Carrier 19XRV User Manual

5 (1)

19XRV with PIC III Controls Rockwell PowerFlex 755 VFD Option

Start-Up and Service Instructions

SAFETY CONSIDERATIONS

Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.

Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.

DANGER

ONLY QUALIFIED Electrical Personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment.

READ AND UNDERSTAND this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.

DO NOT install modification kits with power applied to the drive. Disconnect and lock out incoming power before attempting such installation or removal. Failure to observe this precaution could result in severe bodily injury or loss of life

UNUSED WIRES in conduit must be grounded at both ends to avoid a possible shock hazard caused by induced voltages. Also, if a drive sharing a conduit is being serviced or installed; all drives using this conduit should be disabled to eliminate the possible shock hazard from cross-coupled motor leads. Failure to observe these precautions could result in bodily injury.

DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrigerating, and Air Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.

PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.

DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.

NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.

DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen. DO NOT VALVE OFF any safety device.

BE SURE that all pressure relief devices are properly installed and functioning before operating any chiller.

THERE IS A RISK OF INJURY OR DEATH by electrocution. High voltage may be present on the motor leads even though the motor is not running. Open the power supply disconnect before touching motor leads or terminals.

WARNING

DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant (liquid and vapor) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases.

DO NOT work on high-voltage equipment unless you are a qualified electrician.

DO NOT WORK ON electrical components, including control panels, switches, VFD, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.

LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.

AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.

DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.

CAUTION

TO AVOID an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before servicing. Check the DC bus voltage at the Power Terminal Block by measuring between the +DC and - DC terminals, between the +DC terminal and the chassis, and between the -DC terminal and the chassis. The voltage must be zero for all three measurements.

THE USER is responsible to conform with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

THIS DRIVE contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. For static control procedures, reference Rockwell publication Guarding Against Electrostatic Damage, or any other applicable ESD protection handbook.

DO NOT alter the setting of any jumper. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

USE OF power correction capacitors on the output of the drive can result in erratic operation of the motor, nuisance tripping, and/or permanent damage to the drive. Remove power correction capacitors before proceeding. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

MOST CODES require that upstream branch circuit protection be provided to protect input power wiring. If fuses are chosen as the protection method, refer to the PowerFlex 750 user manual. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

DO NOT route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

DISTRIBUTION SYSTEM short circuit capacity shall not exceed the rating of the drive. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.

DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.

USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance.

BE AWARE that certain automatic start arrangements CAN ENGAGE THE VFD, TOWER FAN, OR PUMPS. Open the disconnect ahead of the VFD, tower fans, or pumps.

USE only repair or replacement parts that meet the code requirements of the original equipment.

PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53190012-01

Printed in U.S.A.

Form 19XRV-3SS

Pg 1

711 3-11

Replaces: New

CONTENTS

Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

ABBREVIATIONS AND EXPLANATIONS . . . . . . . . . . 2

Required Publications. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Getting Assistance from Rockwell Automation . . . 2

IDENTIFYING DRIVE COMPONENTS. . . . . . . . . . . . 2-5 Opening the VFD Access Door . . . . . . . . . . . . . . . . . . . 3 Drive Assembly Catalog Number . . . . . . . . . . . . . . . . . 3

Components and Physical Data . . . . . . . . . . . . . . . . . . 3

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8 Alternate Wire Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Verify Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Configure the VFD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Commissioning the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 6 Check Internal Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . 7

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27 Troubleshooting the Drive . . . . . . . . . . . . . . . . . . . . . . . . 8

ICVC ALERT CODES

ICVC ALARM CODES

TEST EQUIPMENT NEEDED TO TROUBLESHOOT

VERIFYING THAT DC BUS CAPACITORS ARE DISCHARGED

HIGH TEMPERATURE ALARMS

MAIN CONTROL BOARD (MCB) COMPONENTS

Checking Power Modules and Motor Input

with Input Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Servicing the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

REMOVING THE DRIVE

RIGGING THE ENCLOSURE

REPLACING THE GATEWAY (A-B20-750-20COMM OPTION CARD)

CHILL PLATE FAN AND INTERNAL FAN REPLACEMENT

Parts Identification and Location . . . . . . . . . . . . . . . . 26 APPENDIX A — WIRING SCHEMATICS . . . . . . . 28-31

APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING . . . . . . . . . . . . . . . 32-38

INTRODUCTION

The Carrier VFD option Start-Up and Service Manual is intended for trained and qualified service personnel, and is to be used during start up, operation, and maintenance of Rockwell/ Allen-Bradley PF755L drive.

