Yokogawa HIMHART User Manual

November 2005 224-778-00C
Smart HART® Loop
Interface and Monitor
HIM
Loop
®
Interface and Monitor
Smart HART
HIM

Table of Contents

The HIM ..............................................................................................................3
About this Manual ...............................................................................................................3
Specifications .....................................................................................................................4
HIM Dimensions .................................................................................................................5
Terminal Designations ........................................................................................................ 5
Configuring the HIM .........................................................................................6
Installing the HIM ..............................................................................................7
Installing the HIM into the Loop ........................................................................................... 7
Bench Checking the HIM ....................................................................................................9
PC Configuration Software............................................................................10
HART Parameters ............................................................................................................ 11
Display Parameters .......................................................................................................... 13
Alarms Parameters ........................................................................................................... 14
Analog Outputs Parameters ..............................................................................................16
Custom Curve Parameters ................................................................................................ 18
Scaling Parameters .......................................................................................................... 19
Customer Service ...........................................................................................20
Appendix A: HIM MODBUS Feature .............................................................21
2 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor

The HIM

The Moore Industries HIM HART Interface Module unlocks the full potential of new and in-place HART multivariable transmitters, valves, meters and other smart instruments.
Converts HART to 4-20mA Signals
The HIM allows up to three additional analog process variable measurements from a multivariable transmit­ter or valve with no additional process penetrations. Installed transparently across the 4-20mA instrument loop, the HIM reads the HART digital process data that rides on the loop wires. It converts the digital informa­tion for up to three isolated analog (4-20mA) process signals that are readily accepted by in-place control systems, such as a DCS or PLC.
Provides Process and Diagnostic Alarms
Relay alarm trips (optional) can be individually user-set either to trip when unwanted high/low process condi­tions occur, or provide a diagnostic health warning to alert of loop or instrument fault conditions.
Takes Advantage of Legacy Instruments
The device lets you leave existing smart HART trans­mitters and valves in place, yet still take advantage of all the information they have to offer.
Works with every Smart HART Device
The instrument can be programmed in minutes to inter­face with every HART-compatible monitoring and con­trol device.

About this Manual

Wherever you see a “ pay particular attention.
•A “
Note
” provides information to help you in avoiding minor inconveniences during calibration, installation or operation of the HIM.
•A “
Caution
to avoid procedures and practices that could risk damage to the HIM or other equipment.
•A “
WARNING
take to avoid procedures and practices that could pose safety risks to personnel.
Note
”, “
Caution
” provides information on steps to take
” provides information on steps to
”, or “
WARNING
Figure 1. The HIM Accepts a Digital HART Signal and Outputs Both Analog Signals and Alarm Relays
HART Communicator can
be connected anywhere
along the 4-20mA loop
(HART Secondary Master)
4-20mA Representing the
Primary Variable (Mass Flow)
HART Digital Signal Carrying Primary, Second, Third, Fourth Variable Process Data, and Instrument Diagnostic Information
HIM HART Interface Module
"Breaks Out" Data from
Smart HART Instruments
(HART Primary Master)
4-20mA Proportional to 2nd Variable (DP) 4-20mA Proportional to 3rd Variable (P)
4-20mA Proportional to 4th Variable (T) High Alarm in Response to 4th Variable (T)
HART Transmitter Fault Alarm
Smart HART Multivariable Mass Flow Transmitter
Flow
Control System
(DCS or PLC)
The Interface Solution Experts 3
HIM
Smart HART Loop Interface and Monitor

