YASKAWA PVI 60TL, PVI 50TL Installation And Operation Manual

Page 1
PVI 50TL PVI 60TL
INSTALLATION AND OPERATION MANUAL
Revision E
Page 2
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 2 of 102
IMPORTANT REGISTRATION AND
WARRANTY INFORMATION
For warranty to become active, this inverter must be registered. To activate warranty and register inverter, please visit the link below.
www.solectria.com/registration
Page 3
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 3 of 102
Before You Start…
This manual contains important information regarding installation and safe operation of the PVI 50/60TL. Be sure to read this manual carefully before using the inverter.
Thank you for choosing a Yaskawa – Solectria Solar grid-tied PV Inverter. This PV Inverter is a high performance and highly reliable product specifically designed for the North American Solar market.
If you encounter any problems during installation or operation of this unit, first check the user manual before contacting your local dealer or supplier. This user manual is applicable for the following models: PVI 50TL & PVI 60TL.
Instructions inside this user manual will help you solve most installation and operation difficulties. Contact your local supplier if the problem still exists.
Please keep this user manual on hand for quick reference. Always check online for an updated version of this product manual. The contents of this document are subject to change without notice.
Page 4
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 4 of 102
IMPORTANT Safety Instructions
SAVE THESE INSTRUCTIONS
Please read this user manual carefully before product installation. Yaskawa - Solectria Solar reserves the right to refuse warranty claims for equipment damage if the user fails to install the equipment according to the instructions in this manual.
Warnings and Symbols in this Document
DANGER:
DANGER indicates a hazardous situation which, if not avoided, may result in death or serious injury.
DANGER indique une situation dangereuse qui, si elle n'est pas évitée, entraînera la mort ou des blessures graves.
WARNING:
WARNING indicates a hazardous situation which, if not avoided, may result in death or serious injury.
AVERTISSEMENT indique une situation dangereuse qui, si elle n'est pas évitée, pourrait entraîner la mort ou des blessures graves.
CAUTION:
CAUTION indicates a hazardous situation which, if not avoided, may result in minor or moderate injury.
ATTENTION indique une situation dangereuse qui, si elle n'est pas évitée, peut entraîner des blessures mineures ou modérées.
NOTICE:
NOTICE indicates a hazardous situation which, if not avoided, may result in equipment working abnormally or property loss.
INSTRUCTION:
INSTRUCTION indicates important supplementary information or provides skills or tips that can be used to help you solve a problem or save you time.
Page 5
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 5 of 102
Markings on the Product
HIGH VOLTAGE:
This inverter works with high voltages. All work on the product must only be performed as described in this document.
HOT SURFACE:
The equipment is designed to meet international safety standards, but surfaces can become hot during operation. Do not touch the heat sink or peripheral surfaces during or shortly after operation.
EARTH GROUND:
This symbol marks the location of grounding terminal, which must be securely connected to the earth through the PE (Protective Earth) cable to ensure operational safety.
WARNING:
All installation and wiring connections should be performed only by qualified technical personnel. Disconnect the inverter from PV modules and the Power Grid before maintaining and operating the equipment.
Toutes les installations et les connexions de câblage doivent être effectuées uniquement par le personnel technique qualifié. Débrancher l'onduleur de modules photovoltaiques et le grid électrique avant l'entretien et la marche de l'équipement.
Risk of electric shock and fire. Use only with PV modules with maximum system voltage of rating of 1000V or higher.
Risque de choc électrique et d'incendie. Utiliser uniquement avec les modules photovoltaiques avec la tension maximum du système de Ratinf de 1000V ou plus.
Electric Shock Hazard. The DC conductors of this photovoltaic system are normally ungrounded but will become intermittently grounded without indication when the inverter measures the PV array isolation.
Risque de choc électrique. Les conducteurs c.c. de ce système photovoltaïque sont normalement non mis à la terre mais deviendront par intermittence mis à la terre sans indication lorsque l’onduleur mesure l’isolement du champ photovoltaïque.
Shock Hazard. Energized from both AC and DC sources. Disconnect all sources before servicing.
Risque de choc électrique. Alimenté à partir de deux sources c.a. et c.c. Débrancher toutes les sources avant de mettre en service.
Page 6
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 6 of 102
For continued protection against risk of fire, replace only with same type and ratings of fuse.
Pour une protection continuelle contre tout risque d'incendie, remplacez les fuses uniquement avec le même type et calibre."
DANGER:
Please disconnect the inverter from AC grid and PV modules before opening the equipment. Make sure hazardous high voltage and energy inside the equipment have been discharged. Do not operate or maintain the inverter until at least 5 minutes after disconnecting all sources from DC and AC sides.
Veuillez débrancher l'onduleur du grid C.A. et des modules photovoltaiques avant l'ouverture de l'équipement. Assurez-vous que la haute tension et l'énergie dangereuses à l'intérieur de l'équipement a été déchargée. Ne pas utiliser ou entretenir l'onduleur jusqu'à au moins 5 minutes après avoir débranché toutes les sources du côté C.C. et C.A.
CAUTION:
PVI 50-60TL inverter is 123.5lbs and the wiring box is 33lbs. Please ensure the mounting bracket is properly installed before hanging the inverter on the bracket.
Veuillez vous assurer que le montage est correctement installé avant d'accrocher le l'onduleur sur le support.
INSTRUCTION:
Please check with your local electricity supply company before selecting a grid standard. If the inverter is operated with a wrong grid standard, the electricity supply company may cancel the interconnection agreement. Putting the inverter into operation before the overall system complies with the national rules and safety regulation of the application is not permitted.
DANGER! Danger to life due to fire or explosion:
Despite careful construction, electrical devices can cause fires.
-Do not mount the inverter on flammable construction materials.
-Do not mount the inverter in areas where highly flammable materials are stored.
-Do not mount the inverters in areas with a risk of explosion
SAVE THESE INSTRUCTIONS
Page 7
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 7 of 102
BEFORE YOU START… ................................................................................. 3
PLEASE KEEP THIS USER MANUAL ON HAND FOR QUICK REFERENCE.
ALWAYS CHECK ONLINE FOR AN UPDATED VERSION OF THIS PRODUCT
MANUAL. THE CONTENTS OF THIS DOCUMENT ARE SUBJECT TO CHANGE
WITHOUT NOTICE. ..................................................................................... 3
IMPORTANT SAFETY INSTRUCTIONS .......................................................... 4
1.0: OVERVIEW ........................................................................................ 10
1.1 INVERTER FOR GRID-TIED PV SYSTEMS ............................................ 10
1.2 PRODUCT FEATURES ..................................................................... 10
1.3 PRODUCT PROTECTION FUNCTIONS ................................................. 11
1.4 CIRCUIT STRUCTURE DESIGN .......................................................... 11
1.5 APPEARANCE DESCRIPTION ............................................................ 12
1.6 ANTI-ISLANDING .......................................................................... 12
1.7 DC GROUND FAULT PROTECTION .................................................... 13
1.8 SURGE SUPPRESSION .................................................................... 13
1.9 DC ARC FAULT DETECTION ............................................................. 13
2.0: INSTALLATION ................................................................................... 13
2.1 RECOMMENDATIONS BEFORE INSTALLATION ..................................... 16
2.2 MECHANICAL INSTALLATION ........................................................... 17
2.3 ELECTRICAL INSTALLATION .............................................................. 29
2.3.1 DC Connection .............................................................................33
2.3.1.1 DC Connection for Standard Wiring Box ..................................36
2.3.1.2 DC Connection for H4 Wiring Box ............................................38
2.3.1.3 Individual Maximum Power Point Tracking .............................39
2.3.2 AC and Ground Connections .......................................................40
2.4 INVERTER COMMUNICATION CONNECTIONS ...................................... 46
2.4.2 Preparing the Inverter for Modbus Communications .................52
2.4.2 Installing the Ethernet Network Card .........................................53
2.4.3 Connecting the Ethernet Network Card to other inverters. ........54
2.4.4 Connecting a 3rd Party Monitoring System to the Ethernet
Network Card .......................................................................................54
2.4.5 Preparing the Ethernet Network Card ........................................54
3.0: COMMISSIONING .............................................................................. 55
3.1 COMMISSIONING CHECKLIST .......................................................... 55
Page 8
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 8 of 102
3.1.1 Mechanical Installation ...............................................................55
3.1.2 Cable Connections .......................................................................55
3.1.3 Electrical Check ...........................................................................55
3.2 COMMISSIONING STEPS................................................................. 55
4.0: USER INTERFACE ............................................................................... 58
4.1 DESCRIPTION OF THE INTERFACE ..................................................... 58
4.2 OPERATION STATE ........................................................................ 59
4.3 INTERFACE TYPES .......................................................................... 60
4.4 MENU FUNCTIONS ....................................................................... 61
4.4.1 Measurement Data .....................................................................61
4.4.2 Setting .........................................................................................63
4.4.2.1 System Parameters ..................................................................64
4.4.2.2 Control Command ....................................................................64
4.4.2.3 Protect Parameters ..................................................................66
4.4.2.4 L/HVRT Parameters ..................................................................69
4.4.2.5 Power Derating Setting ............................................................72
4.4.2.6 Reactive Derating Setting ........................................................73
4.4.2.7 Arc Parameters ........................................................................76
4.4.2.8 Other Parameters ....................................................................76
4.4.3 Power ON/OFF ............................................................................78
4.4.4 History .........................................................................................78
4.4.5 Device Information ......................................................................79
5.0: OPERATION ....................................................................................... 80
5.1 START-UP ................................................................................... 80
5.2 SHUTDOWN ................................................................................ 80
5.3 OPERATION MODE ....................................................................... 80
5.4 GRID-TIED POWER GENERATION ..................................................... 82
6.0: MAINTENANCE AND REMOVAL OF INVERTER ................................... 83
6.1 FAULT SHUTDOWN AND TROUBLESHOOTING ..................................... 83
6.1.1 LED Fault and Troubleshooting ...................................................83
6.1.2 LCD Fault and Troubleshooting ...................................................83
6.2 PRODUCT MAINTENANCE .............................................................. 90
6.2.1 Check the Electrical Connection ..................................................90
6.2.2 Clean the Air Vent Filter ..............................................................90
6.2.3 Replace Cooling Fans ..................................................................90
Page 9
PVI 50/60 TL Installation and Operation Manual (Rev E)
DOCR-070645-E Page 9 of 102
6.2.4 Replace the Inverter ....................................................................92
6.3 UNINSTALLING THE INVERTER ......................................................... 94
7.0: PRODUCT WARRANTY AND RMA POLICY .......................................... 94
8.0: TECHNICAL DATA ............................................................................... 95
9.0: ACCESSORY OPTIONS ...................................................................... 100
9.1 FUSE BYPASS ...................................................................... 100
9.2 SHADE COVER .................................................................... 101
APPENDIX A PVI 50/60TL DATASHEET ............................................. 103
APPENDIX B STRING SIZING TOOL .................................................... 103
APPENDIX C CONTACT INFORMATION ............................................... 103
APPENDIX D AUTHORIZED DISTRIBUTORS .......................................... 103
APPENDIX E UL 1741 / UL 1699B/ IEEE 1547 / CSA 22.2#107.1.... 104
Page 10
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 10 of 102
1.0: Overview
1.1 Inverter for Grid-Tied PV Systems
The PVI 50/60TL inverter is suitable for use on commercial and utility-scale rooftop, carport and ground mount grid-tied PV systems. A system is generally made up of PV modules, DC power distribution equipment, PV inverter and AC power distribution equipment (Figure 1.1). The inverter converts DC from PV modules to AC with the same frequency and phase as the AC grid. All or part of the AC power is supplied to local loads, and the surplus power is supplied to the electricity grid.
DC power distribution equipments
AC Grid
Bidirectional
electric meter
AC power distribution equipments
Figure 1.1 - Grid-Tied PV System
1.2 Product Features
High Conversion Efficiency: Advanced 3-level conversion technology;
Max. Efficiency: 99%CEC Efficiency: 98.5%
Strong Grid Adaptability: Multi grid standards applicable; Reactive power
adjustable; Power Factor (PF) value: ±0.8, Remote Curtailment
Flexible Communication: Supports standard Modbus communications to
ensure compatibility with 3rd party monitoring and control systems
Wide DC Input Voltage Range: Operating DC Input Voltage Range: 200-950Vdc;
Max DC input voltage: 1000V
Long Service Life: Uses thin-film capacitors to extend inverter’s service life 3 MPPTs: Multichannel independent MPPT (Maximum Power Point Tracking)
enable maximum design flexibility and optimize energy harvest over the life of the system
High Protection Degree: NEMA 4X protection meets the needs of both indoor
and outdoor use; Embedded DC surge protection device (SPD)
Intelligent Integration: Embedded DC/AC switches and up to 15 fused string
inputs eliminate the need for external combiner boxes and simplify installation.
Page 11
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 11 of 102
1.3 Product Protection Functions
Reverse polarity protection on the DC inputs Short circuit protection Arc-Fault Circuit Interruption Anti-islanding protection Input and output over-voltage protection Input over-current protection Monitoring of:
DC input insulation against ground AC output voltage and frequency Leakage current against ground DC injection from AC output Ambient temperature IGBT module temperature
1.4 Circuit Structure Design
The basic schematic diagram of PVI 50/60TL inverter is shown in Figure 1.2. The input of PV modules passes through surge protection circuitry, DC EMI wave filter, and the front-end boost circuitry to achieve maximum power tracking and boost up voltages. The output of the inverter converts the DC voltage to 3-phase AC voltage. The high frequency AC components are removed with a wave filter. The 3-phase AC voltage is then passed through two-stage relays and EMI wave filter to produce high quality AC power.
Figure 1.2 - Schematic Diagram of PVI 50/60TL Inverter
Page 12
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 12 of 102
1.5 Appearance Description
Figure 1.3 - Sketch of PVI 50/60TL Inverter
Main Items of the Inverter:
1) Main inverter section
2) Wiring box of the inverter
3) Mounting bracket
4) External cooling fans
5) LED indication lights
6) LCD
7) Key buttons
8) DC switch: DC power on/off
9) AC switch: AC power on/off (right side of the wiring box when facing the inverter)
1.6 Anti-Islanding
This inverter includes active Anti-Islanding detection as required by UL1741/IEEE1547. The inverter will automatically make small variations in reactive power output in order to detect a possible islanding condition. If the grid is stable,
Page 13
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 13 of 102
these small variations will have negligible effects on system voltage and frequency. However, in an islanded condition the small amount of reactive power changes will force the system voltage or frequency to change significantly, which will trigger the inverter to shut down. This function is always on and cannot be turned off by the user.