ABBREVIATIONS AND EXPLANATIONS

Frequently used abbreviations in this manual include:

CCM

Chiller Control Module

DC

Direct Current

DPI

Drive Peripheral Interface

ENET

Ethernet

ICVC

International Chiller Visual Controller

IGBT

Insulated Gate Bipolar Transistor

I/O

Inputs/Outputs

IP

Internet Protocol

IPWM

Inverter Pulse Width Modulation

MCB

Main Control Board

MOV

Metal Oxide Varistor

PE

Protective Earthing Conductor

SIO

Sensor Input/Output

STS

Status

Required Publications — The Carrier VFD option Start-Up and Service Manual must be used with the following manuals:

The latest version of the PowerFlex 750-Series AC Drives manuals

The latest revision of the Start-Up, Operation, and Maintenance Instructions for the 19XRV with PIC III Controls

Getting Assistance from Rockwell Automa-

tion — Contact the local Rockwell Automation sales office with any questions or problems relating to the products described in this manual. For technical support on drives between the hours of 7:00 am and 6:00 pm CST, M-F, call 1-262-512- 8176. For information about after-hours phone support and onsite support call 1-800-800-0522.

Before calling, have the following information available from the Allen-Bradley data nameplate located inside the enclosure on the right wall. See Fig. 1.

Allen-Bradley ID or CAT. NO.

Carrier VFD Code

Allen-Bradley serial number

Fig. 1 — Allen Bradley Data Nameplate

A19-1830

IDENTIFYING DRIVE COMPONENTS

A chiller control schematic and a VFD schematic are included in Appendix A.

WARNING

DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter rated for the DC bus voltage to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.

An isolated multimeter will be needed to measure DC bus voltage and to make resistance checks. The drive’s DC bus capacitors retain hazardous voltages after input power has been disconnected.

711

2

Opening the VFD Access Door

WARNING

Before removing the drive enclosure, open access door and verify that the DC bus voltage has dropped to zero by checking the terminals behind the access door. Failure to observe this precaution could result in severe bodily injury or loss of life.

1.Using recommended screwdriver = 6.4 mm (0.25 in.) flat or T20 star, open access door. See Fig. 2.

2.Check to be sure that the voltage between DC+ and DCand from each DC terminal to the chassis is zero before proceeding. See Fig. 3.

Drive Assembly Catalog Number — See Fig. 4 for an example Catalog Number.

Components and Physical Data — The AllenBradley PF755 Frame 6 drive is used for the 230-amp rated application (carrier Part No. 19XRV0230...). See Fig. 5.

The Allen-Bradley PF755 Frame 7 drive is used for the 335-amp and 445-amp rated application (Carrier Part No. 19XVR0335... and 19XVR0445... respectively). See Fig. 6.

See Fig. 7 for the dimensions of Frames 6 and 7.

Fig. 2 — Opening Access Door

A19-1831

1 L1 L2 L3

I

LOCKOUT/TAGOUT

O

2

0V

 

DC BUS TEST

DC+ DC–

 

TERMINALS

0V

MULTIMETER

LOCATED INSIDE

 

ACCESS DOOR

A19-1842

21P 1 0248

21P PF755 VFD

Voltage Rating

1– 460 to 480 v, 60 Hz

2– 380 to 415 v, 50 Hz

3– 380 to 400 v, 60 Hz 4– 401 to 439 v, 60 Hz

PF755 Full Load Amp Rating (Maximum Continuous Amps)* 0248 – 248 0361 – 361 0477 – 477

* For Carrier applications, maximum continuous amp ratings are 230, 335, and 445.

Fig. 3 — Check DC Bus Terminals

A19-1814

3 - 3 - 0 - 0 - C

Customer

C – Carrier

Meter Package

0 – No Meter Package

1 – Analog Meter Package

Input Reactor

0 – No Input Reactor

1 – 3% Input Line Reactor

Disconnect/Breaker Options

3 – 65 KAIC Capacity Breaker

4 – 100 KAIC Capacity Breaker

Drive Assembly

3 – Unit Mount NEMA 1 Liquid Cooled

Fig. 4 — Drive Assembly Catalog Number Nomenclature

3

Carrier 19XRV User Manual

 

 

 

A19-

 

 

1832

 

 

LEGEND

NO.

