York D1NA018, D2NA060 User Manual

®
CAUTION
THE ENCLOSED INST AL LAT I ON INSTRUCT I ONS AND ANY APPL ICABL E
LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMI TED
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
THIS PRODUCT MUST B E INSTALLED IN STRICT COMPLIANCE WITH
WARNING
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAM AGE.
I NCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE
INSTALLATION INSTRUCTION
CHAMPION®SERIES
SINGLE PACKAGE AIR CONDITIONERS
GAS/ELECTRIC, AIR-COOLED
Supersedes: 035-18265-000-A-0801
MODELS D1NA018 THRU 048
AND MODEL D2NA060
1-1/2 THRU 5 TON
(10 SEER)
GENERAL
YORK Model D1NAandD2NAunits are cooling/heating air con ditioners designed for outdoor installation. Only gas piping, elec tric power and duct connections are required at the point of installation.
035-18265-001-A-0202
-
-
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
·
Do not try to light any appliance.
·
Extinguish any open flames.
·
Do not touch any electrical switch; do not use any phone in your building.
·
Immediately call your gas supplier from aneighbor's phone. Follow the gas supplier's instructions.
·
If you cannot reach your gas supplier, call the fire department.
The gas-firedheaters have hot surfacetopilot ignition. The tu bular heat exchangers are aluminized steel.
INSPECTION
As soon as a unit is received, it should be inspected for possi ble damage during transit. If damage is evident, the extent of thedamage shouldbe notedonthe carrier'sfreight bill.Asepa­rate request for inspection by the carrier's agent should be made in writing. Refer to Form 50.15-NM for additional infor­mation.
REPLACEMENT PARTS
Refer to Replacement Parts, Form 530.46-RP1Y, RP2Y, RP3Y, RP4Yand RP5Y for Key Replacement Parts.
All forms referenced in this instruction may be ordered from:
Standard Register Norman, OK 73069 Toll Free: Tel. 877-318-9675/Fax. 877-379-7920
APPROVALS
Design certified by CGA and AGAlisted as follows:
1. For use as a forced air furnace with cooling unit.
2. For outdoor installation only.
3. For installation directly on combustible flooring or, in U.S., on wood flooring or Class A; B; C roof covering material.
4. For installation on combustible material.
5. For use with natural gas and/or propane (LP) gas.
-
-
-
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING.Notes are intended to clarify or make theinstallationeasier.Cautions and/or equipment damage may result if installation procedure is not handled properly.
aregiven topreventequipment damage.Warningsare giventoalert installerthatpersonal injury
035-18265-001-A-0202
TABLE OF CONTENTS
General Inspection Replacement Parts Approvals Nomenclature
Limitations Location Rigging and Handling Clearances Ductwork Roof Curb Filters Condensate Drain Service Access Thermostat Power and Control Wiring Compressors Combustion Discharge Gas Piping Gas Connection Flue Vent Hoods
Heating............................................................................ 9
Cooling ............................................................................ 9
Circulating Fan................................................................. 9
Pre-start Check List......................................................... 9
Operating Instructions...................................................... 9
To Turn Off Gas To Unit................................................... 9
Post-Start Check List (Gas)............................................. 9
Manifold Gas Pressure Adjustment................................. 10
Burner Instructions Hot Surface Pilot Instructions Adjustment of Temperature Rise Checking Gas Input Secure Owner's Approval
Normal Maintenance Cleaning Flue Passages and Heating Elements
............................................................................
........................................................................
..........................................................
.........................................................................
..................................................................
INSTALLATION
........................................................................
...........................................................................
......................................................
......................................................................
..........................................................................
........................................................................
...............................................................................
............................................................
................................................................
.......................................................................
................................................
...................................................................
....................................................
.......................................................................
...............................................................
..............................................................
SEQUENCE OF OPERATION
START-UP
...........................................................
..........................................
.....................................
.........................................................
................................................
MAINTENANCE
........................................................
.............
