YOKOGAWA HGM300, RDM800 User Manual

!
Archived Document
! ! ! ! ! INTRODUCTION!TO!THE!HGM300/RDM800!YOKOGAWA!REFRIGERANT!
!
!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!MONITOR!SYSTEM!!!!!
! !
Welcome!ñ!This!is!an!introduction!the!Yokogawa! HGM300/RDM800!refrigerant! monitor! system.!As! you!open!the! shipping!carton!locate!the!following!items;! HGM300!ñ!Manufactured! to!your!order!specifications,!that!is,!number!of!zones,!type!of!air!sample!fittings!and!dual! 4-20ma!DC!option!(if!ordered)!!!! RDM800!ñ!Remote!Display!Module!(if!ordered).! Charcoal!filter!with!ìTî!bolt!bracket;!line! end!filter!assembly!(quantity!dependant!on!number!of!zones!ordered!ñ!for! 4! zones! ñ! 5! filters,! for! 8! zones,! 9! filters,! 12! zones! 13! filters! and! 16! zones! 17! filters.! Do! not! use! a! filter! on! the! exhaust!line).! Operations!manual! Optional! items! ñ! Audio/Visual! alarms,! visual! alarm,! audio! alarm,! air! sample! tubing,! etc.! as! ordered.
! !
!
Proper!mounting!of!HGM300!and!RDM800!-!!
!
!
! ! ! ! ! ! ! !
HGM300!Mounting!Specs!!!!
!!!!
7.0"
14.0"
!
! ! ! !
!!
RDM800!Mounting!Specs!
!
7.0"
9.0"
!
! ! ! !
Rev.!10/22/01!!
HGM300/RDM800!mini!manual.doc
1
!
The! HGM300! should! be! centrally! located! in! the! mechanical! room! and! be! readily! accessible! for! easy! visual!
g
y
Archived Document
monitoring! and! servicing.! Air! sample! tubing! may! be! run! in! lengths! up! to! 500í.! The! fresh! air! purge! line! should! draw! from!an! area ! that!does! not! contain!any! refrigerant! gas! and! cannot! exceed! 300í! in! length.! The! exhaust! line!should!run!to!an!out!side!location!if!possible.!The!length!of!the!exhaust!line!cannot!exceed!100í.!!
!Ideally,!two!to!three!pick!up!points!spaced!around!each!chi ller!will!provide!sufficient!coverage.!It!may!be! necessary!
to!perform!a!ìsmokeî!test!of!the!mechanical!room!to!determine!the!best!locations.!The!smoke!test!would!provide!the! pattern!of!air!currents!present!in!the!mechanical!room.!
!
HGM300/RDM800!Refrigerant!Gas!leak!monitor!mechanical!room!placement!
!
!
! ! ! ! !
!
Sample! Inlet! Pickup!Point!
! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! Picture!of!HGM300!alarm!wiring)!
! ! ! ! !
!
!
!
!
!
!
!The!RDM800!should!be! mounted! outside! of!the! mechanical! room!or! at!least!just!inside!of!a!door! to! the!room.!
This!is!the! ì split! architecture! designî ! for! safety!of! the!operator.!The! RDM800!can! be! located! up! to! 4500í ! from!the! HGM300.!The! RDM800! is! the! man! machine! interface! by!which! you! program! the! HGM300,! acknowledge! alarms! and!observe!conditions!inside!of!the!mechanical!room.!Note!that! there!are!two!additional!alarm!relay!contacts!in!the! RDM800!that!can!be!programmed!to!alarm!with!ì leak,!spill,!evacuate,!fault!or!monitor!onî .!
! ! ! ! ! ! ! ! ! ! !
Rev.!10/22/01!!
Exhaust Fan
Chiller!
Outside Hallwa
Machine Room
Aux. Horn/Strobe Remote Alarm
HGM300 Halo Monitor
Sample Inlet Pickup Points
HGM300/RDM800!mini!manual.doc
RDM800 Remote Display Module
en Gas
2
!
WIRING!THE!HGM300!
Archived Document
!
!
!
!
! ! ! ! ! !
Dual!4-20!mAdc!
!
Outputs!
! ! ! ! ! ! ! !
RS485!
AC!Power!(In!/!Out)!--!RS485!--!4-20!mAdc!
!
Node!Address!
Switch
On/Off!Power!
Switch
Main!120Volt!Power!
!
! ! ! ! !
(Used!to!supply!power!for!audio/visual!alarms)!
Auxiliary!Power!120Volt!
!
!
!
Leak,!Spill,!Evac uate!&! Fault!alarm!wiring!block
Rev.!10/22/01!!
HGM300/RDM800!mini!manual.doc
3
!
WIRING!THE!RDM800
r
Archived Document
! ! ! !
!
HGM300!RS485!
Connector!
Terminator!for!
Building!Automation!
RS485!Connecto
Building!
Automation!
System!RS485!
Connector!
Terminator!for!
HGM300!RS485!
!
Connector!
RDM800!
relays!
Main!Power!
Rev.!10/22/01!!
HGM300/RDM800!mini!manual.doc
4
!
HGM300!Relay!Wiring!
N
Archived Document
!
!
!
!
!!!!!!!!!!!!LEAK!!!!!!!!!!!!!!!SPILL!!!!!!!!!!EVACUATE!!!!!!!FAULT!
!!!!!!!!!!!!1!!!!!!!!!!!!!!!!2!!!!!!!!!!!!!!!!!!3!!!!!!!!!!!!!!4!