NAME

 

DESCRIPTION

1

Power Terminals

 

R/L1, S/L2, T/L3, U/T1, V/T2, W/T3

2

PE Grounding Studs

 

Terminating point to chassis ground

 

 

for incoming motor shield

 

 

 

3

DC Bus and Brake

 

+DC, -DC, BR1, BR2

Terminals

 

 

 

 

 

4

PE-A and PE-B

 

MOV and CMC Jumper Wires

5

DC+ and DC-

 

Bus Voltage Test Points

Fig. 5 — Frame 6 Drive Components

A19-1833

LEGEND

NO.

NAME

DESCRIPTION

1

Power Terminals

R/L1, S/L2, T/L3, U/T1, V/T2, W/T3

2

PE Grounding Studs

Terminating point to chassis ground

 

for incoming motor shield

 

 

3

DC Bus and Brake

+DC, -DC, BR1, BR2

Terminals

 

 

 

4

PE-A and PE-B

MOV and CMC Jumper Wires

5

DC+ and DC-

Bus Voltage Test Points

Fig. 6 — Frame 7 Drive Components

4

A19-1834

Fig. 7 — Enclosure Dimensions - Frames 6 and 7

START-UP

DANGER

Internal components and circuit boards of the drive are live when the drive is connected to incoming power. Coming into contact with this voltage is extremely dangerous and will result in severe personal injury or death.

The motor terminals U, V, W and the DC-link/brake resistor terminals B+/R+, R- are live when the drive is connected to incoming power, even if the motor is not running.

Do not make any connections when the drive is connected to the incoming power.

After having disconnected the drive, wait until the indicators on the keypad go out (if no keypad is attached see the indicator through the keypad base). Wait 5 more minutes before doing any work on drive connections. Do not even open the cover before this time has expired..

Before connecting the drive to the incoming power, make sure that the switchgear enclosure door is closed.

WARNING

The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O terminals may have a dangerous control voltage present even when the drive is disconnected from incoming power. Coming into contact with this voltage could result in severe personal injury.

CAUTION

If other than refrigerant cooling is used, before connecting the drive to the incoming power, make sure that the coolant is circulating and has no leaks.

CAUTION

When working with the Drive Explorer, never use the Rotate function as the motor will immediately start and severe compressor damage could result.

Alternate Wire Lugs — In the case where the incoming power wire size does not fit the standard lug, alternate lugs may be used. See Table 1. Note that lugs rated for a higher current than the circuit breaker may be used.

Table 1 — Wire Lugs

CIRCUIT

STANDARD

STANDARD

ALTERNATE

ALTERNATE

LUG CABLE

LUG CABLE

BREAKER

ABB LUG

RANGE

ABB LUG

RANGE

 

 

 

65 KAIC

 

 

 

 

(Standard)

K6TJ

(3) 2/0 - 400

K6TH

(2) 250 - 500

100 KAIC

MCM

MCM

 

 

(Optional)

 

 

 

 

Verify Installation — Record the following job information:

1.Job Name

2.Job Number

3.City

4.State

5.Zip Code

Record the following nameplate information:

1.From the Allen-Bradley nameplate (Fig. 1) located inside the VFD enclosure:

a.Allen-Bradley ID or CAT NO.

b.Allen-Bradley Serial Number

c.Carrier Part Number

2.From the machine nameplete (Fig. 8) located inside the VFD enclosure:

a.Chiller Serial Number

b.Chiller Model

c.Motor rated load amps

d.Motor nameplate rpm

e.Motor nameplate kW

f.Motor nameplate voltage

g.IPWM (pulse width modulation) frequency

h.Voltage

3.From the drive module label (Fig. 9) located on the drive module:

a.Model or Cat. Number

b.Serial Number

4.From the ICVC control panel screen:

a.Carrier Part Number and Revision

b.ICVC Software Number

Rockwell PowerFlex 750 drive start-up must be registered on the Rockwell website. Rockwell Registration site URL: http://www.automation.rockwell.com/warp/default.asp