10 10 11 11 11
12 12
1 1 1 1 2
3 3 3 3 3 4 4 4 4 4 4 4 5 5 5 6
Troubleshooting Chart
No. Description
Page
1 Units Application Data 2 Natural Gas Application Data 3 LP Gas Application Data 4 Natural Gas Pipe Sizing 5 LP Gas Pipe Sizing 6 Physical Data 7 Unit Weights 8 Electrical Data
9 Gas Rate - Cubic Feet Per Hour
10 Superheat Charging Table, 018
11 Superheat Charging Table, 024 12 Superheat Charging Table, 030 13 Superheat Charging Table, 036
14 Superheat Charging Table, 042................... 14
15 Superheat Charging Table, 048................... 14
16 Superheat Charging Table, 060................... 14
TROUBLESHOOTING
.....................................................
TABLES
.................................
......................
.............................
..............................
......................................
...............................................
................................................
.............................................
...................
...................
...................
...................
.................
15
3 5 5 5 5 6 7 7
11 13 13 13 13
FIGURES
No. Description
Page
1 Field Wiring Diagram................................... 4
2 External Supply Connection........................ 5
3 Flue Vent Hood 4 Center of Gravity 5 Dimensions and Clearances 6 Gas Valves 7 Proper Flame Adjustment 8 Ignitor and Flame Sensor Assembly 9 Typical Wiring Diagram, (208/230-1-60)
10 Typical Wiring Diagram, (208/230-3-60)
11 Typical Wiring Diagram, (460-3-60)
............................................
.........................................
........................
..................................................
............................
............
......
......
.............
6 7
8 10 10 10 16 16 17
NOMENCLATURE
1 N A 0 602 6N
D
PRODUCT CATEGORY
D = Single Package
Air Conditioner
PRODUCT GENERATION
1 = 1st Generation
2 = 2nd Generation
PRODUCT IDENTIFIER
NA = 10 SEER
Gas Heat / Electric Cool
2 Unitary Products Group
NOMINAL COOLING
CAPACITY(MBH)
018 = 18,000 BTUH 024 = 24,000 BTUH 030 = 30,000 BTUH 036 = 36,000 BTUH 042 = 42,000 BTUH 048 = 48,000 BTUH 060 = 60,000 BTUH
0 34
FACTORY
INSTALLED
GAS HEAT
N = Natural Gas
Heat Installed
VOLTAGE CODE
06 = 208/230-1-60 25 = 208/230-3-60 46 = 460-3-60
58 = 575-3-60
NOMINAL GAS HEATING
OUTPUT CAPACITY
036 = 36,000 BTUH 065 = 65,000 BTUH 056 = 56,000 BTUH 090 = 90,000 BTUH
072 = 72,000 BTUH 110 = 110,000 BTUH
INSTALLATION
Not suitable for use with conventional venting systems.
LIMITATIONS
These units must be installed in accordance with the following national and local safety codes.
1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions).
2. NationalFuel Gas Code Z223.1 or CAN/CGAB149.1 or .2 Installation Code.
3. Local gas utility requirements.
4. Local plumbing and waste water codes and other applica ble local codes.
Refer to Table1 for unit application data and to Table2 for gas heat application data.
If componentsare to be added to a unit to meetlocal codes, they aretobe installedatthe dealer'sand/orthecustomer'sexpense.
Size of unit for proposed installation should be based on heat
TABLE 1 - UNIT APPLICATION DATA
2
/ Max.
208/230V
Voltage Variation
Min. / Max
Wet Bulb Temperature (°F) of Air on Evaporator Coil, Min. / Max.
Dry Bulb Temperature (°F) of Air on Condenser Coil, Min.
1 Rated in accordance with ARI Standard 110, utilization"A".
2
A low ambient accessory is available for operation down to 0°F
3
“T1" transformer primary tap must be moved from the 230 volt connection to the 208 volt
connection for low voltage applications of 208 volt and below.
.1
loss/heat gain calculations made in accordance with industry recognized procedures identified by the Air Conditioning Con­tractors of America.
LOCATION
3
460V 414 / 504 575V 518 / 630
187 / 253
57 / 72
45 / 120
3
035-18265-001-A-0202
gle iron frame providing adequate support under the compressor/condenser section.
