CAUTIONARY NOTES FOR SAFE USE
MODEL AND SUFFIX CODES
OF THE PRODUCT
This User’s Manual should be carefully read before installing and operating the product. The following symbol is used on the product and in
this manual to ensure safe use.
This symbol is displayed on the product when it is
necessary to refer to the User’s Manual for information on
personnel and instrument safety. This symbol is displayed
in the User’s Manual to indicate precautions for avoiding
danger to the operator, such as an electric shock.
The following symbols are used only in this manual.
IMPORTANT
Indicates that operating the hardware or software in a
particular manner may cause damage or result in a system
failure.
NOTE
Draws attention to essential information for understanding
the operations and/or functions of the product.
CHECKING PRODUCT SPECIFICATIONS AND PACKAGED ITEMS
(1) Checking the Model and Product Specifications
Check that the model and specifications indicated on the nameplate
attached to the main unit are as ordered.
(2) Packaged Items
Check that the package contains the following items:
● MU5D: 1
● RJC sensor (A1167HT): 1
(RJC sensor is not attached for the optional specification
“/RJCN.”)
● Spacer (for DIN rail mounting): 1
● Range label: 1
● User’s Manual (this manual: IM 77J04U05-02E): 1
Model
Output
2: 2 outputs
Power supply
1: 15-40V DC (Operating range: 12 to 48 V)
6: 100-240 V AC/DC (Operating range: 85 to 264 V)
Input signal
U: Thermocouple, RTD, mV
Z: (Custom order)
Customized thermocouple or RTD
Output-1 signal
A: 0 to 20 mA DCSpan is 5 mA or more
B: 0 to 5 mA DCSpan is 1 mA or more
1: −10 to +10 V DCSpan is 0.1 V or more
2: −100 to +100 mV DCSpan is 10 mV or more
Z: (Custom order)
Customized current signals or voltage signals
Output-2 signal
A: 4 to 20 mA DC1: 0 to 10 mV DC
B: 2 to 10 mA DC2: 0 to 100 mV DC
C: 1 to 5 mA DC3: 0 to 1 V DC
D: 0 to 20 mA DC4: 0 to 10 V DC
E: 0 to 16 mA DC5: 0 to 5 V DC
F: 0 to 10 mA DC6: 1 to 5 V DC
G: 0 to 1 mA DC7: −10 to +10 V DC
Z: (Custom order)
Customized current signals or voltage signals
Optional specification
/SN: Without socket
/RJCN: Without RJC sensor
MU5D -02 - 0 /
GENERAL
The MU5D is a plug-in type universal temperature converter that is
connected to an IEC/JIS-standard thermocouple, converts the temperature signals into isolated DC current or DC voltage signals.
1
Page 2
1. MOUNTING METHOD
NOTE
Plug/disconnect the main unit into/from the socket
vertically to the socket face. Otherwise the terminals may
bend and it may cause bad contact.
1.1Wall Mounting
Unfasten the upper and lower stoppers of the converter to disconnect
the main unit from the socket. Next, anchor the socket onto the wall
with two M4 screws. Then, plug the main unit into the socket and secure the main unit with the upper and lower stoppers.
Stopper
Main unit
Socket
Mounting
screws
[Mounting Dimensions]
Socket
2-4.5 or 2-M4
Pitch: 56 or more
5 or more
400.2
(51)
1.2DIN Rail Mounting
Locate the converter so that the DIN rail fits into the upper part of the
DIN-rail groove at the rear of the socket, and fasten the socket using
the slide lock at the lower part of the socket.
Push
DIN rail
Spacer
1.3Using Ducts
When using a wiring duct, install the duct at leaset 30 mm away from
the top and bottom faces of the main unit.
Unit: mm
Note:
• When mounting the units
close together, leave a space
of at least 5 mm between
them.
(85)
• Use the supplied spacer to
keep a space of 5 mm for
DIN rail mounting.
Fit into here
DIN rail
(Rear of socket)
Slide lock
2. INSTALLATION LOCATIONS
● Avoid the following environments for installation locations:
Areas with vibration, corrosive gases, dust, water, oil, solvents, direct sunlight, radiation, a strong electric field, and/or a strong
magnetic field
Installation altitude: 2000 m or less above sea level.
● If there is any risk of a surge being induced into the power line
and/or signal lines due to lightning or other factors, a dedicated
lightning arrester should be used as protection for both this converter and a field-installed device.
