Customer Service ...........................................................................................20
Appendix A: HIM MODBUS Feature .............................................................21
2The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor
The HIM
The Moore Industries HIM HART Interface Module
unlocks the full potential of new and in-place HART
multivariable transmitters, valves, meters and other
smart instruments.
Converts HART to 4-20mA Signals
The HIM allows up to three additional analog process
variable measurements from a multivariable transmitter or valve with no additional process penetrations.
Installed transparently across the 4-20mA instrument
loop, the HIM reads the HART digital process data that
rides on the loop wires. It converts the digital information for up to three isolated analog (4-20mA) process
signals that are readily accepted by in-place control
systems, such as a DCS or PLC.
Provides Process and Diagnostic Alarms
Relay alarm trips (optional) can be individually user-set
either to trip when unwanted high/low process conditions occur, or provide a diagnostic health warning to
alert of loop or instrument fault conditions.
Takes Advantage of Legacy Instruments
The device lets you leave existing smart HART transmitters and valves in place, yet still take advantage of
all the information they have to offer.
Works with every Smart HART Device
The instrument can be programmed in minutes to interface with every HART-compatible monitoring and control device.
About this Manual
Wherever you see a “
pay particular attention.
•A “
Note
” provides information to help you in
avoiding minor inconveniences during
calibration, installation or operation of the HIM.
•A “
Caution
to avoid procedures and practices that could risk
damage to the HIM or other equipment.
•A “
WARNING
take to avoid procedures and practices that could
pose safety risks to personnel.
Note
”, “
Caution
” provides information on steps to take
” provides information on steps to
”, or “
WARNING
”
Figure 1. The HIM Accepts a Digital HART Signal and Outputs Both Analog Signals and Alarm Relays
HART Communicator can
be connected anywhere
along the 4-20mA loop
(HART Secondary Master)
4-20mA Representing the
Primary Variable (Mass Flow)
HART Digital Signal Carrying Primary,
Second, Third, Fourth Variable Process Data,
and Instrument Diagnostic Information
HIM HART Interface Module
"Breaks Out" Data from
Smart HART Instruments
(HART Primary Master)
4-20mA Proportional to 2nd Variable (DP)
4-20mA Proportional to 3rd Variable (P)
4-20mA Proportional to 4th Variable (T)
High Alarm in Response to 4th Variable (T)
HART Transmitter Fault Alarm
Smart HART
Multivariable
Mass Flow
Transmitter
Flow
Control System
(DCS or PLC)
The Interface Solution Experts3
HIM
Smart HART Loop
Interface and Monitor
Specifications
Performance
Specifications and information subject to change without notice.
4The Interface Solution Experts
Input Accuracy: Reflects
the accuracy of the HART
field device
Input Impedance: Transmit
Mode: 150 ohms;
Receive Mode: Less than
5kohms
Input Over-Range
Protection: ±5Vdc
ANALOG OUTPUTS
Output Accuracy: ±0.015%
of maximum output span
(20mA). Includes the
combined effects of linearity,
hysteresis, repeatability and
adjustment resolution.
Output Response Time:
<120ms, 10-90%
Isolation: 500Vrms channelto-channel isolation;
1000Vrms between case,
input, outputs and power
terminals, and will withstand
1500Vac dielectric strength
test for one minute with no
breakdown
Ripple: Less than 10mV
peak-to-peak when
measured across a
250 ohm resistor
Output Limiting: 130% of
span maximum; 125% of
span typical
Output Protection:
Transient protection on
output
Load Capability:
0-20mA, 1100 ohms
maximum
Load Effect: ±0.01% of span
from 0 to maximum load
resistance
Line Voltage Effect:
±0.005% of output span for a
1% change in line voltage
Input Fail Modes: PC
programmable to fail high, fail
low, hold last, hold last then
fail high, or hold last then fail
low (configurable hold time, 060 seconds)
Output Limits on Input
Failure: 0-20mA: Fail Low to
0mA orFail High to 23.6mA;
4-20mA: Fail Low to 3.6mA
or Fail High to 23.6mA;
X-20mA (0<X<4): Fail Low to
90% of XmA or Fail High to
23.6mA
Performance
(Continued)
Indicators
+TX Power Supply: 24.0Vdc
±10%@24mA
ALARM OUTPUTS
Digital Response Time:
Defined by HART protocol as
500msec maximum in Normal
HART Mode; 333msec
maximum in HART Burst
Mode
Alarm Response Time:
Digital Response Time +
150msec (Defined as time
from the field instrument’s
reporting a fault until the HIM
alarm is tripped)
Alarm Trip Delay:
Programmable from 0-120sec
MODBUS OUTPUTS
Type: Standard MODBUS
RTU protocol interface over
RS485 (parameters as
specified in U.S. Standard
EIA-RS485)
Address Range:
Configurable from 1 to 247.