5. Maintain level tolerance of unit to 1/8" maximum.
RIGGING OR HANDLING
Care must be exercised whenmovingthe unit. Do not remove anypackaging untilthe unit isnear theplace ofinstallation. Rig unit with slings placed under the unit. Spreader bars of suffi cient length should be used across the top of the unit.
BEFORE LIFTING AUNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT
­WILL LIFT EVENLY.
Units may also be movedorlifted with a fork-lift. Slotted open ings in theskid are provided for this purpose. Forks must pass completely through the base.
RefertoTable7forunit weightsandto Figure4forapproximate center of gravity.
CLEARANCES
All units require certain clearances for proper operation and service. Refer to Figure 5 for the clearances required for com­bustion, construction, servicing and proper unit operation.
WARNING:Donot permit overhanging structures or shrubs to
obstruct the condenser air discharge, combustion air inlet or vent outlet.
DUCT WORK
Theseunits areadaptable todownflow useas wellas rearsup­ply and return air duct openings. To convert to downflow, use the following steps:
-
-
Use the following guidelines to select a suitable location for these units.
1. Unit is designed for outdoor installation only.
2. Condenser must have an unlimited supply of air. Where a choiceof locationispossible, positionunit oneithernorth or east side of building.
WARNING:Excessive exposure of this furnace to contami
nated combustion air mayresult equipment dam age or personal injury. Typical contaminates include: permanent wave solutions, chlorinated
1. Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws secur ing each duct cover (save these screws to use later).
2. Install the duct covers, removed in step one, to the rear supply and return air duct openings. Secure with the four (4) screws used in step one.
3. Seal the duct covers with silicone caulk.
-
Duct work should be designed and sized according to the
-
methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.
waxes and cleaners, chlorine based swimming poolchemicals, watersoftening chemicals,carbon tetrachloride, Halogen type refrigerants, cleaning solvents (e.g. perchloroethylene), printing inks, paint removers, varnishes, hydrochloric acid, ce ments and glues, antistatic fabric softeners for clothes dryers, masonry acid washing materials.
3. For ground level installation, a level pad or slab should be used.The thicknessandsize ofthe padorslab usedshould meet local codes and unit weight. Do not tie the slab to the
A closed return duct system shall be used. This shall not pre clude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to mini
-
mize the transmission of noise.
CAUTION: When fastening duct work to the side duct flanges on
theunit,insertthescrews throughtheduct flangesonly. DONOT insertthescrews throughthecasing. Outdoor duct work must be insulated and waterproofed.
building foundation.
4. For roof top installation, be sure the structure will support
NOTE: Be sure to note supply and return openings.
the weight of the unit plus any field installed components. Unitmust beinstalledon alevelroofcurbor appropriatean
Unitary Products Group 3
-
-
-
-
035-18265-001-A-0202
Refer to Figure 5 for information concerning rear and bottom supply and return air duct openings.
ROOF CURB
Onapplications whena roofcurb isused,theunitmust beposi tioned on the curb so the front of the unit is tight against the curb.
FILTERS
Singlephase unitsare shippedwithout afilter and isthe responsi bilityof the installerto securea filter inthe returnair ductwork or install a Filter/Frame Kit (1FF0110 for the D1NA018 thru D1NA042 and 1FF0112 for the D1NA048 and D2NA060).
A filter rack and filters are standard on three phase units.
NOTE: Filters on the D1NA048 and D2NA060 units require
5
the use of a
" nut driver for removal.
16
Filters must always be used and must be kept clean. When fil ters become dirt laden, insufficient air will be delivered by the blower,decreasingyour unitsefficiencyand increasingoperat ing costs and wear-and-tear on the unit and controls.
Filters should be checked monthly especially since this unit is used for both heating and cooling.
CONDENSATE DRAIN
A condensate trap is recommended to be installed in the con­densatedrain. The plumbingmust conform tolocal codes.Use a sealing compound on male pipe threads. Install the conden­sate drain line (
3
“ NPTF) to spill into an open drain.