● Operating temperature/humidity range: 0 to 50C/5 to 90%RH (no
condensation)
3. EXTERNAL WIRING
WARNING
To avoid the risk of an electric shock, turn off the power
supply and use a tester or similar device to ensure that no
power is supplied to a cable to be connected, before carring
out wiring work.
Wires are connected to the terminals of the converter’s socket. M3.5
screw terminals are provided for the connection of external signals. Attach a crimp-on lug to each wire for connection to the terminals.
● Recommended cables: A nominal cross-sectional area of 0.5 mm
or thicker for signal cables, and that of 1.25 mm2 or thicker for
power cables.
Input Signal (Input type can be changed.)
1 2
mVRTD
+
−
4
Output-1
39
+
1
−
2
Output-2
+
10
−
11
A
4
B
5
6
5
B
6
Signal
line
RJC
sensor
Terminal
screw
TC
RJC
4
+
5
6
−
7
8
9
RJC sensor
8 76 5
10 11
(Unit: mm)
ø3.7 to 4.0
6.5 or more
Power Supply
L
+
N
−
GND
Recommended
crimp-on lug size
7 or less
* Attach the RJC sensor correctly as shown in the figure above
only for thermocouple input.
IMPORTANT
●
The power line and input/output signal lines should be
installed away from noise-generating sources. Other
wise accuracy cannot be guaranteed.
●
The grounding resistance must be 100 Ω (JIS Class D
grounding). The length and thickness of the grounding
cable should be as short and thick as possible. Directly
connect the lead from the ground terminal (terminal no.
9) of the product to the ground. Do not carry out daisychained inter-ground terminal wiring.
●
Use of the product ignoring the specifications may cause
overheating or damage. Before turning on the power, ensure the following:
(a)Power supply voltage and input signal value applied to the
product should meet the required specifications.
(b)The external wiring to the terminals and wiring to ground
are as specifications.
●
Do not operate the product in the presence of flammable
or explosive gases or vapors. To do so is highly dangerous.
●
The product is sensitive to static electricity; exercise
care in operating it. Before you operate the product,
touch a nearby metal part to discharge static electricity.
●
The RJC sensor may be damaged if an excessive force is
applied. When attaching the RJC sensor, be sure not to
pull it or not to bend the crimp-on terminal lugs.
2
2
IM 77J04U05-02E 3rd Edition Oct. 15, 2007-00
Page 3
Power Supply and Isolaion
Power supply rated voltage:
15-40 V DC or 100-240 V AC/DC 50/60 Hz
Power supply input voltage:
15-40 V DC (±20%) or 100-240 V AC/DC (−15, +20%) 50/60
Hz
Power consumption:
24 V DC 2.3 W, 110 V DC 2.2 W
100 V AC 4.6 VA, 200 V AC 6.4 VA
Insulation resistance:
100 MΩ at 500 V DC between input, output, power supply, and
grounding terminals mutually.
Withstand voltage:
2000 V AC for 1 minute between input, output, power supply and
grounding terminals mutually.
1000 V AC for 1 minute between output-1 and output-2 terminals.
4. DESCRIPTION OF FRONT PANEL
The figure below shows the converter of which the front panel cover is
open.
Connector for
communication
Selection
switch
Adjustment
switch
4.1 Operation Indicating Lamp
The operation indicating lamp shows the operation status, abnormalities in a setting, and adjustment operation status by the adjustment
switch on the front panel.
(1) When the lamp is lit:
Power is turned on and the converter is in the normal status provided that the selection switch is set to the position “0.”
(2) When the lamp is blinking rapidly:
The lamp repeats the rapid blinking until the internal processing is
completed during output adjustment and wiring resistance correction by the adjustment switch.
(3) When the lamp is blinking slowly:
The lamp repeats the slow blinking until the converter regains its
normal status when the following abnormalities occur.
• Abnormalities in a parameter setting
• The selection switch is set to the positions other than “0.”
• Input is outside of the range of −10 to 110%.
• OFF of RJC and error of RJC.
4.2 Connector for Communication
Use the connector for communication when setting the parameters using a PC (VJ77 Parameter Setting Tool) or the Handy Terminal.
JUXTA communication cable with
5-pin connector (F9182EE)
JHT200
Handy Terminal
PC which is installed
with the VJ77.
[Provided with VJ77 and JHT200]
Dedicated adapter (E9789HA)
[Provided with VJ77]
Dedicated cable (E9786WK)
[Provided with VJ77]
*: Use the VJ77 of version R1.04 or later.
