Yokogawa HIMHART User Manual

November 2005 224-778-00C
Smart HART® Loop
Interface and Monitor
HIM
Loop
®
Interface and Monitor
Smart HART
HIM

Table of Contents

The HIM ..............................................................................................................3
About this Manual ...............................................................................................................3
Specifications .....................................................................................................................4
HIM Dimensions .................................................................................................................5
Terminal Designations ........................................................................................................ 5
Configuring the HIM .........................................................................................6
Installing the HIM ..............................................................................................7
Installing the HIM into the Loop ........................................................................................... 7
Bench Checking the HIM ....................................................................................................9
PC Configuration Software............................................................................10
HART Parameters ............................................................................................................ 11
Display Parameters .......................................................................................................... 13
Alarms Parameters ........................................................................................................... 14
Analog Outputs Parameters ..............................................................................................16
Custom Curve Parameters ................................................................................................ 18
Scaling Parameters .......................................................................................................... 19
Customer Service ...........................................................................................20
Appendix A: HIM MODBUS Feature .............................................................21
2 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor

The HIM

The Moore Industries HIM HART Interface Module unlocks the full potential of new and in-place HART multivariable transmitters, valves, meters and other smart instruments.
Converts HART to 4-20mA Signals
The HIM allows up to three additional analog process variable measurements from a multivariable transmit­ter or valve with no additional process penetrations. Installed transparently across the 4-20mA instrument loop, the HIM reads the HART digital process data that rides on the loop wires. It converts the digital informa­tion for up to three isolated analog (4-20mA) process signals that are readily accepted by in-place control systems, such as a DCS or PLC.
Provides Process and Diagnostic Alarms
Relay alarm trips (optional) can be individually user-set either to trip when unwanted high/low process condi­tions occur, or provide a diagnostic health warning to alert of loop or instrument fault conditions.
Takes Advantage of Legacy Instruments
The device lets you leave existing smart HART trans­mitters and valves in place, yet still take advantage of all the information they have to offer.
Works with every Smart HART Device
The instrument can be programmed in minutes to inter­face with every HART-compatible monitoring and con­trol device.

About this Manual

Wherever you see a “ pay particular attention.
•A “
Note
” provides information to help you in avoiding minor inconveniences during calibration, installation or operation of the HIM.
•A “
Caution
to avoid procedures and practices that could risk damage to the HIM or other equipment.
•A “
WARNING
take to avoid procedures and practices that could pose safety risks to personnel.
Note
”, “
Caution
” provides information on steps to take
” provides information on steps to
”, or “
WARNING
Figure 1. The HIM Accepts a Digital HART Signal and Outputs Both Analog Signals and Alarm Relays
HART Communicator can
be connected anywhere
along the 4-20mA loop
(HART Secondary Master)
4-20mA Representing the
Primary Variable (Mass Flow)
HART Digital Signal Carrying Primary, Second, Third, Fourth Variable Process Data, and Instrument Diagnostic Information
HIM HART Interface Module
"Breaks Out" Data from
Smart HART Instruments
(HART Primary Master)
4-20mA Proportional to 2nd Variable (DP) 4-20mA Proportional to 3rd Variable (P)
4-20mA Proportional to 4th Variable (T) High Alarm in Response to 4th Variable (T)
HART Transmitter Fault Alarm
Smart HART Multivariable Mass Flow Transmitter
Flow
Control System
(DCS or PLC)
The Interface Solution Experts 3
HIM
Smart HART Loop Interface and Monitor

Specifications

Performance
Specifications and information subject to change without notice.
4 The Interface Solution Experts
Input Accuracy: Reflects the accuracy of the HART field device Input Impedance: Transmit Mode: 150 ohms; Receive Mode: Less than 5kohms
Input Over-Range Protection: ±5Vdc
ANALOG OUTPUTS Output Accuracy: ±0.015%
of maximum output span (20mA). Includes the combined effects of linearity, hysteresis, repeatability and adjustment resolution.
Output Response Time:
<120ms, 10-90% Isolation: 500Vrms channel­to-channel isolation; 1000Vrms between case, input, outputs and power terminals, and will withstand 1500Vac dielectric strength test for one minute with no breakdown Ripple: Less than 10mV peak-to-peak when measured across a 250 ohm resistor Output Limiting: 130% of span maximum; 125% of span typical
Output Protection:
Transient protection on output
Load Capability:
0-20mA, 1100 ohms maximum Load Effect: ±0.01% of span from 0 to maximum load resistance
Line Voltage Effect:
±0.005% of output span for a 1% change in line voltage Input Fail Modes: PC programmable to fail high, fail low, hold last, hold last then fail high, or hold last then fail low (configurable hold time, 0­60 seconds)
Output Limits on Input Failure: 0-20mA: Fail Low to
0mA or Fail High to 23.6mA; 4-20mA: Fail Low to 3.6mA or Fail High to 23.6mA; X-20mA (0<X<4): Fail Low to 90% of XmA or Fail High to
23.6mA
Performance
(Continued)
Indicators
+TX Power Supply: 24.0Vdc
±10%@24mA
ALARM OUTPUTS Digital Response Time:
Defined by HART protocol as 500msec maximum in Normal HART Mode; 333msec maximum in HART Burst Mode
Alarm Response Time:
Digital Response Time + 150msec (Defined as time from the field instrument’s reporting a fault until the HIM alarm is tripped)
Alarm Trip Delay:
Programmable from 0-120sec
MODBUS OUTPUTS Type: Standard MODBUS
RTU protocol interface over RS485 (parameters as specified in U.S. Standard EIA-RS485)
Address Range:
Configurable from 1 to 247. Unit will assume a MODBUS address of 01 by default Baud Rate: Interface supports the following: 300, 600, 1200, 4800, 9600, 19.2k. MODBUS interface will support even, odd and no parities. Unit will assume a baud rate of 9600 and no parity by default Character Format: One start bit, 8 data bits and one stop bit Data Format: User­selectable Standard LSW (Least Significant Word) or Swapped MSW (Most Significant Word). Unit will assume Standard LSW by default
Power Consumption:
2-3.5W, nominal; 4.5W @24Vdc maximum for units using transmitter excitation to supply loop power a 2-wire instrument
LCD Type: Two-line LCD; Top Row, 10mm (0.4 in) high black digits on a reflective background; Bottom Row, 6mm (0.225 in) high digits on a reflective background; two-digit HART address indicator
Indicators
(Continued)
Ambient
Conditions
Weight
Format: Top row is five
alphanumeric characters, plus sign and decimal point; bottom row is five alphanumeric characters Decimal Points: User­selectable for 0, 1, 2 or 3 places after the decimal point or automatically adjusting with a four decimal point maximum
Range: -99999 to 99999 Minimum Display Span:
1.00
Display Update Rate:
100msec LED Type: Dual color red/green indicate: INPUT LED: Whether (green) or not (red) the HART input is connected and functioning properly READY LED: Whether (green) or not (red) the HIM is initialized and operating properly TRIP 1 and 2 LED: Shows the status of alarm off (green) or alarm on (red)
Operating & Storage Range:
-40°C to +85°C (-40°F to +185°F)
Display Range:
-25°C to +85°C (-13°F to +185°F)
Relay Range:
-25°C to +70°C (-13°F to +158°F)
Relative Humidity:
0-95%, non-condensing
Ambient Temperature Effect: ±0.0065% of
span/°C maximum
RFI/EMI Immunity (Standard):
20V/m@20-1000MHz, 1kHz AM, when tested according to IEC1000-4-3-1995
RFI/EMI Immunity (with
-RF Option): 30V/m@
20-1000MHz, 1kHz AM, when tested according to IEC1000­4-3-1995 Noise Rejection: Common Mode: 100dB@50/60Hz
567 grams (16 ounces)