1.7 DC Ground Fault Protection
The PVI 50/60TL includes residual current detection as part of the DC ground fault detection method as required by UL1741. If there is a ground fault in the array, the ground fault detection technology will detect the array leakage current. The inverter will shut down if the leakage current exceeds 500mA.
1.8 Surge Suppression
Standard 1.2/50 μs - 8/20 μs Combination Wave Standard 0.5 μs - 100 kHz Ring Wave
1.9 DC Arc Fault Detection
The PVI 50-60TL includes DC arc fault detection compliant with UL 1699B. The inverter detects electrical noise that typically accompanies a DC series arc. The inverter will shut down should the arc fault sensor detect a series arc.
2.0: Installation
Below is the installation procedure for the inverter. Please read carefully and install the product step-by-step. Before installation, please check that the following items are included in the package:
Table 2.1 - Main Items
No.
Item
Qty
Note
(1)
Main inverter section
1
It is possible to receive and install the wiring box first and the inverter later.
(2)
Wiring box
1
STANDARD WAVEFORM PEAK VALUES
Surge Category
Ring Wave
Combination Wave
B
6 kV/0.50 kA
6 kV/3 kA
Page 14
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 14 of 102
(3)
Mounting bracket
1
Upon which inverter is hung and mounted onto a wall
(4)
User manual
1
Installation and operation manual
(5)
Accessory kit
1
Contains all necessary accessories
The (5) Accessory kit contains items listed below, in Table 2.2:
Table 2.2 – Accessory Kit Components (standard wiring box)
No.
Item
Qty
Note
(1)
M8 Expansion tubes
8
For mounting bracket
(2)
M8×25 assembling bolts
8
For mounting bracket
(3)
M6 X18 screw
11
4 for wiring box and main housing; 6 for inverter and mounting bracket; 1 for Ground connection
(4)
5 pin connector
1
For RS485 communication
(5)
3 pin connector
1
For RS485 communication (for optional model)
(6)
Lifting eye nut M10
2
For lifting the main section
(7)
M8 Nut
4
For AC terminal block
(8)
M8 Flat washer
4
For AC terminal block
(9)
M8 Spring washer
4
For AC terminal block
(10)
DC ferrules
33
30 for DC wires and 3 spares
INSTRUCTION:
The items in the accessory kit table above are for the standard configuration. The accessories may vary if optional parts are purchased.
Page 15
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 15 of 102
Table 2.3 – Accessory Kit Components (H4 wiring box)
No.
Item
Q’ty
Note
(1)
M8 Expansion tubes
8
For mounting bracket
(2)
M8×25 assembling bolts
8
For mounting bracket (3)
M6 X18 screw
11
4 for wiring box and main housing; 6 for inverter and mounting bracket; 1 for Ground connection
(5)
H4 PV Connector(Male)
15
For PV input
(6)
H4 PV Connector(Female)
15
For PV input
(7)
Tool for PV Connector
1
For PV Connector
(8)
M8 Nut
4
For AC terminal block
(9)
M8 Flat washer
4
For AC terminal block
(10)
M8 Spring washer
4
For AC terminal block
Page 16
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 16 of 102
2.1 Recommendations Before Installation
Check that the product environmental specifications (protection degree,
operating temperature range, humidity and altitude, etc.) meet the requirements of the specific project location.
Make sure that the AC grid voltage is within the normal range. Ensure that the local electricity supply authority has granted permission to
connect to the grid.
Installation personnel must be qualified electricians or have received
professional training.
Sufficient space according to Figure 2.3 should be provided to allow the
inverter cooling system to operate normally.
Install the inverter away from flammable and explosive substances. Avoid installing the inverter in locations that exceed the temperature limits
specified in the inverter data sheet to limit undesirable power loss.
Do not install the inverter near an electromagnetic source which can
compromise the normal operation of electronic equipment.
Page 17
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 17 of 102
2.2 Mechanical Installation
1) Dimensions
Figure 2.1 - PVI 50/60TL Inverter Dimensions
2) Installation Method (see Figure 2.2):
Make sure that the mounting structure (wall, rack, etc.) is suitable to support the inverter weight. Follow the mounting guidelines below:
(a) If the location permits, install the inverter vertically. (b) If the inverter cannot be mounted vertically, it may be tilted backward to
horizontal.
The shade cover option must be purchased and installed for any installation angles of 75° or less.
(c) DO NOT mount the inverter leaning forward. (d) DO NOT mount the inverter upside down.
Page 18
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 18 of 102
Figure 2.2 - Inverter Mounting
WARNING: Shade cover accessory required for installation angles of 75° or less.
Page 19
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 19 of 102
3) Installation Space Requirement (see Figure 2.3):
The distances between the inverters or the surrounding objects should meet the following conditions:
Figure 2.3 - Inverter Wall Mounting Specifications
NOTICE:
The spacing between two adjacently mounted inverters should be 500mm (19.7 in.). Ensure that the air space around the inverter is well ventilated.
L'espace entre deux onduleurs montés adjacentes devrait être
500mm (19,7 pouces). Veiller à ce que l'espace d'air autour de l'onduleur est bien aéré.
NOTICE:
The installation clearance between two inverters must be increased to 30 in. when the ambient temperature is higher than 45°C.
Page 20
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 20 of 102
Figure 2.4 - Inverter Pillar Mounting Specifications
La distance d'installation entre deux onduleurs doivent être élargie quand la température ambiante est supérieure à 45℃.
INSTRUCTION:
If the inverter is installed on Unistrut or the array racking (instead of solid wall), the space from the bottom of one inverter to the top of the inverter below may be as small as 4in. (100mm).
Page 21
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 21 of 102
4) Mounting the Inverter onto the Bracket
(1) Mark the 8 holes on the bearing surface for mounting the bracket as shown in Figure 2.5;
Figure 2.5 - Holes on the Bearing Surface Dimensions
(2) Drill holes at the marked positions with a 10mm (0.4in.) drill and put the M8 expansion tubes into the holes; assemble and fasten the mounting brackets with the M8x25 assembling bolts in the accessory kit. Figure 2.6.
Tool: Electric drill (Ф10mm/0.4in. head), 13mm wrench 240 in-lbs
Figure 2.6 – Drilling holes for mounting hardware
4.5”
Page 22
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 22 of 102
1
2
3
Figure 2.7 - Securing the Mounting Bracket
(3) Hang the inverter onto the mounting bracket as shown in Figure 2.8 and Figure 2.9;
Lift mounting: Take out the lifting eye nut M10 (2pcs) from the accessory kit, and screw them onto the studs at the top of the inverter. Use a sling rope or bar (inserted through both lifting eye nuts) to lift the inverter onto the bracket. The minimum angle between the two sling ropes should be less than 90 degrees.
Manual mounting: Two people are needed to properly lift the inverter by the handles detailed in Figure 2.9, and mount the inverter onto the bracket.
CAUTION:
The main PVI 50/60TL inverter section is 123.5 lbs (56 kg). Please ensure the mounting bracket is properly installed before hanging the inverter on the bracket. It is recommended to have at least 2 people mount the inverter due to the weight of the equipment.
ATTENTION: le poids de l'enveloppe principal de PVI 50-60TL est d'environ 56kg (≈123.5 livres).
Veuillez vous assurer que le support est correctement installé avant de suspendre le l'inverseur sur le support. Il est recommandé d'avoir au moins 2 personnes pour monter le convertisseur en raison du poids de l'équipement.
1
2
3
9.84in.
9.84in.
20.55in.
5.51in. (140mm)
(522mm)
(250mm)
(250mm)
Page 23
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 23 of 102
Figure 2.8 - Mounting the Main Inverter Section on the Bracket
Figure 2.9 - Grab Handle Position
(4) Installing the wiring box
Remove the cover plate at the bottom of the main section. (see Figure 2.10) Tool: No.2 Phillips head screwdriver
Page 24
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 24 of 102
Figure 2.10 – Main Section Cover Plate
Remove the cover at the top of the wiring box (see Figure 2.11)
Figure 2.11 - Wiring Box Cover
Connect the wiring box to the main section, using M6x18 screws (4pcs) to
secure the wiring box. (see Figure 2.12)
Tool: No. 10 Wrench, torque value of 25 in-lbs (2.8N.m )
Page 25
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 25 of 102
Figure 2.12 - Wiring Box Installation
(5) Attach the main section and the wiring box to the mounting bracket with the
M6x18 bolts (6 pcs). (see Figure 2.13)
Tool: No.3 Phillips head screwdriver, torque value of 35 in-lbs (4 N.m.)
CAUTION:
The total weight of the PVI 50/60TL inverter is 156 pounds (71kg). Please ensure the mounting is properly installed before hanging the inverter on the bracket.
Le poids total de la PVI 50/60TL onduleur est d'environ 71 kg (156 livres).Veuillez vous assurer que le support est correctement installé avant de suspendre le l'inverseur sur le support.
Page 26
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 26 of 102
Figure 2.13 - Secure the Main Section and Wiring Box to the Bracket
(6) Optional - Install an anti-theft padlock when the installation is complete. The anti-theft padlock is used to help prevent the inverter from being stolen when the equipment is installed outdoors. The inverter may be locked on the bracket, as shown in Figure 2.14:
Figure 2.14 - Anti-Theft Padlock Location
Page 27
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 27 of 102
The anti-theft padlock should meet the requirement of the dimensions shown in Figure 2.15:
B
C
A
Figure 2.15 - Dimensions of Anti-Theft Padlock
(7) Attach the cover board as shown in Figure 2-10 to the left side of the wiring
box. (see Figure 2-16)
Tool: No.2 Phillips head screwdriver, torque value of 10 in-lbs (1.2N.m)
Figure 2.16 - Dimensions of Anti-Theft Padlock
Recommended lock size: A: Ф3~6mm B: 20~50mm C: 20~50mm
Page 28
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 28 of 102
5) Removing/Replacing the Wiring Box Cover:
(1) Use a #3 Phillips screwdriver to remove the 4 screws on the wiring box and pull cover straight off the box. Do not twist or slide the cover while removing. (see Figure 2.17)
Figure 2.17 – Removing the Wiring Box Cover
(2) To replace the cover use a #3 Phillips screwdriver to replace the 4 screws on the cover.
INSTRUCTION:
It is important to use a hand tool (e.g. Screwdriver or T-handle, #3 Phillips) and not power drivers or other types of screw drivers. Also, it is important to hold the cover in alignment with balanced force across the cover, not weighted toward any edge. Partially engage all four screws to the threaded inserts a few rotations before tightening any one screw. This is important to maintain alignment and avoid thread damage. When all four screws are engaged torque to 20 in-lbs (2.2Nm).
Page 29
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 29 of 102
2.3 Electrical Installation
There are two options for wiring box, please confirm which one you have:
Figure 2.18 – (a) Standard wiring box (b) H4 quick connect wiring box
The connection interface of the PVI 50/60TL inverter with Standard wiring box:
Figure 2.19 - Full View of Standard Wiring Box with Options
Page 30
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 30 of 102
7.1in (180mm)
10.2in(258mm)
13.2in(336mm)
17.5in(445mm)
20.5in(520mm)
19.0in(483mm)
1 2 3 2
4
DC INPUT
COMM. PORT
For more details please see the user manual.
WARNING: High touch current . Earth connection essential before connecting supply.
DC INPUT AC OUTPUT
DC INPUT
Figure 2.20 - External Connection Ports
Figure 2.21 - Internal Connection Points of Standard wiring box
1. DC input cable area: 3 x 1.5in. conduit knockouts with an additional plate provided for custom drilled conduit entrances (i.e. use if 2in., 2.5in., 3in. conduit required).
NOTE: Do not enlarge the provided 1.5in. conduit knockouts.
2. Knockout for communication cable 3/4in.
3. Knockout for AC output cable, 1.5in.; additional plate provided for custom 2in.,
2.5in., 3in.
4. External ground connection point
5. DC fuse holders
6. DC Surge Protection Device
6 7 7 8
5
5
5
5
5
5
Page 31
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 31 of 102
7. Internal ground connection point and grounding studs
8. AC output terminal block
The connection interface of the PVI 50/60TL inverter with H4 wiring box:
1
COMM. PORT
Do not disconnect under load.
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
PV 1
PV 2
PV 3
For more details please see the user manual.
WARNING:
High touch current . Earth connection essential before connecting supply.
AC OUTPUT
2 3 4 6
3.9 in.
9.4 in. (237mm)
5
(99mm)
Figure 2.22 – Conduit knock-out Locations of H4 quick connect wiring box
1. H4 quick-fit connectors
2. Knock-outs for communication, 3/4inch Trade Size
3. Knock-out for AC output, 1-1/2inch Trade Size with removable gland plate for custom size conduit (ie use if 2inch or 2.5inch Trade Size is required)
4. External ground connection point
5. Knock-outs for communication in the right side of wire-box, 3/4inch Trade Size
6. Knock-out for AC output in the right side of wire-box, 1-1/2inch Trade Size with removable gland plate for custom size conduit (ie use if 2inch or 2.5inch Trade Size is required)
1+
SPD
2+ 3+ PE
AC Output:Use 90¡ãC wire, either 3~2/0AWG copper or
2~2/0AWG aluminum, torque 110 in-lbs.
AC Ground:Use 90¡ãC copper wire, 6~4AWG for internal
grounding bar or external grounding nut, torque 50 in-lbs.
L1 L2L3N
7
8
9
10
Figure 2.23 – Internal connection points of H4 quick connect wiring box
7. DC Input fuse holder 9. DC SPD (Surge Protective Device)
8. DC SPD (Surge Protective Device) 10. AC output terminal block
Page 32
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 32 of 102
Choose the cables for inverters according to the following configuration table:
Table 2.5 - Cable Specifications
Position
Cable
DC input (/)
#10-8AWG (Copper only) using fuse holders
Up to #2AWG (Copper or Aluminum) using bypass
terminal kit
AC output (L1/L2/L3/N*)
#3-2/0 AWG (Copper)
#2-2/0 AWG Aluminum
*Neutral wire is not current carrying; it is only for
sensing purposes. It can be sized as small as the
EGC (PE), but not smaller than 8AWG.