4
SERVICE ACCESS
Accessto allserviceablecomponents isprovided bythefollow­ing removable panels:
Blower compartment
Gas control/electrical service access
** = Minimum wire size of 18 AWG
wire shuold be used for all field installed 24 volt wire.
PROGRAMABLE
THERMOSTAT ONLY
THERMOSTAT
R
G
W
C
CONTROL WIRING
R
G
YY
W
C
Refer to Figure5 for location of these access panels and mini mum clearances.
THERMOSTAT
The room thermostat should be located on an inside wall ap
-
proximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appli ances. Follow manufacturer's instructions enclosed with the thermostatfor generalinstallationprocedure. Fourcolor coded insulated wires (minimum #18 AWG) should be used to con nect thermostat to unit. See Figure 1.
-
POWER AND CONTROL WIRING
Fieldwiringtotheunit mustconformto provisionsofthe current N.E.C. ANSI/NFPANo. 70 or C.E.C. and/or local ordinances. Theunit mustbe electricallygrounded inaccordance withlocal codes or, in their absence, with the N.E.C./C.E.C. Voltagetol erances which must be maintained at the compressor termi nalsduring startingandrunning conditionsare indicatedon the unit Rating Plate and Table 8.
­The wiring entering the cabinet must be provided with me
-
chanical strain relief. Afused disconnect switch should be fieldprovided for the unit. If
any of the wire supplied with the unit must be replaced, replace­ment wire must be of the type shown on the wiring diagram.
Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.
Referto Figure 1for typical fieldwiring and tothe appropriate unit wiring diagram for control circuit and power wiring information.
COMPRESSORS
Unitsareshipped withcompressormountings factory-adjusted for shipping. CAUTION: Loosen compressor mounting bolts half turn before operating unit.
NOTE: HEATANTICIPATOR SHOULD BE SET AT0.35 AMPS FOR ALL MODELS.
CAUTION: Label all wires prior
to disconnection when
24 VOLT TRANSFORMER
servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
-
-
-
-
-
-
-
POWER WIRING
REFER TO ELECTRICAL
DATA TABLES TO SIZE THE
DISCONNECT SWITCH,
WIRING & OVERCURRENT
FIG. 1 - TYPICAL FIELD WIRING DIAGRAM
4 Unitary Products Group
REFER TO ELECTRICAL
DATA TABLES TO SIZE THE
DISCONNECT SWITCH,
WIRING & OVERCURRENT
Scroll compressors operate in one direction only. If a three phase scroll compressor is experiencing:
Low amperage draw
Similar discharge and suction pressures
Increased noise level
then the compressor is operating in reverse. To correct this condition,switch anytwo (2)line voltageleads atthe contactor. Please note, single phase scroll compressor will start and run in one direction only. The reverse operation is not a concern.
035-18265-001-A-0202
GAS PIPING
Proper sizing ofgas piping depends on the cubic feet perhour ofgasflowrequired,specific gravityofthe gasandthe lengthof run. “National Fuel Gas Code” Z223.1 or CAN/CGAB149.1 or .2 should be followed in all cases unless superseded by local codesorgas companyrequirements.Referto Tables 4and5.
The heatingvalueof the gas may differ withlocality. Thevalue should be checked with the local gas utility.
COMBUSTION DISCHARGE TABLE 2 - NATURALGAS APPLICATION DATA
Input
Capacity
(Mbh)
Output
Capacity
3
(Mbh)
45 36
70 56
1
1
2 & 3 &
90 72 3 &
Available
On
Models
, 2,
2
2
1
TON
3
2
1
2
2
1
3
2
1
3
2
Gas
Number
1
Rate
1
2
Ft.3/Hr.
, 3 &
Burners
42 2 25 55
TON 65 3 30 60 TON 65 3 25 55 TON 84 4 30 60
80 64 4 & 5 TON 74 3 25 55 108 86 4 & 5 TON 100 4 30 60 135 108 4 & 5 TON 126 5 35 65
1 Based on 1075 BTU/Ft.3. 2 The air flow must be adjusted to obtain a temperature rise within the range shown.
Continuous return air temperatures should not be below 55°F.
