informazioni importanti estrapolate dal testo.

Immagazzinamento

Per trasportare e immagazzinare il controller occorre osservare le seguenti condizioni ambientali:
Temperatura: da -20 °C a +70 °C
Umidità relativa: da 0 a 95% (senza condensa)
Istruzioni per l’uso
Immagazzinamento
1
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 9/104
Istruzioni per l’uso
1

Preparazione per l’installazione

Preparazione per l’installazione
Il controller viene fornito in un imballo protettivo speciale; nel caso in cui si presentassero segni di danni che potrebbero essere stati causati durante il trasporto, contattare l’ufficio vendite locale.
Durante l’operazione di disimballo, prestare particolare attenzione a non lasciar cadere il controller e a non sottoporlo ad urti.
Il materiale dell’imballo è completamente riciclabile e risponde alla direttiva CEE 85/399 per la tutela dell’ambiente.
Figura 1 Imballo del controller
10/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
A

Installazione

Istruzioni per l’uso
Installazione
1
VVERTENZA!
ATTENZIONE!
Per la sicurezza dell’operatore il controller 4UHV deve essere alimentato con un cavo di alimentazione a 3 fili dotato di una spina approvata a livello internazionale. Utilizzare questo cavo e spina insieme ad una presa adeguatamente connessa a terra per evitare scosse elettriche e soddisfare i requisiti delle norme CE. Le alte tensione che si sviluppano nel controller possono provocare gravi lesioni o la morte.
Dopo lo spegnimento dell’unità rimane dell’energia residua all’interno del controller per un po’ di tempo.
Attendere circa 1 minuto per essere sicuri che l’energia residua sia stata dissipata.
Il controller può essere utilizzato sia come unità da tavolo che come modulo installato in un rack. In ogni caso deve essere posizionato in modo tale che l’aria possa circolare liberamente attraverso i fori di areazione presenti sulla copertura.
Nel caso in cui il controller viene utilizzato come modulo rack, DEVE essere installato in un’adattatore alto quattro unità rack per evitare che cada all’interno del rack stesso (vedere la tabella delle parti ordinabili). Il pannello frontale del controller 4UHV non è previsto per reggere il peso dell’unità.
Non installare o utilizzare il controller in ambienti esposti ad agenti atmosferici (pioggia, neve, ghiaccio), nella presenza di polvere, gas corrosivi o in ambienti esplosivi o ad alto rischio di infiammabilità.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 11/104
Istruzioni per l’uso
1
Installazione
ATTENZIONE!
NOTA
ATTENZIONE!
Il controller 4UHV appartiene alla seconda categoria di installazione (o sovratensione) prevista dalla normativa EN 61010-1. Connettere quindi il dispositivo ad una linea di alimentazione che soddisfi tale categoria.
Il controller 4UHV ha dei connettori per gli ingressi/uscite e per la comunicazione seriale che devono essere connessi ai circuiti esterni in modo che nessuna parte sotto tensione sia accessibile. Assicurarsi che l’isolamento del dispositivo connesso al controller 4UHV abbia un isolamento adeguato anche in condizione di guasto singolo come previsto dalla normativa EN 61010-1.
Nel caso in cui il controller viene installato in un rack, rimuovere i quattro piedini in modo che venga posizionato con almeno 30 mm di spazio sotto e sopra.
In casi rari di guasto il controller potrebbe emettere fumo. Se il cliente usa il controller in camere pulite è necessario prevedere adeguate protezioni per evitare di contaminare l’ambiente con l’eventuale fumo.
Durante il funzionamento, occorre che siano rispettate le seguenti condizioni ambientali:
Temperatura: da 0 °C a +40 °C
Umidità relativa: 0 - 90% (senza condensa)
12/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
A
Uso
Istruzioni per l’uso
Uso
In questo paragrafo vengono riportate le principali procedure operative. Per ulteriori informazioni e per le procedure riguardanti collegamenti o particolari opzioni fare riferimento al paragrafi “UTILIZZO” nell’appendice “Technical Information”.
Prima di utilizzare il controller effettuare tutti i collegamenti elettrici e fare riferimento al manuale della pompa collegata.
1
VVERTENZA!
Accendere i canali di alta tensione solo se connessi alle pompe ioniche tramite gli appositi cavi di alta tensione dotati del cavo di interlock.
L’uso del controller è inteso con cavo di alta tensione provvisto di interlock.
4UHV
Figura 2 Collegamenti delle masse
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 13/104
Istruzioni per l’uso
1
Uso
NOTA
Se si vuole utilizzare un cavo HV senza interlock nel sacchetto accessori è fornito un apposito kit di cavetti per interlock preassemblati. Con questo utilizzo si perde la funzionalità di sicurezza offerta dall’utilizzo dell’interlock.
Fare riferimento alla seguente figura per montare correttamente il cavo di interlock fornito nel sacchetto accessori, qualora si voglia rinunciare al cavo di alta tensione dotato di interlock.
Figura 3
NOTA
14/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
L’interlock del cavo viene chiuso sulla massa della pompa. Se il collegamento è interrotto l’alta tensione viene disabilitata.
L’interlock del cavo viene chiuso sulla massa della pompa. Se il collegamento è interrotto l’alta tensione viene disabilitata. Per collegare il controller alla pompa, utilizzare un cavo HV dotato di interlock (vedere nelle parti ordinabili).
Istruzioni per l’uso
Uso
Nella figura “Collegamenti delle masse” sono riportati i corretti
legamenti delle masse, del cavo HV tra il controller e la pompa e
col del cavo di interlock.
1
ATTENZIONE!

Accensione del controller dal pannello frontale (modalità LOCAL)

NOTA
Se si monta il cavo di interlock fornito nel sacchetto accessori fare molta attenzione affinchè nessuna parte cada accidentalmente all’interno del controller.
Per accendere l’alta tensione (HV) occorre che l’interlock del cavo HV (cable interlock) sia chiuso (connettore inserito).
Procedere come segue per alimentare il controller e abilitare la tensione sui connettori di alta tensione (H.V.):
Spegnere il controller.
Collegare il cavo HV e l’interlock del cavo H.V. nei relativi
connettori sul pannello posteriore.
Selezionare la modalità LOCAL premendo per breve tempo il
tasto “MODE” fino a quando appare sul display la scritta LOCAL.
Tenere premuto il pulsante HV ON/OFF (2) mentre si preme il
pulsante HV-x (3,4,5,6) dove x è il numero del canale che si vuole accendere o spegnere.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 15/104
Istruzioni per l’uso
1
Uso
(2)
(1) (3) (4)
(5) (6)
Figura 4 Front Panel 4UHV Ion Pump Controller
Figura 5 Rear Panel 4UHV Ion Pump Controller
Per spegnere i canali HV:
Tenere premuto il pulsante HV ON/OFF (2) mentre si preme il pulsante HV-x (3,4,5,6) dove x è il numero del canale che si vuole accendere o spegnere.
Per ulteriori dettagli sull’uso del controller e sulla descrizione delle informazioni del display fare riferimento alla sezione “Technical Information”.
16/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Istruzioni per l’uso
A
Uso
1
VVERTENZA!
In condizioni di emergenza per spegnere l’unità e tutti i canali alta tensione disattivare l’interruttore generale (1) posto sul pannello anteriore.
Mettendo in off l’interruttore generale si spegnerà l’unita HV.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 17/104
Istruzioni per l’uso
1

Manutenzione

Manutenzione
Il controller 4UHV non richiede alcun intervento di manutenzione. Qualsiasi tipo di intervento sull’unità deve essere eseguito da personale tecnico autorizzato. In caso di guasto è possibile usufruire del servizio di riparazione Agilent o del "Agilent advanced exchange service", che permette di ottenere un controller rigenerato in sostituzione di quello guasto.
Qualora un controller dovesse essere rottamato, procedere nel rispetto delle normative nazionali specifiche.

Smaltimento

Significato del logo "WEEE" presente sulle etichette. Il simbolo qui sotto riportato è applicato in ottemperanza alla direttiva CE denominata "WEEE". Questo simbolo (valido solo per i paesi della Comunità Europea) indica che il prodotto sul quale è applicato, NON deve essere smaltito insieme ai comuni rifiuti domestici o industriali, ma deve essere avviato ad un sistema di raccolta differenziata. Si invita pertanto l'utente finale a contattare il fornitore del dispositivo, sia esso la casa madre o un rivenditore, per avviare il processo di raccolta e smaltimento, dopo opportuna verifica dei termini e condizioni contrattuali di vendita.
18/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Agilent 4UHV Ion Pump Controller User Manual

2 Gebrauchsanleitung

Allgemeines 20 Lagerung 21 Vor der Installation 22 Installation 23 Gebrauch 25 Einschalten des Controllers vo
Schalttafel (LOKAL-Modus) 28 Wartung 30 Entsorgung 30
etzung der Originalanleitungen
Übers
n der vorderen
19/104
Gebrauchsanleitung
2

Allgemeines

Allgemeines
Dieser Apparat ist für Fachbetriebe bestimmt. Vor Gebrauch sollte der Benutzer dieses Handbuch sowie alle weiteren mitgelieferten Zusatzdokumentationen genau lesen. Bei Nichtbeachtung - auch teilweise - der enthaltenen Hinweise, unsachgemäßem Gebrauch durch ungeschultes Personal, nicht autorisierten Eingriffen und Missachtung der einheimischen, hier zur Geltung kommenden Bestimmungen übernimmt die Firma Agilent keinerlei Haftung.
In den folgenden Abschnitten sind alle erforderlichen Informationen für die Sicherheit des Bedieners bei der Anwendung des Geräts aufgeführt. Detaillierte technische Informationen sind im Anhang " Technical Information " enthalten.
In dieser Gebrauchsanleitung werden Sicherheitshinweise folgendermaßen hervorgehoben:
VORSICHT!
WARNUNG!
HINWEIS
20/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Die Vorsichtshinweise vor bestimmten Prozeduren machen den Bediener darauf aufmerksam, dass bei Nichteinhaltung Schäden an der Anlage entstehen können.
Die Warnhinweise lenken die Aufmerksamkeit des Bedieners auf bestimmte Vorgänge oder Praktiken, die bei unkorrekter Ausführung schwere Verletzungen hervorrufen können.
Die HINWEISE enthalten wichtige Informationen, die im Text hervorgehoben werden.