5

a19-

1846

A United Technologies Company

MODEL NUMBER

SERIAL NUMBER

MACHINE NAMEPLATE SUPPLY DATA

VOLTS/PHASE/HERTZ

LOCKED ROTOR AMPS

OVERLOAD TRIP AMPS

MAX FUSE/CIRCUIT BREAKER SIZE

MIN SUPPLY CIRCUIT AMPACITY

MACHINE ELECTRICAL DATA

MOTOR NAMEPLATE VOLTAGE

COMPRESSOR 100% SPEED

RATED LINE VOLTAGE

RATED LINE AMPS

RATED LINE KILOWATTS

MOTOR RATED LOAD KW

MOTOR RATED LOAD AMPS

MOTOR NAMEPLATE AMPS

MOTOR NAMEPLATE RPM

MOTOR NAMEPLATE KW

INTERTER PWM FREQUENCY

SAFETY CODE CERTIFICATION

THE COMPRESSOR MOTOR CONTROLLER AND OVERLOAD PROTECTION MUST BE

IN ACCORDANCEWITH CARRIER SPECIFICATION Z-420.

19XV05008701 REV. 3

Fig. 8 — Machine Nameplate

a19-

1924

Fig. 9 — Drive Module Label

Configure the VFD — All configurations required by the VFD are supplied by the ICVC through the VFD Gateway. Any configuration changes necessary and possible are made on the ICVC screens. A complete set of configurations is transmitted to the VFD each time the controls are powered up.

The following is from the 19XRV PIC III ICVC screen. Parameters in italics are to be entered or confirmed at start-up. Parameters in bold are to be changed only after consulting with Carrier service engineering. See Table 2.

Table 2 VFD Configurations

PARAMETER

DEFAULT VALUE

Motor Nameplate Voltage

460

Compressor 100% Speed

 

Line Freq=60 Hz? (No=50)

Yes

Rated Line Voltage*

460

Rated Line Amps*

200

Rated Line Kilowatts *

100

Motor Rated Load kW*

100

Motor Rated Load Amps*

200

Motor Nameplate Amps

100

Motor Nameplate RPM

3456

Motor Nameplate KW

100

Inverter PWM Frequency (0 = 4 kHz, 1 =

1

2 kHz)

 

Skip Frequency 1 (Hz)

102.0

Skip Frequency 2 (Hz)

102.0

Skip Frequency 3 (Hz)

102.0

Skip Frequency Band Line (Hz)

0.0

Voltage % Imbalance

10

Line Volt Imbalance Time (sec)

10

Line Current % Imbalance

40

Line Current Imbal Time (sec)

10

Motor Current % Imbalance

40

Motor Current Imbal Time

10

Increase Ramp Time (sec)

30

Decrease Ramp Time (sec)

30

Single Cycle Dropout (DSABLE/ENABLE)

DSABLE

* Parameters marked with an * are not downloadable to the VFD but are used in other calculations and algorithms in the ICVC.

NOTES:

1.Parameters in italics are to be entered or confirmed at start-up.

2.Parameters in bold are to be changed only after consultation with service engineering.

Commissioning the Unit — The commission procedure is as follows:

1.If the chiller has been stored outdoors, allow at least 24 hours room temperature stabilization prior to commissioning. Ensure any condensation that occurs as a result of the ambient temperature is allowed to evaporate.

2.Enter parameters in the VFD_CONF screen.

3.Install surge suppression devices if required.

4.Review the power wiring and grounding to ensure that it has been properly connected.

5.Visually examine the inside of the drive enclosure to:

a.Look for signs of corrosion or moisture residue.

b.Remove any dirt or debris.

c.Make sure all vents are clear.

6.Apply power to the drive and take thermal measurements of the capacitor bank and power connections. Do this again before start-up.

7.Measure and record the incoming line voltage. Line-to- line voltages should be balanced within 3% as calculated by Rockwell’s procedure below:

Measure voltages phase-to-phase and phase-to-ground.

6

Vmax = Maximum measured phase-to-phase voltage (A to B, B to C, C to A)

Vmin = Minimum measured phase-to-phase voltage Imbalance Calculation Formula

Vavg

=

(VAB + VBC + VCA)

 

 

3

Imbalance %

=

(Vmax – Vmin) x 100

 

 

Vavg

8.Take a final thermal measurement of the capacitor bank and power after finalizing the installation to ensure all connections are good.

9.If a ground fault occurs, then do the following:

a.Check for a ground in the motor or motor wiring.

b.Check for damage to wiring insulation and that wiring is dry.

c.Verify the motor wiring is separated from ground and there is no connection between phases.

d.Check for failed IGBTs.