Figure 2. HIM Dimensions

65mm
(2.56 in)
T1
T5
T3
T2
T4
T7
T6
HIM
Smart HART Loop
Interface and Monitor
138mm
133mm
(5.25 in)
T8
T9
T10 T11
T12
(5.45 in)
READYINPUT
60.278
ADDR
0
B2
B1

Table 1. Terminal Designations

HART Input, 2 Analog Outputs (2AO)
HART Input, 3 Analog Outputs (3AO)
COM
B3
B4
DEG C
HIM
B5
INPUT / OUTPUT
B8
B7
B6
TRIP 2TRIP 1
HART INTERFACE MODULE
B9
B11
B10
B12
100mm
(3.94 in)
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12
+I Source
+TX
+TX
+IN
+IN
–IN
–IN
+I
Source
(AO3)
No Label
–I Source
or
+I Sink
(AO3)
–I Sink (AO3)
(AO2)
+I Source
(AO2)
–I Source
–I Source
or
+I Sink
(AO2)
or
+I Sink
(AO2)
–I Sink
(AO2)
–I Sink
(AO2)
+I Source
(AO1)
+I Source
(AO1)
–I Source
or
+I Sink
(AO1)
–I Source
or
+I Sink
(AO1)
–I Sink
(AO1)
–I Sink
(AO1)
HART Input, 2 MODBUS Oututs
and 1 Analog Output (MB1AO)
HART Input, 2 MODBUS Outputs (MB)
ALARM RELAYS / POWER
No Alarm
Single Alarm (–1PRG)
Dual Alarm (–2PRG)
KEY:
+IN/–IN = Current input to HIM from HART device +TX = Transmitter Excitation Current +I/–I Source = Analog Source Output +I/–I Sink = Analog Sink Output A/B = MODBUS Output NO/NO# = Normally Open NC/NC# = Normally Closed CM/CM# = Common DC/DCC = 24VDC Connection (AO#) = Analog Output
+TX
+IN
–IN
Source
+TX
+IN
–IN
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12
No Label
NO1 CM 1 NC1
NO1 CM1 NC1 NO2 CM2 NC2
Relay 1
NO2 CM 2 NC2
Relay 1
A
+I
(AO)
Relay 2
–I Sink
–I Source
or
+I Sink
(AO)
No Label
NOTES:
1. The standard Single Alarm unit (1PRG) utilizes a DPDT relay.
2. Terminal blocks can accommodate 14-22 AWG solid wiring (torque to 4 inch-pounds, maximum).
(AO)
MODBUS
MODBUS
B
MODBUS
2
B
MODBUS
2
No Label
MODBUS
MODBUS
2
A
2
The Interface Solution Experts 5
A
S
MODBUS
2
S
MODBUS
2
DC
DC
DC
B
MODBUS
1
A
MODBUS
1
DCC
DCC
DCC
S
MODBUS
1
1
S
B
MODBUS
1
1
Ground
Ground
Ground
HIM
Smart HART Loop Interface and Monitor

Configuring the HIM

One of the benefits of the HIM is that there are no internal or external controls to adjust or settings to change. All operating parameters are set using the PC Configuration software.
Once these software settings are made, they are downloaded to the monitor in the form of a Configuration File and stored in the unit’s non-volatile memory. You can choose to save a backup copy of the file on your PC hard drive or external media. The HIM communi­cates with the PC through a proprietary communica­tions cable to the PC’s serial (COM) port.
Begin by installing the PC Configuration Software.
Installing the PC Configuration Software
Refer to Table 2 for the equipment needed.
1. Insert the
PC Configuration Software
of the PC. Access the CD and open the
PC Configuration Software
2. Double-click the installation program located in the folder. Follow the prompts to correctly install the program.
Moore Industries Interface Solution
CD into the CD drive
HIM
folder.
Table 2. Assembling the Necessary Equipment
Device Specifications
Precision Load
Resistor
Multimeter or
Ammeter
Power
Supply
Personal Computer
PC Operating
System
Moore Industries
PC Configuration
Software
Communication
Cable
250 ohms, ±0.01%
Accurate to ±0.009% of span; e.g. HP Model 3487A
24Vdc, ±10%
80386-based(or faster) IBM PC, or 100% compatible; (Pentium recommended) CD Drive 4Mb free RAM; 16Mb recommended 20Mb free disk space on hard drive 1 (one) serial port (COM 1, 2, 3 or 4)
Microsoft Windows® 95, 98, 2000, ME, or NT with Internet Explorer 4.0+
Microsoft Windows® NT with Service Pack 3 or greater
Version 1.0 or higher, successfully installed to the hard drive
Part Number: 803-053-26, or equivalent
or
Once the Configuration Program is installed on the PC, the unit can be connected either into the loop or to test equipment to simulate input and monitor output. With the PC program, the user can then view and/or change its operating parameters. To begin the process, connect the HIM either into the loop (see
the Loop Checking the HIM
6 The Interface Solution Experts
) or into a configuration setup (see
).
Installing the HIM into
Bench
HIM
Smart HART Loop
Interface and Monitor