Lagerung

Gebrauchsanleitung
Lagerung
Bei Transport und Lagerung der Controller müssen folgende Umgebungsbedingungen eingehalten werden:
Temperatur: -20 °C bis +70 °C
Rel. Luftfeuchtigkeit: 0-95 % (nicht kondensierend)
2
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 21/104
Gebrauchsanleitung
2

Vor der Installation

Vor der Installation
Der Controller wird mit einer speziellen Schutzverpackung geliefert. Eventuelle Transportschäden müssen sofort der zuständigen örtlichen Verkaufsstelle gemeldet werden.
Das Verpackungsmaterial muss korrekt entsorgt werden. Es ist vollständig recyclebar und entspricht der EG-Richtlinie 85/399 für Umweltschutz.
Abbildung 1 Verpackung des Controllers
22/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Installation

Gebrauchsanleitung
Installation
2
WARNUNG!
VORSICHT!
Zur Sicherheit des Controller-Bedieners muss der 4UHV an ein 3-Draht­Speisekabel mit einem international anerkannten Stecker angeschlossen sein. Dieses Kabel und dieser Stecker müssen an eine angemessen geerdete Steckdose angeschlossen sein, um Stromschläge zu vermeiden und den Anforderungen der CE-Normen gerecht zu werden. Die Hochspannungen, die im Controller entstehen, können schwere Verletzungen oder den Tod verursachen.
Nach Ausschalten des Geräts bleibt noch einige Zeit lang Reststrom im Controller.
Warten Sie etwa 1 Minute, um sicher zu sein, dass der restliche Strom dissipiert ist.
Der Controller kann auf einen Tisch oder ein Gestell montiert werden. In beiden Fällen muß eine ungehinderte Zirkulation der Kühlluft durch die im Gehäuse vorne und unten eingelassen Luftöffnungen gewährleistet sein.
Wenn der Controller in einem Gestell montiert wird, MUSS er in einer vier Rackeinheiten hohen Adapter-Einheit installiert werden, um zu vermeiden, daß der Controller nicht in das Gestell fällt (siehe dazu Tabelle der bestellbaren Zubehörteile). Die vordere Schalttafel des 4 HV-Controllers ist nicht geeignet, das gesamte Gewicht der Einheit zu tragen.
Der Controller darf nicht in Umgebungen installiert u/o benutzt werden, die Witterungseinflüssen (Regen, Frost, Schnee), Staub und aggressiven Gasen ausgesetzt sind und in denen Explosions- und erhöhte Brandgefahr besteht.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 23/104
Gebrauchsanleitung
2
Installation
VORSICHT!
HINWEIS
VORSICHT!
Der Controller 4UHV gehört zu der zweiten Einbaukategorie (oder auch Überspannung), die von der Norm EN 61010-1 geregelt ist. Schließen Sie daher das Gerät an eine Stromleitung an, die dieser Kategorie gerecht wird.
Der Controller 4UHV hat Anschlüsse für die Ein-/Ausgänge und die Serienkommunikation, die an externe Kreisläufe angeschlossen sein müssen, so dass man zu keinem unter Strom stehenden Teil Zugriff hat. Vergewissern Sie sich, dass die Isolierung des Gerätes, das an den Controller 4UHV angeschlossen ist, auch bei Einzelstörungen, wie sie von der Vorschrift EN 61010-1 vorgesehen sind, angemessen isoliert ist.
Wenn der Controller in einem Gestell installiert werden soll, müssen alle vier Füße abmontiert und über- und unterhalb wenigstens 30 mm (1,2 Zoll) Platz gelassen werden.
In seltenen Fällen könnte der Controller bei Störungen Rauch ausstoßen. Wenn der Controller in sauberen Räumlichkeiten verwendet wird, muss er mit angebrachten Schutzvorrichtungen versehen werden, um zu verhindern, dass die Räumlichkeiten durch den Rauch verschmutzt werden.
Während des Betriebs müssen folgende Umgebungsbedingungen eingehalten werden:
Temperatur: 0 °C to +40 °C
Rel. Luftfeuchtigkeit: 0 - 90 % (nicht kondensierend)
24/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Gebrauch

Gebrauchsanleitung
Gebrauch
In diesem Kapitel sind die wichtigsten Betriebsvorgänge aufgeführt. Für weitere Hinweise bezüglich Anschluß und Montage des bestellbaren Zubehörs verweisen wir auf das Kapitel "Gebrauch" im Anhang zu "Technical Information". Vor Benutzung des Controllers müssen sämtliche elektrischen Anschlüsse ausgeführt und die Betriebsanleitung der angeschlossenen Pumpe durchlesen werden.
2
WARNUNG!
Schalten Sie die Hochspannungsleitungen erst ein, wenn diese mit Hilfe der dafür bestimmten Hochspannungskabel des Interlock-Kabels an die Ionenpumpen angeschlossen sind.
Der Gebrauch des Controllers muss unter Verwendung eines Hochspannungskabels mit Interlock erfolgen.
4UHV KABEL PUMPE
LEITUNG
PUMPEN-ERDE
Abbildung 2 Erdung
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 25/104
Gebrauchsanleitung
2
Gebrauch
WARNUNG!
Soll ein HV-Kabel ohne Interlock zum Einsatz kommen, befindet sich in dem Zubehörbeutel ein dafür bestimmtes Kabelset für vormontierte Interlock-Teile. Bei diesem Gebrauch geht die Sicherheitsfunktion verloren, die man bei der Interlock-Verwendung hat.
Sehen Sie sich folgende Abbildung genau an, um das im Zubehörbeutel mitgelieferte Interlock-Kabel richtig zu montieren, wenn auf das Hochspannungskabel mit Interlock verzichtet werden soll.
ZAHNSCHEIBE
UNTERLEGSCHEIBE
FEDERRRING
SCHRAUBE
INTERLOCK-KABEL 1 oder 2 Stk.
RÜCKSEITE
Abbildung 3
HINWEIS
Die Verriegelung des Kabels wird auf der Masse der Pumpe geschlossen. Wenn die Verbindung unterbrochen wird, wird die Hochspannung deaktiviert.
Die Verriegelung des Kabels wird auf der Masse der Pumpe geschlossen. Wenn die Verbindung unterbrochen wird, wird die Hochspannung deaktiviert. Beim Anschluss des Controller an die Pumpe ist ein HV-Kabel mit Interlock (siehe Bestellteile) zu verwenden.
26/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Gebrauchsanleitung
Gebrauch
Auf der Abbildung “Anschlüsse” sind die richtigen Anschlüsse der Erdungen, des HV-Kabels des Controller an die Pumpe und des Interlock-Kabels ersichtlich.
2
VORSICHT!
Beim Montieren des im Zubehörbeutel mitgelieferten Interlock-Kabels gehen Sie sehr vorsichtig vor, damit dabei kein Teil in den Controller fällt.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 27/104
Gebrauchsanleitung
(2) (1) (3) (4) (5) (6)
2
Gebrauch

Einschalten des Controllers von der vorderen Schalttafel (LOKAL-Modus)

HINWEIS
Um die Hochspannung (HV) einzuschalten, muss der Interlock des HV-Kabels (Kabel-Iinterlock) geschlossen sein (Verbinder eingesteckt).
Gehen Sie wie folgt vor, um den Controller mit Strom zu versorgen und die Spannung an den Hochspannungsverbindern (H.V.) freizugeben:
Schalten Sie den Controller aus.
Schließen Sie das HV-Kabel und den Interlock des H.V-Kabels an die jeweiligen Verbinder am Rückenteil.
Wählen Sie die Modalität LOCAL, indem Sie kurz die Taste “MODE” drücken bis auf dem Display die Aufschrift LOCAL erscheint.
Halten Sie die Taste HV ON/OFF (2) ) gedrückt und drücken Sie gleichzeitig die Taste HV-x (3,4,5,6) ), wobei x die Nummer der Leitung ist, die ein- oder ausgeschaltet werden soll.
Abbildung 4
28/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Vorderteil 4UHV Ionenpumpen-Controller
Gebrauchsanleitung
2
Gebrauch
WARNUNG!
Abbildung 5
Rückenteil 4UHV Ionenpumpen-Controller
Um die HV-Leitungen auszuschalten:
Halten Sie die Taste HV ON/OFF (2) gedrückt und drücken Sie gleichzeitig die Taste HV-x (3,4,5,6), wobei x die Nummer der Leitung ist, die ein- oder ausgeschaltet werden soll.
Weitere Einzelheiten zum Gebrauch des Controllers und zur Beschreibung der Display-Angaben entnehmen Sie bitte dem Abschnitt “ Technical Information ”.
Bei Not-Aus schalten Sie den Hauptschalter (1) auf dem vorderen Bedienfeld aus, um das Gerät und sämtliche Hochspannungsleitungen auszuschalten.
Wenn Sie den Hauptschalter auf Off stellen, wird das HV-Gerät ausgeschaltet.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 29/104
Gebrauchsanleitung
2