EGC (PE)
#8-2 AWG(Copper)
#6-2 AWG(Aluminum)
RS-485 communication
UTP CAT-5e or 3x#22-18AWG communication cable
(eg. Belden 9841)
DC and AC GROUND
Even though the inverter operates with an ungrounded PV array, the PV system still requires equipment grounding.
Figure 2.24 - Equipment Grounding Locations (Standard wiring box)
Page 33
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 33 of 102
1+
SPD
2+
3+
PE
AC Output:Use 90¡ãC wire, either 3~2/0AWG copper or
2~2/0AWG aluminum, torque 110 in-lbs.
AC Ground:Use 90¡ãC copper wire, 6~4AWG for internal
grounding bar or external grounding nut, torque 50 in-lbs.
L1 L2 L3 N
Figure 2.25 - Equipment Grounding Locations (H4 wiring box)
2.3.1 DC Connection
1) Working Mode
The PVI 50/60TL inverters have three PV input sections: DC Input-1, DC Input-2 and DC Input-3. These three sections can work only in “Independent mode”.
In Independent mode each PV input section works with an independent MPP Tracker.
2) DC Fuse Configuration
Table 2.6 - DC Input Power Specification
PVI 50/60TL
(Independent mode –
per zone - DEFAULT)
PVI 50TL
PVI 60TL
Rated DC power
17.5kW (36A)
20.5kW (38A)
Max DC power allowed
25kW
30kW
Absolute Max open
circuit Voltage
1000V
1000V
Operating voltage
200-950V DC
200-950VDC
Max power input voltage
range (MPPT)
480-850V DC
540-850VDC
Maximum available PV
current (Isc x 1.25)
60A
60A
Page 34
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 34 of 102
The PVI 50/60TL inverters are equipped with standard 15A DC fuses. Customers must verify that the appropriate fuses are installed depending on the PV system design.
(a) Each independent PV DC input string needs fuse protection. (b) The rated voltage of fuses should be 1000V (c) The rated current of fuses is generally 1.56 × short circuit current from the PV
strings, rounded up to the next available fuse size.
The following table lists the fuse type, specifications and number under the rated voltage and power range of 10 strings of PV panels.
Table 2.7 - DC Fuse Selection
NOTE 1: The 1000VDC Littelfuse fuse series is recommended. Detailed information
is available at: http://www.littelfuse.com/. NOTE 2: The fuse holders can also accept a 20A (SPF020), 25A (SPF025) and a 30A (SPF030) fuse for combined input strings if needed.
NOTE 3: Two 30A fuses should not be used next to each other. NOTE 4: If string fuses other than the provided 15A fuses are desired, it is the customers’ responsibility to source and install these extra fuses.
WARNING:
Use of different fuses or wrongly sized fuses can cause damage to equipment or create un-safe working conditions. Any damage resulting from incompatible fuses is not covered by warranty.
3) DC Conductors Connections
To ensure the optimum performance of the inverter, please read the following guidelines before making DC connections:
(a) Confirm the DC configuration referring to Table 2.6 and ensure that the
maximum open circuit voltage of the PV modules is lower than 1000 VDC under any conditions.
(b) Confirm that the PV strings for each MPPT of the inverter are of the same
module type, power level and string length before connection. The number, orientation, and tilt of PV strings may differ for different applications.
(c) Configure the external wiring according to the conditions in Table 2.8.
50-60 kW
Brand
Standard fuses
(15A)
20A
25A
30A
Littelfuse
SPF015
SPF020
SPF025
SPF030
15A/1000V
20A/1000V
25A/1000V
30A/1000V
Page 35
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 35 of 102
WARNING:
Working with live voltage is dangerous. It is recommended to have all live circuits disabled prior to performing connections.
Table 2.8 - DC Input Configuration
*Note that the provided fuse is 15A, your string combination may require a
larger rated fuse. Always verify the Isc rating of the input prior to connecting to the fuse holder.
**Mixed input signifies a combination of fuse holder connections and fuse
bypass terminal utilization. Such combinations are very rare, but possible. The wire size for the fuse holder connection is #10-8 AWG (30 in-lbs) and up to #2 AWG for the bypass terminal (50 in-lbs).
NOTE: The temperature rating of the input wiring should be 90 or greater.
(d) Check the polarity of each PV string pair (Figure 2.26) before connecting to
the DC fuses or fuse bypass points by following these steps:
i. Using a multi-meter: connect the positive lead from the multi-meter to the
positive lead from the string and the negative lead from the multi-meter to the negative lead from the string. If the value on the multi-meter is
DC
Inputs
Configuration for
each MPPT zone
Z1/Z2/Z3
DC Wire
Size
Conductors
Torque
Connect to:
15
5/5/5
#10-8AWG
30 in-lbs
PV Fuseholder
14
5/5/4
#10-8AWG
30 in-lbs
PV Fuseholder
13
5/4/4
#10-8AWG
30 in-lbs
PV Fuseholder
12
4/4/4
#10-8AWG
30 in-lbs
PV Fuseholder
11
4/4/3
#10-8AWG
30 in-lbs
PV Fuseholder *
10
4/3/3
#10-8AWG
30 in-lbs
PV Fuseholder *
9
3/3/3
#10-8AWG
30 in-lbs
PV Fuseholder *
8
3/3/2
#10-8AWG
30 in-lbs
PV Fuseholder *
7
3/2/2
#10-8AWG
30 in-lbs
PV Fuseholder *
6
2/2/2
#10-8AWG
30 in-lbs
PV Fuseholder *
5
2/2/1
Mixed**
Mixed**
Mixed**
4
2/1/1
Mixed**
Mixed**
Mixed**
3
1/1/1
Up to #2
AWG
50 in-lbs
Bypass
terminals
2
1/1/0
Up to #2
AWG
50 in-lbs
Bypass
terminals
1
1/0/0
Up to #2
AWG
50 in-lbs
Bypass
terminals
Page 36
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 36 of 102
positive, the polarity of the strings is correct.
ii. The positive (+) end of the PV string conductor should match the positive (+)
terminal of inverter’s DC input.
iii. The negative (-) end of the PV string conductor should match the negative (-)
terminal of inverter’s DC input.
Figure 2.26 - Polarity Check
2.3.1.1 DC Connection for Standard Wiring Box
(a) Remove the plug from the DC conduit knockout holes and install the suitable
1.5 inch conduits via the knockouts. Then pull the cables through the conduits into the wiring box.
(b) Connect the DC cables to the fuse holders and fasten the screws, as shown
in Figure 2.21. If you are using H4 wiring box, connect DC wires to H4 connectors as shown in Figure 2.21: Note: If you are using the fuse bypass-
skip this step and move to 8.1 Fuse bypass. Tools: #2 Phillips bit and a Torque driver. Torque value: 3.4N-m (30 in-lbs)
NOTE: If the installer does not use a torque driver to secure the conductors
there is risk of potential damage to the equipment, which is not covered by
the warranty.
NOTICE:
It is important to use a multi-meter to check the polarity of the DC input cables to avoid any risk of reverse polarity.
Il est important d'utiliser un multimètre pour vérifier la polarité des câbles d'entrée C.C. pour éviter tout risque d'inversion de polarité.
Page 37
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 37 of 102
Figure 2.27- DC Input Cable Connection (standard wiring box)
(c) If you prefer to route all DC cables thru a single hole inside the wiring box
please refer to Figure 2.28
Figure 2.28- DC Input Cable Connection
Remove the 4 screws on the wiring box and take off the adaptor plate (refer to Fig.2.22). Using a knockout punch tool, create the appropriate hole on the adaptor plate. Note that for your convenience there are guidelines for a 2”, 2.25” and 3” hole. Attach the board to the wiring box with the screws (4 pcs). Torque to 35 in-lbs.
Page 38
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 38 of 102
2.3.1.2 DC Connection for H4 Wiring Box
(a) Check the polarity of the DC input cables to avoid any risk of reverse polarity. (b) Put the positive (negative) DC cable through the gland and cable fastener, and then crimp the cable with the cord end terminals shown in Table 2-9.
Table 2-9 Cord end terminals for DC cables
No.
Item
Function
1 For Positive DC cable
2 For Negative DC cable
(c) Insert the crimped positive and negative terminals into the male and female housing respectively, and then tighten the seal glands, as shown in Figure 2-29 and Figure 2-30:
Figure 2-29 Assemble the male connector for DC positive cable
Figure 2-30 Assemble the female connector for DC negative cable
Remark: Confirm the following points before connecting the DC cables to the
inverter:
Make sure the PE cable is well connected. Please refer to “DC and AC ground
connection” for detailed information of ground connection.
Turn off the DC switch. (d) Plug the assembled DC cable connectors with the positive and negative
connectors on the inverter side respectively, as shown in Figure 2-31:
NOTICE: It is required to use the attached or the same type of DC input connectors. Otherwise, poor contact may happen, causing problems or damage, which is not covered under the warranty.
Page 39
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 39 of 102
Figure 2-31 Plug DC cable connectors
2.3.1.3 Individual Maximum Power Point Tracking
The inverter is designed with three separate MPP Trackers (MPPT), which operate independently.
PV1+
PV1-
PV2+
PV2-
1 2
3 4
Inverter
IN1+
IN1-
IN2+
IN2-
5
2 3 4 5
2 3 4 5
2 3 4 5
1
1
1
PV3+
PV3-
IN3+
IN3-
2 3 4 5
2 3 4 5
1
1
Figure 2.32 - Three MPPTs Operating Independently
Independent mode can be very useful for sites with shading on parts of the array or with arrays consisting of different orientations. However, this also means that
one must consider these three zones as three separate inverters and power must be balanced as much as possible between the three MPPT zones. See Table 2.8 for string/zones combinations.
NOTE: Always try connecting an equal number of wires to PV1, PV2 and PV3 to each individual MPPT zone.
Page 40
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 40 of 102
NOTE: Connecting all of the inputs at zone “PV1” will result in only utilizing 33% of the inverter power
2.3.2 AC and Ground Connections
The following describes how to connect the AC and ground conductors between the inverter and the AC grid:
1) Use a #3 Phillips head screwdriver to loosen the 4 screws on the wiring box
and remove the cover. (see Figure 2.33)
2) Remove the knockout plugs from the holes of the AC side and install the
suitable conduits of 1-1/4 inch through the holes. Then pull the cables
through the conduit into the wiring box.
3) The inverter supports 3 kinds of conductor connection on the AC side
depending on the grounding connection method. The conductor set-up
procedures are illustrated below.
Use Tables 2.10 and 2.11 for required tools and torque values
Figure 2.33 - Remove the Wiring Box Cover
Table 2.10 - Required Tools
WARNING:
Strings must be balanced for optimum performance and AC output. When doing DC/AC ratio sizing, perform calculations at the zone level. Maximum DC/AC oversizing ratio is 1.5 STC conditions of the modules. Each zone maximum input power is 25kW (50TL) and 30kW (60TL). Note for any application that may experience higher than 1000 W per m2 on a regular basis, a smaller DC/AC ratio is recommended. Also, the combined Isc rating of all strings multiplied by 1.25 must be less than 60A for Individual mode. Failure to follow those guidelines will result in damage to the inverter which is not covered under the warranty.
Page 41
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 41 of 102
No.
Tools
Where used
1.
#3 Phillips screwdriver
Remove cover, external grounding
2.
1/4” flat head bit
Internal grounding bar
3.
14mm hex socket wrench
AC terminal block
4.
Torque wrench
AC terminal block
5.
Diagonal pliers
Cut cables
6.
Wire stripping pliers
Remove insulation of wires
7.
Crimping pliers
Crimp terminal
Table 2.11 - Torque Values
AC output terminal block
132 in-lbs (15 N.m.)
Internal grounding bar
50 in-lbs (4 N.m.)
Internal grounding stud
50 in-lbs (4 N.m.)
External grounding point
50 in-lbs (4 N.m.)
Figure 2.34 - AC cables’ crimp lug specification (a) Standard (b) Metric
Page 42
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 42 of 102
For more details please see the user manual.
WARNING:
High touch current . Earth connection essential before connecting supply.
1 2
AC Output:Use 90¡ãC wire, either 3~2/0AWG copper or
2~2/0AWG aluminum, torque 110 in-lbs.
AC Ground:Use 90¡ãC copper wire, 6-4AWG for internal
grounding bar or external grounding stud, torque 50 in-lbs.
L1 L2 L3 N
AC Output:Use 90¡ãC wire, either 3~2/0AWG copper or
2~2/0AWG aluminum, torque 110 in-lbs.
AC Ground:Use 90¡ãC copper wire, 6-4AWG for internal
grounding bar or external grounding stud, torque 50 in-lbs.
L1 L2 L3 N
Figure 2.35 - AC Output and Ground Cable Connections
(1) Use the OT type terminal to connect the AC (L1, L2, L3, N) cables to the terminal block and connect the ground cable to the internal grounding bar inside the wiring box. (See the first diagram in Figure 2.35)
Page 43
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 43 of 102
Pre-insulated end ferrule 1pcs
OT type terminal,4pcs
Pre-insulated end ferruleCore wire
OT type terminalCore wire
Figure 2.36 - AC Output and Ground Cable setup
(2) Use the OT type terminal to connect the AC (L1, L2, L3, N) cables to the terminal block and use the OT type terminal to connect the ground cable to the external grounding point at the bottom of the wiring box. (See the second diagram in Figure
2.35)
COMM. PORT
Do not disconnect under load.
1 2 3 4 5
1 2 3
4 5
1 2 3 4 5
PV 1
PV 2
PV 3
For more details please see the user manual.
WARNING:
High touch current . Earth connection essential before connecting supply.
AC OUTPUT
3.9 in.
9.4 in. (237mm)
(99mm)
Figure 2-37 External Chassis Ground
NOTE: If you need a larger AC conduit hole, punch one by removing the AC output
adaptor plate and following the steps from Section 3: “DC Input Cable Connection”.
(3) Connecting the inverter to the grid would require a breaker.
NOTICE: Please connect the Ground cable before any AC cable.
It is required to use the AL9CU OT type terminal or equivalent if you chose the aluminum cable for AC output.
Page 44
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 44 of 102
(4) The Grid connection type should be (L1, L2, L3, N, PE). A dedicated Neutral wire is required for proper internal voltage balance.