Unit will assume a MODBUS
address of 01 by default
Baud Rate: Interface
supports the following: 300,
600, 1200, 4800, 9600, 19.2k.
MODBUS interface will
support even, odd and no
parities. Unit will assume a
baud rate of 9600 and no
parity by default
Character Format: One start
bit, 8 data bits and one stop
bit
Data Format: Userselectable Standard LSW
(Least Significant Word) or
Swapped MSW (Most
Significant Word). Unit will
assume Standard LSW by
default
Power Consumption:
2-3.5W, nominal; 4.5W
@24Vdc maximum for units
using transmitter excitation to
supply loop power a 2-wire
instrument
LCD Type: Two-line LCD;
Top Row, 10mm (0.4 in) high
black digits on a reflective
background; Bottom Row,
6mm (0.225 in) high digits
on a reflective background;
two-digit HART address
indicator
Indicators
(Continued)
Ambient
Conditions
Weight
Format: Top row is five
alphanumeric characters,
plus sign and decimal point;
bottom row is five
alphanumeric characters
Decimal Points: Userselectable for 0, 1, 2 or 3
places after the decimal point
or automatically adjusting with
a four decimal point maximum
Range: -99999 to 99999
Minimum Display Span:
1.00
Display Update Rate:
100msec
LED Type: Dual color
red/green indicate:
INPUT LED: Whether (green)
or not (red) the HART input is
connected and functioning
properly
READY LED: Whether
(green) or not (red) the HIM is
initialized and operating
properly
TRIP 1 and 2 LED: Shows the
status of alarm off (green) or
alarm on (red)
Operating & Storage
Range:
-40°C to +85°C
(-40°F to +185°F)
Display Range:
-25°C to +85°C
(-13°F to +185°F)
Relay Range:
-25°C to +70°C
(-13°F to +158°F)
Relative Humidity:
0-95%, non-condensing
Ambient Temperature
Effect: ±0.0065% of
span/°C maximum
RFI/EMI Immunity
(Standard):
20V/m@20-1000MHz, 1kHz
AM, when tested according to
IEC1000-4-3-1995
RFI/EMI Immunity (with
-RF Option): 30V/m@
20-1000MHz, 1kHz AM, when
tested according to IEC10004-3-1995
Noise Rejection: Common
Mode: 100dB@50/60Hz
567 grams (16 ounces)
Figure 2. HIM Dimensions
65mm
(2.56 in)
T1
T5
T3
T2
T4
T7
T6
HIM
Smart HART Loop
Interface and Monitor
138mm
133mm
(5.25 in)
T8
T9
T10 T11
T12
(5.45 in)
READYINPUT
60.278
ADDR
0
B2
B1
Table 1. Terminal Designations
HART Input, 2 Analog Outputs (2AO)
HART Input, 3 Analog Outputs (3AO)
COM
B3
B4
DEG C
HIM
B5
INPUT / OUTPUT
B8
B7
B6
TRIP 2TRIP 1
HART INTERFACE
MODULE
B9
B11
B10
B12
100mm
(3.94 in)
T1T2T3T4T5T6T7T8T9T10T11T12
+I Source
+TX
+TX
+IN
+IN
–IN
–IN
+I
Source
(AO3)
No Label
–I Source
or
+I Sink
(AO3)
–I Sink
(AO3)
(AO2)
+I Source
(AO2)
–I Source
–I Source
or
+I Sink
(AO2)
or
+I Sink
(AO2)
–I Sink
(AO2)
–I Sink
(AO2)
+I Source
(AO1)
+I Source
(AO1)
–I Source
or
+I Sink
(AO1)
–I Source
or
+I Sink
(AO1)
–I Sink
(AO1)
–I Sink
(AO1)
HART Input, 2 MODBUS Oututs
and 1 Analog Output (MB1AO)
HART Input, 2 MODBUS Outputs (MB)
ALARM RELAYS / POWER
No Alarm
Single Alarm (–1PRG)
Dual Alarm (–2PRG)
KEY:
+IN/–IN = Current input to HIM from HART device +TX = Transmitter Excitation Current
+I/–I Source = Analog Source Output+I/–I Sink = Analog Sink Output
A/B = MODBUS OutputNO/NO# = Normally Open
NC/NC# = Normally ClosedCM/CM# = Common
DC/DCC = 24VDC Connection(AO#) = Analog Output
+TX
+IN
–IN
Source
+TX
+IN
–IN
B1B2B3B4B5B6B7B8B9B10B11B12
No Label
NO1 CM 1 NC1
NO1 CM1 NC1 NO2 CM2 NC2
Relay 1
NO2 CM 2 NC2
Relay 1
A
+I
(AO)
Relay 2
–I Sink
–I Source
or
+I Sink
(AO)
No Label
NOTES:
