WATER SYSTEMS

Features

Horizontal air return

Twin centrifugal fans

High static pressure up to 250 Pa

2 and 4 pipe systems

Air distribution plenum

Electric heater option

Optional paint finish

Blower

YEFB 130-440

A complete range from 4 kW up to 24 kW

Thermostats

CSR00 (Wall mounted)

Fan speed selector

CMR00 (Wall mounted)

Thermostat with manual fan speed and S/W change over

CER00 (Wall mounted)

Thermostatwithmanualfanspeed andautomaticchangeover

CER20 (Wall mounted)

Thermostat with auto. fan speed and automatic change over

CER30 (Wall mounted)

Thermostat with auto. fan speed and automatic change over

for modulating valve

Technical features

Model

 

YEFB

130

140

230

240

330

340

430

440

 

 

max

6.01

6.92

8.81

10.61

11.15

14.06

17.86

23.31

Total cooling capacity [kW]

(1)

 

 

 

 

 

 

 

 

 

med

5.13

5.81

7.27

8.55

9.39

11.58

16.28

20.95

 

 

min

3.22

3.49

6.08

7.01

7.51

9.00

14.40

18.21

 

 

max

7.90

8.90

12.34

14.62

15.20

18.84

24.38

30.36

Heating capacity [kW]

(2)

 

 

 

 

 

 

 

 

 

med

6.61

7.32

9.84

11.36

12.49

15.07

21.83

26.79

 

 

min

3.96

4.20

8.01

9.04

9.71

11.33

18.90

22.77

 

 

max

1153

1130

2158

2116

2639

2587

4129

4048

Air volume [m3/h]

 

 

 

 

 

 

 

 

 

 

 

med

916

898

1553

1523

1994

1955

3505

3436

 

 

min

494

484

1174

1151

1422

1394

2853

2797

Max. available external static pressure [Pa]

 

100

100

175

175

250

250

250

250

 

 

 

 

 

 

 

 

 

 

 

 

 

max

56

56

60

60

60

60

67

67

Sound pressure level [dB(A)](3)

 

med

51

51

54

54

54

54

64

64

 

 

 

 

 

 

 

 

 

 

 

 

 

min

41

41

49

49

48

48

59

59

 

 

 

 

 

 

 

 

 

 

 

Power supply [V-ph-Hz]

 

 

 

 

 

230 - 1- 50

 

 

 

Water connections

 

 

G 1/2” F

G 1/2” F

G 1/2” F

G 1/2” F

G 1/2” F

G 1/2” F

G 1” M

G 1” M

(1)Room temperature 27°C d.b., 48% R.H. - Water temperature 7/12 °C

(2)Room temperature 20°C, 50% R.H. - Water inlet temperature: 50°C -

Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

(3) Sound pressure level in 1 meter distance open field and 0 Pa external static pressure