10.If an Overcurrent fault occurs, then do the following:

a.Check for excessive load and verify load limit settings on the ICVC.

b.Check motor and wiring insulation.

c.Check parameter settings on VFD_CONF screen in the ICVC.

Check Internal Jumpers — On the Main VFD Control board there are two jumpers labeled J1 HARDWARE ENABLE and J2 SAFETY ENABLE. J1 should be removed and J2 should be in place. See Fig. 10.

There are two jumper wires that connect a particular terminal to chassis ground. The MOV and AC EMI jumper should be connected to the PE-A terminal. The COMMON MODE CAPACITORS to GROUND jumper should be connected to a standoff rather than the PE-B terminal.

Use the recommended tools as follows when connecting jumper wires in Frame 6 and in Frame 7:

Recommended torque (screws and nuts) = 1.36 N·m (120.0 lb·in)

Recommended hex socket = 7 mm

Recommended screwdriver = T20 star type

See Fig. 11A and Fig. 11B for the correct positions of the jumpers.

 

 

LEGEND

NO.

NAME

DESCRIPTION

1

HIM Connector

DPI Port 1 (HIM Cradle) connection.

2

Fan Connector

Power supply for internal cooling fan

 

(Frames 2 & 3).

 

 

 

Battery

User installed CR1220 lithium coin cell

 

Receptacle

battery provides power to the Real Time

3

 

Clock (Optional, not supplied).

 

 

 

 

 

4

DPI Port 2

Cable connection for handheld and

 

remote HIM options.

 

 

5

Embedded EtherNet/

Rotary switches for setting lowest octet

IP Address Selectors

of EtherNet address (forces address to

 

 

192.168.1.xxx).

6Embedded EtherNet/ Network cable connection. IP Connector

7

Jumper J2 SAFETY

Safety enable jumper. Removed when

 

safety option is installed.

 

 

8

Jumper J1 ENABLE

Hardware enable jumper. Removed

 

when a hardware enable configuration is

 

 

utilized.

9

TB1

I/O terminal block.

a19-1921

 

 

TB1 I/O Terminal Designations

FIXED I/O

TERMINAL

NAME

DESCRIPTION

 

Di 0ac

Digital Input 120V AC

Connections for AC power supply.

Di 0ac

Di C

Digital Input Common

Digital input common

Di 0dc

Digital Input 24V DC

Connections for DC power supply.

Di C

Di 0dc

+24V

+24 Volt Power

Connections for drive supplied 24V power.

+24V

 

24 Volt Common

 

 

24VC

 

24VC

 

 

IMPORTANT: Wiring to pluggable terminal block connectors should be supported by wire ties or other means to help prevent unintentional disconnection

Fig. 10 — PF755 Main Control Board

7

A19-1835

Fig. 11A — Jumper Wire Locations — Frame 6

A19-1836

Fig. 11B — Jumper Wire Locations — Frame 7

SERVICE

WARNING

DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.

Troubleshooting the Drive — The drive can display two kinds of error codes on the ICVC called the Alert and Alarm codes. These codes signal a problem detected during self tuning or drive operation. Alert and Alarm codes are located in the 19XRV Start-Up, Operation and Maintenance Instructions. Note the following differences between Carrier and Allen-Bradley terminology:

A warning message on the ICVC is an ALERT.

The same warning viewed with Rockwell Drive Explorer is a VFD ALARM.

A failure resulting in a shutdown is seen as an ALARM on the ICVC and as a VFD FAULT when viewed with Drive Explorer.

CONDITION CODES

ICVC ALERT

=

VFD ALARM

ICVC ALARM

=

VFD FAULT

See Tables 3-6 and Fig. 12.

ICVC ALERT CODES — An alert condition is indicated by a message at the top of the ICVC default screen. In addition, an exclamation point (!) will appear next to any affected point on an ICVC display screen. The drive will continue to operate during the alert condition. Investigate the cause of the alert to ensure it does not lead to a fault condition. The alert code will automatically be cleared from the ICVC when the condition causing the alert no longer exists. See Table 4.

ICVC ALARM CODES — An alarm condition is also indicated by a message at the top of the ICVC default screen. If an alarm occurs, the drive coasts to stop. The STS (status) light on the drive will turn from Green to Red or Yellow (see Table 3). The detected fault message is maintained on the display until it is cleared by pressing the RESET softkey. See Table 5.