1. The standard Single Alarm unit (1PRG) utilizes a DPDT relay.
2. Terminal blocks can accommodate 14-22 AWG solid wiring
(torque to 4 inch-pounds, maximum).
(AO)
MODBUS
MODBUS
B
MODBUS
2
B
MODBUS
2
No Label
MODBUS
MODBUS
2
A
2
The Interface Solution Experts5
A
S
MODBUS
2
S
MODBUS
2
DC
DC
DC
B
MODBUS
1
A
MODBUS
1
DCC
DCC
DCC
S
MODBUS
1
1
S
B
MODBUS
1
1
Ground
Ground
Ground
HIM
Smart HART Loop
Interface and Monitor
Configuring the HIM
One of the benefits of the HIM is that there are no
internal or external controls to adjust or settings to
change. All operating parameters are set using the PC
Configuration software.
Once these software settings are made, they are
downloaded to the monitor in the form of a Configuration
File and stored in the unit’s non-volatile memory. You
can choose to save a backup copy of the file on your
PC hard drive or external media. The HIM communicates with the PC through a proprietary communications cable to the PC’s serial (COM) port.
Begin by installing the PC Configuration Software.
Installing the PC Configuration Software
Refer to Table 2 for the equipment needed.
1.Insert the
PC Configuration Software
of the PC. Access the CD and open the
PC Configuration Software
2.Double-click the installation program located in
the folder. Follow the prompts to correctly
install the program.
Moore Industries Interface Solution
CD into the CD drive
HIM
folder.
Table 2. Assembling the Necessary Equipment
Device Specifications
Precision Load
Resistor
Multimeter or
Ammeter
Power
Supply
Personal Computer
PC Operating
System
Moore Industries
PC Configuration
Software
Communication
Cable
250 ohms, ±0.01%
Accurate to ±0.009% of span;
e.g. HP Model 3487A
24Vdc, ±10%
80386-based(or faster) IBM PC, or 100%
compatible; (Pentium recommended)
CD Drive
4Mb free RAM; 16Mb recommended
20Mb free disk space on hard drive
1 (one) serial port (COM 1, 2, 3 or 4)
Microsoft Windows® 95, 98, 2000, ME, or
NT with Internet Explorer 4.0+
Microsoft Windows® NT with
Service Pack 3 or greater
Version 1.0 or higher, successfully
installed to the hard drive
Part Number: 803-053-26, or equivalent
or
Once the Configuration Program is installed on the PC,
the unit can be connected either into the loop or to test
equipment to simulate input and monitor output. With
the PC program, the user can then view and/or change
its operating parameters. To begin the process, connect
the HIM either into the loop (see
the Loop
Checking the HIM
6The Interface Solution Experts
) or into a configuration setup (see
).
Installing the HIM into
Bench
HIM
Smart HART Loop
Interface and Monitor
Installing the HIM
There are two methods for connecting the HIM for
Mounting
The HIM is designed to snap easily onto 32mm, G-type
(EN50035) or 35mm Top Hat (EN50022) DIN rails.
configuration. The recommended method requires you
to install the instrument into the loop before it is
configured. The secondary method allows you to bench
check the HIM by attaching it to test equipment that
will simulate the input and monitor the output.
Electrical Connections
After mounting, you are ready to connect the HIM to
the loop. Each unit comes equipped with a transmitter
excitation terminal which allows it to supply power to
the monitored HART instrument, if necessary. Figures
Installing the HIM into the Loop
Installation consists of physically mounting the unit,
2 and 3 show the connection diagrams for an HIM with
or without using the transmitter excitation current.
grounding the instrument, and completing the electrical
connections. To install the HIM into the loop for
configuration, use the equipment in Table 2 to hookup
the HIM into the loop as shown in Figure 3 (without
using the HIM to power a transmitter) or Figure 4 (using
the TX terminal to power a transmitter). If you need a
CE Conformity
Installation of any Moore Industries products that carry
the CE certification (Commission Electrotechnique)
must
adhere to the guidelines in
order to meet the requirements set forth in applicable
complete terminal description, refer to Table 1.