Operation indicating lamp:
Turns on at power on.
Modular jack conversion
adapter (E9786WH)
[Provided with VJ77]
4.3 Selection Switch and Adjustment Switch
The following adjustments can be performed using the switches on the
front panel (selection switch and adjustment switch) without the dedicated setting tool (refer to“4.2 Connector for Communication”).
The adjusted value is saved about 1 second after operating the adjustment switch. Also when the rotation direction of the adjustment switch
is changed, the adjusted value becomes effective about 1 second after
the change.
Position of selection switch
No function
0
Output-1 zero adjustment
1
Output-1 span adjustment
2
Output-2 zero adjustment
3
Output-2 span adjustment
4
Wiring resistance correction
5
ON/OFF of RJC
7
Rotation direction of adjustment switch
Clockwise
Counterclockwise
Increase of output adjusted value, execution of
wiring resistance correction and ON of RJC
Decrease of output adjusted value, reset of wiring
resistance corrected value and OFF of RJC
[Adjusted volume by the adjustment switch]
One click changes about 0.005% of output range.
For thermocouple input, turn off the RJC.
4.3.1
Adjusting Output Using the Switches on the Front
Panel
(1) Output-1 zero adjustment
Apply the 0% input signal. Turn the selection switch to “1.” Then
turn the adjustment switch clockwise to increase the output, or
turn it counterclockwise to decrease the output.
(2) Output-1 span adjustment
Apply the 100% input signal. Turn the selection switch to “2.” Then
turn the adjustment switch clockwise to increase the output, or
turn it counterclockwise to decrease the output.
Output-2 can be adjusted by the same operation as the above.
(3) Output-2 zero adjustment
Apply the 0% input signl. Turn the selection switch to “3.” Use the
adjustment switch for adjustment.
(4) Output-2 span adjustment
Apply the 100% input signal. Turn the selection switch to “4.” Use
the adjustment switch for adjustment.
4.3.2
Correcting the Wiring Resistance Using the Switches on the Front Panel
When an error occurs due to the influence of the input wiring resistance, perform the wiring as the figure below, apply a stable input, and
execute the following operations. Then the wiring resistance can be
corrected automatically.
<Thermocouple>
Short-circuit at the cable end.
<RTD>
Short-circuit at the cable end.
Be sure to turn the adjustment switch counterclockwise to reset the
corrected value before executing the wiring resistance correction.
(1) Executing the wiring resistance correction
Turn the selection switch to “5”, and turn the adjustment switch
clockwise. Then the wiring resistance is adjusted after 1 second
automatically.
(2) Resetting the wiring resistance corrected value
Turn the selection switch to “5”, and turn the adjustment switch
counterclockwise. Then the adjusted value is reset after 1 second.
Item to be adjusted
Adjustment operation
MU5D
MU5D
3
IM 77J04U05-02E 3rd Edition Oct. 15, 2007-00
Page 4
4.3.3 Turning on/off the RJC Using the Switches on the
Front Panel.
This operation is only for thermocouple input.
Turn the selection switch to “7”. Turn the adjustment switch counterclockwise to turn off the RJC sensor after 1 second. Turn the
adjustment switch clockwise to turn on the RJC sensor after 1
second.
NOTE
●
Be sure to set the selection switch back to the
position“0” after each adjustment. Otherwise it may
cause an incorrect operation or malfunction because
the positions other than“0” are adjustment modes.
●
When the selection switch is set to the positions other
than“0”, the setting tool can not be used for the setting.
●
The RJC is turned on when the power is turned on again
after turned off.
5. SETTING PARAMETERS
Set the parameters using a PC (VJ77 Parameter Setting Tool) or the
Handy Terminal. Refer to “6. List of Parameters” in this manual and the
User’s Manual for VJ77 PC-based Parameters Setting Tool (IM
77J01J77-01E) or the User’s Manual for JHT200 Handy Terminal (IM
JF81-02E). Parameters are indicated inside the [ ].
The initial value of the input range is set up according to the selected
values of the input sensor type, input type and temperature unit.
Set the parameters as follows.
Setting regarding to the input: set sequentially from 1.
(1) Set the input sensor type.
(2) Set the input type.
(3) Set the temperature unit for temperature input.
(4) Set the input range.
5.1Setting Thermocouple Type
Set the thermocouple type to be connected to the input in [D08: TC
TYPE].