3 Heating capacity valid for elevations up to 2000 feet above sea level. For elevations
above 2000 feet, rated capacity should be reduced by 4% for each 1000 feet above sea level.
of
Temp. Rise °F
At Full Input
Min. Max.
TABLE 3 - PROPANE (LP) GAS APPLICATION DATA
Input
Capacity
(Mbh)
Output
Capacity
3
(Mbh)
45 36
70 56
1
1
2
2 & 3 &
90 72 3 &
Available
On
Models
, 2,
2
1
TON
3
2
1
2
2
1
3
2
1
3
2
Gas
Number
1
Rate
1
2
Ft.3/Hr.
, 3 &
Burners
18 2 25 55
TON 28 3 30 60 TON 28 3 25 55 TON 36 4 30 60
80 64 4 & 5 TON 32 3 25 55 108 86 4 & 5 TON 43 4 30 60 135 108 4 & 5 TON 54 5 35 65
1 Based on 2500 BTU/Ft.3. 2 The air flow must be adjusted to obtain a temperature rise within the range shown.
Continuous return air temperatures should not be below 55°F.
3 Heating capacity valid for elevations up to 2000 feet above sea level. For elevations
above 2000 feet, rated capacity should be reduced by 4% for each 1000 feet above sea level.
4 Propane applications are accomplished by field installation of a Propane Conversion
Accessory, Model 1NP0805 for 1.5 thru 3.5 ton units and Model 1NP0806 for 4 and 5 ton units.
of
Temp. Rise °F
At Full Input
Min. Max.
NOTE: Theremay bea localgasutilityrequirementspecifying
a minimum diameter for gas piping. All units require a
2
1/2 inch pipe connection at the gas valve.
GAS CONNECTION
The gas supply line can be routed through the hole located on theleft sideof the unit.Refer toFigure5 tolocate theseaccess openings. Typical supply piping arrangements are shown in Figure 2.
AUTOMATIC GAS VALVE
121
UNION
x
2
121
GAS COCK
x
2
2
1
2
DRIP LEG
FIG. 2 - EXTERNAL SUPPLY CONNECTION
EXTERNAL SHUT-OFF
Gas piping recommendations:
1. Adrip leg and a ground joint union must be installed in the gas piping.
2. Whenrequiredby localcodes, amanual shut-offvalvemay have to be installed outside of the unit.
- 14 NPT
TABLE 4 - NATURALGAS PIPE SIZING CHART
Length
in
Feet
1/2 in. 3/4 in. 1 in. 1-1/4 in.
10 132 278 520 1,050 20 92 190 350 730 30 73 152 285 590 40 63 130 245 500 50 56 115 215 440 60 50 105 195 400 70 46 96 180 370 80 43 90 170 350 90 40 84 160 320
100 38 79 150 305
Maximum Capacity of Pipe in Cubic Feet of Gas Per Hour (Based Upon APressure Drop of 0.3 Inch Water Column and 0.6 Specific Gravity Gas).
Nominal Inches Iron Pipe Size
TABLE 5 - PROPANE (LP) GAS PIPE SIZING CHART
Length
in
Feet
1/2 in. 3/4 in. 1 in. 1-1/4 in.
10 275 567 1,071 2,205 20 189 393 732 1,496 30 152 315 590 1,212 40 129 267 504 1,039 50 114 237 448 913 60 103 217 409 834 70 96 196 378 771 80 89 185 346 724 90 83 173 322 677
100 78 162 307 630
Maximum Capacity of Pipe in Thousands of BTU Per Hour (Based Upon APressure Drop of 0.5 Inch Water Column).
Nominal Inches Iron Pipe Size
Unitary Products Group 5
035-18265-001-A-0202
3. Use wrought iron or steel pipe for all gas lines. Pipe dope should be applied sparingly to male threads only.
CAUTION: If flexible stainless steel tubing is allowed by the
authority having jurisdiction, wrought iron or steel pipe must be installed at the gas valve and extend a minimumoftwo (2)inchesoutside oftheunit casing.