Figure 3. Installing a HIM Into the Loop Without Using the Transmitter Excitation (+TX) Terminal
HART Communicator
can be connected
anywhere on the loop
➤
➤
➤
7
➤
8
4
9
5
1
6
2
0
3
.
➤
—
➤
➤
Sensor
Input
24Vdc
Power
+–
+
4-20mA
Installing the HIM
R must be > 250 and <1100 Ohms
R
in
–
HART Multivariable
Field Instrument
(Temperature
Pressure, Level
and Flow)
NO (normally open)
COMMON
NC (normally closed)
+IN
NO
READYINPUT
ADDR
0
COM
COM
–IN
NC
TRIP 2TRIP 1
DC
DCC
24Vdc
Power
Source
GND
DCS
Analog Output tied to
Any Process Variable
50.7
25.1
80.1
deg-c
20.3
Event Recorder
The Interface Solution Experts7
HIM
Smart HART Loop
Interface and Monitor
EMC (Electromagnetic Compatibility) directives
(EN55011, EN 50082-1, EN50082-2, etc.). Consult the
factory for the most current information on products
that have been CE certified.
• All input signals to, and output signals
from, Moore Industries’ products should be
wired using a shielded, twisted pair
technique. Shields are to be connected to an
earth or safety ground at the unit itself.
Recommended Ground Wiring Practices
Moore Industries recommends the following ground
wiring practices:
• Any Moore Industries product in a metal
case or housing should be grounded.
• The protective earth conductor must be
connected to a system safety earth ground
before making any other connections.
• The maximum length of unshielded input
and output signal wiring should be 2 inches.
Power Sourcing Parameters for General
Locations, Intrinsically Safe, and
Non-Incendive/Type N applications
In accordance with IEC 1010.1 Annex H
(all models), the input terminals must be
connected to and/or supplied from a certified
energy limiting Class 2 or a Separate Extra Low
Voltage (S.E.L.V.) power supply separated from
all mains by double/reinforced insulation.
Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal
➤
➤
➤
7
➤
8
4
9
5
1
6
2
0
3
.
➤
—
➤
➤
HART Communicator
can be connected
anywhere on the loop
R must be > 250 and <1100 Ohms
Sensor
Input
HART Multivariable
Field Instrument
(Temperature,
Pressure, Level
and Flow)
–
4-20mA
+
NO (normally open)
COMMON
NC (normally closed)
+IN
+TX–IN
READYINPUT
ADDR
0
COM
NO
NC
COM
TRIP 2TRIP 1
DC
24Vdc
Power
Source
DCC
R
DCS
Analog Output tied to
Any Process Variable
Event Recorder
GND
8The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor
Bench Checking the HIM
If you would like to configure the HIM before
attaching it to the loop, you need to hook it up
with the equipment listed in Table 1. Refer to
Figures 5 and 6 for instructions on how to bench
check the HIM either with or without taking
advantage of the Transmitter Excitation (+TX)
terminal. If you need further descriptions of the
terminals, see Table 2.
Figure 5. Bench Checking the HIM Using the Transmitter
Excitation (+TX) Terminal to Power a Transmitter
Sensor
Input
HART
Field Device
or
Simulator
Equipment Hook-Up
for HART field device using
Transmitter Excitation
–
+
+TX
R must be > 250 and <1100 Ohms
R
+IN
–IN
+
–
READYINPUT
ADDR
0
COM
TRIP 2TRIP 1
+
Multimeter
–
Figure 6. Bench Checking the HIM Without Using the
Transmitter Excitation (+TX) Terminal to Power a Transmitter
For a HART Transmitter, the
resistor must be >250 and <1100 ohms.
For a HART Receiver, such as a
valve positioner, no resistor is necessary.
R
–IN
READYINPUT
ADDR
0
COM
NO
NC
COM
+
TRIP 2TRIP 1
DC
24Vdc
Power
–
DCC
GND
+
Multimeter
–
Sensor
Input
HART
Field Device
or
Simulator
Optional
24Vdc
Power
+–
+
–
+IN
Multimeter
Checks for
continuity
Optional
NO
COM
Multimeter
Checks for
continuity
Optional
NC
DC
24Vdc
Power
DCC
GND
The Interface Solution Experts9
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.