Wartung

Wartung

Entsorgung

Die 4UHV-Controller sind wartungsfrei. Eventuell erforderliche Eingriffe müssen von dazu befugtem Fachpersonal ausgeführt werden. Bei Störungen kann der Agilent-Reparaturdienst in Anspruch genommen werden oder schließen Sie einen Vertrag für “Agilent Advanced Exchange Service” ab, mit dem ein defekter Controller gegen einen general-überholten ausgetauscht wird.
Eine eventuelle Verschrottung muß unter Einhaltung der einschlägigen landesüblichen Vorschriften erfolgen.
Bedeutung des "WEEE" Logos auf den Etiketten.
Das folgende Symbol ist in Übereinstimmung mit der EURichtlinie WEEE (Waste Electrical and Electronic Equipment) angebracht.
Dieses Symbol (nur in den EU-Ländern gültig) zeigt an, dass das betreffende Produkt nicht zusammen mit Haushaltsmüll entsorgt werden darf sondern einem speziellen Sammelsystem zugeführt werden muss.
Der Endabnehmer sollte daher den Lieferanten des Geräts - d.h. die Muttergesellschaft oder den Wiederverkäufer - kontaktieren, um den Entsorgungsprozess zu starten, nachdem er die Verkaufsbedingungen geprüft hat.
30/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Agilent 4UHV Ion Pump Controller User Manual

3 Mode d’emploi

Indications Generales 32 Emmagasinage 33 Preparation pour l’Installation 34 Installation 35 Utilisation 37 Allumage du Contrôleur du Panneau Frontal
(Modalité LOCAL) Entretien 42 Mise au Rebut 42
Traduction de la
40
mode d’emploi originale
31/104
Mode d’emploi
A
3

Indications Generales

Indications Generales
Cet appareillage a été conçu en vue d'une utilisation professionnelle. Il est conseillé à l'utilisateur de lire attentivement cette notice d'instructions ainsi que toute autre indication supplémentaire fournie par Agilent, avant l'utilisation de l'appareillage. Agilent décline par conséquent toute responsabilité en cas d'inobservation totale ou partielle des instructions données, d'utilisation incorrecte de la part d'un personnel non formé, d'opérations non autorisées ou d'un emploi contraire aux réglementations nationales spécifiques.
Les paragraphes suivants donnent toutes les indications nécessaires à garantir la sécurité de l'opérateur pendant l'utilisation de l'appareillage. Des renseignements plus détaillés se trouvent dans l'appendice " Technical Information ".
Cette notice utilise les signes conventionnels suivants:
ATTENTION!
VERTISSEMENT!
NOTE
32/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Les messages d'attention apparaissent avant certaines procédures qui, si elles ne sont pas observées, pourraient endommager sérieusement l'appareillage.
Les messages d’avertissement attirent l'attention de l'opérateur sur une procédure ou une manoeuvre spéciale qui, si elle n'est pas effectuée correctement, risque de provoquer de graves lésions.
Les notes contiennent des renseignements importants, isolés du texte.

Emmagasinage

Pour transporter et emmagasiner le contrôleur il faut observer les conditions suivantes d’environnement:
température: de -20°C à +70°C
humidité relative: 0 - 95 % (non condensante).
Mode d’emploi
Emmagasinage
3
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 33/104
Mode d’emploi
3

Preparation pour l’Installation

Preparation pour l’Installation
Le contrôleur est fourni dans un emballage de protection spécial; si l'on constate des dommages pouvant s'être produits pendant le transport, contacter tout de suite le bureau de vente local. Pendant l'opération d'ouverture de l'emballage, veiller tout particulièrement à ne pas laisser tomber le contrôleur et à ne lui faire subir aucun choc. Le matériel est entièrement recyclable et il est conforme aux directives CEE 85/399 en matière de protection de l'environnement.
Figure 1 Emballage du contrôleur
34/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
A

Installation

Mode d’emploi
Installation
3
VERTISSEMENT!
ATTENTION!
Pour la sécurité de l’opérateur, le contrôleur 4UHV doit être alimenté par un câble d’alimentation à 3 fils doté d’une prise mâle approuvée à un niveau international. Brancher le câble avec prise mâle à une prise femelle raccordée à la terre de façon adéquate afin d’éviter tout risque d’électrocution et de pouvoir remplir les conditions de conformité prescrites par les normes CE. Les hautes tensions qui se développent à l’intérieur du contrôleur peuvent être susceptibles de provoquer des blessures graves voire de causer la mort.
Après l’extinction de l’unité, il reste de l’énergie à l’intérieur du contrôleur pendant quelques instants.
Attendre environ 1 minute pour être sûr que l’énergie résiduelle s’est dissipée.
Le contrôleur peut être utilisé soit comme unité de table que comme module installé dans une armoire. De toute façon, il doit être placé de manière à ce que l’air puisse circuler librement à travers les trous d’aération présents dans la couverture.
Lorsque le contrôleur est utilisé comme module armoire il DOIT être installé dans un adaptateur d’une hauteur de quatre unités armoire afin d’éviter qu’il ne tombe à l’intérieur de l’armoire même (voir tableau des pièces détachées). Le panneau frontal du contrôleur n’est pas prévu pour supporter le poids de l’unité. Ne pas installer ou utiliser le contrôleur 4UHV dans des milieux exposés aux agents atmosphériques (pluie, neige, glace). En présence de poussière, de gaz corrosifs ou dans des milieux explosifs ou à fort risque d’inflammabilité.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 35/104
Mode d’emploi
3
Installation
ATTENTION!
NOTE
ATTENTION!
Le contrôleur 4UHV appartient à la seconde catégorie d’installation (ou surtension) prévue par la norme EN 61010-1. Il est donc nécessaire de brancher le dispositif à une ligne d’alimentation qui soit adaptée à cette catégorie d’appareils.
Le contrôleur 4UHV dispose de connecteurs pour entrées/sorties et pour la communication en série qui doivent être branchés à des circuits externes de façon à ce qu’aucune des parties sous tension ne soitaccessible. Veiller à ce que le système d’isolation du dispositif branché au contrôleur 4UHV soit adapté, même en cas de pannes individuelles, et ce, tel que prévu par la norme EN 61010-1.
Si le contrôleur est installé dans une armoire, enlever les quatre pieds de manière à ce qu’il soit placé avec au moins 30 mm d’espace en haut et en bas.
Dans quelques rares cas de panne, il est possible que le contrôleur dégage de la fumée. Si l’unité est utilisée dans des environnements propres, il est nécessaire de prévoir la mise en place de protections adéquates afin d’éviter que la fumée ne puisse contaminer la pièce.
Pendant le fonctionnement, il est nécessaire de respecter les conditions d’environnement suivantes:
température: de 0°C à +40°C
humidité relative: 0 - 90% (non condensante).
36/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
A

Utilisation

Mode d’emploi
3
Utilisation
Dans ce paragraphe, on indique les principales procédures opérationnelles. Pour tous autres détails et pour les procédures concernant des connexions ou des éléments en option, se reporter au paragraphe "Usage" de l'appendice "Technical Information". Avant d'utiliser le contrôleur, effectuer toutes les connexions électriques et se reporter à la notice de la pompe connectée.
VERTISSEMENT!
N’allumer les canaux haute tension que s’ils ont été branchés aux pompes ioniques par l’intermédiaire des câbles haute tension prévus à cet effet et dotés de câble Interlock.
L’usage du contrôleur est subordonné à l’usage d’un câble haute tension doté d’Interlock.
4UHV
LIGNE
BRANCHEMENT DE TERRE DE LA POMPE
Figure 2 Connexions des masses
POMPE
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 37/104
Mode d’emploi
3
Utilisation
NOTE
Si l’opérateur veut utiliser un câble HV sans interlock, le sachet d’accessoires contient un kit spécial de câbles pour interlocks préassemblés. L’utilisation de ces accessoires provoque la perte des fonctions de sécurité offertes par l’utilisation de l’interlock.
Consulter la figure ci-dessous pour monter correctement le câble d’interlock contenu dans le sachet d’accessoires en cas de non utilisation du câble de haute tension équipé d’un interlock.
Figure 3
NOTE
38/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
L’interlock du câble est serré sur la masse de la pompe. Si le branchement est coupé, la haute tension est interrompue.
L’interlock du câble est serré sur la masse de la pompe. Si le branchement est coupé, la haute tension est interrompue.
Pour relier le contrôleur à la pompe, utiliser un câble HV équipé d’un interlock (voir le bordereau de commande des pièces).
Mode d’emploi
Utilisation
Les branchements corrects des masses, du câble HV entre le contrôleur et la pompe, ainsi que du câble d’interlock sont reportés sur la figure “Connexions des masses”.
3
ATTENTION!
En cas d’utilisation du câble d’interlock contenu dans le sachet d’accessoires, il faut veiller en particulier à ce qu’aucune pièce ne tombe à l’intérieur du contrôleur.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 39/104
Mode d’emploi
3
Utilisation