Installing the HIM

There are two methods for connecting the HIM for
Mounting
The HIM is designed to snap easily onto 32mm, G-type (EN50035) or 35mm Top Hat (EN50022) DIN rails.
configuration. The recommended method requires you to install the instrument into the loop before it is configured. The secondary method allows you to bench check the HIM by attaching it to test equipment that will simulate the input and monitor the output.
Electrical Connections
After mounting, you are ready to connect the HIM to the loop. Each unit comes equipped with a transmitter excitation terminal which allows it to supply power to the monitored HART instrument, if necessary. Figures
Installing the HIM into the Loop
Installation consists of physically mounting the unit,
2 and 3 show the connection diagrams for an HIM with or without using the transmitter excitation current.
grounding the instrument, and completing the electrical connections. To install the HIM into the loop for configuration, use the equipment in Table 2 to hookup the HIM into the loop as shown in Figure 3 (without using the HIM to power a transmitter) or Figure 4 (using the TX terminal to power a transmitter). If you need a
CE Conformity
Installation of any Moore Industries products that carry the CE certification (Commission Electrotechnique)
must
adhere to the guidelines in
order to meet the requirements set forth in applicable
complete terminal description, refer to Table 1.
Figure 3. Installing a HIM Into the Loop Without Using the Transmitter Excitation (+TX) Terminal
HART Communicator can be connected anywhere on the loop
7
8
4
9
5
1
6
2
0
3
.
Sensor
Input
24Vdc Power
+–
+
4-20mA
Installing the HIM
R must be > 250 and <1100 Ohms
R
in
HART Multivariable
Field Instrument
(Temperature
Pressure, Level
and Flow)
NO (normally open)
COMMON
NC (normally closed)
+IN
NO
READYINPUT
ADDR
0
COM
COM
–IN
NC
TRIP 2TRIP 1
DC
DCC
24Vdc Power
Source
GND
DCS
Analog Output tied to Any Process Variable
50.7
25.1
80.1
deg-c
20.3
Event Recorder
The Interface Solution Experts 7
HIM
Smart HART Loop Interface and Monitor
EMC (Electromagnetic Compatibility) directives (EN55011, EN 50082-1, EN50082-2, etc.). Consult the factory for the most current information on products that have been CE certified.
• All input signals to, and output signals from, Moore Industries’ products should be wired using a shielded, twisted pair technique. Shields are to be connected to an earth or safety ground at the unit itself.
Recommended Ground Wiring Practices
Moore Industries recommends the following ground wiring practices:
• Any Moore Industries product in a metal case or housing should be grounded.
• The protective earth conductor must be connected to a system safety earth ground before making any other connections.
• The maximum length of unshielded input and output signal wiring should be 2 inches.
Power Sourcing Parameters for General Locations, Intrinsically Safe, and Non-Incendive/Type N applications
In accordance with IEC 1010.1 Annex H (all models), the input terminals must be connected to and/or supplied from a certified energy limiting Class 2 or a Separate Extra Low Voltage (S.E.L.V.) power supply separated from all mains by double/reinforced insulation.
Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal
7
8
4
9
5
1
6
2
0
3
.
HART Communicator can be connected anywhere on the loop
R must be > 250 and <1100 Ohms
Sensor
Input
HART Multivariable
Field Instrument
(Temperature,
Pressure, Level
and Flow)
4-20mA
+
NO (normally open)
COMMON
NC (normally closed)
+IN
+TX –IN
READYINPUT
ADDR
0
COM
NO
NC
COM
TRIP 2TRIP 1
DC
24Vdc Power
Source
DCC
R
DCS
Analog Output tied to Any Process Variable
Event Recorder
GND
8 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor

Bench Checking the HIM

If you would like to configure the HIM before attaching it to the loop, you need to hook it up with the equipment listed in Table 1. Refer to Figures 5 and 6 for instructions on how to bench check the HIM either with or without taking advantage of the Transmitter Excitation (+TX) terminal. If you need further descriptions of the terminals, see Table 2.
Figure 5. Bench Checking the HIM Using the Transmitter Excitation (+TX) Terminal to Power a Transmitter
Sensor
Input
HART
Field Device
or
Simulator
Equipment Hook-Up
for HART field device using
Transmitter Excitation
+
+TX
R must be > 250 and <1100 Ohms
R
+IN –IN
+
READYINPUT
ADDR
0
COM
TRIP 2TRIP 1
+
Multimeter
Figure 6. Bench Checking the HIM Without Using the Transmitter Excitation (+TX) Terminal to Power a Transmitter
For a HART Transmitter, the resistor must be >250 and <1100 ohms. For a HART Receiver, such as a valve positioner, no resistor is necessary.
R
–IN
READYINPUT
ADDR
0
COM
NO
NC
COM
+
TRIP 2TRIP 1
DC
24Vdc Power
DCC
GND
+
Multimeter
Sensor
Input
HART
Field Device
or
Simulator
Optional
24Vdc Power
+–
+
+IN
Multimeter
Checks for
continuity
Optional
NO
COM
Multimeter
Checks for
continuity
Optional
NC
DC
24Vdc Power
DCC
GND
The Interface Solution Experts 9
HIM
Smart HART Loop Interface and Monitor