Specifications

Performance
Specifications and information subject to change without notice.
4 The Interface Solution Experts
Input Accuracy: Reflects the accuracy of the HART field device Input Impedance: Transmit Mode: 150 ohms; Receive Mode: Less than 5kohms
Input Over-Range Protection: ±5Vdc
ANALOG OUTPUTS Output Accuracy: ±0.015%
of maximum output span (20mA). Includes the combined effects of linearity, hysteresis, repeatability and adjustment resolution.
Output Response Time:
<120ms, 10-90% Isolation: 500Vrms channel­to-channel isolation; 1000Vrms between case, input, outputs and power terminals, and will withstand 1500Vac dielectric strength test for one minute with no breakdown Ripple: Less than 10mV peak-to-peak when measured across a 250 ohm resistor Output Limiting: 130% of span maximum; 125% of span typical
Output Protection:
Transient protection on output
Load Capability:
0-20mA, 1100 ohms maximum Load Effect: ±0.01% of span from 0 to maximum load resistance
Line Voltage Effect:
±0.005% of output span for a 1% change in line voltage Input Fail Modes: PC programmable to fail high, fail low, hold last, hold last then fail high, or hold last then fail low (configurable hold time, 0­60 seconds)
Output Limits on Input Failure: 0-20mA: Fail Low to
0mA or Fail High to 23.6mA; 4-20mA: Fail Low to 3.6mA or Fail High to 23.6mA; X-20mA (0<X<4): Fail Low to 90% of XmA or Fail High to
23.6mA
Performance
(Continued)
Indicators
+TX Power Supply: 24.0Vdc
±10%@24mA
ALARM OUTPUTS Digital Response Time:
Defined by HART protocol as 500msec maximum in Normal HART Mode; 333msec maximum in HART Burst Mode
Alarm Response Time:
Digital Response Time + 150msec (Defined as time from the field instrument’s reporting a fault until the HIM alarm is tripped)
Alarm Trip Delay:
Programmable from 0-120sec
MODBUS OUTPUTS Type: Standard MODBUS
RTU protocol interface over RS485 (parameters as specified in U.S. Standard EIA-RS485)
Address Range:
Configurable from 1 to 247. Unit will assume a MODBUS address of 01 by default Baud Rate: Interface supports the following: 300, 600, 1200, 4800, 9600, 19.2k. MODBUS interface will support even, odd and no parities. Unit will assume a baud rate of 9600 and no parity by default Character Format: One start bit, 8 data bits and one stop bit Data Format: User­selectable Standard LSW (Least Significant Word) or Swapped MSW (Most Significant Word). Unit will assume Standard LSW by default
Power Consumption:
2-3.5W, nominal; 4.5W @24Vdc maximum for units using transmitter excitation to supply loop power a 2-wire instrument
LCD Type: Two-line LCD; Top Row, 10mm (0.4 in) high black digits on a reflective background; Bottom Row, 6mm (0.225 in) high digits on a reflective background; two-digit HART address indicator
Indicators
(Continued)
Ambient
Conditions
Weight
Format: Top row is five
alphanumeric characters, plus sign and decimal point; bottom row is five alphanumeric characters Decimal Points: User­selectable for 0, 1, 2 or 3 places after the decimal point or automatically adjusting with a four decimal point maximum
Range: -99999 to 99999 Minimum Display Span:
1.00
Display Update Rate:
100msec LED Type: Dual color red/green indicate: INPUT LED: Whether (green) or not (red) the HART input is connected and functioning properly READY LED: Whether (green) or not (red) the HIM is initialized and operating properly TRIP 1 and 2 LED: Shows the status of alarm off (green) or alarm on (red)
Operating & Storage Range:
-40°C to +85°C (-40°F to +185°F)
Display Range:
-25°C to +85°C (-13°F to +185°F)
Relay Range:
-25°C to +70°C (-13°F to +158°F)
Relative Humidity:
0-95%, non-condensing
Ambient Temperature Effect: ±0.0065% of
span/°C maximum
RFI/EMI Immunity (Standard):
20V/m@20-1000MHz, 1kHz AM, when tested according to IEC1000-4-3-1995
RFI/EMI Immunity (with
-RF Option): 30V/m@
20-1000MHz, 1kHz AM, when tested according to IEC1000­4-3-1995 Noise Rejection: Common Mode: 100dB@50/60Hz
567 grams (16 ounces)

Figure 2. HIM Dimensions

65mm
(2.56 in)
T1
T5
T3
T2
T4
T7
T6
HIM
Smart HART Loop
Interface and Monitor
138mm
133mm
(5.25 in)
T8
T9
T10 T11
T12
(5.45 in)
READYINPUT
60.278
ADDR
0
B2
B1