Allumage du Contrôleur du Panneau Frontal (Modalité LOCAL)

NOTE
Pour allumer la haute tension (HV), il faut que l’interlock du câble HV (câble interlock) soit fermé (connecteur branché).
Procéder comme suit pour alimenter le contrôleur et habiliter la tension au niveau des connecteurs de haute tension (H.V.) :
Eteindre le contrôleur.
Brancher le câble HV et l’interlock du câble H.V. sur les connecteurs correspondants situés sur le panneau arrière.
Appuyer brièvement sur la touche "MODE" pour sélectionner la modalité LOCAL jusqu’à ce que l’inscription LOCAL s’affiche sur l’écran.
Maintenir le bouton HV ON/OFF (2) enfoncé tout en appuyant sur le bouton HV-x (3,4,5,6) ; x correspond au numéro du canal à allumer ou à éteindre.
(2)
(1) (3) (4)
Figure 4 Panneau avant 4UHV sur le contrôleur de pompe
40/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
(5) (6)
Mode d’emploi
3
Utilisation
Figure 5 Panneau arrière 4UHV sur le contrôleur de pompe
Pour éteindre les canaux HV :
Maintenir le bouton HV ON/OFF (2) enfoncé tout en appuyant sur le bouton HV-x (3,4,5,6)) ; x correspond au numéro du canal à allumer ou à éteindre.
Pour plus de renseignements sur l’usage du contrôleur et sur la description des informations de l’écran, consulter la section “ Technical Information ”.
AVERTISSEMENT!
En cas de situation d’urgence nécessitant un arrêt immédiat de l’unité et de tous les canaux haute tension, désactiver l’interrupteur général (1) situé sur le panneau avant.
En plaçant l’interrupteur général sur OFF, l’unité H.T. s’arrête.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 41/104
Mode d’emploi
3

Entretien

Entretien

Mise au Rebut

Le contrôleur 4UHV n’a besoin d’aucun entretien. N’importe quel entretien sur l’unité doit être effectué par un personnel technique autorisé. En cas de panne contacter le Support technique Agilent ou bien s’abonner au Agilent Advanced Exchange Service” où le contrôleur endommagé est remplacé par un contrôleur reconditionné.
En cas de mise au rebut du contrôleur, procéder à son élimination conformément aux réglementations nationales en la matière.
Signification du logo "WEEE" figurant sur les étiquettes.
Le symbole ci-dessous est appliqué conformément à la directive CE nommée "WEEE".
Ce symbole (uniquement valide pour les pays de la Communauté européenne) indique que le produit sur lequel il est appliqué NE doit PAS être mis au rebut avec les ordures ménagères ou les déchets industriels ordinaires, mais passer par un système de collecte sélective. Après avoir vérifié les termes et conditions du contrat de vente, l’utilisateur final est donc prié de contacter le fournisseur du dispositif, maison mère ou revendeur, pour mettre en oeuvre le processus de collecte et mise au rebut.
42/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Agilent 4UHV Ion Pump Controller User Manual

4 Instructions for Use

General Information 44 Storage 33 Prior to Installation 46 Installation 47 Usage 49 Powering On the Controller from the Front Panel
(LOCAL Mo Maintenance 54 Disposal 54
al Instructions
Origin
de) 52
43/104
Instructions for Use
4

General Information

General Information
This equipment is intended for professional use. Prior to using this equipment the user must carefully read this Instruction Manual in its entirety and any additional information provided by Agilent. Agilent declines all responsibility for damage caused by the total or partial misuse of the instructions provided herein, by the improper use of the equipment by untrained personnel, by unauthorized interventions or by negligence in complying with any specific national rule or regulation.
The following sections provide you with all the information needed to guarantee the operator’s safety when using the equipment. Detailed information is provided in the appendix entitled “Technical Information”.
The following conventions are used in this manual:
CAUTION!
WARNING!
NOTE
44/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Caution messages are provided before procedures that could cause damage to the equipment if not complied with.
Warning operation that could cause serious injury if not performed correctly.
Notes provide you with important information extracted from the text.
messages call the operator’s attention to a specific procedure or

Storage

Instructions for Use
Storage
The following environmental conditions must be met when transporting and storing the controller:
Temperature: -20 °C to +70 °C
Relative humidity: 0 - 95% (non-condensing)
4
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 45/104
Instructions for Use
4

Prior to Installation

Prior to Installation
The controller comes in a special protective packaging; if there is any sign of damage that could have been caused during transportation, contact your local sales office immediately.
When unpacking the controller, be particularly careful to avoid dropping it or knocking it against anything.
The packaging material is totally recyclable and complies with EEC directives 85/399 for the safeguard of the environment.
Figure 1 Controller Packaging
46/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Installation

Instructions for Use
Installation
4
WARNING!
CAUTION!
For the safety of the operator, the 4UHV controller must be powered with a 3­wire power cable connected to a plug approved at international level. Use this cable and plug together with an adequately earthed socket so as to prevent electrical shocks and satisfy the requirements of EC norms. The high voltages that develop in the controller can provoke serious injuries or death.
After switching off the unit, residual energy is present inside the controller for some time.
Wait approx. 1 minute to be sure that the residual energy has been dissipated.
The controller can be used either as a desktop unit or as a rack module. In any case it must be positioned in a way that the air can circulate freely through the ventilation slots on the cover.
If the controller is used as a rack module, it MUST be inserted into a four-rack high adapter to prevent it from falling inside the rack itself (see the table of orderable parts). The 4UHV controller front panel is not designed to support the weight of the unit.
Do not install or use the controller in an environment exposed to atmospheric agents (rain, snow, ice), in the presence of dust, corrosive gases or in a highly flammable or explosive environment.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 47/104
Instructions for Use
4
Installation
CAUTION!
NOTE
CAUTION!
The 4UHV controller belongs to the second installation category (or overvoltage) as provided for in normative EN 61010-1. Therefore the device must be connected to a power supply line satisfying the requirements for this category.
The 4UHV controller has connectors for inputs/outputs and for serial communications that must be connected to the external circuits in such a way that no powered part is accessible. Make sure that the insulation of the device connected to the 4UHV controller provides an adequate insulation even in the case of a single fault condition as stipulated in the EN 61010-1 normative.
If the controller is installed in a rack, remove its four feet and place it so as to leave at least 30 mm (1.2 inches) of free space above and below.
In rare circumstances, a controller fault could result in the emission of smoke. If the customer is using the controller in clean environments, they should take adequate measures to avoid the environment being contaminated by any eventual smoke.
The controller must be used in the following environmental conditions:
Temperature: 0 °C to +40 °C
Relative humidity: 0 - 90% (non-condensing).
48/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Usage

Instructions for Use
Usage
This section provides you with the major operating procedures. For more information and for the procedures that concern connections or specific options, refer to the section “USAGE” in the “Technical Information” appendix. Before using the controller, perform all electrical connections and refer to the manual of the connected pump.
4
WARNING!
Switch on the high voltage channels only if they are connected to the ionic pumps by means of the special purpose high voltage cables equipped with interlock cable.
It is assumed that the controller will be used together with the high voltage cable having a safety interlock.
4UHV
Figure 2 Ground Connections
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 49/104
Instructions for Use
4
Usage
WARNING!
If an HV cable without interlock is to be used, the accessories bag contains a specific kit of preassembled interlock leads. However, with this type of use, the safety capability furnished using the interlock is lost.
Refer to the figure below for correct assembly of the interlock cable furnished in the accessories bag in the case in which an HV cable with interlock is not used.
Figure 3
NOTE
50/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
The cable interlock closes on pump ground. The high voltage is disabled if the connection is interrupted.
The cable interlock closes on pump ground. The high voltage is disabled if the connection is interrupted. To connect the controller to the pump, use a HV cable with interlock (see parts that can be ordered).
Correct connection of masses, of the HV cable between the controller and pump and of the interlock cable is illustrated in the “Connections” figure.
Instructions for Use
Usage
4
CAUTION!
When using the interlock cable furnished in the accessories bag, make sure that no parts drop accidentally inside the controller.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 51/104
Instructions for Use
4
Usage

Powering On the Controller from the Front Panel (LOCAL Mode)

NOTE
To switch on the High Voltage (HV), the interlock of the HV cable (cable interlock) must be closed (connector inserted).
Proceed as follows to power the controller and apply voltage to the high voltage (HV) connectors:
Switch off the controller.
Connect the HV cable and the interlock of the HV cable in the related connectors on the rear panel.
Select LOCAL mode, briefly pressing the “MODE” key until LOCAL is shown on the display.
Hold down the HV ON/OFF button (2) while pressing the HV-x (3,4,5,6) button where x is the number of the channel to be switched on/off.
(2)
(1) (3) (4)
Figure 4 Front Panel 4UHV Ion Pump Controller
52/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
(5)
(6)
Instructions for Use
4
Usage
Figure 5 Rear Panel 4UHV Ion Pump Controller
To switch off the HV channels:
Hold down the HV ON/OFF (2) button while pressing the HV-x (3,4,5,6) button where x is the number of the channel to be switched on/off.
For further details on using the controller and for a description of the information appearing on the display, refer to the section “Technical Information”.
WARNING!
In situations of emergency, to switch off the unit and all the high voltage channels, turn off the main power switch (1) situated on the front panel.
When the main switch is turned off, the HV unit is switched off.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 53/104
Instructions for Use
4

Maintenance

Maintenance
The 4UHV controller does not require any maintenance. Any form of servicing on the unit must be performed by authorized personnel.
If servicing is needed, contact Agilent Technical Support or subscribe to the “Agilent Advanced Exchange Service” where the faulty controller is replaced by a refurbished one.
If the controller needs to be scraped, proceed to do so in compliance with the specific national norms.