PC Configuration Software

Figure 7. HIM PC Configuration Software Screen
1
3
2
The HIM PC Configuration Software can be used to program all of the HIM’s parameters. Once the default configuration has been saved, it is safe to program other parameters. The PC Software is made up of these sections:
1. HIM Status and Information Section–The left side of the screen includes seven boxes that display the different settings of the attached HIM.
Program Status–Displays the activity of the connected HIM. It will show you if the unit is
Uploading, Downloading, Monitoring
HIM Device Info–Displays the individual charac teristics of the attached HIM, such as its Identifi­cation, Hardware and Software Revisions, and the last date that the device was configured.
HIM Tag–A phrase used to identify a HIM.
10 The Interface Solution Experts
or
Searching.
Idle,
HIM Device Status–Displays how the HIM is function­ing, giving a brief summary of any errors or displaying
OK
if it is operating normally.
HIM Displayed Data–this display mirrors what the at­tached HIM is displaying.
Progress–This bar stays in motion any time the HIM is monitoring, uploading or downloading.
Communication Status–monitors the PC Software’s ability to communicate with the HIM.
2. HART/Display/ Alarms/Analog Outputs/Custom Curve/ Scaling Tabs–These tabs change the right side of the screen to allow you to set the appropriate part of the HIM’s configuration. Refer to the associ­ated pages in this document for additional information on these tabs.
3. Menu Bar/Tool Bar– Dropdown menus and corre- sponding icons allow you to perform various functions throughout the PC Configuration Program.
HIM
Smart HART Loop
Interface and Monitor

HART Parameters

To program the HART parameters, change the settings in the
Communications Settings
Set
. See the descriptions below of the various
sections of the screen.
HART Address
The
HART Address
that the HIM will be monitoring.
Number of Retries
The
Number of Retries
and will determine how many times the HIM will attempt to poll the HART transmitter (without success), before it indicates a HART Fault condition.
Normal/Burst/Listen (Passive) Modes
The HIM can operate in one of four modes:
Burst
, or
Listen (Passive)
In each of these modes, the HIM attempts to find a HART transmitter.
In
Normal
transmitter, then polls the HART instrument twice per second, requesting the current process status and the HART instrument’s diagnostic status. The HART instrument responds with the requested data.
In
Burst
programmed to continuously transmit its process variable and health status. The HIM samples the continuous HART data three times per second.
Listen (Passive)
loop that already has primary and secondary HART masters. In connects passively, continuously sampling HART data from a smart instrument without affecting normal loop operation. When using this mode, either the monitored smart HART instrument must be set in HART master must be continuously polling the smart HART slave device.
mode, the HIM polls the HART loop for a
mode, the monitored HART instrument is
Listen (Passive)
is the address of the HART device
can be set between 1 and 9,
mode allows the HIM to operate on a
box, then press
and
Listen (Specified Slave)
mode, the monitor
Burst Mode
Quick
Normal
,
or a
The HART protocol allows for two communications masters on the loop, a Primary and a Secondary. Setting the HIM to function as the Primary HART Master in the application means that any other HART device in the loop must be configured either as a HART Secondary Master (1 per loop) or as a HART Slave (up to 16 per loop). Conversely, setting the HIM to function as the Secondary HART Master allows other HART devices to function either as a Primary Master or as slaves. Configuring more than one device on a single loop as a Primary or Secondary HART Master will cause a communications failure.
Listen (Specified Slave)
When multiple HART instruments are present, the
Listen (Passive)
returned from one instrument will overwrite the data previously stored in the HIM. If multiple HART slave instruments are communicating on the loop, the HIM
.
will overwrite its internal HART data sets with the latest device read from the bus, no matter where the data originates. To allow selective monitoring on a multi­instrument loop, and to allow multiple HIMs to be used on a digital loop, the used.
If the HIM is in “Listen” mode it is not a HART commu­nication master and therefore is not in control of communication. Other HART masters are controlling the polling of slaves and the HIM can only “Listen”.
The HIM must be able to detect when it has not heard from its assigned slave device so that it can declare a “No HART” input and force outputs to the values specified by the user. The HIM must therefore be told to wait an appropriate amount of time for the slave device to send its message before the HIM declares “No HART”. This timing coordination is accomplished with
Timeout Period
Timeout Period
must be greater than the period between polls by the HART master of the Specified Slave. For example, assume that there are five HART transmitters on the same multi-drop loop as the HIM. The HART master is configured to poll each device every second. It then takes the HART master five seconds to repeat the poll to the one device being monitored by the HIM. the HIM
Timeout Period
mode cannot be used because data
Listen (Specified Slave)
.
is a value between 1 and 30sec and
must be set at a value greater than five
feature is
The Interface Solution Experts 11
HIM
Smart HART Loop Interface and Monitor
seconds. In this example, we will use seven seconds. The HIM then sees its slave device speak and waits seven seconds for it to speak again. As long as the HIM sees a new message from its slave device its outputs are updated based upon the measured vari­ables. If the slave device does not speak within the seven second period, the HIM declares a “No HART” situation and sends its outputs to the failed communi­cations values.
To use this feature, proceed with the following steps:
1. Select the
2. Enter your desired value into the text box.
Factory default is 5 seconds. The maximum Timeout Period is 30 seconds.
3. Set the exact slave address of the instrument you wish to monitor. Click the This brings up the
Address Settings
information into the appropriate text boxes.
Listen (Specified Slave)
Set Slave Address
HART Slave Device Long Format
screen (Figure 8). Enter the required
button.
Timeout Period(s)
button.
To convert HEX to Decimal code, perform the following steps:
Access the Calculator feature in Microsoft Windows® by opening the select
Programs
Calculator
Ensure that the Calculator is in To do this, select the and choose
Click the code value.
Next, click the converted into the Decimal value.
Enter the converted value into the proper param eter.
The the exact device to which the HIM will listen.
4. Once complete, press OK.
Hex
Device ID Number
then
.
Scientific
radio button and enter the HEX
Dec
button and the value will be
Start
menu. Next,
Accessories
View
dropdown menu
.
is the serial number of
and finally
Scientific
mode.
Figure 8. HART Slave Device Long Format Address Settings Screen
The
Manufacturer’s ID
instrument that the HIM will listen to are available from the HART Foundation website at www.hartcomm.org and/or the instrument manufacturer.
Values obtained from the HART website are in HEX code. The HIM does not use HEX code; you must convert this value to Decimal code.
and
Device Type ID
for the
Download the information to your instrument once you are finished.
Auto Clear Status Bit
Most HART instruments indicate when a device's configuration has been changed. This indication (status bit) can be reset by sending HART command 38–reset configuration changed. Checking the
Clear Status Bit
command whenever the HART instrument it is monitoring has its configuration changed. However, the HIM can also be set to alarm on this bit (see
Programming the Alarm Parameters
both set to alarm and to auto clear, then it will do both–going into alarm mode and resetting that indication.
Quick Read/Set
The
Quick Read
Software to read the communications information from the attached HIM; the software to configure the HIM’s communications settings to match those of the PC Software.
box causes the HIM to issue this
). If the HIM is
button causes the PC Configuration
Quick Set
button causes the
Auto
12 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor
HART Device Info
This box displays the identification and revision information of the monitored HART instrument.
HART Device Status
The HART Device Status box displays the current status of the monitored HART transmitter. In a small double-box, the software displays the code (hex number) associated with the status.
Variables
The device will monitor up to the first four HART variables sent by your transmitter. This portion of the screen displays those variables and the Loop Current.
HART Device Range & Limits
This portion of the screen displays the range and the sensor limits of the monitored HART transmitter.