Either a 3-pole or 4-pole AC circuit breaker should be selected as per the following specifications. Choosing any other breaker size may result in nuisance tripping or
rejection from the AHJ.
Table 2.12 - Breaker Values
Inverter
AC breaker rated currentA
PVI 50TL
80
PVI 60TL
100
NOTE: If you are using aluminum wires you need to follow the following steps to prep each cable prior to connecting to the AC terminal block:
a) Using a utility knife, gently strip the top layer of the aluminum conductors
Figure 2-38 Preparing aluminum wires prior to connecting
b) After removing the oxidized layer immediately apply neutral grease (Noalox or acid­and alkali-free Vaseline) and connect the cable immediately to the terminal. Perform one cable at a time. If you need to stop the process before applying the grease, and continue later- you will need to scrape it again. It takes 30-60 seconds for an oxidized layer to form on top of the conductors.
Acceptable transformer configurations:
Page 45
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 45 of 102
Table 2.13 – Transformer configurations
When interfacing with a Wye-grounded transformer winding, a neutral is required. Since the neutral is used by the inverter for voltage sensing only, the neutral does not carry current. The size of the neutral may be reduced to a conductor no smaller than the EGC or 8 AWG, which is the smallest acceptable wire for the terminal block. Note that if AHJ approves, you can install a jumper across the EGC and the Neutral terminal, this will satisfy the inverter sensing purposes.
When installing multiple inverters for parallel operation connected to a single transformer winding, the kVA rating of the transformer must be at least 5% greater than the total connected inverters’ kVA rating. Up to 50 inverters may be connected in parallel for use with a single transformer.
Page 46
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 46 of 102
2.4 Inverter Communication Connections
The PVI 50/60TL inverter supports industry standard Modbus RS485 communications for monitoring purposes. In addition to SolrenView and/or third party monitoring, these inverters are also able to send data to an online portal which is used for remote diagnostic purposes. This capability can be used by Yaskawa-Solectria Solar for remote diagnostics, remote firmware upgrades and remote troubleshooting. This function is performed by the Ethernet Network Card. Each Ethernet Network Card can handle up to 32 inverters. If a site has more than 32 inverters, additional Ethernet Network Cards will be needed. When a third party monitoring system is used, the DAS should be connected to the Ethernet Network Card, and the Ethernet Network Card is then connected to the inverters. Each inverter has a Communication Board installed in the wiring box which is used to daisy chain the inverters using RS485 for communication purposes. The Ethernet Network Card should be mounted on the communications card of the first or last inverter in the daisy chain. The following sections describe an overview of the Communication Board and Ethernet Network Card.
2.4.1 Communication Board:
Each inverter has a Communication Board (shown below) which is installed in the top right corner of the wiring box. This board is used for daisy chaining inverters for connection to the Ethernet Network Card.
Figure 2-39: Communication Board
Page 47
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 47 of 102
Below is a brief description of the communication board:
Table 2.14 – Communication Board Connections and Configuration Switches
Item
Picture
Configuration Description
1. USB port S200
Firmware upgrade via USB drive
2. RS-485 ports (5pin connector)
1 -----12V+ 2 -----12VGND 3 -----RS485- 4 -----RS485+ 5 -----COM
3. Selector switch for setting the 120Ω termination resistor of the RS485 communication
S1
1-----Disable the termination resistor 2-----Enable the termination resistor
ON
OFF
S1
RS485+
RS485-
GND
RS485 1
RS485 2
ON
OFF
S1
RS485+
RS485-
GND
RS485 1
1
2
Figure 2-40 - Communication Connections
1- Cable connection of RS485 communication: 5 pin connector 2- Cable connection of RS485 network communication: 5 pin connector
Page 48
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 48 of 102
2.4.2 Ethernet Network Card:
A maximum of 32 inverters can be connected to this device. When provided with an internet connection, it can send data to an online portal which Solectria can use for troubleshooting and remote diagnostic purposes. It is also used for allowing the connection of a 3rd party monitoring system. Customers are required to provide internet to the Ethernet Network Card in order for it to be used for remote diagnostic purposes. Once connected, Solectria can remotely check inverter parameters (currents, voltages, parameter settings, etc.) and alarm messages. Solectria can also use this device to remotely update firmware on all the inverters connected to it. Below is a brief overview of the Ethernet Network Card:
Figure 2-41: Ethernet Network Card
Internal RS485
S4
S3
External RS485
+ - GND
USB port
Ethernet Port
Reset Switch
Page 49
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 49 of 102
Table 2.15 – Overview of Ethernet Card
Item
Configuration Description and Function
Ethernet Port
For connecting to the internet
USB Port
Firmware upgrade via USB drive
External RS485
1.RS485+
2. RS485- 3 .Ground For RS485 communication with other inverters
Internal RS485
For RS485 communication with the inverter communication board
S3 Switch
Selector switch for setting the 120Ω terminal resistor of the third party data logger RS485 communication.
S4 Switch
Selector switch for setting the 120Ω terminal
resistor of the RS485 communication between the inverters.
Reset Switch
When pressed for over 5sec, the inverter’s Ethernet Network Card will be restored to the factory setting.
2.4.3 Modbus Connections for Third Party Monitoring Systems The PVI 50/60TL inverters can be connected to an external Data Acquisition System (DAS) via an RS485 shielded twisted pair serial connection as shown in Figure 2.42. These inverters can communicate with an external monitoring system via the standard Modbus RTU protocol.
Figure 2-42 - PVI 50/60TL Inverters in a RS-485 Daisy Chain Connection to an
External DAS
Page 50
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 50 of 102
Figure 2-43 - PVI 50/60TL Inverters in a RS-485 Daisy Chain Connection to an
External DAS, connectors and termination resistance details
When connected to an external DAS, Solectria PVI 50/60TL inverters support up to 32
inverters/devices on the RS485 daisy chain. The Inverter Modbus IDs are configurable from 1 to 128.
Yaskawa - Solectria Solar recommends limiting the RS485 daisy chain for PVI 50/60TL
inverters to a maximum length of 3000 ft. (914m). Additionally, no individual run should be longer than 300 ft. (91.4m).
Care must be taken when daisy chaining the inverters, utilizing a shielded twisted pair
cable such as Belden 9841 or Southwire 58165802.
The shield continuity should be maintained for the entire length of the daisy chain and
should only be connected to ground (GND) at the DAS. The shield should not be connected to any of the inverters to prevent any possible grounding loops.
It is important to terminate the Modbus (RS485) daisy chain correctly to minimize any
bus noise and reflections. The daisy chain should be terminated at the source (the DAS) and at the last Modbus device in the daisy chain. The PVI 50-60TL Modbus termination resistor is turned on by flipping switch S1 to the ON position as shown in Figure 2-45. S1 should always be left in the off position except for the last inverter in the daisy chain.
Non-serial, such as star or ring, network topologies should always be avoided.
S1 ON
S1 OFF
S3 ON
S4 ON
Page 51
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 51 of 102
Figure 2-44 Correct and incorrect topologies
It is important to daisy chain the inverter RS485 connections to minimize noise and bus reflections. Any network topologies shown in the left column in figure 2.44 should be avoided. Equivalent daisy chain topologies shown to the right should be used instead.
1. Open the inverter wiring box.
2. Bring the communication cables into the wiring box through the provided knockout
holes at the bottom.
3. Connect the RS-485 wires to the green 5 pin connector ensuring correct polarity and
using a shielded twisted pair cable.
WARNING: Risk of Electric Shock. Make sure all DC and AC power to the unit has been disconnected before opening the inverter wiring box and ensure that hazardous high voltage and power inside the equipment has been discharged. Wait at least 5 minutes before opening the wiring box.
Page 52
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 52 of 102
4. If the inverter is the last Modbus device in the daisy chain and the inverter without the
Ethernet Network Card, make sure the Modbus termination switch S1 is in the ON position, enabling Modbus termination. Ensure the switch is in the OFF position for all other inverters in the daisy chain, including the one where the Ethernet Network Card is installed.
S1 - Selector switch for the 120Ω RS-485 termination resistor
On - Enable the Modbus (RS-485) bus termination (Applies only for the last inverter in the daisy chain)
Off - Disable the Modbus (RS-485) bus termination. (Factory default)
Figure 2-45 - The Modbus (RS485) Termination Switch (S1) Location and Settings on the
LCD/Communication Board.
5. Close the wiring box.
6. Reconnect the AC and DC power and turn the inverter on when it is safe.
7. Configure the Inverter Modbus ID and Baud rate.
2.4.2 Preparing the Inverter for Modbus Communications
To ensure correct Modbus communications, each inverter Modbus communications settings need to be configured properly. Please follow the steps below to adjust the inverter Modbus ID and Modbus Baud rate.
Please refer to “3.2 Commissioning Steps
WARNING:
Risk of Electric Shock. Make sure all shield wires are properly secured and insulated to prevent shorting to any other components inside the inverter.
Page 53
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 53 of 102
2.4.2 Installing the Ethernet Network Card
Figure 2-46 Communication card and location for Ethernet Network card
The Ethernet Network Card will be installed in the first or last inverter of the daisy chain.
1. Obtain the Ethernet Network Card that was shipped to you.
2. Remove the screws from the Communication Card and Install the included standoffs in the 3 locations shown.
3. Install the Ethernet Network Card, taking care to line up the black connector in the upper left corner on the pins of the Communication Card. Ensure the pins are seated in the connector. Install the 3 screws and torque to 7 in-lbs using #2 Phillips bit.
Figure 2-47 Ethernet Network card installed
Page 54
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 54 of 102
2.4.3 Connecting the Ethernet Network Card to other inverters.
1. The connector in the upper left corner of the Ethernet Network Card allows for a connection of the inverter daisy chain on the Communication Card.
2. Since the Ethernet Network Card acts as the end of the inverter daisy chain, termination must be turned on. Set the termination resistor S4 to the ON position on the Ethernet
Network Card. Set the termination resistor S1 to the ON position on the Communication Card in the inverter at the opposite end of the inverter daisy chain.
2.4.4 Connecting a 3rd Party Monitoring System to the Ethernet Network Card
1. From the DAS, connect the RS485 to the 3 pin connector on the Ethernet Network Card. Do not connect to the communication card.
2. Tighten all wires securely.
3. If the Ethernet Network Card is the last device in the DAS chain, set the termination resistor S3 ON.
Figure 2-48 Ethernet Network wiring to DAS
2.4.5 Preparing the Ethernet Network Card
The Ethernet Network Card comes preset with DHCP settings. It will automatically pull a dynamic IP address and connect to the Internet. If you need to assign a static IP address please refer to the documentation provided with the board or go to Solectria.com and search for “Ethernet Network Card”.
Connect
external RS485
(DAS) here
Page 55
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 55 of 102
3.0: Commissioning
3.1 Commissioning Checklist
3.1.1 Mechanical Installation
Make sure that the mounting bracket is secure and all the screws have been tightened to the specified torque values. (Please refer to 2.2 Mechanical Installation)
3.1.2 Cable Connections
(a) Make sure that all cables are connected to the right terminals. (b) The appropriate cable management is important to avoid physical damage. (c) The polarity of DC input cables should be correct and the DC Switch should be in the “OFF” position.
(Please refer to 2.3 Electrical Installation)
3.1.3 Electrical Check
(a) Make sure that the AC circuit breaker is appropriately sized. (b) Test whether the AC voltage is within the normal operating range. (c) Make sure the DC open circuit voltage of input strings is less than 1000V.
3.2 Commissioning Steps
Complete the checklist above before commissioning the inverter as follows:
1.) Turn on the AC circuit breaker.
2.) Turn on the DC circuit breaker. (Skip this step if there is no circuit breaker.)
3.) Switch the DC Switch to the “ON” position. When the energy supplied by the PV
array is sufficient, the LCD of inverter will light up. The inverter will then start up with the message “sys checking”.
4.) You may change the grid standard. The default setting is IEEE 1547.
WARNING:
Please follow the guidelines below before on-grid operation to eliminate possible dangers and to ensure safety.
Veuillez suivre les directives ci-dessous avant l'opération on-grid pour éliminer les dangers possibles pour assurer la sécurité.
INSTRUCTION:
Please check with your local electricity provider before selecting the grid standard. If the inverter is operated with a wrong grid standard, the electricity provider may cancel the interconnection agreement. Putting the inverter into operation before the overall system complies with the national rules and safety regulation of the application is not permitted.
Page 56
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 56 of 102
(a) When the inverter completes “sys checking”, the LCD shows the screen as
Figure 3.1 below. Press ENTER to the standard selection interface, as shown in Figure 3.1.
(b) The default grid standard is IEEE 1547. If a different standard is needed please
go to “Menu Functions” section for further instructions on how to change it. Available grid standards are shown in
Grid Connection Rule
Rule-21
HECO-ML
HECO-HM
IEEE1547
Figure 3.1 - Select Grid Standard; ML-Molokai/Lanai; OHM- O`ahu, Maui, and
Hawai`i
5.) Set up the system time and language according to “4.4.2.1 System parameters”.
6.) To check the real time operation information, you can refer to “4.4.1 Operation
information”.
7.) Communication Parameter Setting: The communication baud rate and Modbus
address can be set in this menu (Figure 3.2):
Com setting
Baud
Addr32
P1/1
9600
Figure 3.2 – Selecting Baud Rate and Modbus ID
Page 57
PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E Page 57 of 102
8.) Time Setting: The date and time can be set as in Figure 3.3:
Time setting
2016–05 - 21 Date
Time12 21 03
P1/1
Figure 3-3 Time Setting
9.) When the LCD screen shows the normal operation status (Figure 3.4) and the “RUN”
light on the LED panel lights up, it indicates that the grid connection and power generation are successful.
E-total: KWh
2015-10-22 1000:00
E-Today: kWh
Status Addr:000
Running Status Cycle Display
3 6 9 12 15 18 21 24
kWh
h
15
30
45
60
Figure 3.4 Normal Operation Status
REMARK: The Running status cycle display include: NoErr (Error information), Pdc(kW),
Udc(V), Idc(A), Pac(kW) and Q(kvar).
10.) If the inverter fails to operate normally, the “FAULT” light will illuminate and the
fault information will show on the LCD screen as shown in the Figure 3.5.