Disposal

Meaning of the "WEEE" logo found in labels
The following symbol is applied in accordance with the EC WEEE (Waste Electrical and Electronic Equipment) Directive.
This symbol (valid only in countries of the European Community) indicates that the product it applies to must NOT be disposed of together with ordinary domestic or industrial waste but must be sent to a differentiated waste collection system.
The end user is therefore invited to contact the supplier of the device, whether the Parent Company or a retailer, to initiate the collection and disposal process after checking the contractual terms and conditions of sale.
54/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Agilent 4UHV Ion Pump Controller User Manual

5 Technical Information

4UHV Controller Description 57 Specifications 59 Controller Outline 60 Front Panel Description 61 Keys 61 Rear Panel Description 63 Operating Mode 65 Selecting “Operating Mode” from Front Panel 65 Selecting “Operating Mode” via Serial 66 Start-Up 67 Connection of Input remote 72 Serial 73 Connector Examples 74 Window Protocol 74 Error Description 84 Error Code 84 Old Serial Protocol (“Binary Pr
Original Instructions
otocol”) 87
55/104
Technical Information
5
Display and Menus 91 Displaying Channel-Related Inf Commands 93 Menu 94 Orderable Parts 98
ormation 74
56/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

4UHV Controller Description

The 4UHV controller is a power supply for ion pumps. It supplies a high voltage on output, selectable as 3kV, 5kV or 7kV, and measures the output current.
The controller has the following features:
Front panel with keypad and a 4-row display (4x20, 146 x 62 mm) for displaying the operating values (voltage, current, pressure)
Remote I/O card with DB37 connector
RS232 and RS485 serial communications.
Technical Information
4UHV Controller Description
5
Figure 6 4 UHV Controllers
The controller contains one or two high voltage modules.
Each high voltage module can have one 200 W channel or one 120 W channel or two 80 W channels.
Some examples of how HV channels can be configured are given below (for details see the Orderable Parts table):
Four independent channels with a maximum of 80 W power per channel
Two independent channels with a maximum of 200 W power per channel
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 57/104
Technical Information
5
4UHV Controller Description
One 200 W channel and two 80W channels.
One 120 W channel
The 4UHV controller can be operated in the modes: LOCAL, SERIAL or REMOTE.
58/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Specifications

Table 1 Specifications
Component Description
Input Voltage 100 - 240 Vac (+/-10%)
Input Frequency 50/60 Hz
Input Power 600 VA Output HV Voltage +/- 7000 Vdc +/- 5%
Output HV Short circuit current
Output HV Power max
Operating temperature
Storage temperature
Fuse 5x20 T6.3A 250V
Voltage measurement
Current measurement
Weight 6.5 kg
Compliance with: EN 61010-1 2001: Safety requirements for electrical
Technical Information
Specifications
40 mA (for 80W channels) 100 mA (for 200 W channels)
200 W or 80 W each channel
0 °C to 40 °C
-20 °C to +70 °C
Resolution 100 V Accuracy: +/- 5%
Measurement range: 10 nA to 100 mA, logarithmic scale Resolution : 2 digit of the mantissa (maximum 10 nA) Accuracy: +/- 6%
equipment for measurement control and laboratory use. EN 61326-1 2006: Electrical equipment for measurement
control and laboratory use EMC requirements
5
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 59/104
Technical Information
5
Specifications

Controller Outline

8000
7000
6000
5000
4000
Voltage (V)
3000
2000
1000
0
020406080100120
Output curve (200W) Output curve (80W)
Current (mA)
Figure 7 Output voltage vs Output current
The outline dimensions for the 4UHV controller are shown in the following figures:
Figure 8 Controller Model Dimensions
Front View
211.40
141.20
177.00
164.30
Rear View
60/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Specifications

Front Panel Description

Figure 9 Front Panel

Keys

Table 2 Keys
Main Power This is the main switch for switching on and off the controller. HV-ON/OFF To switch a high voltage channel on or off, keep the HV-ON/OFF key
pressed while you press the HV-x key, where x is the number of the channel you want to switch on or off.
Fixed/Step To change the output voltage choosing between: 7kV, 5kV, 3kV, Step-Mode
and Fixed-Mode, keep the Fixed/Step key pressed while you press the HV-x key, where x is the number of the channel for which you want to change the output voltage.
The output voltage will change cyclically between “STEP, 7kV, 5kV, 3kV”.
Protect To activate or disactivate Protect mode, keep the Protect key pressed while
you press the HV-x key, where x is the number of channel for which you want to activate or disactivate the “Protect” functionality.
Mode By pressing this key briefly (< 2 sec), the ”operating mode” changes
cyclically between: Serial, Front, Remote. You exit from this display automatically after 5 seconds. By keeping this key pressed for a long time (> 2 sec), you enter the menu. To exit from the menu, press the Mode key again for a long time.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 61/104
Technical Information
5
Specifications
Graphic Signals
Four black squares are present for each channel indicating, respectively, the 4 states of the channel. The meaning of the 4 indicators is the following:
1. HV-x Square lit (black)= HV on
Square not lit = HV off Square flashing = Error
2. Protect-x Square lit (black)= Protect on
Square not lit = Protect off Square flashing = Protect error
3. SP-x Square lit (black)= Set-point activate
Square not lit = Set-point not active
4. Step-x Square lit (black)= Step
Square not lit = Fixed
62/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Specifications

Rear Panel Description

HV Connectors
Interlock connector
Fuses
Serial Port
Remote I/O
Figure 10 Rear Panel
The following are present on the rear panel:
The HV connectors ( 1, 2, 3 or 4 according to model)
The interlock connectors associated to each channel
The fuses
The DB9 connector for RS232 and RS485 serial communication
The DB37 connector for Remote I/O signals.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 63/104
Technical Information
5
Specifications
Fuse Holder
The following figure shows the location of this assembly.
Figure 11 Rear Panel
Proceed as follows to replace one or both fuses:
1 Disconnect the mains cable 2 Waiting for 15 second 3 Remove the fuse with a small screwdriver 4 Replace the fuse 5 Use only 5x20 T6.3A 250V fuses
64/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Operating Mode

The controller 4UHV for ion pumps can be operated in three different modes:
Local
Serial
Remote.
The commands sent to the controller (for example, HVON/OFF, Target voltage etc) can only be given in the mode chosen, while the data (for example, current, pressure, voltage etc…) can be read in all the modes.
E.g.: If you select Local mode, the HV channels can only be switched on via the keys on the Front Panel, but the current supplied can be read via the Front Panel, Serial and Remote.
Change from one mode to the next can be done either via the Front Panel or a serial command.
Technical Information
Operating Mode
5
NOTE
Change from one mode to another can be done with the high voltage switched on. However, the channels switch off if Remote mode is selected but no commands for switching on are present on the remote connector.

Selecting “Operating Mode” from Front Panel

To display the current mode, press the Mode key briefly (less than 2 seconds).
To change mode, press the Mode key again. The three modes will be displayed in a cyclic fashion: Local, Serial, Remote.
After selecting the required mode, wait approximately 5 seconds to return to the previous screen.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 65/104
Technical Information
5
Operating Mode

Selecting “Operating Mode” via Serial

Using serial communications via the protocol “WIN protocol” (see chapter: SERIAL – Window Protocol), write the chosen value in window 8:
Table 3 Keys
Value Description
0 Serial 1 Remote
2 Local
66/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Start-Up