Display Parameters

The
Display
program the Display parameters, change the settings in the
Display Source
the following descriptions of the various sections of the screen.
Figure 9. Display Tab
tab configures the HIM’s LCD display. To
box, then press
Quick Set
. See
Toggle, Variable List
The
Toggle
display two HART variables in five second increments. Directly below the to select the variables that you would like to be displayed. Notice that if you select a scaled variable, it is important to check on the that you have set all of the scaling parameters.
Use Custom Label
The
Custom Label
scaled variable. Clicking the causes the HIM to always display the custom label as Engineering Units (EGUs).
Precision
The
Precision
of decimal places displayed by the HIM.
Quick Set
The
Quick Set
information on the Display page.
Display Format
The HIM reads the dynamic process variable supported by HART sensors. Generally, the HIM’s LCD displayed values range from -99999 to 99999. Occasionally, these process variable values may extend past this range. To improve the displayed readings, values below -XXXXX and above XXXXX are translated into exponential form. Below is an example of the appear­ance of the display when certain values are sensed.
checkbox causes the HIM to sequentially
Toggle
is used to display a calculated or
buttons allow you to change the number
button programs the HIM with the
checkbox are two list boxes
Scaling
Use Custom Label
page to verify
box
Value Display
12345 12345
1234500 1.23E06
-500000 -5.00E05
The Interface Solution Experts 13
HIM
Smart HART Loop Interface and Monitor

Alarms Parameters

The Alarms tab controls the programmable alarm trip(s) option. This screen will be grayed out if the attached HIM is not equipped with at least one alarm trip. To program the Alarm parameters, change the settings in the
Quick Set
below.
Figure 10. Alarms Tab
Alarm1
. The sections of the screen are described
and/or
Alarm2
box, then press
Device Malfunction (Bit 7)
Relay trips whenever it detects that a hardware error or failure has occurred in the connected HART device.
Configuration Changed (Bit 6)
Relay trips whenever it detects that the connected HART device has had its configuration changed.
Cold Start (Bit 5)
Relay trips whenever the power to the HART device is interrupted. It will also trip during a HART Master Reset or Self Test Command.
Additional Status (Bit 4)
Relay trips whenever the connected HART device reports a condition requiring HART Command #48, which is Read Additional Information. This indicates that the instrument needs attention from a device with full HART command capability.
Output Current Fixed (Bit 3) Relay trips whenever the HIM detects that the connected HART device’s output is no longer responding to changes in its input, and is being held at a predefined level.
Trip/Fault Alarms
A
Trip Alarm
either when the variable exceeds a set value (Trip High) or when the variable falls below a selected value (Trip Low). The monitored, while the the alarm will trip. After the alarm trips, the
Band
determines how far past the trip point the variable will have to go before the alarm condition returns to normal.
There are two types of Fault Alarms. A
Alarm
trip whenever the internal error status word is set. For example, if the HIM’s configuration file becomes corrupt, this alarm will trip and the monitor will display BAD_CONFIG. A the health of the HART transmitter. This fault alarm will trip for any of these eight malfunctions:
monitors a selected variable and trips
Source
monitors the health of the HART monitor. It will
specifies which variable will be
Trip Point
Field Device Fault Alarm
sets the point at which
HIM Fault
Dead
monitors
PV Analog Output Saturated (Bit 2)
Relay trips whenever it detects that both its analog and digital representations of the Primary Variable are outside rated operating limits, and no longer reflect the true sensor input.
Non-PV Out of Limits (Bit 1)
Relay trips whenever one of the HART ancillary variables (second, third or fourth), is operating outside the limits that can be effectively measured.
PV Out of Limits (Bit 0)
Relay trips whenever the HART Primary Variable is operating outside the limits that can be effectively measured.
Delay & Fail Safe
By entering a value in the how long (in seconds) the alarm condition needs to exist before the alarm trips. checked) de-energize when in alarm condition;
Non-Failsafe
alarms energize when tripped.
Delay
box, you can specify
Failsafe
alarms (box
14 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor
HART Additional Status Alarm Bits
HART Additional Status also called “More Status” and “Command 48” is where device manufacturers install the custom diagnostics for the specific device. For your particular application, you may choose all of these diagnostics to cause the HIM relay to trip or just one diagnostic bit to trip the HIM relay (or any combination in between). The manufacturer of the HART device will be the source for the specific diagnostic information.
Selecting the
Alarms
alarm states, when in fault mode, based on the bit settings of the additional status information returned by certain HART instruments. This provides flexibility to the requirement of alarming on additional status infor­mation.
Choosing this feature, you are given the ability to specify the bit(s) on which to alarm. To access this feature, check the button will appear in the section of the screen. Clicking the the
Additional HART Status Alarm Bits Settings
(Figure 11). Check the box(es) that correspond to the bits you wish to use; click OK.
Field Device Fault Alarm
screen allows you to enable the HIM to set
Additional Status
HART Additional Status Bits
function in the
box. The
Edit
box brings up
Edit
window
Read & Quick Set Buttons
The
Read
button causes the PC Configuration Software to read the alarm information from the attached HIM; The
Quick Set
the HIM's alarm settings to match those currently entered in the PC Software.
button causes the software to configure
Download the information to your instrument once you are finished.
Figure 11. Additional HART Status Alarm Bits Settings Window
The Interface Solution Experts 15
HIM
Smart HART Loop Interface and Monitor