TEST EQUIPMENT NEEDED TO TROUBLESHOOT — An isolated multimeter adequately rated for the DC bus voltage will be needed to measure DC bus voltage and to make resistance checks. Note that dedicated troubleshooting test points are not provided.

Allen-Bradley

7

8

9

4

5

6

1

2

3

 

 

A1

9-

1815

Fig. 12 — Drive Status Indicator

8

Table 3 Drive Status Indicator Descriptions

NAME

COLOR

STATE

DESCRIPTION

 

Green

Flashing

Drive ready but not running, and no faults are present.

 

 

Steady

Drive running, no faults are present.

 

Yellow

Flashing

Drive is not running. A type 2 (non-configurable) alarm condition exists and the

 

 

 

drive cannot be started.

 

 

Steady

Drive is not running, a type 1 alarm condition exists. The drive can be started.

STS (Status)

Red

Flashing

A major fault has occurred. Drive cannot be started until fault condition is

 

 

cleared.

 

 

Steady

A non-resettable fault has occurred.

 

Red/Yellow

Flashing Alternately

A minor fault has occurred. When running, the drive continues to run. System is

 

 

 

brought to a stop under system control. Fault must be cleared to continue. Use

 

 

 

parameter 950 [Minor Flt Config] to enable. If not enabled, acts like a major

 

 

 

fault.

 

Green/Red

Flashing Alternately

Drive is flash updating.

 

None (Unlit)

Off

Adapter and/or network is not powered, adapter is not properly connected to

 

 

 

the network, or adapter needs an IP address.

 

Red

Flashing

An EtherNet/IP connection has timed out.

ENET

 

Steady

Adapter failed the duplicate IP address detection test.

Red/Green

Flashing Alternately

Adapter is performing a self-test.

 

 

Green

Flashing

Adapter is properly connected but is not communicating with any devices on

 

 

 

the network.

 

 

Steady

Adapter is properly connected and communicating on the network.

 

None (Unlit)

Off

Adapter is not powered or is not transmitting on the network.

LINK

Green

Flashing

Adapter is properly connected and transmitting data packets on the network.

 

 

Steady

Adapter is properly connected but is not transmitting on the network.

NOTES:

1.A Type 1 alarm indicates that a condition exists. Type 1 alarms are user configurable.

2.A Type 2 alarm indicates that a configuration error exists and the drive cannot be started. Type 2 alarms are not configurable.

VERIFYING THAT DC BUS CAPACITORS ARE DISCHARGED — The drive’s DC bus capacitors retain hazardous voltages after input power has been disconnected. Perform the following steps before touching any internal components:

1.Turn off and lock out input power. Wait five minutes.

2.Verify that there is no voltage at the drive’s input power terminals.

3.Measure the DC bus potential with a voltmeter while standing on a non-conductive surface and wearing insulated gloves (1000 V). Measure the DC bus potential. See Fig. 5 for the 248-amp drive and Fig. 6 for the 361 and 477-amp drives. The voltage between DC+ and DC-, and from each DC terminal to the chassis must be zero before proceeding.

4.Once the drive has been serviced, reapply input power.

HIGH TEMPERATURE ALARMS — Coolant flow through the cold plate is controlled by an orifice in the refrigerant line leaving the cold plate. The orifice looks like one of the O-ring face seal connectors and in fact is used as one of the connections on the coolant tubing. The difference is that the passage through the fitting is 0.375 in. (9.5 mm). If the orifice is present and condenser liquid flow is present, the liquid will flash to cooler temperature at the orifice. This temperature difference is great enough to be easily felt.

MAIN CONTROL BOARD (MCB) COMPONENTS — Figure 13 shows the drive module with the cover removed. To access the control boards, loosen the screw on the face of the keypad mount and swing the keypad mount upward.

The components on the main control board (MCB) are shown in Fig. 14. Note the location of the terminals labeled MCB I/O. The high pressure switch is wired to these terminals as shown in Fig. 15. In the event of a high condenser pressure alarm, the connections at these terminals should be checked and tightened if necessary.

A typical wiring schematic is shown in Appendix A.