Display
TYPE K
TYPE E
TYPE J
TYPE T
TYPE W3
TYPE W3: W97Re3-W75Re25
TYPE W5: W95Re5- W74Re26
Measuring Range
−270 to 1372 C
−270 to 1000 C
−210 to 1200 C
−270 to 400 C
0 to 2300 C
(Tungsten 97% Rhenium 3% - Tungsten 75% Rhenium 25%)
The abbreviation of ASTM E988 Standard.
(Tungsten 95% Rhenium 5% - Tungsten 74% Renium 26%)
The abbreviation of ASTM E988 Standard.
Measuring
or more
span
3mV
Display
TYPE R
TYPE S
TYPE B
TYPE N
TYPE W5
Measuring Range
−50 to 1768 C
−50 to 1768 C
0 to 1820C
−270 to 1300 C
0 to 2300 C
5.2Setting RTD Type
Set the RTD type to be connected to the input in [D09: RTD TYPE].
Display
Pt100-68
JPt100
Pt50
Pt100-90
Type of Input
Pt100 (IPTS-68: JIS'89)
JPt100 (JIS'89)
Pt50 (JIS'81)
Pt100 (ITS-90: JIS'97)
Set the temperature unit of the input range in [D19: UNIT].
5.4Setting Burnout Action
Set the burnout action in [D43:BURN OUT].
Set "OFF", "UP", or "DOWN."
NOTE
●
Changing the input range and the burnout action
direction resets the input adjusted value and the wiring
resistance corrected value.
●
Execute the wiring resistance correction when the
burnout action direction or input wiring is changed.
Measuring
span
3mV
or more
Measuring span
10°C
or more
5.5Setting Input Range
Set the input range 0% in [D27:INPUT1L_RNG], and the input range
100% in [D28:INPUT1H_RNG].
5.6Correcting Wiring Resistance
Correct the wiring resistance in [P01:WIRING R].
Select “EXECUTE” for correction, and “RESET” for resetting the corrected value.
Perform wiring as the figure shown in “4.3.2 Correcting the Wiring Resistance Using the Switches on the Front Panel” before correcting the
wiring resistance.
6. LIST OF PARAMETERS
Parameter DisplayItem
MODEL
TAG NO
SELF CHK
A
DISPLAY1
A01
INPUT1
A07
OUTPUT1
A08
OUTPUT2
A54
STAT US
A56
REV NO
A58
MENU REV
A60
SELF CHK
B
DISPLAY2
B01
INPUT1
B07
OUTPUT1
B08
OUTPUT2
B60
SELF CHK
D
SET (I/O)
D01
TAG NO.1
D02
TAG NO.2
D03
COMMENT1
D04
COMMENT2
D07
SENSOR TYPE
D08
TC TYPE
D09
RTD TYPE
D13
LINEARIZE
D19
UNIT
D27
INPUT1 L_RNG
D28
INPUT1 H_RNG
D38
OUT1 L_RNG
D39
OUT1 H_RNG
D40
OUT2 L_RNG
D41
OUT2 H_RNG
D43
BURN OUT
D49
OUT1 DR
D50
OUT2 DR
D60
SELF CHK
P
ADJUST
P01
WIRING R
P02
IN1 ZERO ADJ
P03
IN1 SPAN ADJ
P26
OUT1ZERO ADJ
P27
OUT1SPAN ADJ
P28
OUT2ZERO ADJ
P29
OUT2SPAN ADJ
P60
SELF CHK
Q
TEST
Q01
RJC
Q03
OUT1 TEST
Q04
OUT2 TEST
Q60
SELF CHK
*1 The displayed status is to let the service staff know the past records of the
product.
*2 Displayed only when the parameter D07:SENSOR TYPE is set to “TC”.
*3 Displayed only when the parameter D07:SENSOR TYPE is set to “RTD”.
*4 Displayed only when the parameter D07:SENSOR TYPE is set to “mV”.
Model
Tag number
Self-check result
Display1
Input-1
Output-1
Output-2
1
Status *
REV No.