Analog Outputs Parameters

The HIM comes with either two (–2AO) or three (–3AO) analog outputs. The specify which HART variable is to be monitored as the source of the analog output, the input range and output range, and how the output will react when the variable input is out of range. To program the Analog Outputs parameters, change the settings in the boxes, then press below of the various sections of the screen.
Figure 12. Analog Outputs Tab
Analog Outputs
Quick Set
. See the descriptions
tab allows you to
Output1/2/3
For example, you have a vortex flow meter with an imbedded RTD that measures the process temperature, and that temperature is assigned to the HART Secondary Variable. The full range of the RTD sensor is from –400°F to +1760°F, but your flow stream will always be between 0° and 400°F. To scale the analog output, for Output 1, set the Set the
Range
the new configuration file to the HIM.
Output Current Box
The displays up-to-the-second information on the value, in mA, of the analog output.
Fail Mode
The respond when its monitored input fails. If set to or any detected error occurs in the HART transmitter, the analog output will output a 23.6mA signal. If Fail Mode is set to range, or any detected error occurs in the HART transmitter, the analog output will output a signal that is 90% of the lower range value below 4mA; it will output 0mA if the lower range is set to 0mA.
Input Range
to 4mA to 20mA. Click
Output Current
Fail Mode
High
and the measured input goes out of range,
to 0° and 400°F, and the
Quick Set
Box on the
setting determines how the HIM will
Low
and the measured input goes out of
Analog Outputs
Source
as SV.
Output
to download
Tab
Fail Mode
is
Source
Source
monitor. Notice that selecting one of the scaled outputs will require you to make changes to the
Scaling
require you to make changes to the
Input/Output Range
The source input and the range of the analog output. These two sets of fields can be used to scale the HIM’s output.
defines the variable that the analog output will
tab, and selecting the Custom Curve option will
Custom Curve
Input or Output Range
defines the range of the
tab.
If
Fail Mode
to output the last value it recorded before the input failed. If
Hold Last Then Low
last value recorded for a set amount of time (according to Hold Last Duration box), then either fail high or fail low, respectively.
Quick Set Button
The
Quick Set
the instrument’s analog output settings to match those currently entered in the PC Software.
Trim Button
The
Trim
to set the device’s output to match the reading of the loop. Refer to the
Parameters
information.
is set to
Fail Mode
button brings up the Trim Menu, allowing you
section of this manual for more
Hold Last
is set to
, the HIM will continue to output the
button causes the software to configure
Programming the Trimming
, the HIM will continue
Hold Last Then High
or
16 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor
Configuring Analog Output Trimming
The
Analog Output Trimming
allows you to match the HART monitors analog output to the output measured by a calibration device. This will require a calibrated multimeter, such as a HP Model 3478A or equivalent, accurate to ±0.009%.
Trimming the analog output of the monitor
nullifies any scaling that may have been
performed in the
Figure 13. Trimming Window
section of the software
Note:
Scaling
tab.
Fix Current Utility
The
Fix Current Utility
output any current value from 0-20mA. This can be used to match the calibration of your other equipment. To fix the current, simply enter the value in the box (in mA) that you want the HIM to output, and click
Fix Output
press the return to normal operation.
. When you are finished, make sure to
Unfix Output
allows you to force the HIM to
Current
button so that the HIM can
User Trimming
To trim the device, attach a multimeter to the analog output, then click the Read the value on the multimeter, enter it into the
Measured Output Loop Current
box, and press analog output matches the minimum point (4mA for a 4-20mA output) when you click the
Point
button.
After the low point is trimmed, press the
High Point
enter it into the of the sequence until the analog output matches the maximum point (20mA for a 4-20mA output) when you click the
When finished, press the
button. Read the value on the multimeter,
Trimming
Fix Output at High Point button
Fix Output at Low Point
portion of the
Trim
. Repeat this sequence until the
Fix Output at Low
Measured Output Loop Current
box, and press
Trim
. Repeat this
Unfix Output
button.
Trimming
Fix Output at
.
button.
portion
The Interface Solution Experts 17
HIM
Smart HART Loop Interface and Monitor