Current Fault
P1/1
Num Time&Date
Error Code
001 2015/10/22 12:20:08 W0130
003 2015/10/22 13:20:08
F0140
002 2015/10/22 12:30:11 P0020
004 2015/10/24 10:20:04 F0150
006 2015/10/25 12:20:08
F0070
005 2015/10/24 09:31:08 W0130
2015/10/25 16:11:18
008 2015/10/25 17:21:07 P0050
007 P0360
Figure 3.5 Fault Information Interface
Page 58
DOCR-070645-E Page 58 of 102
4.0: User Interface
4.1 Description of the Interface
The inverter’s user interface screen mainly consists of LCD, LED indicator lights, buzzer and 4 keys, as shown in Figure 4.1.
POWER
RUN
GRID
FAULT
Figure 4.1 - LCD
Interpretation for the indicator lights is shown in Table 4.1 and function of the keys is shown in Table 4.2.
Table 4.1 - LED Indication
LED Indicator
Name
Status
Indication
POWER
Working
power
light
Light
on
Energized (control panel starts to work)
Light
off
Power supply not working
RUN
Grid-tied
operation
indication
light
Light
on
In grid-tied power generation state
Flash
Derated running status (light on 0.5s, light off 1.6s)
Light
off
In other operation status or power supply not working
GRID
Grid
status
indication
light
Light
on
Grid is normal
Flash
Grid fault (light on 0.5s, light off 1.6s)
Light
off
Power supply not working
Page 59
DOCR-070645-E Page 59 of 102
FAULT
Fault
status
indication
light
Light
on
Indicates a Fault
Slow flash
Indicates Alarm (light on 0.5s, light off 2s)
Fast
flash
Protective action (light on 0.5s, light off
0.5s)
Light
off
No fault or power supply not working
Table 4.2 - Definition of the Keys
Key
Description
Definition of function
Escape key
Back/end/mute
Enter key
Confirm entering the menu/confirm set value/Switch to parameter setting mode
Up
Page up in selection menu/+1 when setting parameters
Down
Page down in selection menu/-1 when setting parameters
4.2 Operation State
Table 4.1 describes the meaning of LED indicators (i.e. it indicates the inverter’s operational state).
“POWER” will light up to indicate that the system is energized and
under DSP control.
“RUN” will light up when the inverter detects that the grid connection
conditions meet the requirements and power is fed into the grid. “RUN” will blink if the grid is in de-rated running state during the period of feeding power into the grid.
GRID” will light up when the grid is normal during the operation of the
inverter. Otherwise, “GRID” will blink until the grid restores to normal.
“FAULT” will blink quickly as a fault (except grid fault) occurs. “FAULT
will not turn off until the fault is eliminated. The light will blink slowly when an alarm occurs. “FAULTremains illuminated when an internal fault occurs. The buzzer will give an alarm if a fault (involving power grid fault) occurs.
Page 60
DOCR-070645-E Page 60 of 102
4.3 Interface Types
Users can perform the corresponding operations with the 4 function keys according to the indications of the LCD.
(1) The LCD interface starts with the company logo once the system is energized,
as shown in Figure 4.2.
Figure 4.2 - Logo Screen
(2) Indication of inverter operation mode:
E-total: KWh
2015-10-22 1000:00
E-Today: kWh
Status Addr:000
Running Status Cycle Display
3 6 9 12 15 18 21 24
kWh
h
15
30
45
60
Figure 4.3 – Default Display Interface for Normal Operation
History
P1/1
Num Time&Date
Error Code
001 2015/10/22 12:20:08 W0130
003 2015/10/22 13 :20:08
F0140
002 2015/10/22 12:30:11 P0020
004 2015/10/24 10:20:04 F0150
006 2015/10/25 12 :20:08
F0070
005 2015/10/24 09:31:08 W0130
2015/10/25 16:11:18
008 2015/10/25 17:21:07 P0050
007 P0360
Figure 4.4 – Fault Indication Interface
LCD will display different mode interfaces based on the operation modes of the inverter. There are 3 operation modes: startup system check mode (as shown in Figure 4.2), normal operation mode (as shown in Figure 4.3), and fault mode (as shown in Figure 4.4).
The default interface mainly shows PV voltage, PV current, grid voltage, instant power,
Yaskawa Solectria Solar
Initialization
Page 61
DOCR-070645-E Page 61 of 102
daily generated power and time information under normal operation.
The fault information of the most recent / currently present fault will be shown on the LCD when the inverter is in fault mode.
4.4 Menu Functions
LCD displays “Main user interface” when the inverter is in operation mode. Press ESC in this interface to escape the default interface and to enter the main operation interface. The main operation interface is shown in Figure 4.5.
Main Menu
Measurement Data
History Record
Power On/Off
Device Information
Setting
Figure 4.5 - Main Menus on the LCD
The main operation interface of LCD screen has 5 menus, i.e. “1 Measurement Data”, “2 Settings”, “3 Power ON/OFF”, “4 History Record”, and “5 Device Information”. The
users may select options with and , and then press ENT to confirm selection. The users can return to the default indication interface by pressing ESC.
4.4.1 Measurement Data
When the cursor moves to “Measurement data” in the main screen, you should press ENT to select the operation information as shown in Figure 4.6. Check the information by pressing UP and DOWN. Return to the previous menu by pressing ESC.
Page 62
DOCR-070645-E Page 62 of 102
PV Information
PdcTotal(kW)
PV Input Mode
Independent
PV3
0.0
PV1
PV2
Vdc(V)
Idc(A)
0.0
0.0
0.00.0
0.0
0.0
Energy E-Today(kWh) 0.0
E-Month(kWh)
0.0
E-Total(kWh)
AC Output
L3-NL1-N
L2-N
V(V)
I(A)
0.0
0.0
0.00.0
0.0
0.0
0.00.0
0.0
F(Hz)
Others
Ambient Temp(℃)
Heatsink Temp(℃)
-37.0
-49.9
P1/4
P2/4
P3/4
P4/4
Pac(Kw) P Ref PF Ref
0.0
100.0%
1.000
0.0
Grid Connection Rule
IEEE1547
Power Derating
Main Menu
Measurement Data
History Record
Power On/Off
Device Information
Setting
Figure 4.6 – Measurement Data
Page 63
DOCR-070645-E Page 63 of 102
4.4.2 Setting
Move the cursor to “Settings” in the main interface. Press ENT, you will be asked for a password. Enter the password: “1111”as shown Figure 4.7. Change the password digits by pressing and . Then press ENT to input the next digit and Press ENT to confirm the password or Press ESC return back to setting.
Password
P1/1
Please enter password:
0 0 0 0
Figure 4.7 – Password Screen for Settings Menu
Press ENT to confirm, and set the current system parameters, as shown in Figure 4.8.
There are 10 submenus in “Parameters Setting”: “1 System Parameters”, “2 Control Command”, “3 Protection Parameters”, “4 L/HVRT Parameters”, “5 Active Derating Setting”, “6 Reactive Derating Setting”, “7 ARC Parameters”, “8 Other Parameters”.
Setting
P2/2
LVRT/HVRT Setup
Others Parameters
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
4-8 System Settings Menu
Page 64
DOCR-070645-E Page 64 of 102
4.4.2.1 System Parameters
(1) “Language Setting One language, i.e. English is available in “Language” menu. (2) “Grid Rule”: There are four grid standards. Selecting the corresponding grid
standard and press ENT confirm the selection as shown in Figure 4-9.
Grid Connection Rule
Rule-21
HECO-ML
HECO-HM
IEEE1547
Figure 4-9 Setting Grid Rule
(3) “PV Input Mode”: The inverter can work only under “Independent Mode” (4) “Com Setting”: In this interface you can set the address and baud rate for communication.
(5) “Time”: Move the cursor to the “Time” set the system time. Press “ ” or
” set the value, then press “ENT” to move to the next option. e.g.: Year to Month. Finally Press “ENT” to confirm your selection. (6) “LCD Contrast Setting”: Setting the LCD contrast grade.
4.4.2.2 Control Command
There are 8 submenus in the “Control Command”: (1) Restart” menu: If a fault shutdown happens, a severe fault may have occurred inside the inverter. The user can perform a manual reboot once using this menu if the user needs to restart the inverter.
INSTRUCTION:
Please check with your local electricity supply company before selecting the grid standard. If the inverter is operated with a wrong grid standard, the electricity supply company may cancel the operation license. Putting the inverter into operation before the overall system complies with the national rules and safety regulation of the application is not permitted.
INSTRUCTION:
This function is effective only when the fault “IntFault0010~0150” in the
troubleshooting table occurs. The inverter may return to normal operation
Page 65
DOCR-070645-E Page 65 of 102
(2) Factory Default” menu: The manufacturer’s default parameters value can be restored when the inverter is not in operation mode. If you try to change the parameters while the unit is operational “Fault Operated” will be displayed. (3) Auto Test” menu: Used for factory test only. Not intended to be used by the user. (4) MPPT Scan” menu: “MPPTScan” is to execute the MPPT scanning manually. Move the cursor to this item, and press ENT to initiate the scanning. The LCD screen will skip to normal operation interface if the MPPT scanning succeeds, or remain on the “MPPTScan menu” interface if the scanning fails. MPPT scan function is used for multi-MPP point tracking, if the PV panels are partly shadowed or installed with different angle. The factory default setting of MPPT scan is Enabled, and it can also be Disabled. When the MPPT scan function is enabled, the scan period is 60 minutes; the inverter will scan the maximum power point in the
MPPT range, according to below condition
In independent mode, each input power is lower than 75% of the rated power of each MPPT tracker. Once this MPPT scan function is activated thru the LCD, it will search the maximum power point at a voltage step of 5V in the MPPT range for full load,
and get the maximum power point. (5) ARC Detect” In the “Parameters Setting””Control Command” menu, execute the “ARC Detect”, the inverter will stop working and test ARC. Arcing check and protection is mainly divided into two parts, the Arcing check board is responsible for detecting if there is arcing in the PV line, and sends the arcing protection signal to the DSP in the control board. The control board DSP is responsible for turning the inverter off the grid after receiving the arcing signal to ensure safety. The arcing board failure will cause ‘arc board err’ shown on the LCD and it will not connect to the grid until the arc board is OK. If there is Arcing fault, the LCD displays the fault which can only be cleared manually. (6) ARC Clear” is used to clear the ARC fault. Move the cursor to this menu, and press ENT. The operation result will appear on the LCD, ie. “Succeed” or “Failed”.
automatically if alarm or protection faults occur. This function will not
respond when the inverter is in operation mode and a “FaultOperated”
alarm interface is indicated.
Page 66
DOCR-070645-E Page 66 of 102
4.4.2.3 Protect Parameters
In this interface you can change the Protect parameters of grid voltage, frequency and recovery, etc., as shown in Figure 4-10. But you can’t enable/disable the function. The protect parameters are shown in Table 4.3.
Voltage Moving Average
P6/7
MaxTripT(S)
VolMax
MinTripT(S)
VolMin
600.00
88.00%
600.00
110.00%
Grid Over Voltage Protection
VolMaxTripT1(S)
GridVolMax1
P1/7
VolMaxTripT2(S)
GridVolMax2
VolMaxTripT3(S)
GridVolMax3
0.16
120.00%
1.00
110.00%
0.16
120.00%
Grid Low Voltage Protection
P2/7
VolMinTripT1(S)
GridVolMin1
VolMinTripT2(S)
GridVolMin2
VolMinTripT3(S)
GridVolMin3
1.00
60.00%
2.00
88.00%
0.16
45.00%
Grid Low Frequency Protection
P4/7
FrqMinTripT1(S)
GridFrqMin1(Hz)
GridMinTripT2(S)
GridFrqMin2(Hz)
FrqMinTripT3(S)
GridFrqMin3(Hz)
0.16
57.0
2.00
59.5
0.16
57.0
Grid Recovery
P5/7
VolMin
VolMax
FrqMax(Hz)
VolRecoveryT(S)
FrqRecoveryT(S)
FrqMin(Hz)
60.3
300.00
90.00%
107.92%
300.00
59.8
Enable
Disable
Disable
Grid Voltage Balance
P7/7
GridVolBalance
10.00% Disable
Enable
Disable
Enable
Enable
Enable
Grid Over Frequency Protection
P3/7
FrqMaxTripT1(S)
GridFrqMax1(Hz)
GridMaxTripT2(S)
GridFrqMax2(Hz)
FrqMaxTripT3(S)
GridFrqMax3(Hz)
0.16
62
2.00
60.5
0.16
Enable
Enable
Disable Disable
Enable
Enable
62
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
Figure 4.10 Protection Parameters Setting
REMARK: Switching between parameters is done by pressing and . Then
press “ENT” to select it, change the parameter value by pressing and then press “ENT” to send the parameter to inverter. The LCD will display new
parameters if the setting is successful. Otherwise the old parameters will display on the LCD.
Page 67
DOCR-070645-E Page 67 of 102
Table 4.3 Protection Parameters (IEEE1547)
REMARK: Please contact Applications Engineering if you need to change any of the
voltage settings.