Technical Information
Start-Up
This chapter explains how to switch on and off the unit and the high voltage channels. In the following chapters, all the functions of the controller are explained in detail.
1 Put the main power switch situated on the front panel to OFF 2 Insert the power cable into the correct connector on the rear
panel
3 Connect the HV cables to the controller and to the ion pumps 4 Make sure that “Interlock” of HV cable is connected 5 To switch on the unit, put the main power switch to ON 6 Select Local for the Operating mode 7 Press the keys HV-ON/OFF keys and HV-x, where x is the number
of the channel you want to switch on.
Key HV-ON/OFF
5
Figure 12 Front Panel
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 67/104
Main power switch
Keys HV-x
Technical Information
5
Start-Up
Table 4
Component Description
Remote I/O Signal Listing
Pin 4 +24V +/- 10%, max. current 60mA Pin 5 Reserved
Fault A unique fault relay for all channels and for all
Pin 12 NC Fault Relay
Pin 13 NO Fault Relay Pin 31 Common Fault Relay
Channel 1
Input
Pin 6 CH1 on/off
Pin 7 CH1 protect Pin 8 CH1 step
Pin 22 Digital Gnd Analog Output
Pin 1 Analog 1
Pin 3 Analog Gnd
Digital Output Pin 17 CH1 NC Set-point Relay
Pin 18 CH1 (Common) Relay
Pin 19 CH1 NO Set-point Relay
Channel 2
Input
Pin 9 CH2 on/off
Pin 10 CH2 protect
Pin 11 CH2 step Pin 22 Digital Gnd
Analog Output
Pin 2 Analog 2
Pin 3 Analog Gnd
errors.
68/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Start-Up
Digital Output
Pin 14 CH2 NC Set-point Relay Pin 15 CH2 (Common) Relay
Pin 16 CH2 NO Set-point Relay
Channel 3
Input
Pin 23 CH3 on/off
Pin 24 CH3 protect
Pin 25 CH3 step Pin 22 Digital Gnd Analog Output
Pin 20 Analog 3
Pin 3 Analog Gnd Digital Output
Pin 35 CH3 NC Set-point Relay
Pin 36 CH3 (Common) Relay Pin 37 CH3 NO Set-point Relay
Channel 4
Input
Pin 26 CH4 on/off Pin 27 CH4 protect
Pin 28 CH4 step
Pin 22 Digital Gnd
Analog Output
Pin 21 Analog 4 Pin 3 Analog Gnd
Digital Output
Pin 32 CH4 NC Set-point Relay Pin 33 CH4 (Common) Relay
Pin 34 CH4 NO Set-point Relay
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 69/104
Technical Information
A
5
Start-Up
Figure 13 Recorder Output Pressure
nalog remote vs Pressure
5.0
4.0
Analog remote (Volt)
3.0
2.0
1.3E-12 kPa
1.0
0.0
1.0E-12 1.0E-11
1.0E-10 1.0E-09 1.0E-08 1.0E-07 1.0E-06 1.0E-05
Pressure (kPa)
1.3E-6 kPa
Figure 14 Analog remote vs Pressure (kPa)
70/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
4
5
Start-Up
Analog remote vs Pressure
5.0
4.0
3.0
2.0
Ana log remote (V olt)
1.0
1.3E-11 mbar
0.0
1.0E-11 1.0E-10 1.0E-09 1.0E-08 1.0E-07 1.0E-06 1.0E-05 1.0E-0
Pressure (mbar)
Figure 15 Analog remote vs Pressure (mbar)
1.3E-5 mbar
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 71/104
Technical Information
5
Start-Up

Connection of Input remote

In order to activate the inputs remote (CH on/off, Ch protect, CH Step) connect the pins as following:
+24V
A
Controller
Figure 16 Input
72/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Customer device’s

Serial

Technical Information
Serial
The following figure shows the 4UHV interconnections.
Figure 17 4UHV interconnections
This is a 9-pin D-type serial input/output connector that allows the 4UHV to be controlled via an RS232 or RS485 connection.
Table 5
PIN No. Signal Name
1 +5 V (OUT) 2 TX (RS232)
3 RX (RS232)
4 Reserved 5 GND
6 A + (RS485)
7 Reserved
8 B - (RS485) 9 Reserved
5
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 73/104
Technical Information
5
Serial

Connector Examples

5
2
PC
3
Figure 18 RS–232 Connection
Ion controller 1
Ion controller 2
Figure 19 RS–485 Connection
5
2
3
Cont ro ll er 4UHV

Window Protocol

Both RS232 and the RS485 interfaces are available on the 9-pin D­type serial input/output connector. The communications protocol is the same (see the structure below), but only the RS485 handles the address field. Therefore, to enable the RS485, you need to select both the type of communication and the device address using the front panel menu or the Navigator software.
74/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Serial
The Window Protocol is the same of the Turbo Pump, but the meaning of the Window is different (see the below chapter: Windows Description).
Communications Format
8 data bit
No parity
1 stop bit
Baud rate: 9600
Communications Protocol
The communications protocol is of MASTER/ SLAVE type, where:
Host = MASTER
Controller = SLAVE
The communication takes place as follows: 1 The host (MASTER) sends a MESSAGE + CRC to the controller
(SLAVE)
2 The controller answers with an ANSWER + CRC to the host. 3 The MESSAGE is a string in the following format: 4 <STX>+<ADDR>+<WIN>+<COM>+<DATA>+<ETX>+<CRC>
NOTE
When data is indicated between two quotes (‘...’), it implies that the data indicated is the corresponding ASCII character.
Where:
<STX> (Start of transmission) = 0x02
<ADDR> (Unit address) = 0x80 (for RS232)
<ADDR> (Unit address) = 0x80 + device number (0 to 31) (for RS485)
<WIN> (Window) = a string of 3 numerics indicating the window
number (from ‘000’ to ‘999’); for the meaning of each window, see the relevant paragraph.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 75/104
Technical Information
5
Serial
<COM> (Command) = 0x30 to read the window, 0x31 to write in
the window
<DATA> = an alphanumeric ASCII string with the data to be
written in the window. In the case of a read command, this field is not present. The field length varies according to the data type, as shown in the following table:
76/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Serial
Table 6
Data Type Field Length Valid Characters
Logic (L) 1 ‘0’ = OFF
‘1’ = ON
Numeric (N) 6 ‘-‘, ‘.’, ‘0’ . . . ‘9’ right justified with ‘0’
Alphanumeric (A) 10 From blank to ‘_’ (ASCII)
<ETX> (End of transmission) = 0x03
<CRC> = XOR of all characters following <STX> and including the
<ETX> terminator. The value is hexadecimal coded and represented by two ASCII characters.
The SLAVE addressed responds with an ANSWER whose structure depends on the MESSAGE type.
When the MESSAGE is a read command, the SLAVE responds transmitting a string with the same structure as the MESSAGE.
NOTE
Using the RS485 interface, the message structure is identical to that used for the RS232 interface, the only difference being the value assigned to the ADDRESS <ADDR>.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 77/104
Technical Information
5
Serial
The controller can reply with the following types of response:
Table 7
Type Length Value Description
Logic - After a read instruction of a logic window. Numeric 6 bytes - After a read instruction of a numeric window.
Alphanumeric 10 bytes - After a read instruction of a alphanumeric window.
ACK 1 byte (0x6) Execution of the command has been successful. NACK 1 byte (0x15) Execution of the command has failed.
Unknown Window 1 byte (0x32) The window specified in the command is not a valid window.
Data Type Error 1 byte (0x33) The data type specified in the command (Logic, Numeric or
Alphanumeric) is not in agreement with the Window specified.
Out of Range The value expressed during a write command is not within
the range value for the specified window.
Win Disabled 1 byte (0x35) The window specified is Read Only or is temporarily disabled.
Table 8 Windows Description
WIN R/W Type Description Range
11 R/W L HV ON/OFF
CH1
12 R/W L HV ON/OFF
CH2
13 R/W L HV ON/OFF
CH3
14 R/W L HV ON/OFF CH4 0 = OFF(def) ; 1=ON
108 R/W N Baud rate (1-4) [1200-2400-4200-9600]
205 R N Status 206 R N Error code
319 R/W Controller Model
323 R/W Controller Serial number 503 R/W N RS485 Serial Address [0-31]; 1=def
504 R/W L Serial Type Select 0= RS232(def) ;
0 = OFF(def) ; 1=ON
0 = OFF(def) ; 1=ON
0 = OFF(def) ; 1=ON
78/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
Serial
WIN R/W Type Description Range
1= RS485
505 R/W N Channel Selection (see below) 600 R/W N Unità di misura
Pressione
601 R/W A Operating Mode (see below)
602 R/W A Protect (see below)
603 R/W A Fixed/Step (see below) 610 R/W N Device Number CH1 (see below)
612 R/W N Power max CH1 20 W – 80 W
613 R/W N V target CH1 [3000,7000] V
614 R/W N I protect CH1 [1,100] step 1 mA
615 R/W A Set Point CH1 [X.XE-XX] 620 R/W N Device Number CH1 (see below)
622 R/W N Power max CH2 20 W – 80 W
623 R/W N V target CH2 [3000,7000] V
624 R/W N I protect CH2 [1,100] step 1 mA 625 R/W A Set Point CH2 [X.XE-XX]
630 R/W N Device Number CH3 (see below)
632 R/W N Power max CH3 20 W – 80 W
633 R/W N V target CH3 [3000,7000] V
634 R/W N I protect CH3 [1,100] step 1 mA 635 R/W A Set Point CH3 [X.XE-XX]
640 R/W N Device Number CH4 (see below)
642 R/W N Power max CH4 20 W – 80 W 643 R/W N V target CH4 [3000,7000] V
0 = Torr ; 1=mBar (def) ; 2=Pa
step 1000; def=7000
step 1000; def=7000
step 1000; def=7000
5
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 79/104
Technical Information
5
Serial
WIN R/W Type Description Range
step 1000; def=7000
644 R/W N I protect CH4 [1,100] step 1 mA 645 R/W A Set Point CH4 [X.XE-XX]
800 R N Temperature
FAN
801 R N Temperature
HV1
802 R N Temperature
HV2
803 R A Interlock Status (see below)
804 R A Status Set Point (see below)
808 R N Temperature
HV3
809 R N Temperature
HV4
810 R N V measured CH1 [0, 7000] V ;
811 R A I measured CH1 [1E-10, 9E-1] A 812 R N Pressure CH1 [X.XE-XX]
820 R N V measured CH2 [0, 10000] V ;
821 R A I measured CH2 [1E-10, 9E-1] A 822 R N Pressure CH2 [X.XE-XX]
830 R N V measured CH3 [0, 10000] V ;
831 R A I measured CH3 [1E-10, 9E-1] A
832 R N Pressure CH3 [X.XE-XX]
840 R N V measured CH4 [0, 10000] V ;
841 R A I measured CH4 [1E-10, 9E-1] A
842 R N Pressure CH4 [X.XE-XX]
[0, 200] °C
[0, 200] °C
[0, 200] °C
[0, 200] °C
[0, 200] °C
step 100 V
step 100 V
step 100 V
step 100 V
80/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Serial
Example:
Turn ON Channel 1
PC
´ Controller
02 80 30 31 31 31 31 03 42 33
STX ADDR WINDOW WR DATA ETX CRC
Controller ´ PC
02 80 06 03 38 33
STX ADDR ACK ETX CRC
Turn OFF Channel 1
PC
´ Controller
02 80 30 31 31 31 30 03 42 32
STX ADDR WINDOW WR DATA ETX CRC
Controller ´ PC
02 80 06 03 38 35 STX ADDR ACK ETX CRC
Read Pressure (win 812) Channel 1
PC
´ Controller
02 80 38 31 32 30 03 38 38 STX ADDR WINDOW RD ETX CRC
Controller ´ PC
02 80 38 31 32 30 20 20 20 31 2E 35 45 2D 30 38 03 45 32
STX ADDR WINDOW WR DATA ETX CRC
Data=1.5E-8
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 81/104
Technical Information
5
Serial
Read Voltage (win 810) Channel 1
´Controller
PC
02 80 38 31 30 30 03 38 41 STX ADDR WINDOW RD ETX CRC
Controller ´ PC
02 80 38 31 32 30 30 30 33 30 30 30 03 38 39
STX ADDR WINDOW WR DATA ETX CRC
Data=3000
Read Current (win 811) Channel 1
PC
´ Controller
02 80 38 31 31 30 03 38 42 STX ADDR WINDOW RD ETX CRC
Controller ´ PC
02 80 38 31 31 30 20 20 20 32 2E 39 45 2D 30 35 03 45 33
STX ADDR WINDOW WR DATA ETX CRC
Data=2.9E-5
Operating mode (Win 601)
Autostart ON
PC
´Controller
02 80 36 30 31 30 30 30 30 30 30 30 30 30 30 31 03 38 34
STX ADDR WINDOW WR DATA ETX CRC
Controller ´ PC
02 80 06 03 38 35
STX ADDR ACK ETX CRC
Autostart OFF
PC
´ Controller
02 80 36 30 31 31 30 30 30 30 30 30 30 30 30 30 03 38 35
STX ADDR WINDOW WR DATA ETX CRC
82/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Serial
Controller
02 80 06 03 38 35
STX ADDR ACK ETX CRC
´ PC
Protect (Win 602)
PC
´ Controller
02 80 36 30 32 30 03 38 37
STX ADDR WINDOW RD ETX CRC
Controller ´ PC
02 80 36 30 32 30 30 30 30 30 30 30 30 31 30 30 03 38 36
STX ADDR WINDOW WR DATA ETX CRC
Fixed/Step (603)
PC
´ Controller
02 80 36 30 33 30 03 38 36
STX ADDR WINDOW RD ETX CRC
Controller ´ PC
02 80 36 30 33 30 30 30 30 30 30 30 30 30 30 31 03 38 37 STX ADDR WINDOW WR DATA ETX CRC
Status Set Point (804)
PC
´ Controller
02 80 38 30 34 30 03 38 46
STX ADDR WINDOW RD ETX CRC
Controller ´ PC
02 80 38 30 34 30 30 30 30 30 30 30 30 30 30 31 03 38 45
STX ADDR WINDOW WR DATA ETX CRC
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 83/104
Technical Information
5
Serial