SWING UP KEY PAD

MOUNT TO ACCESS

CONTROL BOARDS

a19-1843

Fig. 13 — Drive Module with Cover Removed

9

DPI PORT 02 (COMPUTER PORT)

DIGITAL INPUT TERMINAL BLOCKS (SLOTS 04 & 05)

ETHERNET/IP ADDRESS SWITCHES

DIGITAL OUTPUT TERMINAL BLOCKS (SLOTS 04 & 05)

EMBEDDED ETHERNET/IP PORT

MCB I/O TERMINALS (AUX FAULT /

HIGH PRESSURE FAULT / ENABLE INPUT)

Fig. 14 — MCB (Main Control Board) Components

a19-1844

*Located outside of starter; connected by field wiring.

Fig. 15 — High Pressure Switch Wiring

a19-1925

10

Table 4 — ICVC Alert Codes

PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

100

PRESTART

STARTS LIMIT

100 Excessive compressor starts

Depress the RESET softkey if additional start

 

ALERT

EXCEEDED

(8 in 12 hours).

is required. Reassess start-up requirements.

101

PRESTART

HIGH BEARING

101 Comp Thrust Brg Temp [VALUE]

Check oil heater for proper operation.

 

ALERT

TEMPERATURE

exceeded limit of [LIMIT]*.

Check for low oil level, partially closed oil sup-

 

 

 

 

ply valves, clogged oil filters.

 

 

 

 

Check the sensor wiring and accuracy.

 

 

 

 

Check Comp Thrust Brg Alert setting in

 

 

 

 

SETUP1 screen.

102

PRESTART

HIGH MOTOR

102 Comp Motor Winding Temp

Check motor sensors for wiring and accuracy.

 

ALERT

TEMPERATURE

[VALUE] exceeded limit of [LIMIT]*.

Check motor cooling line for proper operation,

 

 

 

 

or restrictions.

 

 

 

 

Check for excessive starts within a short time

 

 

 

 

span.

 

 

 

 

Check Comp Motor Temperature Override

 

 

 

 

setting in SETUP1 screen.

103

PRESTART

HIGH

103 Comp Discharge Temp [VALUE]

Allow discharge sensor to cool.

 

ALERT

DISCHARGE

exceeded limit of [LIMIT]*.

Check sensor wiring and accuracy.

 

 

TEMP

 

Check for excessive starts.

 

 

 

 

Check Comp Discharge Alert setting in

 

 

 

 

SETUP1 screen.

104

PRESTART

LOW

104 Evaporator Refrig Temp [VALUE]

Check transducer wiring and accuracy.

 

ALERT

REFRIGERANT

exceeded limit of [LIMIT]*.

Check for low chilled fluid supply

 

 

TEMP

 

temperatures.

 

 

 

 

Check refrigerant charge.

 

 

 

 

Check Refrig Override Delta T in SETUP1

 

 

 

 

screen.

105

PRESTART

LOW OIL

105 Oil Sump Temp [VALUE]

Check oil heater contactor/relay and power.

 

ALERT

TEMPERATURE

exceeded limit of [LIMIT]*.

Check oil level and oil pump operation.

106

PRESTART

HIGH

106 Condenser Pressure [VALUE]

Check transducer wiring and accuracy.

 

ALERT

CONDENSER

exceeded limit of [LIMIT]*.

Check for high condenser water

 

 

PRESSURE

 

temperatures.

 

 

 

 

Check high condenser pressure switch wiring.

107

PRESTART

LOW LINE

107 Percent Line Voltage [VALUE]

Check voltage supply.

 

ALERT

VOLTAGE

exceeded limit of [LIMIT]*.

Check voltage transformers and switch gear.

 

 

 

 

Consult power utility if voltage is low.

108

PRESTART

HIGH LINE

108 Percent Line Voltage [VALUE]

Check voltage supply.

 

ALERT

VOLTAGE

exceeded limit of [LIMIT]*.

Check power transformers.

 

 

 

 

Consult power utility if voltage is high.

109

PRESTART

GUIDE VANE

109 Actual Guide Vane Pos

Press STOP button on ICVC and perform

 

ALERT

CALIBRATION

Calibration Required Before Startup.

Guide Vane Calibration in Controls Test

 

 

 

 

screen.

 

 

 

 

Check guide vane actuator feedback

 

 

 

 

potentiometer.

110

PRESTART

HIGH

110 Rectifier Temperature [VALUE]

Check that VFD refrigerant isolation valves

 

ALERT

RECTIFIER

exceeded limit of [LIMIT]*.

are open.