Grid Over Voltage Protection
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridVoltMax1
Threshold value of Level 1 Max.
grid voltage
{100.00%, 110.00%,
150.00%}
VoltMaxTripTime1(s)
Threshold value of Level 1 Max.
grid trip voltage
{0, 1.00, 655}
GridVoltMax2
Threshold value of Level 2 Max.
grid voltage
{100.00%, 120.00%,
135.00%}
VoltMaxTripTime2(s)
Threshold value of Level 2 Max.
grid trip voltage
{0, 0.16, 655}
GridVoltMax3
Threshold value of Level 3 Max.
grid voltage
{100.00%, 120.00%,
135.00%}
VoltMaxTripTime3(s)
Threshold value of Level 3 Max.
grid trip voltage
{0, 0.16, 655}
Grid Low Voltage Protection
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridVoltMin1
Threshold value of Level 1 Min.
grid voltage
{30.00%, 88.00%,
100.00%}
VoltMinTripTime1(s)
Threshold value of Level 1 Min.
grid trip voltage
{0, 2.0, 655.36}
GridVoltMin2
Threshold value of Level 2 Min.
grid voltage
{30.00%, 60.00%,
100.00%}
VoltMinTripTime2(s)
Threshold value of Level 2 Min.
grid trip voltage
{0, 0.16, 655}
GridVoltMin 3
Threshold value of Level 3 Min.
grid voltage
{30.00%, 45.00%,
100.00%}
VoltMinTripTime3(s)
Threshold value of Level 3 Min.
grid trip voltage
{0, 1.2, 655}
Grid Low Frequency Protection
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridFrqMin1
Protection threshold value of
Level 1 Min. grid frequency
{54, 59.5, 60}
FrqMinTripT1(s)
Trip time of Level 1 Min. grid
frequency
{0, 2, 655 }
Page 68
DOCR-070645-E Page 68 of 102
GridFrqMin2
Protection threshold value of
Level 2 Min. grid frequency
{54, 57, 60}
FrqMinTripT2(s)
Trip time of Level 2 Min. grid
frequency
{0, 0.16, 655}
GridFrqMin3
Protection threshold value of
Level 3 Min. grid frequency
{54, 57, 60}
FrqMinTripT3(s)
Trip time of Level 3 Min. grid
frequency
{0, 0.16, 655}
Grid Over Frequency Protection
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridFrqMax1
Protection threshold value of
Level 1 Max. grid frequency
{60, 60.5, 66}
FrqMaxTripT1(s)
Trip time of Level 1 Max. grid
frequency
{0, 2, 655}
GridFrqMax2
Protection threshold value of
Level 2 Max. grid frequency
{60, 62, 66}
FrqMaxTripT2(s)
Trip time of Level 2 Max. grid
frequency
{0, 0.16, 655}
GridFrqMax3
Protection threshold value of
Level 3 Max. grid frequency
{60, 62, 66}
FrqMaxTripT3(s)
Trip time of Level 3 Max. grid
frequency
{0, 0.16, 655}
Grid Recovery
Parameter name
Description
Setup range (lower limit,
default & upper limit)
VolMax(V)
Recovery Max threshold grid
voltage protection
{80.00%, 107.92%,
135.00%}
VolMin(V)
Recovery Min threshold. grid
voltage protection
{20.00%, 90.08%,
100.00%}
VolRecoveryT(s)
Recovery time of grid voltage
protection
{0, 300, 655}
FrqMax(Hz)
Recovery Max threshold grid
Frequency protection
{54, 60.3, 66}
FrqMin(Hz)
Recovery Min threshold. grid
Frequency protection
{48, 59.8, 60}
FrqRecoveryT(s)
Recovery time of grid frequency
protection
{0, 300, 655}
Grid Voltage Balance
Page 69
DOCR-070645-E Page 69 of 102
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridVolBalance
Threshold value of grid voltage
unbalance
(0.01%,10%,10%)
4.4.2.4 L/HVRT Parameters
“L/HVRT” is for setting the Low Voltage Ride-Through (LVRT) and High Voltage Ride-Through (HVRT) parameters. Move the cursor to this item, and press ENT to set the parameters. Set the parameters as shown in Figure 4.11, the LVRT curve as shown in Figure 4.12 and the HVRT curve as shown in Figure 4.13.
LVRT Curve
LVRTTime1
LVRTVol1
P1/7
1.20
0.00%
0.00
0.00%
LVRTVol2
45.00%
1.20
P2/7
10.50
65.00%
10.50
45.00%
65.00%
20.50
LVRTTime2
LVRTTime3
LVRTVol3
LVRTVol4 LVRTTime4 LVRTVol5 LVRTTime5
LVRTTime6
LVRTVol6
P3/7
20.50
83.00%
20.50
83.00%
LVRTTime7
LVRTTime8
LVRTVol7
LVRT Curve LVRT Curve
LVRTVol8
HVRT Curve
HVRTTime1
HVRTVol1
P4/7
0.80
125.00%
0.00
125.00%
HVRTVol2
124.00%
0.80
P5/7
12.50
115.00%
12.50
124.00%
115.00%
12.50
HVRTTime2
HVRTTime3
HVRTVol3
HVRTVol4 HVRTTime4 HVRTVol5 HVRTTime5
HVRTTime6
HVRTVol6
P6/7
12.50
115.00%
12.50
115.00%
HVRTTime7
HVRTTime8
HVRTVol7
HVRT Curve HVRT Curve
HVRTVol8
LVRT and HVRT Control
LVRTTripVolt
LVRTModeSetting
P7/7
200.0%
150.0%
80.0%
0
LVRTPstReactiveI
0
110.0%
HVRTTripVolt
HVRTModeSetting
LVRTNegReactiveI
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
Figure 4.11 L/HVRT Parameters Setting
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1 0
2 4 6 8 10 12 14 16 18 20 22
1
2
3 4
5 6
7,8
Through
Trip
Voltage N*rated
Time/S
Figure 4.12 LVRT graph
Page 70
DOCR-070645-E Page 70 of 102
1.3
1.25
1.2
1.15
1.1
1.05 1
2 4 6 8 10 12 14 16 18 20 22
1
2
3 4
56,7,8
Through
Trip
Voltage N*rated
Time/S
Figure 4.13 HVRT graph
Table 4.4 LVRT and HVRT parameters
LVRT
Parameter name
Description
Setup range (lower limit,
default & upper limit)
LVRTVolt (1,2)
Threshold value of Low voltage ride
through(first or second point)
{0%, 0%, 100%} {0%, 0%, 100%}
LVRTTime(1,2)
Time of Level Low voltage ride
through(t first or second point)
{0, 0, 655}
{0, 1.2, 655}
LVRTVolt (3,4)
Threshold value of Low voltage ride
through(third or fourth point)
{0%, 45%, 100%} {0%, 45%, 100%}
LVRTTime(3,4)
Time of Level Low voltage ride
through(third or fourth point)
{0,1.2, 655}
{0, 10.5, 655}
LVRTVolt (5,6)
Threshold value of Low voltage ride
through(fifth or sixth point)
{0%, 65%, 100%} {0%, 65%, 100%}
LVRTTime(5,6)
Time of Level Low voltage ride
through(fifth or sixth point))
{0, 10.5, 655} {0, 20.5, 655}
LVRTVolt (7,8)
Threshold value of Low voltage ride
through(seventh or eighth point)
{0%, 83%, 100%} {0%, 83%, 100%}
LVRTTime(7,8)
Time of Level Low voltage ride
through(seventh or eighth point)
{0, 20.5, 655} {0, 20.5, 655}
HVRT
HVRTVolt(1,2)
Threshold value of high voltage ride
{100%, 125%, 135%}
Voltage PU (per unit)
Page 71
DOCR-070645-E Page 71 of 102
through(first or second point)
{100%, 125%, 135%}
HVRTTime (1,2)
Time of Level high voltage ride
through(t first or second point)
{0, 0, 655}
{0, 0.8, 655}
HVRTVolt(3,4)
Threshold value of high voltage ride
through(third or fourth point)
{100%, 124%, 135%} {100%, 124%, 135%}
HVRTTime (3,4)
Time of Level high voltage ride
through(third or fourth point)
{0, 0.8, 655}
{0, 12.5, 655}
HVRTVolt (5,6)
Threshold value of high voltage ride
through(fifth or sixth point)
{100%, 115%, 135%} {100%, 115%, 135%}
HVRTTime(5,6)
Time of Level high voltage ride
through(fifth or sixth point))
{0, 12.5, 655} {0, 12.5, 655}
HVRTVolt (7,8)
Threshold value of high voltage ride
through(seventh or eighth point)
{100%, 115%, 135%} {100%, 115%, 135%}
HVRTTime(7,8)
Time of Level high voltage ride
through(seventh or eighth point)
{0, 12.5, 655} {0, 12.5, 655}
LHVRT Control
LVRTTripVol
Threshold value of Low voltage trip
(70.0%,80.0%,100.0%)
LVRTPstReactive1
The factor LVRT PositiveReactive
Current
(0.0%,150.0%,300.0%)
LVRTNegReactive1
The factor LVRT Negative Reactive
Current
(70.0%,200.0%,100%)
HVRTTripVol
Threshold value of high voltage trip
(100.0%,110.0%,135.0%)
Page 72
DOCR-070645-E Page 72 of 102
4.4.2.5 Power Derating Setting
Power Derating Setting” menu is to set the active power derating parameters include active power derating, over frequency derating, low frequency derating and high temperature frequency derating, etc. The parameters are shown in Table 4.5.
Active Power Derating
Percentage
CtrMode
P3/3
100.0%
0
Power vs Voltage
OvrVolSlop(Pn/s)
OvrVoltTrip
P1/3
OvrVolFilterT(s)
60
0.0%
110.00 %
OvrFrqMax(Hz)
OvrFrqMin(Hz)
P2/3
OvrFrqSlop(Pn/s)
60.0
0.16%
61.4
60.4
OvrFrqRecoveryT(S)
RecovryFrq(Hz)
60
OvrFrqDeratingMode
0
Disable
Power vs Friquency
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup ARC Parameters
Control Command
Figure 4-14 Active Power Derating
Table 4.5 Active Power Derating Settings
Voltage-Watt Over
Parameter name
Description
Setup range (lower limit,
default & upper limit)
OvrVoltTrip
Threshold value of grid over
voltage derating
{480,528,648}
OvrVoltSlop
Slope of grid over voltage derating
{0,0,1}
Page 73
DOCR-070645-E Page 73 of 102
OvrVoltFilterT(s)
Recovery time of grid over voltage
derating
{1,60,90}
Grid Over Frequency Derating
Parameter name
Description
Setup range (lower limit,
default & upper limit)
OvrFrqMin(Hz)
Min Threshold value of grid over
Frequencyderatingstarted
{60,60.2,72}
OvrFrqMax(Hz)
Max Threshold value of grid over
Frequencyderating over
{60,61.4,72}
OvrFrqSlop
Slop of grid over
Frequencyderating
{0,0.16%,1}
RecoveryFrq(Hz)
Recovery value of grid over
Frequencyderating
{58.8,60,66}
OvrFrqRecoveryT(s)
Recoverytime of grid over
Frequencyderating
{0,60,655}
4.4.2.6 Reactive Derating Setting
“Reactive Power Derating Parameters” menu is to set the Grid reactive power derating parameters including PF parameters and Q parameters, etc. The parameters are shown in Table 4.6
NOTE: The PF and Q value can be adjusted by remote software if “Remote” is
selected. Remote can be selected thru the Modbus map and the appropriate register.
PF vs Voltage
pFCurveP1
pFSetValue
P1/4
pFCurvepF1
100.0%
1.000
50.0%
1.000
pFCurvepF2
pFCurveP2
pFCurveTriVolt
pFCurveUndoVolt
-0.900
100.00%
90.00%
QuCurveQ2i
P3/4
5.0%
20.0%
50.0%
QuCurveTriPower
QuCurveUndoPower
Reactive Power vs Grid Voltage Grid Reactive Power Derating
P4/4
CtrMode
0
Percentage
0.0%
Reactive Power vs Grid Voltage
QuCurveQ1
QuCurveU1
P2/4
-50.0%
110.00%
0.0%
107.99%
92.01%
0.0%
90.00%
QuCurveU2 QuCurveQ2 QuCurveU1i
QuCurveQ1i
QuCurveU2i
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup ARC Parameters
Control Command
Figure 4-15 Reactive Power Derating
Page 74
DOCR-070645-E Page 74 of 102
(1) CtrMode Set the control mode of reactive power 0: Disable dispatch mode
1: Remote dispatch mode 2: Local control, by Q 3: Local control, by PF 4: PF(P) curve 5: Q(U) curve
(2) PF Set Set the PF value NOTE: You can change the reactive power by adjusting the power factor
(3) PF(P) CurvePF curve mode NOTE: The power factor changes according to the power change, as shown in Figure
4-16:
Figure 4-16 PF(P) Curve Mode
(4) Q(U) CurveQ(U) curve mode Note: The reactive compensation changes according to the grid voltage change, as
shown in Figure 4.17.
Capacitive
PF
-1
1
Inductive
(PFCurveP1,PFCurvePF1)
(PFCurveP2,PFCurvePF2)
(P%)
INSTRUCTION:
The PF (P) Curve function is only available for IEEE-1547 grid standard.
INSTRUCTION:
The Q(U) curve function is only available for IEEE-1547 grid standards.
Page 75
DOCR-070645-E Page 75 of 102
Figure 4.17 Q(U) Curve Mode
The Table 4.6 lists the parameters of PF Set, PF(P) Curve and Q(U) Curve modes. After you setup the parameters, press ENT to activate the modes.
Table 4.6 - Parameters of Reactive Power Control (IEEE-1547)
Grid Reactive Power Derating
Parameter name
Setup range (lower limit,
default & upper limit)
Description
PFSetValue
{-1,1,1}
Figure 4-14
PFCurveP1
{0,0.5,1}
Figure 4-14
PFCurvepF1
{-1,1,1}
Figure 4-14
PFCurveP2
{0,1,1}
Figure 4-14
PFCurvepF2
{-1,-0.9,1}
Figure 4-14
PFCurveTriVol(V)
{480,480,528}
PF curve trip voltage
PFCurveUndoVol(V)
{432,441.6,480}
PF curve revocation
voltage
QuCurveU1(V)
{480,518.4,528}
Figure 4-15
QuCurveQ1
{-1,0,1}
Figure 4-15
QuCurveU2(V)
{518.4,528,528}
Figure 4-15
QuCurveQ2
{-1,-0.5,1}
Figure 4-15
Capacitive
Q(%)
_
+
Inductive
(QuCurveU2i,QuCurveQ2i)
U(V)
(QuCurveU1i,
QuCurveQ1i)
(QuCurveU1,
QuCurveQ1)
(QuCurveU2,QuCurveQ2)
Page 76
DOCR-070645-E Page 76 of 102
QuCurveU1i(V)
{432,441.4,456}
Figure 4-15
QuCurveQ1i
{-1,0,1}
Figure 4-15
QuCurveU2i(V)
{384,432,441.4}
Figure 4-15
QuCurveQ2i
{-1,0.5,1}
Figure 4-15
QuCurveTriPower
{0.05,0.2,1}
Qu curve trip power
QuCurveUndoPower
{0.05,0.05,1}
Qu curve revocation
power
4.4.2.7 Arc Parameters
The ARC Parameters submenu is to enable/disable the ARC detection function and set the ARC parameters. NOTE: always check with your AHJ before disabling this function.