FLUE VENT HOOD
Theflue venthoodwithscreenis notshipped attached.Thishood must beinstalled to assure proper unitoperation. The hood must be fastened to the outside of the side gas control/electrical com partment with the screws provided in the bag attached to the in side of the gas control/electrical compartment, see Figure 3.
-
-
WARNING:Naturalgas may contain some propane. Propane,
being an excellent solvent, will quickly dissolve white lead or most standard commercial com pounds. Therefore, a special pipe dope must be applied when wrought iron or steel pipe is used. Shellacbase compoundssuchas GaskolacorSta lastic, and compounds such as Rectorseal #5, Clyde's or John Crane may be used.
4. Allpipingshould becleaned ofdirtandscaleby hammering onthe outsideof the pipeand blowingout theloose dirtand scale. Beforeinitial start-up, besure that all ofthe gas lines external to the unit have been purged of air.
5. The gas supply should be a separate line and installed in ac cordance with all safety codes as prescribed under “Limita tions”. Afterthe gas connections have been completed,open the main shut-off valve admitting normal gas pressure to the mains. Check all joints for leaks with soap solution or other material suitable for the purpose. NEVER USE A FLAME.
6. The furnace and its individual manual shut-off valve must be disconnected from the gas supply piping system during any pressure testing ofthatsystem at test pressures in ex­cess of 1/2 psig (3.48 kPa).
The furnace must be isoulated from the gas supply piping system by closing its individual manual shut-off valve dur­ing any pressuretesting of the gas supply piping systemat test pressures equal to or less than 1/2 psig (3.48 kPa).
The unit iscontrolled by a conventional four wire heating/cool ing thermostat common to this class of equipment.
-
-
WARNING: FLUE HOOD SURFACES
MAY BE HOT.
VENT OUTLET SCREEN
FLUE VEN T O U TLET
AIR HOOD
-
-
FIG. 3 - FLUE VENT OUTLET AIR HOOD
CAUTION
The flueexhaust hood must be properlyinstalled and within the recommended clearances.Further communications and action must be given to the home or building owner(s) to eleiminate any unauthorized humon contact around this area during the heating cycle. Flue hood surface and immediate area is de­signedtooperate athightemperatures duringtheheating cycle.
-
TABLE 6 - PHYSICAL DATA
1
2
DNA
3
4
1
4
NPTI
1
2
3
4
1
4
NPTI
1.0 1.0
1
4
1
NPTI
2
1
2
NPTI
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FAN
CONDENSER
COIL
MODELS
CENTRIFUGAL BLOWER (Dia. x Wd. in.) 10 X 8 10 X 8 10 X 8 11 x 10 11 x 10 12 x 11 12 x 11 FAN MOTOR HP(Three Speed) ROWS DEEP 2222333 FINS PER INCH 14 13 13 15 13 13 13 FACE AREA(Sq. Ft.) 2.25 3.5 3.5 3.5 3.5 4.5 4.5 PROPELLER DIA. (in.) 22 22 22 22 22 22 22 FAN MOTOR HP NOM. CFM TOTAL 1,800 2,200 2,400 2,400 2,400 3,000 3,000 ROWS DEEP 1111111 FINS PER INCH 13 13 16 20 20 20 20 FACE AREA(Sq. Ft.) 8.3 8.3 11.7 11.7 11.7 14.8 14.8
018 024 030 036 042 048 060
1
2
1
4
1
2
1
4
1
2
1
4
CHARGE REFRIGERANT 22 (lbs./oz.) 3 / 2 3 / 6 4 / 12 4 / 3 4 / 12 6 / 0 5 / 4
FILTER* FACE AREA(Sq. Ft.) / SIZE (NOMINAL) 2.6/20x20 2.6/20x20 2.6/20x20 2.6/20x20 2.6/20x20 3.3/20x12 3.3/20x12
NATURALGAS BURNER ORIFICE NO.
FURNACE
SECTION
(Qty./Drill size) PROPANE BURNER ORIFICE NO.