Error Description

Controller errors can be displayed in two windows:
WIN 505 where the user writes the channel whose error is to be
viewed
WIN 206 where the controller shows the error code of the
channel written in window 505.
If the value 0 is written in window 505, the errors of all the channels remain displayed in window 206.
Table 9
WIN 505 value Channel
0 All channels 1
2
3 4
Channel 1 Channel 2 Channel 3 Channel 4

Error Code

The error code is displayed in decimal format. Binary representation of this number provides indications regarding the type of error that has occurred.
The error table is shown below:
Table 10
Error code in decimal format
0 0000000000000 No error
1 0000000000001 FAN error 2 0000000000010 Power input error from HV
4 0000000000100 Power input error from PFC
8 0000000001000 Overtemp PFC
16 0000000010000 Error communication CPU-HV
84/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Binary Description
Technical Information
5
Serial
Error code in decimal format
32 0000000100000 Interlock cable
64 0000001000000 Overtemp HV 128 0000010000000 Protect
256 0000100000000 Measurement error
512 0001000000000 HV out error 1024 0010000000000 Short circuit
2048 0100000000000 HV disabled
Binary Description
Example:
Interlock cable
Error code: 32 (decimal)
´ 0000000010000 ( binary) ´Interlock
cable error
Interlock cable + Overtemp HV
Error code: 96 (decimal)
´ 0000000110000 ( binary) ´Interlock
cable error + Overtemp HV
Error code (Win 206)
Error interlock
02 80 32 30 36 30 03 38 37
STX ADDR WINDOW RD ETX CRC
02 80 32 30 36 30 30 30 30 30 33 32 03 38 36
STX ADDR WINDOW WR DATA ETX CRC
Channel selection (Win 505)
Read
02 80 35 30 35 30 03 38 33
STX ADDR WINDOW RD ETX CRC
02 80 35 30 35 30 30 30 30 30 30 30 03 38 33
STX ADDR WINDOW WR DATA ETX CRC
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 85/104
Technical Information
5
Serial
Write 1
02 80 35 30 35 31 30 30 30 30 30 31 03 38 33
STX ADDR WINDOW WR DATA ETX CRC
02 80 06 03 38 35
STX ADDR ACK ETX CRC
Error code (Win 206)
Interlock error:
02 80 32 30 36 30 03 38 37
STX ADDR WINDOW RD ETX CRC
02 80 32 30 36 30 30 30 30 30 33 32 03 38 36 STX ADDR WINDOW WR DATA ETX CRC
Channel selection (Win 505)
Write 2
02 80 35 30 35 31 30 30 30 30 30 32 03 38 30 STX ADDR WINDOW WR DATA ETX CRC
02 80 06 03 38 35
STX ADDR ACK ETX CRC
Error code (Win 206)
Interlock not present error because channel 2 has been selected:
02 80 32 30 36 30 03 38 37 STX ADDR WINDOW RD ETX CRC
02 80 32 30 36 30 30 30 30 30 30 30 03 38 37
STX ADDR WINDOW WR DATA ETX CRC
86/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Serial

Old Serial Protocol (“Binary Protocol”)