ARC Bandwith Setting
StartFrq1
Bandwidth1
P1/4
20%
25
20K
10K
Threshold1(dB)
Proportion1
SigPerApdLimit1(dB)
455
65
ARC Others Parameters
P4/4
60%
0K
5K
0%
6
7
PctStartBW2 Roughness1
Roughness2
EffectivePeriod
TestPeriod
Filter1
PctStartBW1
ARC Percentage Setting
P3/4
30K
0K
PctStartFrq1
PctStartFrq2
ARC Bandwith Setting
StartFrq2
Bandwidth2
P2/4
20%
25
50K
10K
Threshold2(dB)
Proportion2
SigPerApdLimit2(dB)
420 60
Filter2
ARCParaGro
up
ARCEnble
0 Enble
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
Figure 4-18 ARC Submenu Parameters
4.4.2.8 Other Parameters
The Other Parameters submenu is to set parameters such as MPPT scan period, nominal derating step, GFCI and DCI parameters. Press ENT and use and to set the parameters and enable/disable the function. Then press ENT to confirm
your selection. The parameters are shown in Figure 4.19 (Parameters in gray cannot be changed)
Page 77
DOCR-070645-E Page 77 of 102
Others
PVSlowStartSlope
PowerOnDelay(s)
P1/5
ErrSoftStartP
Others
P2/5
83.0
95.0
NormSoftStopP
NormalDeratingStep
FaultPowerT(C)
FaultEnvT(C)
6.00%
0.16%
10.00%
5
4.00%
6.00%
Disable
Others GFCIStaticValue(mA)
P3/5
0.50%
100.0%
0.2
250
GFCIStaticT(s)
10.00 950
1.00
Others
P4/5
140K
3600
330
GFCIDynProFactor
DCIProtectionT1(s)
DCIProtection1
DCIProtection2(mA)
PVStarupVolt(V) MPPTScanPeriod(s) ISOProtection
Enable
Disable
Enable
Enable
NormSoftStartP
DCIProtectionT2(s)
Enable
Enable
Enable
4
0%
-30.0
StartUPMinTemp(C) DuplicationGroup CtrParaGroup
PID Check Setting
0
Others
P5/5
Enable
Enable
Islang Protect Fan Detect
Setting
P2/2
Others Parameters
Figure 4.19 Settings Menu Structure
Page 78
DOCR-070645-E Page 78 of 102
4.4.3 Power ON/OFF
A manual power cycle ON/OFF is required after any parameter change, after getting an error message or updating the software. The unit will automatically go into the OFF state. Press ESC or ENT to enter into the Main Menu, then press ENT and go to the submenu “Power On/OFF”. Then move the cursor to “ON” and press ENT to start the inverter, the inverter will start up normally and operate if the start-up conditions are met. Normally it is not necessary to turn OFF the inverter, but if this is needed, you can do so from this menu simply by selecting “OFF” and pressing ENT to confirm.
4.4.4 History
Move the cursor to “4 History” in the main interface. Press ENT to check the history information, as shown in Figure 4.20. There are 2 submenus in “2 History”: “Running History” and “Fault Record”.
(1) The log can store up 100 running history messages in the “Running History” menu. (2) The log can store up 100 fault records in the “Fault Record” menu.
History Record
Running Record
Fault Record
Current Error
Current Error
P1/1
Date Error 2015/10/22 12:20:08 ArcboardErr
2015/10/22 12:20:08
2015/10/22 12:20:08 Fault0040
2015/10/22 12:20:08 2015/10/22 12:20:08
Time
Fault0040
Fault0040
Fault0040
Fault Record
P1/1
Num Date
Error
001 15/1 0/22 12:20:08
003 15/10/22 12:20:08
002 15/1 0/22 12:20:08
004
15/10/22 12:20:08
005 15/1 0/22 12:20:08
Time
Fault0040
Fault0040
Fault0040
Fault0040
ArcboardErr
Action
ON
ON
ON
ON
ON
Running Record
P1/1
Num Date
Event
001 15/1 0/22 12:20:08
003 15/10/22 12:20:08
002 15/1 0/22 12:20:08
004 15/1 0/22 12:20:08
006 15/10/22 12:20:08
005 15/1 0/22 12:20:08
Fault
Standby
Standby
On-grid
Off-grid
SysStart
Time
Figure 4-20 History Menu and Submenu
Page 79
DOCR-070645-E Page 79 of 102
4.4.5 Device Information
Move the cursor to the main operation interface “Main Menu”. Press ENT and go to sub menu “Device Information” and press ENT to check the device information as shown in Figure 4-21.
Inverter information
P1/2
Device Model: SCA60KTL-DO/US­480
Device SN: 0 0000 0000 0000 DSP Ver: 01.00 0x505A
LCD Ver: 01.00
DSP Bootloader Ver: 01.00
LCD Bootloader Ver: 01.00 MiniMCU Ver: 01.00
Data Logger Information
P2/2
IP 0.0.0.0
Data Logger SN 0 0000 0000 0000
Subnet Mask 0.0.0.0
DNS Server 0.0.0.0
Gateway 0.0.0.0
Address Range
Main Menu
Measurement Data
History Record
Power On/Off
Device Information
Setting
Figure 4-21 History Menu and Submenu
PVI-50/60TL
Page 80
DOCR-070645-E Page 80 of 102
5.0: Operation
5.1 Start-Up
Manual Start-up: Manual start-up is required after regulation setting change or
manual (fault) shut-down. Move the cursor from the main operation interface to Setting”. Press ENT and go to submenu “1 ON/OFF”. Then move the cursor to “ON” and press ENT to start the inverter. The inverter will start up and operate normally if the start-up conditions are met. Otherwise, the inverter will go to stand-by mode.
Automatic Start-up: The inverter will start up automatically when the output voltage and power from the PV arrays meet the required values, AC power grid is normal, and the ambient temperature is within allowable operating range.
5.2 Shutdown
Manual Shutdown: Normally, it is not necessary to shut down the inverter, but it can
be shut down manually if regulation setting or maintenance is required.
Move the cursor from the main operation interface to “4 Setting”. Press ENT and go to submenu “1 ON/OFF”. Move the cursor to “OFF” and press ENT, and then the inverter
will shut down.
Automatic Shutdown: The inverter will be shut down automatically when the output voltage and power of PV modules are lower than the required values, AC power grid fails, or the ambient temperature exceeds the normal range.
5.3 Operation Mode
There are 4 operation modes. The following are corresponding indications for each mode.
(1) System-check mode and logo for startup, as shown in Figure 5.1.
Figure 5.1 - System Self-Check Ongoing
This mode indicates that the inverter is checking whether it is ready for normal operation after the manual start-up of inverter.
(2) Normal operation mode: Default indication interface for normal operation is
shown in Figure 5.2.
Page 81
DOCR-070645-E Page 81 of 102
E-total: KWh
2015-10-22 1000:00
E-Today: kWh
Status Addr:000
Running Status Cycle Display
3 6 9 12 15 18 21 24
kWh
h
15
30
45
60
Figure 5.2 - Default Indication Interface for Normal Operation
In this mode, the inverter converts the power generated by PV modules to AC continuously and feeds into the power grid.
(3) Standby mode, as shown in Figure 5.3:
The inverter will enter standby mode when the output voltage and power of PV modules do not meet the startup conditions or PV voltage and input power are lower than the set values. The inverter will check automatically whether it meets the startup conditions in this mode until it turns back to normal mode. The inverter will switch from standby mode to fault mode if a malfunction occurs.
E-total: KWh
2015-10-22 0500:00
E-Today: kWh
Standby 485Addr
Running Status Cycle Display
6 8 10 12 14 16 18 20
kWh
h
200
40
80
120
160
Figure 5.3 - Inverter System in Standby Mode
(4) Fault mode, as shown in Figure 5.4.
The inverter will disconnect from the power grid and turn into fault mode when the inverter or power grid fails. Check the specific cause in Troubleshooting Table” (Table
6.2) according to the fault message displayed on the LCD and eliminate the fault referred to in the instructions.
Page 82
DOCR-070645-E Page 82 of 102
Current Error
P1/1
Date Error
2015/10/22 12:20:08 ArcboardErr
2015/10/22 12:20:08
2015/10/22 12:20:08 Fault0040
2015/10/22 12:20:08 2015/10/22 12:20:08
Time
Fault0040
Fault0040
Fault0040
Figure 5.4 - Fault Indication Interface
5.4 Grid-Tied Power Generation
PVI 50/60TL series inverter has an automatic grid-tied power generation process. It will check whether AC power grid meets the conditions for grid-tied power generation constantly and test whether the PV array has enough energy. After all conditions are met, the inverter will enter grid-tied power generation mode. While in the grid-tied power generation mode, the inverter can detect the power grid at all times, and also keep the photovoltaic array output in maximum power point tracking (MPPT) mode. In case of any abnormity, the inverter will enter the protection program immediately. In low light conditions when the PV power is not enough to keep the inverter in operation, the inverter will enter standby mode. When the voltage of the PV array changes and becomes stable and higher than the required set value, the inverter will attempt to start grid-tied power generation again.
WARNING:
All installation and wiring connections should be performed by qualified technical personnel. Disconnect the inverter from PV modules and the AC supply before performing maintenance. Do not work on the inverter until at least 5 minutes after disconnecting all sources of DC and AC.
Toutes les installations et les connexions de câblage doivent être effectuées uniquement par le personnel technique qualifié. Débrancher l'onduleur de modules photovoltaiques et le grid électrique avant l'entretien et la marche de l'équipement. Ne pas utiliser ou entretenir l'onduleur jusqu'à au moins 5 minutes après avoir débranché toutes les sources du côté C.C. et C.A.
Page 83
DOCR-070645-E Page 83 of 102
6.0: Maintenance and Removal of Inverter
6.1 Fault Shutdown and Troubleshooting
6.1.1 LED Fault and Troubleshooting
When contacting Solectria for support please provide the serial number of the inverter and the fault message. If the fault is regarding a voltage issue, please measure the AC and DC voltage at the inverter prior to calling.
Please refer to the definition of LED lights in Table 4.1 and troubleshoot according to Table 6.1.
Table 6.1 - Troubleshooting of LED Lights
LED fault status
Solutions
Neither the “Power” LED nor the LCD lights up.
1. Turn off the external AC breaker
2. Switch the DC switch to “OFF” position
3. Check the PV input voltage and polarity
The GRID LED is blinking.
1. Turn off the external AC breaker
2. Switch the DC switch to “OFF” position
3. Check whether the grid voltage is normal and whether the cable connection of AC side is installed correctly and secure
The “RUN” LED turns off or “FAULT” LED lights up.
Refer to Table 7.2 for troubleshooting
6.1.2 LCD Fault and Troubleshooting
The inverter will be shut down automatically if the PV power generation system fails. This can happen due to an output short circuit, grid overvoltage / under voltage, grid over frequency / under frequency, high environmental temperature or internal malfunction of the machine. The fault information will be displayed on the LCD. Please refer to “Present Fault” for detailed operation.
The causes of a fault can be identified based on the faults listed in Table 6.2. Proper analysis is recommended before contacting after-sales service. There are 3 types of fault: alarm, protection and hardware fault.
Page 84
DOCR-070645-E Page 84 of 102
Table 6.2 - LCD Troubleshooting Table
Alarm
1.CommErr
Definition: Communication inside inverter failed
Possible causes: Terminal block connecters of internal communication wires have poor contact
Recommended solutions:
1.Observe for 5 minutes and see whether the alarm will be eliminated automatically;
2.Turn off both AC and DC disconnect for 2 minutes and reset the inverter;
3.Contact after-sales service personnel if the error persists
2.ExtFanErr
Definition: Cooling fan failure
Possible causes:
1.Fan is blocked;
2.Fan service life has expired;
3.Fan socket connecter has poor contact.
Recommended solutions:
1.Observe for 5 minutes and see whether the alarm will be eliminated automatically;
2.Check for foreign objects on fan blades;
3.Turn off both AC and DC disconnect for 2 minutes and reset the inverter;
4. Contact after-sales service personnel if the error persists
3. IntFanErr
Recommended solutions:
1.Observe for 5 minutes and see whether the alarm will be eliminated automatically;
2.Check for foreign objects on fan blades;
3.Turn off both AC and DC disconnect for 2 minutes and reset the inverter;
4. Contact after-sales service personnel if the error persists
Page 85
DOCR-070645-E Page 85 of 102
Warn
Warn0030
(EepromErr)
Definition: Internal alarm
Recommended solutions:
1.Observe for 5 minutes and see whether the alarm will be eliminated automatically;
2. Contact after-sales service personnel if the error persists
Warn0040 (DC SPD
fault)
Recommended solutions:
1. Visually check the DC SPD device to see if its indicator is red.
2. If it is red, a surge has occurred and the SPD needs to be replaced.
3. Contact after-sales service personnel to purchase a replacement SPD or for additional information.
Warn0050
(TempSensorErr)
Recommended solutions:
1.Observe temperature display;
2. Turn off both AC and DC disconnect for 2 minutes and reset the inverter;
3. Contact after-sales service personnel if the error persists
Warn0100 (AC SPD
fault)
Recommended solutions:
1. Contact after-sales service personnel.
Protection
Protect0090
(Bus over voltage)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Protect0070
(Bus imbalance)
1. Contact after-sales service personnel if the error persists
Protect0030
(Inverter Over
Current)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
GridV.OutLim
1. Make sure the grid connection is good.
2. Restart the inverter again.
GridF.OutLim
1. Check the AC wires connection and AC frequency is in range;
2. Check the measurement value in LCD, if the grid frequency is in limit, restart the inverter.
Protect0020
(Grid relay error)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
Page 86
DOCR-070645-E Page 86 of 102
2. Contact after-sales service personnel if the error persists
TempOver
(Over-temperature
protection)
1.Confirm that external ambient temperature is within the specified range of operating temperature;
2.Check whether air inlet is blocked;
3.Check whether fan is blocked;
4.Check whether the location of installation is appropriate or not;
5.Observe for 30 minutes and see whether the alarm will be eliminated automatically;
6.Contact after-sales service personnel
Protect0180
(The sampling offset
of DCI)
1. If the inverter can start up, then recalibrate.
2. Contact after-sales service personnel if the error persists.
Protect0170
(DCI high)
1. Contact after-sales service personnel if the error persists
IsolationErr
(Insulation resistance
low)
Check wires of PV and ground:
1.Turn OFF AC switch to disconnect inverter from Grid.