(Qty./Drill size) GAS CONNECTION SIZE
COMPRESSOR
TYPE
* = Three phase 018 thru 042 size units are supplied with one (1) filter and on three phase 048 and 060 size units two (2) filters are supplied. Single phase units are shipped without filters.
See “FILTERS” on page 4.
HERMETICALLYSEALED (R = RECIPROCATING, S = Scroll)
43 43 43 43 43 40 40 55 55 55 55 55 53 53
1
2
NPTI
1
2
NPTI
1
2
NPTI
RRRRRSS
1
4
6 Unitary Products Group
TABLE 7 - UNIT WEIGHTS
MODEL
DNA
UNIT
SHIPPING
WEIGHT
(lbs.)
UNIT
OPERATING
WEIGHT
(lbs.) 018 365 360 91 88 89 92 024 365 360 91 88 89 92 030 395 390 98 95 96 99 036 400 395 100 96 98 101 042 405 410 104 100 101 105 048 475 470 119 115 116 120 060 480 475 120 116 117 122
CORNER OPERATING WEIGHTS
(lbs., location, see Figure 4)
“A” “B” “C” “D”
035-18265-001-A-0202
CORNER “D”
CENTER OF GRAVITY
CORNER “C”
CORNER “A”
FRONT
OF
UNIT
1
47
49
1
8
25
FIG. 4 - CENTER OF GRAVITY
24
CORNER “B”
4
TABLE 8 - ELECTRICAL DATA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MODEL
DNA
POWER SUP
PLY
VOLTAGE
LIMITATIONS
-
1
COMPRESSOR
MIN. MAX. RLA LRA
COND.
FAN
MOTOR,
FLA
018 208/230-1-60 187 253 9.0 48.0 1.1 2.2 14.5 20 20 .96 40 024 208/230-1-60 187 253 11.5 60.0 1.1 2.2 17.7 25 25 .96 40 030 208/230-1-60 187 253 14.7 73.0 1.1 2.2 21.7 30 30 .96 40 036 208/230-1-60 187 253 17.3 94.0 1.1 3.5 26.2 35 35 .96 40 042 208/230-1-60 187 253 20.5 120.0 1.1 3.5 30.2 40 40 .96 40 048 208/230-1-60 187 253 24.4 140.0 1.3 7.0 38.8 50 50 .96 40 060 208/230-1-60 187 253 28.9 175.0 1.3 7.0 44.4 60 60 .96 40 036 208/230-3-60 187 253 10.9 78.0 1.1 3.5 18.2 25 25 .96 75 042 208/230-3-60 187 253 14.1 110.0 1.1 3.5 22.2 30 30 .96 75 048 208/230-3-60 187 253 14.1 105 1.3 7.0 25.9 35 35 .96 75 060 208/230-3-60 187 253 15.5 125 1.3 7.0 29.5 40 40 .96 75 036 460-3-60 414 504 5.8 40.0 0.6 1.8 9.6 15 15 .96 75 042 460-3-60 414 504 7.1 54.0 0.6 1.8 11.2 15 15 .96 75 048 460-3-60 414 504 7.1 55.0 0.7 3.5 13.1 20 20 .96 75 060 460-3-60 414 504 8.8 66.5 0.7 3.5 15.4 20 20 .96 75 036 575-3-60 518 630 4.5 32.0 0.4 1.5 7.5 15 15 .96 75 042 575-3-60 518 630 5.8 44.0 0.4 1.5 9.1 15 15 .96 75 048 575-3-60 518 630 5.7 45.0 0.6 2.8 10.5 15 15 .96 75 060 575-3-60 518 630 7.1 50.0 0.6 2.8 12.3 15 15 .96 75
Note; Electrical data based on 104°F outdoor air ambient temperature.
1
= Rated in accordance with ARI Standard 110, utilization range “A”.
3
= If economizer or motorized damper are to be used, 75 VAis required. Refer to price pages for future details.
2
= Dual element, time delay type.
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
3
Unitary Products Group 7
Loading...
+ 14 hidden pages