MENU REV
Self-check result
Display2
Input-1
Output-1
Output-2
Self-check result
Setting (I/O)
Tag number-1
Tag number-2
Comment-1
Comment-2
Input sensor type
Thermocouple type
RTD type
*3
Linearization
Temperature unit
*2
*4
*2, *3
Input-1 low range
Input-1 high range
Output-1 low range
Output-1 high range
Output-2 low range
Output-2 high range
Burnout
Direction of output-1 action
Direction of output-2 action
Self-check result
Adjustment
Wiring resistance correction
Input-1 zero adjustment
Input-1 span adjustment
Output-1 zero adjustment
Output-1 span adjustment
Output-2 zero adjustment
Output-2 span adjustment
Self-check result
Test
ON/OFF of RJC
*2
Forced output-1
Forced output-2
Self-check result
4
IM 77J04U05-02E 3rd Edition Oct. 15, 2007-00
Page 5
7. MAINTENANCE
The product starts running immediately when the power is turned on; however, it needs 10 to 15 minutes of warm-up before it meets the specified performance.
7.1Calibration Apparatus
● A DC voltage/current standard (Yokogawa 7651 or the equivalent)
● A 6-dial variable resistor (Yokogawa M&C 279301 or the equivalent)
● A digital mutimeter (Yokogawa 7561 or the equivalent)
● A precision resistor of 250 Ω ±0.01%, 1 W
● A setting tool for adjustment
(Refer to “4.2 Connector for Communication” in this manual.)
7.2Calibration Procedure
(1) Connect the instruments as shown below.
(2) When the input type is thermocouple:
(2-1) Turn off the RJC using the switches on the front panel, or through the setting tool.
(2-2) Use the DC voltage/current standard and apply the electromotive force equivalent to 0, 25, 50, 75, and 100% of the measuring range to the
(3) When the input type is RTD:
(4) When the input type is mV DC:
(5) Check to see the corresponding output voltages are 0, 25, 50, 75, and 100% respectively and within the specified accuracy rating.
● Use the setting tool (VJ77 Parameter Setting Tool or JHT200 Handy Terminal) or the switches on the front panel (selection switch and adjustment
Input Adjustment Procedure
(1) Input the value equivalent to 0% value of input range.
(2) Call the display item (A: DISPLAY1) to check the input value in A01: INPUT1.
(3) If the adjustment is necessary, call the adjustment item (P: ADJUST).
(4) Select P02: IN1 ZERO ADJ to enter the adjustment mode. Select EXECUTE (adjustment) for adjustment. (If RESET is selected, the adjusted
(5) Input the value equivalent to 100% value of input range.
(6) Call the display item (A: DISPLAY1) to check the input value in A01: INPUT1.
(7) If the adjustment is necessary, call the adjustment item (P: ADJUST).
(8) Select P03: IN1 SPAN ADJ to enter the adjustment mode. Select EXECUTE (adjustment) for adjustment. (If RESET is selected, the adjusted
Output Adjustment Procedure
(1) When adjusting 0% value of output-1, call the adjustment item (P: ADJUST) to select P26: OUT1ZERO ADJ.
(2) If it slips out to (+) side, set (−) value equivalent to slipout; if slips out to (−) side, set (+) value equivalent to slipout.
*: The 100% value of output-1 and the 0% value and 100% value of output-2 can be adjusted by the same operation as the above.
converter.
Use the 6-dial variable resistor and apply the resistance equivalent to 0, 25, 50, 75, and 100% of the measuring range to the converter.
Use the DC voltage/current standard and apply input signals equivalent to 0, 25, 50, 75, and 100% of the input span to the converter.
“R0” is used for current output.
switch) to adjust the input/output signals.
For thermocouple input, turn off the RJC.
value is reset to the factory-set default.)
value is reset to the factory-set default.)
For adjustment using a setting tool, refer to the User’s Manual for each setting tool and “6. List of Parameters” in this manual.
For adjustment using the switches on the front panel, refer to “4.3 Selection Switch and Adjustment Switch.”
User’s Manual for VJ77 [Document No.: IM 77J01J77-01E]; however, use the VJ77 of version R1.04 or later.
User’s Manual for JHT200 [Document No.: IM JF81-02E]
Power supply
L
7
N
8
GND
9
Output-2
10
Digital
R
0
multimeter
11
R0: 250 Ω precision resistor
for current output
1
R
2
R0: 250 Ω precision resistor
for current output
8 76 5
10 11
Output-1
Digital
0
multimeter
4
39
1 2
5
6
4
5
6
Input
TC, mV
RTD
A
B
B
+
DC voltge/
current
standard
−
6-dial
variable
resistor
5
IM 77J04U05-02E 3rd Edition Oct. 15, 2007-00
Page 6
6
IM 77J04U05-02E 3rd Edition Oct. 15, 2007-00