2.Open fuse holders to de-couple PV strings from each other. Test strings with string test set.
3.Add one PV string at a time, and start up inverter to see if alarm occurs.
4.If there is no alarm, turn OFF AC switch to disconnect from Grid and add in the next string. Start the inverter again.
5. Continue until you can find the string that triggers the alarm. Trace wirings of faulted string to find any leakage to Earth Ground.
6. Contact after-sales service personnel if the error persists.
GFCIErr
(leakage current
high)
Check wires of PV and ground:
1.Turn OFF AC switch to disconnect inverter from Grid.
2.Open fuse holders to de-couple PV strings from each other. Test strings with string test set
3.Add one PV string at a time, and start up inverter to see if alarm occurs.
4.If there is no alarm, turn OFF AC switch to disconnect from Grid and add in the next string. Startup inverter again.
5. Continue until you can find the string that triggers the alarm. Trace wiring of faulted string to find any leakage to Earth Ground.
Protect0150
1. Restart inverter by recycle both AC and DC switches.
Page 87
DOCR-070645-E Page 87 of 102
(Mini MCU Fault)
Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Protect0110
(BUS over voltage
(firmware))
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Protect0100
(The sensor fault of
leakage current)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
PVxReverse
(PVx input reverse
connection x=1,2,3)
1. Turn DC Switch OFF
2. Open Fuse holder to isolate PV strings
3. Use meter to find out which PV string is connected in reverse polarity
4. Correct PV string connection
PVx Over current
(PVx Over current
x=1,2,3)
1. Check PV input Current .
2. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
3. Contact after-sales service personnel if the error persists
PV2VoltOver
((PVx Over Volt
x=1,2,3))
1. Measure voltage at DC terminals in wiring box and compare with reading in Measurement menu. PV voltage must be less than 1000V in open circuit condition.
2. Contact after-sales service personnel if the error persists
Protect0230
(Inverter open-loop
self-test fault)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
ARC Protect
1. Clear error from the LCD menu
2. Run Arc Fault Test from Settings Menu
3. Contact after-sales service personnel if the error persists
Arcboard Err
1. Clear error from the LCD menu
2. Run Arc Fault Test from Settings Menu
3. Contact after-sales service personnel if the error
Page 88
DOCR-070645-E Page 88 of 102
persists
Fault
Fault0130
(Bus over total
voltage)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Fault0110
(Bus imbalance)
1. Contact after-sales service personnel if the error persists
Fault0100
(Grid relay fault)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Fault0090
(Dynamic leakage
current high)
Check wires of PV and ground:
1.Turn OFF AC switch to disconnect inverter from Grid.
2.Open fuse drawers to de-couple PV strings from each other. Test strings with string test set
3.Add one PV string at a time, and start up inverter to see if alarm occurs.
3.If there is no alarm, turn OFF AC switches to disconnect from Grid and add in the next string. Startup inverter again.
4. Continue until you can find the string that triggers the alarm. Trace wiring of faulted string to find any leakage to Earth Ground.
Fault0080
(Bus Hardware over
current fault)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Fault0060
(CPLD Fault)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Page 89
DOCR-070645-E Page 89 of 102
Fault0020
(Bus over volt
Hardware)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
Fault0150
(Open-loop self-check
failure)
1. Restart inverter by recycle both AC and DC switches. Wait for 1 minute between OFF and ON for all energy to discharge.
2. Contact after-sales service personnel if the error persists
INSTRUCTION:
*The actual display of “PV.VoltOver” is “PV1VoltOver” or “PV2VoltOver” or “PV3VoltOver”.
*The actual display of “PV.Reverse” is “PV1Reverse” or “PV2Reverse” or “PV3Reverse”.
DANGER:
Please disconnect the inverter from AC grid and PV modules before opening the equipment. Make sure hazardous high voltage and energy inside the equipment has been discharged. Do not work in the inverter until at least 5 minutes after disconnecting all sources of DC and AC.
Veuillez débrancher l'onduleur du grid C.A. et des modules photovoltaiques avant l'ouverture de l'équipement. Assurez-vous que la haute tension et l'énergie dangereuses à l'intérieur de l'équipement a été déchargée. Ne pas utiliser ou entretenir l'onduleur jusqu'à au moins 5 minutes après avoir débranché toutes les sources du côté C.C. et C.A
Page 90
DOCR-070645-E Page 90 of 102
6.2 Product Maintenance
6.2.1 Check the Electrical Connection
Check all the cable connections as a regular maintenance inspection every 6 months or every year.
1.) Check the cable connections. If loose, tighten all the cables according to “2.3 Electrical Installation”.
2.) Check for cable damage, especially whether the cable surface is scratched or smooth. Repair or replace the cables if necessary.
6.2.2 Clean the Air Vent Filter
The inverter can become hot during normal operation. It uses built in cooling fans to provide sufficient air flow to help in heat dissipation. Check the air vent regularly to make sure it is not blocked and clean the vent with a soft brush or vacuum if necessary.
6.2.3 Replace Cooling Fans
If the internal temperature of the inverter is too high or abnormal noise is heard assuming the air vent is not blocked and is clean, it may be necessary to replace the external fans. Please refer to Figure 6.1 for replacing the cooling fans. (1) Use a No.2 Phillips head screwdriver to take off the 10 screws on the fan tray (6 screws on the upper fan tray, and 4 screws on the lower fan tray). (2) Disconnect the waterproof cable connector from the cooling fan. (3) Use a No.2 Phillips head screwdriver to take off the screws. (4) Fix the new cooling fan on the fan tray, and fasten the cable on the fan tray with cable ties Torque value: 8 in-lbs (0.8-1N.m) (5) Install the assembled fans back to the inverter. Torque value: 10 in-lbs (1.2N.m)
Page 91
DOCR-070645-E Page 91 of 102
1
4
Figure 6.1 - Replace Cooling Fans
50~60mm
6
2
4
3
5
Page 92
DOCR-070645-E Page 92 of 102
6.2.4 Replace the Inverter
Please confirm the following before replacing the inverter: (1) The inverter is turned off. (2) The DC switch of the inverter is turned to OFF position. Afterwards replace the inverter according to the following steps: a.) Unlock the padlock if it is installed on the inverter.
Figure 6.2 - Unlock the Padlock
b.) Use a No. 2 Phillips or No. 10 wrench head screwdriver to unscrew the 2 screws on both sides of the inverter.
Page 93
DOCR-070645-E Page 93 of 102
Figure 6.3 - Remove the Screws on Both Sides
c.) Use a No. 10 Hex wrench to remove the 4 screws between the main section and the wiring box. Lift up the main section and disconnect from the wiring box.
Figure 6.4 - Disconnect the Main Section from the Wiring Box
d.) Use a No.2 Phillips head screwdriver to remove the 2 screws on the left side of the wiring box, and take off the cover board. Put the board on the connector of wiring box. Torque value: 10 in-lbs (1.2N.m)
Figure 6.5 - Install the Cover Board on the Connector of the Wiring Box
Page 94
DOCR-070645-E Page 94 of 102
6.3 Uninstalling the Inverter
Uninstall the inverter according to the following steps when the service is due or for other reasons:
1.) Turn off the AC breaker and use Padlocks if provided.
2.) Turn off the DC breaker and use Padlocks if provided. (Skip this step if there is no DC circuit breaker.)
3.) Switch the AC switch to “OFF” position.
4.) Switch the DC switch to “OFF” position.
5.) Wait for 10 minutes to ensure the internal capacitors have been completely
discharged.
6.) Measure the AC output cable terminal voltage against ground and make sure
the voltage is 0V.
7.) Disconnect the AC and EGC cables referring to “2.3.2 AC and Ground
Connection”.
8.) Disconnect the DC cables referring to “2.3.1 DC Connection”.
9.) Uninstall the inverter using the reverse of its installation steps referring to “2.2
Mechanical Installation”.
7.0: Product Warranty and RMA Policy
The current warranty and RMA statement for the product is available online at
http://www.solectria.com/support/documentation/warranty-information/grid-tied-i nverter-warranty-letter/ . If you do not have access to the internet or to request a
copy to be mailed to you, please contact our Technical Service department 978-683-9700 x 2.
DANGER:
Please disconnect the electrical connection in strict accordance with the following steps. Otherwise, the inverter will be damaged and the service personnel’s life will be endangered. Veuillez débrancher la connexion électrique en stricte conformité avec les étapes suivantes. Sinon, l'onduleur sera endommagée et la vie du personnel de service sera mise en danger.
Page 95
DOCR-070645-E Page 95 of 102
8.0: Technical Data
Model Name
PVI 50TL
PVI 60TL
DC Input
Max. PV Power
75kW (25kW/MPPT)
90kW (30kW/MPPT)
Nominal DC Input Power
51.5kW
61.5kW
Max. DC Input Voltage1
1000Vdc
Operating DC Input Voltage Range2
200-950Vdc
Start-up DC Input Voltage / Power
330V/80W
Number of MPP Trackers
3
MPPT Voltage Range
480-850Vdc
540-850Vdc
Operating Current(Imp)
3*36A
3*38A
Short Circuit Current (Isc)
3*60A
Number of DC Inputs
15 inputs, 5 per MPPT
DC Disconnection Type
Load rated DC switch
AC Output
Rated AC Output Power
50kW
60kW
Max. AC Output Power
50KVA
60KVA
Rated Output Voltage
480Vac
Output Voltage Range3
422-528Vac
Grid Connection Type
3Φ/PE/N
Nominal AC Output Current @480Vac
61A
73A
Rated Output Frequency
60Hz
Output Frequency Range4
57-63Hz
Power Factor
>0.99 (±0.8 adjustable)
Current THD
<3%
AC Disconnection Type
Load rated AC switch
System
Topology
Transformerless
1
Exceeding the Max. DC Input Voltage may cause permanent damage to the equipment.
2
Exceeding the Max. DC Input Voltage may cause permanent damage to the equipment.
3
The Output Voltage Range may differ according to specific grid standard.
4
The Output Frequency Range may differ according to specific grid standard.
Page 96
DOCR-070645-E Page 96 of 102
Max. Efficiency
99.0%
CEC Efficiency
98.5%
Stand-by / Night Consumption
<30W / <2W
Environment
Protection Degree
TYPE 4X
Cooling
Variable speed cooling fans
Operating Temperature Range
-22°F to +140°F / -30°C to +60°C (derating from +122°F / +50°C)
Operating Humidity
0-95%, non-condensing
Operating Altitude
13123.4ft / 4000m (derating from 9842.5ft / 3000m)
Display and Communication
Display
LCD + LED
Communication
Standard: RS485 (Modbus RTU)
Optional: TCP/IP card
Mechanical Data
Dimensions (HxWxD)
39.4”×23.6”×10.24”
Weight
inverter:123.5lbs/56kg; wirebox:33lbs/15kg
Orientation**
0 - 90 degrees from horizontal
Safety
PV Arc-Fault Circuit Protection
Type 1
Safety and EMC Standard
UL1741:2010,UL1699B, CSA-C22.2 NO.107.1-01,
IEEE1547, FCC PART15
Grid Standard
IEEE1547,Rule 21,HECO/Rule14H
*The "Output Voltage Range" and "Output Frequency Range" may differ according to specific grid standard. **Shade cover accessory required for installation angles of 75 degrees or less.
Page 97
DOCR-070645-E Page 97 of 102
NOTE 1: When the DC input voltage is lower than 540V (for PVI 60TL) and 480V (for PVI 50TL) or higher than 850V, the inverter begins derating, as shown in Figure 7.1 and Figure 7.2.
Figure 7.1 - PVI 60TL Derating Curve of PV Input Voltage
Figure 7.2 - PVI 50TL Derating Curve of PV Input Voltage
20%
40%
60%
80%
100%
PV Voltage (V)
PInx/PInn
100 200 300 400 500 600 850 950 1000
110%
540
37%
20%
40%
60%
80%
100%
PV Voltage (V)
PInx/PInn
100 200 300 400 500 600 850 950 1000
110%
480
37%
0.8%/V
0.8%/V
Page 98
DOCR-070645-E Page 98 of 102
NOTE 2: When the ambient temperature is higher than 113°F (45°C), the output power may begin derating. For DC voltage as shown in Figure 7.3:
Figure 7.3 - PVI 50/60TL Derating Curve with High Temperature
Note: At 60 degrees C the inverter is likely to shutoff. Depending on various factors like angle of installation, air flow and others, the thermal shutdown may occur at higher temperature like 61-63 degrees C. For designing and modelling purposes one should consider shut down at 60 degrees C.
Output
Power
Celsius
Page 99
DOCR-070645-E Page 99 of 102
NOTE 3: When the altitude is higher than 9843ft (3000m), the power of the inverter will start derating, as shown in Figure 7.3:
Pin/Pn
3000 4000
Altitude(m)
100%
70%
-30%/km
Figure 7.4 - PVI 50/60TL Derating Curve with High Altitude
NOTE 4: The inverter can output the AC power with full loads within 100%~110% of
the rated grid voltage. When the grid voltage is lower than rated voltage, the output current will be limited within the allowable maximum current.
20%
40%
60%
80%
100%
Po/Pn
Un 1.1*Un
Grid Voltage (Vac)
Figure 7.5 - PVI 50/60TL Derating Curve of Grid Voltage
Po/Pn
480
528
Page 100
PVI 50-60TL Installation and Operation Manual PVI Series Inverters
DOCR-070645-E Page 100 of 102
9.0: Accessory Options
The PVI 50/60TL has several orderable options that allow the inverter to support a wide range of real life applications.
9.1 Fuse Bypass
OPT-FUSEBYPASS-PVI-50-60TL allows customers to combine the DC inputs outside of
the inverter and enter with only one or two combined inputs. Torque the provided hardware to 16 in-lbs (1.8 N.m). Note that the negative inputs are combined already. The unit is separated on the positive input.
Figure 8.1 – Fuse Bypass Three Inputs (Three Independent MPPTs)
Bypass Input Terminal Instructions:
1. Remove the protection cover.
2. Use a No. 2 Phillips head screwdriver to install the bypass input terminals, 3 sets, torque value of 14 in-lbs (1.6 N.m.).
3. Use a No. 10 wrench to screw DC input cable on the bypass input terminals, torque value of 50 in-lbs (6.0 N.m.).
4. Reinstall the protection cover.
Loading...