 

 

TEMP

 

Check VFD refrigerant cooling solenoid and

 

 

 

 

refrigerant strainer.

 

 

 

 

Check for proper VFD cooling fan operation

 

 

 

 

and blockage.

111

PRESTART

HIGH

111 Inverter Temperature [VALUE]

Check that VFD refrigerant isolation valves

 

ALERT

INVERTER

exceeded limit of [LIMIT]*.

are open.

 

 

TEMP

 

Check VFD refrigerant cooling solenoid and

 

 

 

 

refrigerant strainer.

 

 

 

 

Check for proper VFD cooling fan operation

 

 

 

 

and blockage.

*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

11

Table 4 — ICVC Alert Codes (cont)

NORMAL RUN WITH OVERRIDES

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

120

RUN CAPACITY

HIGH CONDENSER

120 Condenser Pressure

Check condenser water pump operation.

 

LIMITED

PRESSURE

[VALUE] exceeded limit of

Check for high condenser water temperatures or

 

 

 

[LIMIT]*.

low flow rate. Verify that isolation valves are

 

 

 

 

open.

 

 

 

 

Check Cond Press Override setting in SETUP1.

121

RUN CAPACITY

HIGH MOTOR

121 Comp Motor Winding

Check for closed valves or restriction in motor

 

LIMITED

TEMPERATURE

Temp [VALUE] exceeded

cooling lines.

 

 

 

limit of [LIMIT]*.

Check for closed refrigerant isolation valves.

 

 

 

 

Check Comp Motor Temp Override setting in

 

 

 

 

SETUP1.

122

RUN CAPACITY

LOW EVAP REFRIG

122 Evaporator Refrig

Check refrigerant charge.

 

LIMITED

TEMP

Temp [VALUE] exceeded

Check that optional cooler liquid line isolation

 

 

 

limit of [LIMIT]*.

valve is fully open.

 

 

 

 

Check for excessive condenser flow or low

 

 

 

 

chilled water flow.

 

 

 

 

Check for low entering cooler temperature.

 

 

 

 

Check that condenser inlet and outlet water

 

 

 

 

nozzles are piped correctly.

 

 

 

 

Check for waterbox division plate gasket bypass.

123

RUN CAPACITY

HIGH COMPRESSOR

123 Surge Prevention

Check for high condenser water temperature or

 

LIMITED

LIFT

Override: Lift Too High For

low suction temperature.

 

 

 

Compressor

Check for high Evaporator or Condenser

 

 

 

 

approaches.

 

 

 

 

Check surge prevention parameters in

 

 

 

 

OPTIONS screen.

124

RUN CAPACITY

MANUAL GUIDE VANE

124 Run Capacity Limited:

Target Guide Vane Position has been forced in

 

LIMITED

TARGET

Manual Guide Vane Target.

the COMPRESS screen. Select and RELEASE

 

 

 

 

force to return to normal (automatic) operation.

125

RUN CAPACITY

LOW DISCHARGE

No Alert message.

Check for oil loss or excess refrigerant charge.

 

LIMITED

SUPERHEAT

 

Verify that the valves in the oil reclaim lines are

 

 

 

 

open.

126

RUN CAPACITY

HIGH RECTIFIER TEMP

126 Rectifier Temperature

Check Rectifier Temp Override in SETUP1

 

LIMITED

 

[VALUE] exceeded limit of

screen.

 

 

 

[LIMIT]*.

Check that VFD refrigerant isolation valves are

 

 

 

 

open.

 

 

 

 

Check VFD refrigerant cooling solenoid.

 

 

 

 

Check for proper VFD cooling fan operation and

 

 

 

 

blockage.

127

RUN CAPACITY

MANUAL SPEED

No Alert message.

Chiller is not in automatic temperature control.

 

LIMITED

CONTROL

 

 

128

RUN CAPACITY

HIGH INVERTER TEMP

128 Inverter Temperature

Check Inverter Temp Override in SETUP1

 

LIMITED

 

[VALUE] exceeded limit of

screen.

 

 

 

[LIMIT]*.

Check that VFD refrigerant isolation valves are

 

 

 

 

open.

 

 

 

 

Check VFD refrigerant cooling solenoid.

 

 

 

 

Check for proper VFD cooling fan operation and

 

 

 

 

blockage.

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

12

Loading...
+ 28 hidden pages