Custom Curve Parameters

The custom curve tab allows you to set up a custom curve of up to 128 points. A custom curve can either be created from scratch or loaded from a previously created comma separated value (.csv) file. To program the Analog Outputs parameters, change the settings in the
Table
. See the descriptions below of the various
sections of the screen.
Figure 14. Custom Curve Tab
Custom Curve
tab, then press
Download
Custom Curve Variable
The
Custom Curve Variable
information on the value of the Custom Curve. Press the
Monitor
Custom Curve
The middle section of the screen displays the custom curve table. After enabling custom curve mode and setting the variable to be monitored, continue by selecting the number of points for the curve. Enter the actual linearization points into the custom curve table, inserting the source variable into the X Column, and the corresponding data (i.e. the °C, °F, Gallons, PSIG, Millimeters, etc.) into the Y Column.
When entering data in the linearization table, make
sure that you enter a number into every open cell.
Custom Curve File
These buttons allow you to manipulate custom curve files, including the important will save a table to your hard drive.
Upload Table
Moves a custom curve file from the connected HIM to the PC Software for editing or storage.
button to display the variable information.
displays up-to-the-second
Note:
Save Table
command that
Mode
Check the custom curve.
Source Variable
The custom curve will calculate. Notice that if you select a scaled variable, you may need to click on the tab and verify the settings for your scaled variable.
Quick Set
The the HIM’s custom curve settings to match those currently entered in the PC Software.
Enabled
Source Variable
Quick Set
box to begin programming the
button causes the software to configure
defines the variable that the
Scaling
Download Table
Configures the HIM by downloading the custom curve table from the PC Software to the HIM.
Save Table
Saves a displayed custom curve table to memory on your computer’s hard drive.
Load Table
Loads a previously saved custom curve table.
Clear Table
Clears the displayed custom curve table.
When you have finished changing all your settings, download the information to the HIM using the
Download Table
variable, you should also click on the set the scaling parameters.
button. If you have selected a scaled
Scaling
tab and
18 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor

Scaling Parameters

The
Scaling
scaled variables. To scale the selected variable, enter the values into the appropriate boxes, then click on the
Transfer
scaled values to the HIM. (If any scaled variable was selected in the then the corresponding scaled variable section will become active for editing).
The HIM’s versatile scaling feature has many possible applications, as is shown in the illustration below.
Suppose you are using a digital pressure (DP) transmitter to measure the level of a tank in either centimeters/inches or PSI. Since the tank is only 300 centimeters (10 feet) high, the full range of the primary variable (PV) output from the DP transmitter is 0-4.3 PSI. You want to display the full level range (in centimeters/inches of water) on the HIM. You also need to control the level from 50% to 100%, since the tank must be at least 50% full at all times. Finally, your existing loop indicator and level controller needs 4-20mA to represent 150 to 300 centimeters (60 to 120 inches) of water. How do you do this?
Scaling Illustration
1. Since you want to display the full level range in inches of water (in H2O) on the HIM, and the HIM is reading PSI as the primary variable, first go to the
Display
source.
tab allows you to configure the values for
menu and click
Download
to transfer the new
Display, Alarm or Analog Outputs
tab and select
Scaled PV
as your display
tabs,
Figure 15. Scaling Tab
2. Go to the
PV Full
values. be 4.3 (PSI).
Scaling
tab and set up the
values, and the
PV Zero
would be 0 (PSI) and
Scaled PV
Scaled PV Zero
PV Full
PV Zero
and
and
Full
would
would correlate to zero being 0 in H2O and full being 120 in H2O. The HIM should now (after downloading) display the full range in
in H2O
.
3. To manipulate the HIM’s analog output, go to the
Analog Outputs
tab. Select
Scaled PV
as the Output 1 source. Since you need to control the level from 50% to 100%, the and the
Input Range
Output Range
should be 60 to 120 in H2O
should be 4mA to 20mA.
Figure 16. The HIM’s Scaling feature works to get the most out of your existing process instruments
Control
level range
(50% to 100%
of total level)
Full
Primary
Variable
range
(in PSI)
Digital
Pressure
Transmitter
HART Signal
Loop Display
(reads 0-100%
of control
level)
4-20mA
Signal
HART Monitor
(120 PSI)
4-20mA
Signal
The Interface Solution Experts 19
Controller maintaining
control from 50-100% of full scale
(60-120 inH 0/2.15-4.3 PSI).
4-20mA from HART Monitor
should represent 60-120
2
inH 0.
2
HIM
Smart HART Loop Interface and Monitor

Customer Support

Moore Industries is recognized as the industry leader in delivering top quality to its customers in products and services. We perform a battery of stringent quality assurance checks on every unit we ship. If any Moore Industries product fails to perform up to rated specifi­cations, call us for help. Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide timely, accurate and practical answers to your process instrumentation questions.
Factory phone numbers are listed on the back cover of this manual.
If problems involve a particular instrument, there are several pieces of information that can be gathered
before you call the factory
the answers you need For fastest service, gather the complete model and serial number(s) of the problem unit(s) and the job number of the original sale.
that will help our staff get
in the shortest time possible.
20 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor

Appendix A: HIM MODBUS Feature

The HIM PC program allows you to configure the HART monitor. A HART Monitor with the MODBUS option provides a digital MODBUS output to a con­nected MODBUS-based controller. Selecting the
MODBUS tab
munications parameters. Notice that the will only be available in units with the MODBUS option.
Figure A-1. MODBUS Tab
allows you to set the MODSBUS com-
MODBUS
tab
Comms Settings
The Comms Settings include the following:
MODBUS Address
The
MODBUS Address
monitor uses to identify itself on the MODBUS net­work. The MODBUS address is configurable from 1 to
247. By default, it will assume a MODBUS address of
01.
Baud Rate
The
Baud Rate
should be set to match the baud rate of the attached controller. The interface supports the following baud rates: 300, 600, 1200, 2400, 4800, 9600 and 19200.
Parity
The HART monitor supports even, odd and no The data format is one start bit, 8 data bits and one stop bit.
Floating Point Word Order
By default, the HART monitor will use the
LSW
(least significant word) floating point word order format. This stores the most significant bits in the second register and the least significant bits in the first register. Selecting
word)
will reverse the order, storing the most signifi­cant bits in the first register and the least significant bits in the second register.
is the speed of data transmission. It
is the number that the HIM
Parity.
Standard
Swapped MSW (most significant
MODBUS Registers
The HART Monitor outputs a MODBUS signal to the attached controller. To access the MODBUS registers for variable, input/output or error information, refer to Table A-1 (MODBUS Register Definitons table) and/or Table A-2 (System Status Registers table).
The Interface Solution Experts 21
HIM
Smart HART Loop Interface and Monitor
Figure A-2. Installing a HIM with MODBUS output into the loop using the Transmitter Excitation (+TX) terminal
HART Communicator can be connected anywhere on the loop
R must be > 250 ohms and <1100 ohms
Sensor
Input
Field Instrument
(Temperature,
Flow Multivariable)
HART
Pressure,
Level,
4-20mA
+
NO (normally open)
COMMON
NC (normally closed)
+IN
+TX –IN
READYINPUT
60.278
ADDR
0
COM
NO
NC
COM
DEG C
A
TRIP 2TRIP 1
DC
DCC
24Vdc Power
Source
B
S
(with MODBUS option)
GND
R
RS485 / RS232 Converter
MODBUS output
DCS
TO serial (COM) port of PC
MODBUS Host
22 The Interface Solution Experts
Table A-1. MODBUS Register Definitions
HIM
Smart HART Loop
Interface and Monitor
Register Range
0
1
2
3
4
5
6
7
8
9
10
Description
HART Primary variable
HART Secondary variable
HART Third variable
HART Fourth variable
PV scaled
SV scaled
TV scaled
FV scaled
Linearized variable
Analog Output 1 current x 100mA
Analog output 2 current x 100mA
11
12
13
Analog output 3 currentx 100mA
HIM Status Information Bit 0 = hardware failure Bit 1 = EEPROM fail Bit 2 = EEPROM configuration checksum error Bit 3 = EEPROM calibration checksum error Bit 4 = EEPROM blank Bit 5 = Out of range error Bit 6 = Division by zero error Bit 7 = Configuration data bad error Bit 8 = COP SW fail Bit 9 = RAM test fail Bit 10-13 = not used Bit 14 = HART device malfunction status bit set Bit 15 = No HART communications status
HART status information (as per HART specification)
The Interface Solution Experts 23
HIM
Smart HART Loop Interface and Monitor
14 HART instrument PV EGU (MSB = 0, LSB = HART EGU code)
15
16
17
18
19
20
21
22
23
24
256-257
258-259
260-261
HART instrument SV EGU (MSB = 0, LSB = HART EGU code)
HART instrument TV EGU (MSB = 0, LSB = HART EGU code)
HART instrument QV EGU (MSB = 0, LSB = HART EGU code)
Device ID MSW
Device ID LSW
HART Device Manufacturer ID
HART Device, device type code
HART device, device ID MSW
HART Device, device ID LSW
HIM Alarm Status (Bit 0 = alarm 1, Bit 2 = alarm 2)
HART Primary variable (float format)
HART Secondary variable (float format)
HART Third variable (float format)
262-263
264-265
266-267
268-269
270-271
272-273
274-275
276-277
278-279
24 The Interface Solution Experts
Hart Fourth variable (float format)
Scaled Primary variable (float format)
Scaled Secondary variable (float format)
Scaled Third variable (float format)
Scaled Fourth variable (float format)
Linearized varialbe (float format)
Analog output 1 current x 100mA
Analog output 2 current x 100mA
Analog output 3 current x 100mA
Table A-2. System Status Registers
HIM
Smart HART Loop
Interface and Monitor
MSB/LSB
Int 16
(16 bit integar)
MSB = device status
LSB = device error code
Bit Position Description
Bit 7
Bit 6
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
HART device no comms
HART device malfunction
HW fail
EEPROM fail
EEPROM checksum error
EEPROM calib data error
EEPROM blank
out of range value
division by zero
bad configuration
The Interface Solution Experts 25
Declaration of Conformity
EMC Directive 89/336/EEC
• Manufacturer’s Name: Moore Industries-International, Inc.
• Manufacturer’s Address: 16650 Schoenborn Street
North Hills, CA 91343-6196 USA
Declares that the product(s):
• Product Name: HIM
MODEL / INPUT / OUTPUT / POWER / OPTIONS / HOUSING
• Model Number(s): HIM * * * * *
* Indicates any input, output, power, option and housing as listed on the product data sheet
• Conforms to the following EMC specifications:
EN 61326-1, 1998, Electromagnetic Compliance (EMC) requirements for electrical equipment for control use.
• Supplementary Information:
None
June 20, 2003
Date Fred Adt Robert Stockham
Quality Assurance Director Moore Industries-Europe General Mgr.
European Contact: Your Local Moore Industries Sales and Service Office
United States • info@miinet.com
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • sales@mooreind.com.au
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
China • sales@mooreind.sh.cn
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair –
If you are unsure if your unit is still under warranty, we can use the unit’s serial number to verify the warranty status for you over the phone. Be sure to include the RMA number on all documentation.
Non-Warranty Repair –
If your unit is out of warranty, be prepared to give us a Purchase Order number when you call. In most cases, we will be able to quote you the repair costs at that time.
The repair price you are quoted will be a “Not To Exceed” price, which means that the actual repair costs may be less than the quote. Be sure to include the RMA number on all documentation.
2. Provide us with the following documentation: a) A note listing the symptoms that indicate the unit needs repair b) Complete shipping information for return of the equipment after repair c) The name and phone number of the person to contact if questions arise at the factory
3. Use sufficient packing material and carefully pack the equipment in a sturdy shipping container.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries representative will contact the person designated on your documentation if more information is needed. The repaired equipment, or its replacement, will be returned to you in accordance with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRAN­TIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SER­VICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRAN­TIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWL­EDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IM­PLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY WAY.
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DE­FECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WAR­RANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under normal conditions of use and service, Moore Industries ("The Company") will at its option replace, repair or refund the purchase price for any of its manu­factured products found, upon return to the Company (transportation charges prepaid and otherwise in accordance with the return procedures established by The Company), to be defective in material or workmanship. This policy extends to the original Buyer only and not to Buyer's customers or the users of Buyer's products, unless Buyer is an engineering contractor in which case the policy shall extend to Buyer's immediate customer only. This policy shall not apply if the product has been subject to alteration, misuse, accident, ne­glect or improper application, installation, or operation. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSE­QUENTIAL DAMAGES.
United States • info@miinet.com
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • sales@mooreind.com.au
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
Tel: 86-21-62491499 • FAX: 86-21-62490635
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
Specifications and Information subject to change without notice.© 2005 Moore Industries-International, Inc.
China • sales@mooreind.sh.cn
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
Loading...