Table 1. Terminal Designations

HART Input, 2 Analog Outputs (2AO)
HART Input, 3 Analog Outputs (3AO)
COM
B3
B4
DEG C
HIM
B5
INPUT / OUTPUT
B8
B7
B6
TRIP 2TRIP 1
HART INTERFACE MODULE
B9
B11
B10
B12
100mm
(3.94 in)
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12
+I Source
+TX
+TX
+IN
+IN
–IN
–IN
+I
Source
(AO3)
No Label
–I Source
or
+I Sink
(AO3)
–I Sink (AO3)
(AO2)
+I Source
(AO2)
–I Source
–I Source
or
+I Sink
(AO2)
or
+I Sink
(AO2)
–I Sink
(AO2)
–I Sink
(AO2)
+I Source
(AO1)
+I Source
(AO1)
–I Source
or
+I Sink
(AO1)
–I Source
or
+I Sink
(AO1)
–I Sink
(AO1)
–I Sink
(AO1)
HART Input, 2 MODBUS Oututs
and 1 Analog Output (MB1AO)
HART Input, 2 MODBUS Outputs (MB)
ALARM RELAYS / POWER
No Alarm
Single Alarm (–1PRG)
Dual Alarm (–2PRG)
KEY:
+IN/–IN = Current input to HIM from HART device +TX = Transmitter Excitation Current +I/–I Source = Analog Source Output +I/–I Sink = Analog Sink Output A/B = MODBUS Output NO/NO# = Normally Open NC/NC# = Normally Closed CM/CM# = Common DC/DCC = 24VDC Connection (AO#) = Analog Output
+TX
+IN
–IN
Source
+TX
+IN
–IN
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12
No Label
NO1 CM 1 NC1
NO1 CM1 NC1 NO2 CM2 NC2
Relay 1
NO2 CM 2 NC2
Relay 1
A
+I
(AO)
Relay 2
–I Sink
–I Source
or
+I Sink
(AO)
No Label
NOTES:
1. The standard Single Alarm unit (1PRG) utilizes a DPDT relay.
2. Terminal blocks can accommodate 14-22 AWG solid wiring (torque to 4 inch-pounds, maximum).
(AO)
MODBUS
MODBUS
B
MODBUS
2
B
MODBUS
2
No Label
MODBUS
MODBUS
2
A
2
The Interface Solution Experts 5
A
S
MODBUS
2
S
MODBUS
2
DC
DC
DC
B
MODBUS
1
A
MODBUS
1
DCC
DCC
DCC
S
MODBUS
1
1
S
B
MODBUS
1
1
Ground
Ground
Ground
HIM
Smart HART Loop Interface and Monitor

Configuring the HIM

One of the benefits of the HIM is that there are no internal or external controls to adjust or settings to change. All operating parameters are set using the PC Configuration software.
Once these software settings are made, they are downloaded to the monitor in the form of a Configuration File and stored in the unit’s non-volatile memory. You can choose to save a backup copy of the file on your PC hard drive or external media. The HIM communi­cates with the PC through a proprietary communica­tions cable to the PC’s serial (COM) port.
Begin by installing the PC Configuration Software.
Installing the PC Configuration Software
Refer to Table 2 for the equipment needed.
1. Insert the
PC Configuration Software
of the PC. Access the CD and open the
PC Configuration Software
2. Double-click the installation program located in the folder. Follow the prompts to correctly install the program.
Moore Industries Interface Solution
CD into the CD drive
HIM
folder.
Table 2. Assembling the Necessary Equipment
Device Specifications
Precision Load
Resistor
Multimeter or
Ammeter
Power
Supply
Personal Computer
PC Operating
System
Moore Industries
PC Configuration
Software
Communication
Cable
250 ohms, ±0.01%
Accurate to ±0.009% of span; e.g. HP Model 3487A
24Vdc, ±10%
80386-based(or faster) IBM PC, or 100% compatible; (Pentium recommended) CD Drive 4Mb free RAM; 16Mb recommended 20Mb free disk space on hard drive 1 (one) serial port (COM 1, 2, 3 or 4)
Microsoft Windows® 95, 98, 2000, ME, or NT with Internet Explorer 4.0+
Microsoft Windows® NT with Service Pack 3 or greater
Version 1.0 or higher, successfully installed to the hard drive
Part Number: 803-053-26, or equivalent
or
Once the Configuration Program is installed on the PC, the unit can be connected either into the loop or to test equipment to simulate input and monitor output. With the PC program, the user can then view and/or change its operating parameters. To begin the process, connect the HIM either into the loop (see
the Loop Checking the HIM
6 The Interface Solution Experts
) or into a configuration setup (see
).
Installing the HIM into
Bench
HIM
Smart HART Loop
Interface and Monitor

