144 MAIN CATALOG PLC AUTOMATION
—
AC500-XC
Technical data
AC500-XC CPUs
Typ e PM591-ETH-XC PM592-ETH-XC PM595-4ETH-M-XC
Supply voltage 24 V DC
Current consumption on 24 V DC
Min. (module alone) 0.150 A 0.400 A
Max. (all couplers and I/Os) 0.850 A 1.2 A
User program memory - Flash EPROM and RAM 4096 kB 16384 kB
Integrated user data memor y 5632 kB thereof 1536 kB saved 16384 kB thereof 3072 kB saved
User Flashdisk (Data-storage, program access or also
external with FTP)
Plug-in memory card depending on SD-Card used: no SD- HC card allowed, use MC502 accessor y
Web ser ver's data for user RAM disk 8 MB 32 MB
Data buffering battery no battery needed
Real-time clock (with battery back-up)
Cycle time for 1 instruction (minimum)
Binary 0.002 µs 0.0006 µs
Word 0.004 µs 0.001 µs
Floating-point 0.004 µs 0.001 µs
Max. number of centralized inputs/outputs
Max. number of extension modules on I/O bus up to max. 10 (S500 allowed)
Digital inputs / outputs 320 / 320
Analog inputs / outputs 160 / 160
Max. number of decentralized inputs/outputs depends on the used standard Fieldbus (1)
Program execution
Cyclical / Time controlled / Multi tasking
User program protection by password
Internal interfaces
COM1
RS232 / RS485 configurable
Connection (on terminal bases) pluggable spring terminal block, use TK502 cable in accessory
Programming, Modbus RTU, ASCII, CS31 master
COM2
RS232 / RS485 configurable
Connection (on terminal bases) D-sub 9 female, use TK501 cable in accessory
Programming, Modbus RTU, ASCII
FieldBusPlug
Serial neutral interface
Connection (on terminal bases) M12 male, 5 pole –
Functions programming cable UTF-21-FBP, slave
Ethernet
Ethernet connection (on terminal bases) RJ45 RJ45 2x RJ45
Ethernet functions: online Access, ICMP (Ping),
DHCP, IP configuration protocol, UDP data
exchange, Modbus TCP, HTTP (integrated Web
server), IEC60870-5-104 remote control protocol,
MQTT, SNTP ( Time synchronization), FTP server,
SMTP client, Socket programming
Ethernet based Fieldbus
Ethernet connection (on CPU module) – 4 x RJ45 (2x inter faces with 2-port switch)
Downloadable protocols like:
PROFINET IO RT Controlle r / EtherC AT Master or
Ethernet e.g. Modbus TCP client/server
CPU display LC display and 8 function keys –
Function RUN / STOP, status, diagnosis Status, diagnosis
RUN / STOP, RESET push buttons –
LEDs for various status display –
Timers / Counters unlimited / unlimited
Approvals See detailed page 238 or www.abb.com/plc
(1) e.g. C S31 Fieldbu s: up to 31 stat ions with up to 1 20 DIs / 120 DO s or up to 32 AI s / 32 AOs per station.
– Yes, 4 GB Flash non removable
/ /
communication depending on FieldBusPlug used
(PROFIBUS DP, CANopen, DeviceNet)
–
–
–