Relay
#1
NO
COMMON
Strobe!
Relay
NC
#2
NC
NO
COMMON
Relay
#3
NO
COMMON
Relay
#4
NC
COMMON
NO
Horn!
NC
!
!!!!Aux.!Power! ! !!!!Main!Power!
!
Jumper!the!ëNeutralí!of!the!auxiliary!power!connector!to!the!ëCommoní!on!the!relay!block.!!!
Connect!one!end!of!strobe!or!horn!to!the!ëNOí!of!whichever!level!of!alarm!is!appropriate!for!application.!
The!other!end!of!strobe!or!horn!is!connected!to!a!120VAC!power!source,!or!to!the!ëLineí!of!the!auxiliary! power!connector!(Max!5AAC).!
! ! ! ! ! ! ! ! ! ! ! ! ! ! !
Rev.!10/22/01!!
Line!
Neutral!
eutral!
Line! !
!
!
!
!
HGM300/RDM800!mini!manual.doc
5
!
Power!up!the!monitor!system.!(Warm!up!time!is!15!minutes)!
N
N
N
N
N
N
N
N
Archived Document
! Start!up!checkpoints!!! !
a)! All!b uttons!on!RDM800!ìchirpî!when!pressed.!(Contact!the!factory!if!the!do! not! ìchirpî.!See!last!page! for!
whom!to!call)! b)! Communication!connection!between!HGM300!and!RDM800! c)! Checking!node!address!for!HGM300ís!(multiple!HGM300î s!also)! d)! Terminator!positions!
!
TERMINATOR!
!!!!!!!!!ìINî!! MULTIPLE!HGM300íS!WITH!RDM800
RMD800!
!!!!!!!!!!!RS-485!! RS-485!CONNECTIONS!BETWEEN!HGM300ís!!
! HGM300!
! UNIT!1!
!
ODE!1!
! ! TERMINATOR!! !!TERMINATOR!! ! TERMINATOR!! !!TERMINATOR! !!!ì OUTî ! ! !!!!!!!!ìOUTî !! ! ! !!!!!!ì OUTî ! ! !!!!!!!!ìINî! ! !
The!HGM300!may!be!connected!to!a!building!automation!via!the!RS-485!connector.!The!node!address! switch!on!each!HGM300!may!be!set!from!ì0î!to!ì16î!in!order!to!conform!to!the!building!automation! system!requirements.!Units!set!to!a!ì0î!or!ì1î!address!both!respond!to!messages!from!the!RDM800!as! address!ì1î!therefore!you!should!not!have!a!unit!set!to!ì0î!and!another!set!to!ì1î!on!the!same!network.!If! the!HGM300!network!is!connected!directly!to!a!building!automation!system! the!RDM800.!However,!the!RDM800!has!two!communications!ports,!an!ìupstreamî!port!(labeled!TO! BMS)!and!a!ìdownstream!port!(labeled!TO!MONITORS).!A!BMS!node!may!be!connected!to!the!upstream! RDM800!port!while!the!downstream!RDM800port!talks!to!the!HGM300ís.!In!this!case,!the!BMS!is!talking! ìthroughî!the!RDM800!to!the!HGM300ís,!but!not!physically!on!the!HGM300/RDM800!network.!
Note!ñ!If!the!HGM300!is!not!at!the!end!of!the!line!in!a!series!connection,!then!the!terminator!on!the!HGM! must!be!set!to!ìOUT.î!!Also,!each!end!of!the!network!must!have!the!terminator!set!to!ìINî.!
!!!!!!
!!!!!!!!TERMINATOR!
!!!!!!!!!!!!!!!ìOUTî!
!
!!!!!! !!!!!!
!!!!!!!!!!
!
HGM300!
! ! ! ! !!!!!!!TERMINATOR! !!!!!!!!!!TERMINATOR!! TERMINATOR!! TERMINATOR! !!!! !ìINî! ! !!!! !!ì OUTî !! ! !!!!!!ì OUTî ! ! !!!!!!!!!ìINî!
Rev.!10/22/01!!
ODE!1!
!
! NOTE!ñ!THE!LAST!HGM300!OR!RDM800!ON!EITHER!END!OF!THE!NETWORK!
MUST!HAVE!THE!TERMINATOR!IN!THE!ìINî!POSITION!AND!ALL!OTHER! UNITSMUST!HAVE!THEIR!TERMINATORS!IN!THE!ì OUTî !POSITION.!
! NOTE!ñ!TOTAL!LENGTH!OF!RS-485!CABLE!CANNOT!EXCEED!1500m.!!(Use!
instrument!cable!20!gage!multistrand!shielded!and!twisted!pair!ñ!similar!or!equal!to! Beldon!cable!#8762.)!
THE!RDM800!AND!HGM300!UNIT!4!TERMINATOR!MUST!BE!IN!THE!ìINî! POSITON.!!HGM300!UNITS!1,!2,!&!3!MUST!BE!IN!THE!ì OUTî !POSITION.!
! ! !
HGM300! UNIT!2!
Multiple!HGMís!
!
HGM300! UNIT!3!
ODE!2!
Connecting!To!A!Building!Automation!System!
BMS!
HGM300!
ODE!2!
ODE!3!
HGM300!
ODE!3!
HGM300! UNIT!4!
ODE!4!
may!not!be!connected!to!
HGM300!
ODE!4!
HGM300/RDM800!mini!manual.doc
6
!