Installing the HIM

There are two methods for connecting the HIM for
Mounting
The HIM is designed to snap easily onto 32mm, G-type (EN50035) or 35mm Top Hat (EN50022) DIN rails.
configuration. The recommended method requires you to install the instrument into the loop before it is configured. The secondary method allows you to bench check the HIM by attaching it to test equipment that will simulate the input and monitor the output.
Electrical Connections
After mounting, you are ready to connect the HIM to the loop. Each unit comes equipped with a transmitter excitation terminal which allows it to supply power to the monitored HART instrument, if necessary. Figures
Installing the HIM into the Loop
Installation consists of physically mounting the unit,
2 and 3 show the connection diagrams for an HIM with or without using the transmitter excitation current.
grounding the instrument, and completing the electrical connections. To install the HIM into the loop for configuration, use the equipment in Table 2 to hookup the HIM into the loop as shown in Figure 3 (without using the HIM to power a transmitter) or Figure 4 (using the TX terminal to power a transmitter). If you need a
CE Conformity
Installation of any Moore Industries products that carry the CE certification (Commission Electrotechnique)
must
adhere to the guidelines in
order to meet the requirements set forth in applicable
complete terminal description, refer to Table 1.
Figure 3. Installing a HIM Into the Loop Without Using the Transmitter Excitation (+TX) Terminal
HART Communicator can be connected anywhere on the loop
7
8
4
9
5
1
6
2
0
3
.
Sensor
Input
24Vdc Power
+–
+
4-20mA
Installing the HIM
R must be > 250 and <1100 Ohms
R
in
HART Multivariable
Field Instrument
(Temperature
Pressure, Level
and Flow)
NO (normally open)
COMMON
NC (normally closed)
+IN
NO
READYINPUT
ADDR
0
COM
COM
–IN
NC
TRIP 2TRIP 1
DC
DCC
24Vdc Power
Source
GND
DCS
Analog Output tied to Any Process Variable
50.7
25.1
80.1
deg-c
20.3
Event Recorder
The Interface Solution Experts 7
HIM
Smart HART Loop Interface and Monitor
EMC (Electromagnetic Compatibility) directives (EN55011, EN 50082-1, EN50082-2, etc.). Consult the factory for the most current information on products that have been CE certified.
• All input signals to, and output signals from, Moore Industries’ products should be wired using a shielded, twisted pair technique. Shields are to be connected to an earth or safety ground at the unit itself.
Recommended Ground Wiring Practices
Moore Industries recommends the following ground wiring practices:
• Any Moore Industries product in a metal case or housing should be grounded.
• The protective earth conductor must be connected to a system safety earth ground before making any other connections.
• The maximum length of unshielded input and output signal wiring should be 2 inches.
Power Sourcing Parameters for General Locations, Intrinsically Safe, and Non-Incendive/Type N applications
In accordance with IEC 1010.1 Annex H (all models), the input terminals must be connected to and/or supplied from a certified energy limiting Class 2 or a Separate Extra Low Voltage (S.E.L.V.) power supply separated from all mains by double/reinforced insulation.
Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal
7
8
4
9
5
1
6
2
0
3
.
HART Communicator can be connected anywhere on the loop
R must be > 250 and <1100 Ohms
Sensor
Input
HART Multivariable
Field Instrument
(Temperature,
Pressure, Level
and Flow)
4-20mA
+
NO (normally open)
COMMON
NC (normally closed)
+IN
+TX –IN
READYINPUT
ADDR
0
COM
NO
NC
COM
TRIP 2TRIP 1
DC
24Vdc Power
Source
DCC
R
DCS
Analog Output tied to Any Process Variable
Event Recorder
GND
8 The Interface Solution Experts
HIM
Smart HART Loop
Interface and Monitor

Bench Checking the HIM

If you would like to configure the HIM before attaching it to the loop, you need to hook it up with the equipment listed in Table 1. Refer to Figures 5 and 6 for instructions on how to bench check the HIM either with or without taking advantage of the Transmitter Excitation (+TX) terminal. If you need further descriptions of the terminals, see Table 2.
Figure 5. Bench Checking the HIM Using the Transmitter Excitation (+TX) Terminal to Power a Transmitter
Sensor
Input
HART
Field Device
or
Simulator
Equipment Hook-Up
for HART field device using
Transmitter Excitation
+
+TX
R must be > 250 and <1100 Ohms
R
+IN –IN
+
READYINPUT
ADDR
0
COM
TRIP 2TRIP 1
+
Multimeter
Figure 6. Bench Checking the HIM Without Using the Transmitter Excitation (+TX) Terminal to Power a Transmitter
For a HART Transmitter, the resistor must be >250 and <1100 ohms. For a HART Receiver, such as a valve positioner, no resistor is necessary.
R
–IN
READYINPUT
ADDR
0
COM
NO
NC
COM
+
TRIP 2TRIP 1
DC
24Vdc Power
DCC
GND
+
Multimeter
Sensor
Input
HART
Field Device
or
Simulator
Optional
24Vdc Power
+–
+
+IN
Multimeter
Checks for
continuity
Optional
NO
COM
Multimeter
Checks for
continuity
Optional
NC
DC
24Vdc Power
DCC
GND
The Interface Solution Experts 9
Loading...
+ 18 hidden pages