The “Binary Protocol” serial protocol used by some old controllers is no longer supported.
For new projects, Agilent advises that the new protocol “Window protocol” be used. Nevertheless, for compatibility with the old systems, some commands of the “Binary Dual” have been implemented.
The 4UHV controller cannot implement all the commands of the Dual but only a subset.
Communications Format
These protocols have the following formats:
Table 11
Type No. of
Bytes
Read 1 “?” (3Fh3) performs reads on the Splitter Box
Status 1 “0” (30h) = false = off,
Integer 5 “xxxxx” represented in BCD4 with 5 digits (always positive)
BitField 8 Like integer type, but meanings are associated with the single
Exponential 7 “x.xEsxx” where x is BCD digits, E is the 45h character and s is
String n Sequence of n characters included within the 20h and 7Fh range
3
The “h” notation following a number indicates that the number is
Description
“1” (31h) = true = on
bits of the number.
the (“+” or “-“ sign).
5
expressed in hexadecimal format.
4
BCD: The number is represented by digits included within the “0”
and “9” range (ASCII 30h - 39h).
5
Status can also assume values greater than “1”.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 87/104
Technical Information
5
Serial
The commands have a read and a write mode. By specifying the type of read operation being performed, the Host queries the Splitter Box that, in turn, replies in a format that is compliant with the command sent. As long as a write operation can be carried out, the write and read formats for the same command coincide.
Host to Dual controller command format:
[header command] [length] [command] [channel] [data] [checksum]
Dual controller to Host reply format:
[header response] [length] [command] [channel] [data] [checksum]
Table 12
Field No.
of Bytes
Header command
Header response
Length 2 Data packet length in BCD (command, channel, data
Command See description of commands (byte 0 command, byte 1
Channel 1 30h
Data N See description of commands Checksum 1 XOR of all bytes (checksum excluded) in and with 7Fh.
1 81h
01h
Value Description
Header for the RS232 and RS422 serial.
81h÷A0h
01h÷20h
31h 32h 33h 34h
Header and address for the RS485 (129 – 160) serial.
Header for the serial RS232, RS422. Header and address for the RS485 serial.
fields only).
subcommand).
No channel High Voltage 1 High Voltage 2 High Voltage 3 High Voltage 4
Command Listing
It is not possible to implement all the “Binary Dual” protocol commands on the 4UHV controller. The commands that are implemented on the 4UHV controller are the following:
88/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Serial
Table 13
No. Description ASCII Hex
1 Local/remote Z0 5Ah 30h 3 HV-ON/OFF A0 41h 30h
4 Device number F0 46h 30h
5 Measurement unit D0 44h 30h 7 Protect C0 43h 30h
8 Fixed/Step B0 42h 30h
9 Power supply polarity G0 47h 30h 10 Max. power J0 4Ah 30h
11 Vmax H0 48h 30h
12 Iprotect K0 4Bh 30h
13 Set point P0 50h 30h 14 V meas. S0 53h 30h
15 I meas. T0 54h 30h
16 P meas. U0 55h 30h 17 Set-point status g0 67h 30h
18 Interlock status ]0 5Dh 30h
19 Error status z0 7Ah 30h
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 89/104
Technical Information
5
Serial
Table 14 Interlock Status Coding
Bit Field Interlock Coding (active if 1)
01h HV3 Cable Interlock
02h Reserved 04h Reserved
08h HV1 Cable Interlock
10h HV4 Cable Interlock 20h Reserved
40h Reserved
80h HV2 Cable Interlock
Value Error Status Coding (active if 1)
33h Cable Interlock
36h Excess temperature
37h Power input error 38h FAN Error
39h Protect
31h 30h Short-circuit 31h 31h HV out error
31h 32h Zero Measurement
90/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)

Display and Menus

Switching on the unit, the initial screen that appears is as follows:
Figure 20
Afterwards a screen of the following type appears, which displays for each channel the name of the ion pump selected.
IA
V
UUAC
NOL OTECH
5- 5-40 Dio17 d
5
2
7
4X3XXXlXX
XX
-40S5- 5
XXX
XXX5XX
Technical Information
Display and Menus
NVAR
.M
ES
GI
tarC
lee
5
Figure 21

Displaying Channel-Related Information

The display can be configured easily to display different information, depending on the needs of the customer.
Information on All Channels
The voltage on all the four channels can be displayed simultaneously, or the current of all four channels, or the pressure.
To do this, press the “V/I/P” key; the following screens appear cyclically.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 91/104
Technical Information
5
Display and Menus
Table 15
5- 5-4
5
XXX
2
7
3
4
XXX5XX
-40S5- 5 l
XXXX
XX
6 Press “V/I/P”
1
2 X . XE - bar
3
4
X.X
.XEX
-XXmb
XXm
X-X YYYY
t
XX
YX
d17 0 Dio
arC
arE
Y
Y-X YX.XE
e
el
5 Display the pump type for each
channel
7 Display the pressure for each channel
8 Press “V/I/P”
e
1-7000
2-7000
3+7000S
0+700 e4
St
V
Fi
tVep
VV St
p
x
p
10 Press “V/I/P”
1
4X.XE-XX
X.X
E
X.X -XX A2
XE- X A
AXE-X
XX.3
A
12 Press “V/I/P”
9 Display the voltage and operation
mode “Step Mode” – “Fixed mode” for each channel
11 Display the current for each channel
92/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Display and Menus
Information on a Single Channel
You can display all the information (voltage, current, pressure and pump type) for each single pump. To do this, press the HV-x key, where x corresponds to the channel to display:
Figure 22
In this case, the pump type, pressure, current and voltage of channel 3 are being displayed.

Commands

You can give the controller three types of commands:
Switch on/off channels
Activate/disactivate Protect mode
Change output voltage
Switching Channels On/Off
To switch a high voltage channel on or off, keep the HV-ON/OFF key pressed while you press the HV-x key, where x is the number of the channel you want to switch on or switch off.
-40 arS5-57
5
X.XE
3X.
+70 V
-
XE- X
00 S
elCt
l
X
X
X
a
mB r
A
pet
Activating /Disactivating Protect Mode
To activate or disactivate Protect mode, keep the Protect key pressed while you press the HV-x key, where x is the number of channel for which you want to activate or disactivate the “Protect” functionality.
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 93/104
Technical Information
5
Display and Menus

Menu

Changing the Output Voltage
To change the output voltage choosing between 7KV, 5KV, 3KV, Step­Mode and Fixed-Mode, keep the Fixed Step key pressed while you press the HV-x key, where x is the number of the channel for which you want to change the output voltage.
The output voltage changes cyclically between “STEP 7 KV, 5 KV, 3 KV”.
Keeping the “Mode” key pressed for a long time (> 2 sec), you enter the Menu. In the Menu, you can configure some parameters of the controller. These configurable parameters can be divided into two groups:
Controller general parameters
Specific parameters for each channel.
The general parameters of the controller are the following:
Pressure measurement unit: mbar, torr, pascal
Serial baud rate: 1200, 4800, 9600
Serial Type: RS232, RS485
RS485 Address: from 0 to 31
Auto start: Yes, No
Fan: Always on, switches on if the current descends below 1mA
Set Point: The set-point can be associated with the channels and
a value set
Analog output: Analog output is associated with the channels.
The specific parameters for each channel are the following:
Pump: Select the type of pump
I Protect: Set the Protect current
94/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Technical Information
5
Display and Menus
Power max: Set the maximum power.
Scrolling Through the Menus
The 4UHV controller menu has a three-level structure.
To scroll through the menus, remaining on the same level, press
the keys “ ◄ “ “ ►”.
To go to submenu, press “Enter” in the transition menus.
To escape to go back, press “Esc” at any time.
In multiple-choice menus, the symbol “ “ appears next to the
value currently in use and the value currently used will flash.
To change the value in each menu, press the key + or -. This
causes the symbol “ ■ “to move, but the old value continues to flash.
To save the new value, you must press “Enter”. As you press
“Enter”, the new value is saved and starts to flash.
If it is not possible for all the choices to be displayed simultaneously, the values will scroll across (the titles of the menus remain fixed).
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 95/104
Technical Information
5
Display and Menus
First Level Second Level Third Level
OLNFI GURE
GENERCA
HV1
H■V2
Menu Screens
Examples of all the screens that appear in the Menu are provided below.
Table 16 Menu Screens
G
Pr
ess
ure
mBa r
To r r
COSeNF I GEG- NERL
rial Baud Ra
1200
4800
2RS2 3
5 RS 4 8
CO -NGE
Ser AdFd
la
i
AL
RNF ICO E N EG-
A
te
ENNFIG - GCO
TSer i a l
ERA
eyp
ERN
r
L
LXXAIG
96/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
NERA-GECO N I GF
Aut o
tstar
SYE
O N
CO N F I G - G EN ERAL
Fan
T
HRESHOLD
ALWAYS ON
L
Technical Information
First Level Second Level Third Level
GE N E R A L - S E T PO INT
Hx
CX.XE-XXA
CO G U RNF EI
HV3
HV1
HV2
Se t po i
SET POI NT A
S
ET P BOINT
GENntERCO G -NF I
AL
A
NERALGEON F I G -C
utog Onal
ALOG ANA
BLOGANA
HV
1
Pu
m
p
XXXXX
I Prot
HV1
XX meA
XXXXX
ct
Display and Menus
Se t Po i n t
na Olo
A
gutA
CHx
5
A
TEAL-GE RNE
MORE
Po
w
HV1
XX
er Max
WX
Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A) 97/104
Technical Information
5

Orderable Parts

Orderable Parts
Part Description
Controllers
929-9010 929-9011 929-9020 929-9021 929-9100 929-9101 929-9200 929-9201 929-9400 929-9401 929-9210
929-9211
929-9022
929-9402
929-9212
929-9213
HV Cables
929-0705 929-0707 929-0708 929-0709
4UHV with 1 channel 200W Negative 4UHV with 1 channel 200W Positive 4UHV with 2 channels 200W Negative 4UHV with 2 channels 200W Positive 4UHV with 1 channel 120W Negative 4UHV with 1 channel 120W Positive 4UHV with 2 channels 80W Negative 4UHV with 2 channels 80W Positive 4UHV with 4 channels 80W Negative 4UHV with 4 channels 80W Positive 4UHV with 2 channels 80W Negative + 1 channel 200W Negative 4UHV with 2 channels 80W Positive + 1 channel 200W Positive 4UHV with 1 channel 200W Positive + 1 channel 200W Negative 4UHV with 2 channels 80W Positive + 2 channels 80W Negative 4UHV with 2 channels 80W Positive + 1 channel 200W Negative 4UHV with 2 channels 80W Negative + 1 channel 200W Positive
HV bakeable cable, radiation resistant, 4 meter HV bakeable cable, radiation resistant, 7 meter HV bakeable cable, radiation resistant, 10 meter HV bakeable cable, radiation resistant, 20 meter
98/104 Agilent 4UHV Ion Pump Controller User Manual / 87-900-137-01 (A)
Loading...